Values this chapter turns on
- guard top load within dwelling units
- 0.5 kN/m
- guard top load within dwelling units
- minimum effective depth of a wood stair stringer
- 90 mm
- minimum effective depth of a wood stair stringer
- minimum overall depth of a wood stair stringer
- 235 mm
- minimum overall depth of a wood stair stringer
- storage garage separation from other occupancies
- 1.5 h
- storage garage separation from other occupancies
This chapter collects the structural items scattered through 9.5 to 9.10:
- glass strength and window protection;
- guard and handrail loads;
- stair loads and stair members;
- the fire rules that are really about structure: protecting steel, preventing collapse, and firewalls.
The numbers are close to the Part 4 values from chapter 3. Watch for the places where Part 9 is lighter, such as guards in a dwelling unit and stairs serving one dwelling.
Glass and windows
Glass must meet one of the CGSB or ASTM standards listed in 9.6.1.2. Mirrored glass doors are allowed only at clothes closet entrances OBC Div. B 9.6.1.2.OBC Div. B 9.6.1.2. Material Standards for Glass(1) Glass shall conform to (a) CAN/CGSB-12.1, "Safety Glazing," (b) CAN/CGSB-12.2-M, "Flat, Clear Sheet Glass," (c) CAN/CGSB-12.3-M, "Flat, Clear Float Glass," (d) CAN/CGSB-12.4-M, "Heat Absorbing Glass," (e) CAN/CGSB-12.8, "Insulating glass units," (f) CAN/CGSB-12.9, "Spandrel glass," (g) CAN/CGSB-12.10-M, "Glass….
Structurally, glass is designed to 4.3.6.1 OBC Div. B 9.6.1.3.OBC Div. B 9.6.1.3. Structural Sufficiency of Glass(1) Except as provided in Sentence (2), glass shall be designed in conformance with Article 4.3.6.1. (2) Where the building has an essentially uniform distribution of paths for air leakage, including operable openings, but no large openings that would permit wind gusts to rapidly enter the building and the building is…. Window panes may use the area tables 9.6.1.3.-A to -F only if all of these hold:
- air leakage paths are spread evenly over the building;
- there are no large openings that would let wind gusts in;
- the building is not in an exceptionally exposed spot, such as a hilltop.
Door panes use Table 9.6.1.3.-G.
Article 9.7.2.2 is a signpost for windows and doors OBC Div. B 9.7.2.2.OBC Div. B 9.7.2.2. Other Requirements for Windows, Doors and Skylights(1) Minimum sizes of doorways and doors within a barrier-free path of travel shall conform to Section 9.5. (2) The protection of window and door openings to protect persons from falling through them shall conform to Article 9.8.8.1. (3) Properties of windows and doors within exits shall conform to Section 9.9. (4)…. Protection against falling through openings is in 9.8.8.1 OBC Div. B 9.8.8.1.OBC Div. B 9.8.8.1. Required Guards(1) Except as provided in Sentence (2) and except at the leading edge at the top of a flight, every surface to which access is provided, including but not limited to flights of steps and ramps, exterior landings, porches, balconies, mezzanines, galleries and raised walkways, shall be protected by a guard on each side…. In residential occupancies, an openable window needs either a guard or a tool-release limiter that keeps the opening to 100 mm or less. The exception is a window whose openable part is either:
- more than 900 mm above the floor; or
- less than 1,800 mm above the ground outside.
Glazing over stairs and landings follows the same idea. If it comes within 1,070 mm of the tread (900 mm inside a dwelling unit), it needs a guard, or it must be fixed and designed for the 4.1.5.14 guard loads.
Stud walls around the main bathroom of a dwelling unit get blocking for future grab bars at the water closet, shower and tub OBC Div. B 9.5.2.4.OBC Div. B 9.5.2.4. Stud Wall Reinforcement(1) If wood wall studs or sheet steel wall studs enclose the main bathroom in a dwelling unit, reinforcement shall be installed to permit the future installation of the following: (a) for a water closet, a grab bar described in Clauses 3.8.3.8.(3)(a) and a grab bar described in Clause 3.8.3.8.(3)(c), (b) for a shower….
Guards and handrails
A guard is required wherever a walking surface is more than 600 mm above the adjacent surface within 1.2 m. Guard loads come from Table 9.8.8.2.OBC Div. B Table 9.8.8.2. Minimum Specified LoadsTable 9.8.8.2. — Minimum Specified Loads Forming Part of Sentence 9.8.8.2.(1) Location of Guard | Horizontal Load Applied Inward or Outward at any Point at the Minimum Required Height of the Guard | Horizontal Load Applied Outward on Elements Within the Guard, Including Solid Panels and Balusters | Evenly Distributed…:
| Location | Top of guard, horizontal | Elements (balusters, panels) | Vertical on top |
|---|---|---|---|
| Within dwelling units, and exterior guards serving 2 or fewer dwelling units | 0.5 kN/m or 1.0 kN point | 0.5 kN over 300 x 300 mm | 1.5 kN/m |
| Equipment platform access | 1.0 kN point | 0.5 kN over 100 x 100 mm | 1.5 kN/m |
| All other guards | 0.75 kN/m or 1.0 kN point | 0.5 kN over 100 x 100 mm | 1.5 kN/m |
The loads need not act at the same time. In dwelling units, a balustrade load is spread to engage three balusters where they fall within 300 mm OBC Div. B 9.8.8.2.OBC Div. B 9.8.8.2. Loads on Guards(1) Except as provided in Sentences (2), (3), (5) and (6), guards shall be designed to resist the specified loads prescribed in Table 9.8.8.2. (2) The size of the opening between any two adjacent vertical elements within a guard shall not exceed the limits required by Sentence 9.8.8.5.(1) when each of these elements…. Guards built to SB-7, "Guards for Housing and Small Buildings", are deemed to comply.
Glass in guards is safety glass of the laminated or tempered type to CAN/CGSB-12.1, or wired glass to CAN/CGSB-12.11-M OBC Div. B 9.8.8.7.OBC Div. B 9.8.8.7. Glass in Guards(1) Glass in guards shall be (a) safety glass of the laminated or tempered type conforming to CAN/CGSB-12.1, "Safety Glazing," or (b) wired glass conforming to CAN/CGSB-12.11-M, "Wired Safety Glass.". Garage floors and ramps 600 mm or more above the adjacent level need a curb of at least 140 mm and a guard of at least 1,070 mm. Vehicle guardrails take the 22 kN load of 4.1.5.15 OBC Div. B 9.8.8.4.OBC Div. B 9.8.8.4. Guards for Floors and Ramps in Garages(1) Except for floors of garages referred to in Section 9.35., where garage floors or ramps are 600 mm or more above the adjacent ground or floor level, every opening through a garage floor and the perimeter of floors and ramps that have no exterior walls shall be provided with (a) a continuous curb not less than 140….
Handrails resist a 0.9 kN point load in any direction. Handrails not serving a single dwelling unit also take 0.7 kN/m OBC Div. B 9.8.7.7.OBC Div. B 9.8.7.7. Design and Attachment of Handrails(1) Handrails and their supports shall be designed and constructed to withstand the following loads, which need not be considered to act simultaneously: (a) a concentrated load of not less than 0.9 kN applied at any point and in any direction for all handrails, and (b) for handrails other than those serving a single…. In a single dwelling unit, a handrail fixed to wood studs or blocking is deemed to comply if all three of these are met:
- attachment points at no more than 1.2 m;
- the end attachments within 300 mm of the ends;
- two No. 8 wood screws at each point, penetrating at least 32 mm into solid wood.
Stairs
Stairs and ramps take a uniform load of 1.9 kPa if they serve only one dwelling unit (or a house with a secondary suite), and 4.8 kPa otherwise OBC Div. B 9.8.9.1.OBC Div. B 9.8.9.1. Loads on Stairs and Ramps(1) Except as specified in Articles 9.8.9.4. and 9.8.9.5., stairs and ramps shall be designed for strength and rigidity under uniform loading criteria to support specified loads of (a) 1.9 kPa for stairs and ramps serving not more than one dwelling unit or a house with a secondary suite including their common spaces….
Wood stringers OBC Div. B 9.8.9.4.OBC Div. B 9.8.9.4. Wooden Stair Stringers(1) Wooden stair stringers shall (a) have a minimum effective depth of 90 mm, measured perpendicularly to the bottom of the stringer at the point of minimum cross-section, and an overall depth of not less than 235 mm, (b) be supported and secured top and bottom, (c) be not less than 25 mm actual thickness if supported…:
- effective depth of at least 90 mm, measured square to the bottom edge at the narrowest point after cutting;
- overall depth of at least 235 mm;
- 25 mm thick if supported along their length, 38 mm if not;
- spacing up to 900 mm in single-dwelling stairs (1,200 mm where risers support the tread fronts), and 600 mm in other stairs.
Treads in dwelling units are at least 25 mm thick, or 38 mm with open risers and stringers more than 750 mm apart OBC Div. B 9.8.9.5.OBC Div. B 9.8.9.5. Treads(1) Stair treads of lumber, plywood or O-2 grade OSB within dwelling units shall be not less than 25 mm actual thickness, except that, if open risers are used and the distance between stringers exceeds 750 mm, the treads shall be not less than 38 mm actual thickness. (2) Stair treads of plywood or OSB, that are not….
Exterior concrete stairs with more than 2 risers sit on walls or piers at least 150 mm across, or are cantilevered from the foundation OBC Div. B 9.8.9.2.OBC Div. B 9.8.9.2. Exterior Concrete Stairs(1) Exterior concrete stairs with more than 2 risers and 2 treads shall be (a) supported on unit masonry or concrete walls or piers not less than 150 mm in cross-section, or (b) cantilevered from the main foundation wall. (2) Stairs described in Sentence (1), when cantilevered from the foundation wall, shall be…. Cantilevered steps are designed for their loads. They are anchored to concrete foundation walls at least 200 mm thick and protected against frost uplift OBC Div. B 9.8.10.2.OBC Div. B 9.8.10.2. Anchorage(1) Cantilevered concrete steps referred to in Article 9.8.10.1. shall be anchored to concrete foundation walls not less than 200 mm thick..
Fire-related structure
Several fire rules in 9.10 are really about structure:
- Tents, air-supported structures, transformer vaults, assembly spaces and large basements are sent to Part 3 OBC Div. B 9.10.1.3.OBC Div. B 9.10.1.3. Items Under Part 3 Jurisdiction(1) Tents, air-supported structures, transformer vaults, walkways, elevators and escalators shall conform to Part 3. (2) Where rooms or spaces are intended for an assembly occupancy, such rooms or spaces shall conform to Part 3. (3) Basements containing more than 1 storey or exceeding 600 m² in area shall conform to….
- Structural steel in construction that needs a fire-resistance rating must be protected to give that rating, except as 3.2.2.3 allows OBC Div. B 9.10.7.1.OBC Div. B 9.10.7.1. Protection of Steel Members(1) Except as permitted in Article 3.2.2.3., structural steel members used in construction required to have a fire-resistance rating shall be protected to provide the required fire-resistance rating..
- Combustible framing that bears on or abuts a noncombustible fire separation must be built so that its collapse in a fire does not bring the separation down OBC Div. B 9.10.9.10.OBC Div. B 9.10.9.10. Collapse of Combustible Construction(1) Combustible construction that abuts on or is supported by a noncombustible fire separation shall be constructed so that its collapse under fire conditions will not cause collapse of the fire separation..
- Beam pockets in a masonry or concrete fire separation must leave the equivalent thickness required in SB-2 OBC Div. B 9.10.9.11.OBC Div. B 9.10.9.11. Reduction in Thickness of Fire Separation by Beams and Joists(1) Where pockets for the support of beams or joists are formed in a masonry or concrete fire separation, the remaining total thickness of solid masonry and/or grout and/or concrete shall be not less than the required equivalent thickness shown for Type S monolithic concrete in Table 2.1.1. of MMAH Supplementary….
- A storage garage is separated from other occupancies by 1.5 h, or 1 h if it holds 5 vehicles or fewer. No separation is needed if it serves only the dwelling unit it belongs to OBC Div. B 9.10.9.18.OBC Div. B 9.10.9.18. Separation of Storage Garages(1) Except as provided in Sentences (2) and (3), a storage garage shall be separated from other occupancies by a fire separation having not less than a 1.5 h fire-resistance rating. (2) Except as permitted in Sentence (3), storage garages containing 5 motor vehicles or fewer shall be separated from other occupancies….
- Firewalls in Part 9 buildings follow Part 3 OBC Div. B 9.10.11.3.OBC Div. B 9.10.11.3. Construction of Firewalls(1) Where firewalls are used, the requirements in Part 3 shall apply.. Their structural design load comes from 4.1.5.17.
Chapter review
Chapter at a glance
One line per section: the idea to carry into the exam. Then the answers that most often catch candidates out.
- Glass and windows
Glass must meet one of the CGSB or ASTM standards listed in 9.6.1.2. Mirrored glass doors are allowed only at clothes closet entrances.
- Guards and handrails
A guard is required wherever a walking surface is more than 600 mm above the adjacent surface within 1.2 m.
- Stairs
Stairs and ramps take a uniform load of 1.9 kPa if they serve only one dwelling unit (or a house with a secondary suite), and 4.8 kPa otherwise.
Practice this chapter
Questions on Part 9 stairs, guards, glass and fire-related structure, in the exam format, every answer explained and cited to its article. Sign in to start; a free account gets the free questions.
Code cited in this chapter
Based on the official 2024 Building Code Compendium on ontario.ca.
© King's Printer for Ontario, 2024. Reproduced with permission.
OBC Div. B 9.6.1.2. Material Standards for Glass
Open OBC Div. B 9.6.1.2. in the code viewer(1)Glass shall conform to
(a)CAN/CGSB-12.1, "Safety Glazing,"
(b)CAN/CGSB-12.2-M, "Flat, Clear Sheet Glass,"
(c)CAN/CGSB-12.3-M, "Flat, Clear Float Glass,"
(d)CAN/CGSB-12.4-M, "Heat Absorbing Glass,"
(e)CAN/CGSB-12.8, "Insulating glass units,"
(f)CAN/CGSB-12.9, "Spandrel glass,"
(g)CAN/CGSB-12.10-M, "Glass, Light and Heat Reflecting,"
(h)CAN/CGSB-12.11-M, "Wired Safety Glass," or
(i)ASTM E2190, "Standard Specification for Insulating Glass Unit Performance and Evaluation."
(2)Mirrored glass doors are only permitted to be used at the entrance to clothes closets and shall conform to the requirements of CAN/CGSB-82.6-M, "Doors, Mirrored Glass, Sliding or Folding, Wardrobe." (See Note A-9.6.1.2.(2))
(3)Mirrored glass doors reinforced with a film backing shall meet the impact resistance requirements specified in CAN/CGSB-12.5-M, "Mirrors, Silvered."
OBC Div. B 9.6.1.3. Structural Sufficiency of Glass
Open OBC Div. B 9.6.1.3. in the code viewer(1)Except as provided in Sentence (2), glass shall be designed in conformance with Article 4.3.6.1.
(2)Where the building has an essentially uniform distribution of paths for air leakage, including operable openings, but no large openings that would permit wind gusts to rapidly enter the building and the building is not in an exceptionally exposed location such as a hilltop, the maximum area of individual panes of glass for windows shall conform to
(a)Tables 9.6.1.3.-A to 9.6.1.3.-C, where the building has a height from grade to the uppermost roof of 12 m or less, and is located in a built-up area, no less than 120 m away from the boundary between this area and open terrain, or
(b)Tables 9.6.1.3.-D to 9.6.1.3.-F.
(See Note A-9.6.1.3.(2))
(3)The maximum area of individual panes of glass for doors shall conform to Table 9.6.1.3.-G.
OBC Div. B 9.7.2.2. Other Requirements for Windows, Doors and Skylights
Open OBC Div. B 9.7.2.2. in the code viewer(1)Minimum sizes of doorways and doors within a barrier-free path of travel shall conform to Section 9.5.
(2)The protection of window and door openings to protect persons from falling through them shall conform to Article 9.8.8.1.
(3)Properties of windows and doors within exits shall conform to Section 9.9.
(4)Windows and doors installed to provide the required means of egress from bedrooms shall conform to Subsection 9.9.10.
(5)The location and protection of windows, doors and skylights in order to control the spread of fire shall conform to Subsection 9.10.12.
(6)Doors between dwelling units and attached garages shall conform to Article 9.10.13.15.
(7)The surface flame-spread rating for doors and skylights shall conform to Article 9.10.17.1.
(8)Windows and doors installed to provide the required access to a building for firefighting purposes shall conform to Subsection 9.10.20.
(9)Windows and skylights installed to provide required non-heating season ventilation shall conform to Article 9.32.2.2.
OBC Div. B 9.8.8.1. Required Guards
Open OBC Div. B 9.8.8.1. in the code viewer(1)Except as provided in Sentence (2) and except at the leading edge at the top of a flight, every surface to which access is provided, including but not limited to flights of steps and ramps, exterior landings, porches, balconies, mezzanines, galleries and raised walkways, shall be protected by a guard on each side that is not protected by a wall for the length where the difference in elevation is more than 600 mm between the walking surface and the adjacent surface within 1.2 m.
(2)Guards are not required
(a)at loading docks,
(b)at floor pits in repair garages, or
(c)where access is provided for maintenance purposes only.
(3)Doors in buildings of residential occupancy, where the finished floor on one side of the door is more than 600 mm above the floor or other constructed surface or ground level on the other side of the door, shall be protected by
(a)a guard, or
(b)a mechanism capable of controlling the free swinging or sliding of the door so as to limit any clear unobstructed opening to not more than 100 mm.
(4)Except as provided in Sentence (5), openable windows in buildings of residential occupancy shall be protected by
(a)a guard, or
(b)a mechanism that can only be released with the use of tools or special knowledge to control the free swinging or sliding operation of the openable part of the window so as to limit any clear unobstructed opening to not more than 100 mm measured either vertically or horizontally. (See Note A-9.8.8.1.(4))
(5)Windows need not be protected in accordance with Sentence (4), where the bottom edge of the openable portion of the window is located
(a)more than 900 mm above the finished floor, or
(b)less than 1,800 mm above the floor or ground on the other side of the window. (See Note A-9.8.8.1.(4))
(6)Except as provided in Sentence (7), glazing installed over stairs, ramps and landings that extends to less than 1,070 mm above the surface of the treads, ramp or landing shall be
(a)protected by guards in accordance with this Subsection, or
(b)non-openable and designed to withstand the specified lateral loads for guards as provided in Article 4.1.5.14.
(7)In dwelling units, glazing installed over stairs, ramps and landings that extends to less than 900 mm above the surface of the treads, ramp or landing shall be
(a)protected by guards in accordance with this Subsection, or
(b)non-openable and designed to withstand the specified lateral loads for guards as provided in Article 4.1.5.14.
(8)Glazing installed in public areas that extends to less than 1 m from the floor and is located above the second storey in buildings of residential occupancy shall be
(a)protected by guards in accordance with this Subsection, or
(b)non-openable and designed to withstand the specified lateral loads for guards as provided in Article 4.1.5.14.
OBC Div. B 9.5.2.4. Stud Wall Reinforcement
Open OBC Div. B 9.5.2.4. in the code viewer(1)If wood wall studs or sheet steel wall studs enclose the main bathroom in a dwelling unit, reinforcement shall be installed to permit the future installation of the following:
(a)for a water closet, a grab bar described in Clauses 3.8.3.8.(3)(a) and a grab bar described in Clause 3.8.3.8.(3)(c),
(b)for a shower, a grab bar described in Clause 3.8.3.13.(2)(g), and
(c)for a bathtub, a grab bar described in Clause 3.8.3.13.(7)(e). (See Note A-9.5.2.4.(1))
OBC Div. B Table 9.8.8.2. Minimum Specified Loads
Open OBC Div. B Table 9.8.8.2. in the code viewerTable 9.8.8.2. — Minimum Specified Loads Forming Part of Sentence 9.8.8.2.(1) Location of Guard | Horizontal Load Applied Inward or Outward at any Point at the Minimum Required Height of the Guard | Horizontal Load Applied Outward on Elements Within the Guard, Including Solid Panels and Balusters | Evenly Distributed Vertical Load Applied at the Top of the Guard Guards within dwelling units and exterior guards serving not more than 2 dwelling units | 0.5 kN/m or concentrated load of 1.0 kN applied at any point[1] | 0.5 kN applied over a maximum width of 300 mm and a height of 300 mm[2] | 1.5 kN/m Guards serving access ways to equipment platforms and similar areas where the gathering of many people is improbable | Concentrated load of 1.0 kN applied at any point | Concentrated load of 0.5 kN applied over an area of 100 mm by 100 mm located at any point on the element or elements so as to produce the most critical effect | 1.5 kN/m All other guards | 0.75 kN/m or concentrated load of 1.0 kN applied at any point[1] | Concentrated load of 0.5 kN applied over an area of 100 mm by 100 mm located at any point on the element or elements so as to produce the most critical effect | 1.5 kN/m Notes to Table 9.8.8.2.: (1) The load that creates the most critical condition shall apply. (2) See Sentence (3).
OBC Div. B 9.8.8.2. Loads on Guards
Open OBC Div. B 9.8.8.2. in the code viewer(1)Except as provided in Sentences (2), (3), (5) and (6), guards shall be designed to resist the specified loads prescribed in Table 9.8.8.2.
(2)The size of the opening between any two adjacent vertical elements within a guard shall not exceed the limits required by Sentence 9.8.8.5.(1) when each of these elements is subjected to a specified live load of 0.1 kN applied in opposite directions in the in-plane direction of the guard so as to produce the most critical effect.
(3)For guards within dwelling units and within houses with a secondary suite including their common spaces and for exterior guards serving not more than two dwelling units, where the width and spacing of balusters are such that three balusters can be engaged by a load imposed over a 300 mm width, the load shall be imposed so as to engage three balusters.
(4)None of the specified loads specified in Table 9.8.8.2. need be considered to act simultaneously.
(5)For guards within dwelling units and within houses with a secondary suite including their common spaces and for exterior guards serving not more than two dwelling units, Table 9.8.8.2. need not apply where the guard construction used has been demonstrated to provide effective performance.
(6)Guards constructed in accordance with the requirements in MMAH Supplementary Standard SB-7, "Guards for Housing and Small Buildings" shall be deemed to satisfy the requirements of Sentence (1).
OBC Div. B 9.8.8.7. Glass in Guards
Open OBC Div. B 9.8.8.7. in the code viewer(1)Glass in guards shall be
(a)safety glass of the laminated or tempered type conforming to CAN/CGSB-12.1, "Safety Glazing," or
(b)wired glass conforming to CAN/CGSB-12.11-M, "Wired Safety Glass."
Show all 21 articles
OBC Div. B 9.8.8.4. Guards for Floors and Ramps in Garages
Open OBC Div. B 9.8.8.4. in the code viewer(1)Except for floors of garages referred to in Section 9.35., where garage floors or ramps are 600 mm or more above the adjacent ground or floor level, every opening through a garage floor and the perimeter of floors and ramps that have no exterior walls shall be provided with
(a)a continuous curb not less than 140 mm in height, and
(b)a guard not less than 1,070 mm above the floor level.
(2)Vehicle guardrails shall be designed and constructed to withstand the loading values stipulated in Sentence 4.1.5.15.(1). (See Note A-4.1.5.14. and 4.1.5.15.(1))
OBC Div. B 9.8.7.7. Design and Attachment of Handrails
Open OBC Div. B 9.8.7.7. in the code viewer(1)Handrails and their supports shall be designed and constructed to withstand the following loads, which need not be considered to act simultaneously:
(a)a concentrated load of not less than 0.9 kN applied at any point and in any direction for all handrails, and
(b)for handrails other than those serving a single dwelling unit, a uniform load of not less than 0.7 kN/m.
(2)Where exterior or interior handrails serving a single dwelling unit or a house with a secondary suite including their common spaces are attached to wood studs or blocking, the attachment shall be deemed to comply with Sentence (1), where
(a)the attachment points are spaced not more than 1.2 m apart measured on the horizontal plane,
(b)the first attachment point at either end is located not more than 300 mm from the end of the handrail, and
(c)the fasteners consist of no fewer than 2 No. 8 wood screws at each point, penetrating not less than 32 mm into solid wood.
OBC Div. B 9.8.9.1. Loads on Stairs and Ramps
Open OBC Div. B 9.8.9.1. in the code viewer(1)Except as specified in Articles 9.8.9.4. and 9.8.9.5., stairs and ramps shall be designed for strength and rigidity under uniform loading criteria to support specified loads of
(a)1.9 kPa for stairs and ramps serving not more than one dwelling unit or a house with a secondary suite including their common spaces, and
(b)4.8 kPa for other stairs and ramps.
OBC Div. B 9.8.9.4. Wooden Stair Stringers
Open OBC Div. B 9.8.9.4. in the code viewer(1)Wooden stair stringers shall
(a)have a minimum effective depth of 90 mm, measured perpendicularly to the bottom of the stringer at the point of minimum cross-section, and an overall depth of not less than 235 mm,
(b)be supported and secured top and bottom,
(c)be not less than 25 mm actual thickness if supported along their length and 38 mm actual thickness if unsupported along their length, and
(d)except as permitted in Sentence (2), be spaced not more than 900 mm o.c. in stairs serving not more than one dwelling unit or a house with a secondary suite including their common spaces, and 600 mm o.c. in other stairs.
(2)For stairs serving not more than one dwelling unit or a house with a secondary suite including their common spaces, where risers support the front portion of the tread, the space between stringers shall be not more than 1,200 mm.
OBC Div. B 9.8.9.5. Treads
Open OBC Div. B 9.8.9.5. in the code viewer(1)Stair treads of lumber, plywood or O-2 grade OSB within dwelling units shall be not less than 25 mm actual thickness, except that, if open risers are used and the distance between stringers exceeds 750 mm, the treads shall be not less than 38 mm actual thickness.
(2)Stair treads of plywood or OSB, that are not continuously supported by the riser shall have their face grain or direction of face orientation at right angles to the stringers.
OBC Div. B 9.8.9.2. Exterior Concrete Stairs
Open OBC Div. B 9.8.9.2. in the code viewer(1)Exterior concrete stairs with more than 2 risers and 2 treads shall be
(a)supported on unit masonry or concrete walls or piers not less than 150 mm in cross-section, or
(b)cantilevered from the main foundation wall.
(2)Stairs described in Sentence (1), when cantilevered from the foundation wall, shall be constructed and installed in conformance with Subsection 9.8.10.
(3)The depth below ground level for foundations for exterior steps shall conform to the requirements in Section 9.12.
OBC Div. B 9.8.10.2. Anchorage
Open OBC Div. B 9.8.10.2. in the code viewer(1)Cantilevered concrete steps referred to in Article 9.8.10.1. shall be anchored to concrete foundation walls not less than 200 mm thick.
OBC Div. B 9.10.1.3. Items Under Part 3 Jurisdiction
Open OBC Div. B 9.10.1.3. in the code viewer(1)Tents, air-supported structures, transformer vaults, walkways, elevators and escalators shall conform to Part 3.
(2)Where rooms or spaces are intended for an assembly occupancy, such rooms or spaces shall conform to Part 3.
(3)Basements containing more than 1 storey or exceeding 600 m² in area shall conform to Part 3.
(4)Where rooms or spaces are intended for the storage, manufacture or use of hazardous or explosive material, such rooms or spaces shall conform to Part 3.
(5)Reserved.
(6)Openings through floors that are not protected by shafts or closures shall be protected in conformance with Subsection 3.2.8. (See also Sentence 9.9.4.7.(1))
(7)Chutes and shafts shall conform to Subsection 3.6.3. except where they are entirely contained within a dwelling unit.
(8)Sprinkler systems shall be designed, constructed and installed in conformance with Articles 3.2.5.12. to 3.2.5.15. and 3.2.5.17. (See Note A-9.10.1.3.(8) and (9))
(9)Standpipe and hose systems shall be designed, constructed and installed in conformance with Articles 3.2.5.8. to 3.2.5.11. and 3.2.5.17. (See Note A-9.10.1.3.(8) and (9))
(10)Fire pumps shall be installed in conformance with Articles 3.2.5.17. and 3.2.5.18.
(11)Where fuel-fired appliances are installed on a roof, such appliances shall be installed in conformance with Article 3.6.1.5.
OBC Div. B 9.10.7.1. Protection of Steel Members
Open OBC Div. B 9.10.7.1. in the code viewer(1)Except as permitted in Article 3.2.2.3., structural steel members used in construction required to have a fire-resistance rating shall be protected to provide the required fire-resistance rating.
OBC Div. B 9.10.9.10. Collapse of Combustible Construction
Open OBC Div. B 9.10.9.10. in the code viewer(1)Combustible construction that abuts on or is supported by a noncombustible fire separation shall be constructed so that its collapse under fire conditions will not cause collapse of the fire separation.
OBC Div. B 9.10.9.11. Reduction in Thickness of Fire Separation by Beams and Joists
Open OBC Div. B 9.10.9.11. in the code viewer(1)Where pockets for the support of beams or joists are formed in a masonry or concrete fire separation, the remaining total thickness of solid masonry and/or grout and/or concrete shall be not less than the required equivalent thickness shown for Type S monolithic concrete in Table 2.1.1. of MMAH Supplementary Standard SB-2, "Fire Performance Ratings," for the required fire-resistance rating.
OBC Div. B 9.10.9.18. Separation of Storage Garages
Open OBC Div. B 9.10.9.18. in the code viewer(1)Except as provided in Sentences (2) and (3), a storage garage shall be separated from other occupancies by a fire separation having not less than a 1.5 h fire-resistance rating.
(2)Except as permitted in Sentence (3), storage garages containing 5 motor vehicles or fewer shall be separated from other occupancies by a fire separation of not less than 1 h.
(3)Where a storage garage serves only the dwelling unit to which it is attached or in which it is built, it shall be considered as part of that dwelling unit and the fire separation required in Sentence (2) need not be provided between the garage and the dwelling unit.
(4)Except as provided in Sentence (5), where a storage garage is attached to or built into a building of residential occupancy
(a)an air barrier system conforming to Subsection 9.25.3. shall be installed between the garage and the remainder of the building to provide an effective barrier to gas and exhaust fumes, and
(b)every door between the garage and the remainder of the building shall conform to Article 9.10.13.15. (See Note A-9.10.9.18.(4))
(5)Where membrane materials are used to provide the required airtightness in the air barrier system, all joints shall be sealed and structurally supported.
OBC Div. B 9.10.11.3. Construction of Firewalls
Open OBC Div. B 9.10.11.3. in the code viewer(1)Where firewalls are used, the requirements in Part 3 shall apply.