Building Structural study guideStructure

Part 9 structural requirements, excavation, footings and foundations

Part 9 application items, materials, structural requirements and loads, excavation, footings and foundations, structural floor slabs and wood floors-on-ground, and reinforced concrete slabs.

chapters in this guide
9 of 14
chapters in this guide
to read
7 min
to read
code articles cited
34
code articles cited

Last updated

Values this chapter turns on

minimum Part 9 specified roof snow load
1 kPa
minimum Part 9 specified roof snow load
deflection limit for floor members
span/360
deflection limit for floor members
minimum soil bearing for Section 9.15 footings
75 kPa
minimum soil bearing for Section 9.15 footings
minimum footing depth in clay soils
1.2 m
minimum footing depth in clay soils

Part 9 handles structure through tables and simple rules, but each table only works inside stated limits. Many exam questions are really about those limits. Can the table be used, or must the item be designed to Part 4? Check that first, then read the table.

Application items

Several articles in 9.1.1 just point you elsewhere:

Item Where it goes Article
Signs Section 3.15 9.1.1.2.OBC Div. B 9.1.1.2. Signs(1) Signs shall conform to the requirements in Section 3.15.
Self-service storage buildings Section 3.10 9.1.1.3.OBC Div. B 9.1.1.3. Self-Service Storage Buildings(1) Self-service storage buildings shall conform to the requirements in Section 3.10.
Tents and air-supported structures 3.14.1 and 3.14.2 9.1.1.4.OBC Div. B 9.1.1.4. Tents and Air-Supported Structures(1) Tents shall conform to the requirements in Subsection 3.14.1. (2) Air-supported structures shall conform to the requirements in Subsection 3.14.2.
Shelf and rack storage systems Section 3.16 9.1.1.11.OBC Div. B 9.1.1.11. Shelf and Rack Storage Systems(1) Shelf and rack storage systems shall conform to the requirements of Section 3.16.

Buildings on flood plains must resist the expected vertical and horizontal hydrostatic pressures, and must keep exits usable during flooding OBC Div. B 9.1.1.8.OBC Div. B 9.1.1.8. Building in Flood Plains(1) Buildings constructed on flood plains shall, (a) be designed and constructed in accordance with good engineering practice to withstand anticipated vertical and horizontal hydrostatic pressures acting on the structure, and (b) incorporate floodproofing measures that will preserve the integrity of exits and means of…. A factory-built building is deemed to comply in two cases OBC Div. B 9.1.1.9.OBC Div. B 9.1.1.9. Site Assembled and Factory-Built Buildings(1) Except as provided in Sentence (2) and in Sentence 12.2.1.2.(2), a manufactured building is deemed to comply with this Code if it is designed and constructed in compliance with, (a) CSA Z240.2.1, "Structural requirements for manufactured homes," if the building is constructed in sections not wider than 4.88 m, or…:

  • it meets CSA Z240.2.1, for sections not wider than 4.88 m; or
  • it meets CSA A277.

Site installation and components built off the factory site still follow the Code.

Practice this topic

Structural design routes and loads (9.4)

A Part 9 structural member may follow any of three routes OBC Div. B 9.4.1.1.OBC Div. B 9.4.1.1. General(1) Subject to the application limitations defined elsewhere in this Part, structural members and their connections shall (a) conform to requirements provided elsewhere in this Part, (b) be designed according to good engineering practice such as provided in the CWC 2014, "Engineering Guide for Wood Frame…:

  1. The Part 9 prescriptive rules and tables.
  2. Good engineering practice, such as the CWC Engineering Guide for Wood Frame Construction.
  3. A Part 4 design, using Part 9 or Part 4 loads and limits.

Mixing routes has a limit. If a floor is engineered but the walls or footings below it come from the Part 9 tables, the floor live load may not exceed 2.4 kPa. Climatic and seismic values always come from SB-1.

Part 9 snow load OBC Div. B 9.4.2.2.OBC Div. B 9.4.2.2. Specified Snow Loads(1) Except as provided in Sentences (2) and (4), specified snow loads shall be not less than those calculated using the following formula: S = C_bS_s + S_r where S = specified snow load, C_b = basic snow load roof factor, which is 0.45 where the entire width of a roof does not exceed 4.3 m and 0.55 for all other…. This is simpler than Part 4:

S = C_b S_s + S_r, where C_b is 0.45 if the whole roof width is 4.3 m or less, and 0.55 for every other roof.

There is no importance factor, and S may never be less than 1 kPa. Bowstring and arch trusses spanning more than 6 m go back to 4.1.6. A roof step over 2 m below a large, flat upper roof gets a drift surcharge.

Other Part 9 load rules:

  • Decks and balconies serving a single dwelling unit are designed for the roof snow load or 1.9 kPa, whichever is greater OBC Div. B 9.4.2.3.OBC Div. B 9.4.2.3. Platforms Subject to Snow and Occupancy Loads(1) Balconies, decks and other accessible exterior platforms intended for an occupancy and subject to snow loads shall be designed to carry the specified roof snow load or 1.9 kPa, whichever is greater, where the platform, or each segregated area of the platform, serves a single dwelling unit. (See Note A-9.4.2.3.(1)).
  • Ceilings in attics of limited access are designed for a total load of 0.35 kPa OBC Div. B 9.4.2.4.OBC Div. B 9.4.2.4. Attics and Roof Spaces(1) Ceiling joists or truss bottom chords in residential attic or roof spaces having limited accessibility that precludes the storage of equipment or material shall be designed for a total specified load of not less than 0.35 kPa, where the total specified load is the sum of the specified dead load plus the specified….

Deflection limits come from Table 9.4.3.1.OBC Div. B Table 9.4.3.1. Maximum Deflections — Forming Part of Sentence 9.4.3.1.(1)Table 9.4.3.1 — Maximum Deflections — Forming Part of Sentence 9.4.3.1.(1) Structural Members | Type of Ceiling Supported | Max. Allowable Deflection as an Expressed Ratio of the Clear Span Roof rafters, roof joists and roof beams | No ceiling | 1/180 Roof rafters, roof joists and roof beams | Other than plaster or…. Dead load is ignored when checking them OBC Div. B 9.4.3.1.OBC Div. B 9.4.3.1. Deflections(1) The maximum deflection of structural members shall conform to Table 9.4.3.1. (2) Dead loads need not be considered in computing deflections referred to in Sentence (1)..

Member Limit
Roof members, no ceiling 1/180
Roof members or ceiling joists under a ceiling other than plaster or gypsum board 1/240
Roof members or ceiling joists under plaster or gypsum board 1/360
Floor members (all cases) 1/360
Deck members serving a single dwelling unit 1/240

Bearing pressures OBC Div. B Table 9.4.4.1.OBC Div. B Table 9.4.4.1. Allowable Bearing Pressure for Soil or Rock — Forming Part of Sentence 9.4.4.1.(1)Table 9.4.4.1 — Allowable Bearing Pressure for Soil or Rock — Forming Part of Sentence 9.4.4.1.(1) Type and Condition of Soil or Rock | Maximum Allowable Bearing Pressure, kPa Dense or compact sand or gravel[1] | 150 Loose sand or gravel[1] | 50 Dense or compact silt[1] | 100 Stiff clay[1] | 150 Firm clay[1] | 75 Soft…. Some values: 150 kPa for dense sand or gravel and stiff clay, 75 kPa for firm clay, 40 kPa for soft clay and 500 kPa for sound rock. If the water table under gravel, sand or silt is within one footing width of the bearing surface, use 50% of the table value OBC Div. B 9.4.4.3.OBC Div. B 9.4.4.3. High Water Table(1) Where a foundation bears on gravel, sand or silt, and the water table is within a distance below the bearing surface equal to the width of the foundation, the allowable bearing pressure shall be 50% of that determined in Article 9.4.4.1.. Section 4.2 is required for deep foundations, and for foundations on peat, fill or sensitive clay OBC Div. B 9.4.4.1.OBC Div. B 9.4.4.1. Allowable Bearing Pressures(1) Footing sizes for shallow foundations shall be (a) determined in accordance with Section 9.15., or (b) designed in accordance with Section 4.2. using, (i) the maximum allowable bearing pressures in Table 9.4.4.1., or (ii) allowable bearing pressures determined from subsurface investigation. (2) The design….

Practice this topic

Excavation (9.12)

Before you build:

  • Remove topsoil and vegetable matter under the building.
  • Keep excavations free of standing water and the bottom from freezing.
  • Carry foundations down to undisturbed soil OBC Div. B 9.12.2.1.OBC Div. B 9.12.2.1. Excavation to Undisturbed Soil(1) Excavations for foundations shall extend to undisturbed soil..

Minimum depth comes from Table 9.12.2.2.OBC Div. B Table 9.12.2.2. Minimum Depths of Foundations — Forming Part of Sentence 9.12.2.2.(1)Table 9.12.2.2 — Minimum Depths of Foundations — Forming Part of Sentence 9.12.2.2.(1) Forming Part of Sentence 9.12.2.2.(1) Type of Soil | Min Depth of Foundation Containing Heated Basement or Crawl Space[1] With Good Soil Drainage | Min Depth of Foundation Containing Heated Basement or Crawl Space[1] With Poor Soil…. Read it by three things in turn: soil type, whether the space is heated, and how well the soil drains.

Soil Heated, good drainage Not heated, poor drainage
Rock no limit no limit
Coarse grained no limit below frost penetration
Silt no limit below frost penetration
Clay or not clearly defined 1.2 m 1.2 m, and not less than frost depth

There is a trap here. A foundation insulated so it cuts heat flow to the soil under the footings counts as no heated space OBC Div. B 9.12.2.2.OBC Div. B 9.12.2.2. Minimum Depth of Foundations(1) Except as provided in Sentences (4) to (7), the minimum depth of foundations below finished ground level shall conform to Table 9.12.2.2. (2) Where a foundation is insulated in a manner that will reduce the heat flow to the soil beneath the footings, the foundation depth shall conform to that required for…. Some small structures need no minimum depth:

  • non-masonry accessory buildings of 1 storey, up to 55 m², with no more than 600 mm from ground to the underside of the joists;
  • similar small decks that do not support a roof.

Backfill within 600 mm of the foundation must be free of deleterious debris and of boulders over 250 mm in diameter OBC Div. B 9.12.3.3.OBC Div. B 9.12.3.3. Deleterious Debris and Boulders(1) Backfill that is within 600 mm of the foundation shall be free of deleterious debris and boulders larger than 250 mm diam. (See Note A-9.12.3.3.(1)) (2) Except as permitted in Sentence (3), backfill shall not contain pyritic material or material that is susceptible to ice lensing in concentrations that will damage…. Grade backfill so water drains away from the foundation after settling.

Practice this topic

Footings (9.15.3)

Section 9.15 needs stable soil with a bearing pressure of at least 75 kPa OBC Div. B 9.15.1.1.OBC Div. B 9.15.1.1. General(1) Except as provided in Articles 9.15.1.2. and 9.15.1.3., this Section applies to (a) concrete or unit masonry foundation walls and concrete footings not subject to surcharge (i) on stable soils with an allowable bearing pressure of 75 kPa or greater, and (ii) for buildings of wood-frame or masonry construction, (b)…. On fill, peat or sensitive clay, footings go to Section 4.2. The footing table also needs joist spans of 4.9 m or less and floor live loads of 2.4 kPa or less OBC Div. B 9.15.3.3.OBC Div. B 9.15.3.3. Application of Footing Width and Area Requirements(1) Except as provided in Sentence 9.15.3.4.(2), the minimum footing width or area requirements provided in Articles 9.15.3.4. to 9.15.3.7. shall apply to footings, where (a) the footings support (i) foundation walls of masonry, concrete, or flat insulating concrete form walls, (ii) above ground walls of masonry, flat….

Table 9.15.3.4.OBC Div. B Table 9.15.3.4. Minimum Footing Sizes — Forming Part of Sentence 9.15.3.4.(1)Table 9.15.3.4 — Minimum Footing Sizes — Forming Part of Sentence 9.15.3.4.(1) Forming Part of Sentence 9.15.3.4.(1) Number of Floors Supported | Minimum Width of Strip Footings Supporting Exterior Walls[2], mm | Minimum Width of Strip Footings Supporting Interior Walls[3], mm | Minimum Footing Area for Columns Spaced… gives the base sizes by number of floors supported:

Floors Exterior wall (mm) Interior wall (mm) Column at 3 m o.c. (m²)
1 250 200 0.40
2 350 350 0.75
3 450 500 1.0

Add to the exterior widths for each storey of OBC Div. B 9.15.3.5.OBC Div. B 9.15.3.5. Adjustments to Footing Widths for Exterior Walls(1) The strip footing widths for exterior walls shown in Table 9.15.3.4. shall be increased by (a) 65 mm for each storey of masonry veneer over wood-frame construction supported by the foundation wall, (b) 130 mm for each storey of masonry construction supported by the foundation wall, and (c) 150 mm for each storey…:

  • masonry veneer over wood frame: 65 mm;
  • solid masonry: 130 mm;
  • flat ICF: 150 mm.

Column areas change in proportion to the column spacing. If the water table under sand, gravel or silt is closer than one footing width below the bearing surface, double the width or area OBC Div. B 9.15.3.4.OBC Div. B 9.15.3.4. Basic Footing Widths and Areas(1) Except as provided in Sentences (2) and (3) and in Articles 9.15.3.5. to 9.15.3.7., the minimum footing width or area shall comply with Table 9.15.3.4. (2) Where the supported joist span exceeds 4.9 m in buildings with light wood-frame walls, floors and roofs, strip footing widths shall be determined according to….

Practice this topic

Foundation walls (9.15.4, 9.15.5)

For unreinforced walls, Table 9.15.4.2.-AOBC Div. B Table 9.15.4.2-A. Maximum Height of Finish Ground Above Basement Floor or Crawl Space Ground Cover, mTable 9.15.4.2.-A. — Maximum Height of Finish Ground Above Basement Floor or Crawl Space Ground Cover, m Forming Part of Sentence 9.15.4.2.(1) Solid concrete and concrete core in flat wall insulating concrete forms[3], 15 MPa min. strength Minimum Thickness of Concrete or Concrete Block, mm | Maximum Height of Finish… gives the maximum height of finished ground above the basement floor. Read it by material and strength, then by wall thickness, then by whether the wall is laterally supported at the top and how tall it is. For example, a 200 mm, 15 MPa concrete wall supported at the top and up to 2.5 m high may retain 2.15 m of earth. The same wall unsupported at the top retains only 1.2 m.

A wall counts as laterally supported at the top in four cases OBC Div. B 9.15.4.3.OBC Div. B 9.15.4.3. Foundation Walls Considered to be Laterally Supported at the Top(1) Sentences (2) to (4) pertain to lateral support for walls described in Sentence 9.15.4.2.(1). (2) Foundation walls shall be considered to be laterally supported at the top if (a) such walls support a solid masonry superstructure or flat insulating concrete form wall, (b) the floor joists are embedded in the top of…:

  • it carries solid masonry or a flat ICF wall;
  • the joists are embedded in it;
  • the floor is anchored to it with anchor bolts;
  • it stands no more than 300 mm above grade with backfill on both sides.

The part of the wall under an opening wider than 1.2 m is unsupported unless it is reinforced. So is the wall where openings total more than 25% of its length. Exterior foundation walls rise at least 150 mm above finished ground OBC Div. B 9.15.4.6.OBC Div. B 9.15.4.6. Extension Above Ground Level(1) Exterior foundation walls shall extend not less than 150 mm above finished ground level.. Walls over 25 m long need crack control joints at no more than 15 m. Hollow masonry under joists is capped, and beams on masonry sit on at least 190 mm of solid masonry OBC Div. B 9.15.5.2.OBC Div. B 9.15.5.2. Support of Beams(1) Not less than a 190 mm depth of solid masonry shall be provided beneath beams supported on masonry. (2) Where the beam referred to in Sentence (1) is supported below the top of the foundation walls, the ends of such beams shall be protected from the weather..

Practice this topic

Floors-on-ground and reinforced slabs

A floor-on-ground that carries loads from the superstructure must be designed to Part 4 OBC Div. B 9.16.1.2.OBC Div. B 9.16.1.2. Structural Floor Slabs(1) Floors-on-ground that support loads from the superstructure shall be designed in conformance with Part 4.. Where groundwater may push up on it, it must be a poured concrete slab designed for that pressure OBC Div. B 9.16.3.2.OBC Div. B 9.16.3.2. Hydrostatic Pressure(1) Where groundwater levels may cause hydrostatic pressure beneath a floor-on-ground, the floor-on-ground shall be (a) a poured concrete slab, and (b) designed to resist such pressures.. Wood floors-on-ground follow CSA S406 OBC Div. B 9.16.5.1.OBC Div. B 9.16.5.1. Wood-Frame Floors(1) Floors-on-ground constructed of wood shall conform to CSA S406, "Specification of permanent wood foundations for housing and small buildings.".

Section 9.40 covers a reinforced slab over a basement cold room. The slab may span no more than 2.5 m on its short side and must have no interior supports OBC Div. B 9.40.1.1.OBC Div. B 9.40.1.1. Application(1) This Section applies to (a) reinforced concrete slabs that are suspended over cold rooms in basements, and are supported by foundation walls along the perimeter of the slab with no additional interior supports, and (b) slabs in which the clear span between supporting walls is not more than 2.5 m along the shortest…. Vehicle-bearing slabs and anything larger go to Part 4. The prescriptive slab is OBC Div. B 9.40.1.4.OBC Div. B 9.40.1.4. Slab Construction(1) Concrete shall be cast against formwork in accordance with CSA A23.1, "Concrete materials and methods of concrete construction." (2) The slab shall be not less than 125 mm thick. (3) The slab shall be reinforced with 10 M bars spaced not more than 200 mm o.c. in each direction, with 30 mm clear cover from the…:

  • at least 125 mm thick;
  • 10M bars at no more than 200 mm each way, with 30 mm bottom cover;
  • at least 75 mm of bearing;
  • 10M bent dowels at 600 mm.

Practice this topic

Chapter review

Chapter at a glance

One line per section: the idea to carry into the exam. Then the answers that most often catch candidates out.

  • Application items

    Buildings on flood plains must resist the expected vertical and horizontal hydrostatic pressures, and must keep exits usable during flooding.

  • Structural design routes and loads (9.4)

    S = C_b S_s + S_r, where C_b is 0.45 if the whole roof width is 4.3 m or less, and 0.55 for every other roof.

  • Excavation (9.12)

    Backfill within 600 mm of the foundation must be free of deleterious debris and of boulders over 250 mm in diameter.

  • Footings (9.15.3)

    Section 9.15 needs stable soil with a bearing pressure of at least 75 kPa.

  • Foundation walls (9.15.4, 9.15.5)

    For unreinforced walls, gives the maximum height of finished ground above the basement floor.

  • Floors-on-ground and reinforced slabs

    A floor-on-ground that carries loads from the superstructure must be designed to Part 4. Where groundwater may push up on it, it must be a poured concrete slab designed for that…

Practice this chapter

Questions on Part 9 materials, structural requirements, excavation, footings and foundations, in the exam format, every answer explained and cited to its article. Sign in to start; a free account gets the free questions.

Code cited in this chapter

Based on the official 2024 Building Code Compendium on ontario.ca.

© King's Printer for Ontario, 2024. Reproduced with permission.

  • OBC Div. B 9.1.1.2. Signs

    (1)Signs shall conform to the requirements in Section 3.15.

    Open OBC Div. B 9.1.1.2. in the code viewer
  • OBC Div. B 9.1.1.3. Self-Service Storage Buildings

    (1)Self-service storage buildings shall conform to the requirements in Section 3.10.

    Open OBC Div. B 9.1.1.3. in the code viewer
  • OBC Div. B 9.1.1.4. Tents and Air-Supported Structures

    (1)Tents shall conform to the requirements in Subsection 3.14.1.

    (2)Air-supported structures shall conform to the requirements in Subsection 3.14.2.

    Open OBC Div. B 9.1.1.4. in the code viewer
  • OBC Div. B 9.1.1.11. Shelf and Rack Storage Systems

    (1)Shelf and rack storage systems shall conform to the requirements of Section 3.16.

    Open OBC Div. B 9.1.1.11. in the code viewer
  • OBC Div. B 9.1.1.8. Building in Flood Plains

    (1)Buildings constructed on flood plains shall,

    (a)be designed and constructed in accordance with good engineering practice to withstand anticipated vertical and horizontal hydrostatic pressures acting on the structure, and

    (b)incorporate floodproofing measures that will preserve the integrity of exits and means of egress during times of flooding.

    Open OBC Div. B 9.1.1.8. in the code viewer
  • OBC Div. B 9.1.1.9. Site Assembled and Factory-Built Buildings

    (1)Except as provided in Sentence (2) and in Sentence 12.2.1.2.(2), a manufactured building is deemed to comply with this Code if it is designed and constructed in compliance with,

    (a)CSA Z240.2.1, "Structural requirements for manufactured homes," if the building is constructed in sections not wider than 4.88 m, or

    (b)CSA A277, "Procedure for certification of prefabricated buildings, modules, and panels."

    (2)The requirements of this Code shall apply to,

    (a)building components designed and constructed outside the place of manufacture, and

    (b)site installation of such buildings.

    Open OBC Div. B 9.1.1.9. in the code viewer
  • OBC Div. B 9.4.1.1. General

    (1)Subject to the application limitations defined elsewhere in this Part, structural members and their connections shall

    (a)conform to requirements provided elsewhere in this Part,

    (b)be designed according to good engineering practice such as provided in the CWC 2014, "Engineering Guide for Wood Frame Construction," or

    (c)be designed according to Part 4 using the loads and deflection and vibration limits specified in,

    (i)this Part, or

    (ii)Part 4.

    (2)Where floor framing is designed in accordance with Clause (1)(b) or (c) and where supporting wall framing and fastenings, or footings, are designed according to Clause (1)(a), the maximum specified live load on the floor according to Table 4.1.5.3. shall not exceed 2.4 kPa.

    (3)Location-specific information for structural design, including snow and wind loads and seismic spectral response accelerations, shall be determined according to MMAH Supplementary Standard SB-1, "Climatic and Seismic Data." (See Note A-9.4.1.1.(3))

    Open OBC Div. B 9.4.1.1. in the code viewer
  • OBC Div. B 9.4.2.2. Specified Snow Loads

    (1)Except as provided in Sentences (2) and (4), specified snow loads shall be not less than those calculated using the following formula:

    S = C_bS_s + S_r

    where

    S = specified snow load,

    C_b = basic snow load roof factor, which is 0.45 where the entire width of a roof does not exceed 4.3 m and 0.55 for all other roofs,

    S_s = 1 -in-50 year ground snow load in kPa, determined according to MMAH Supplementary Standard SB-1, "Climatic and Seismic Data," and

    S_r = associated 1-in-50 year rain load in kPa, determined according to MMAH Supplementary Standard SB-1, "Climatic and Seismic Data."

    (2)In no case shall the specified snow load be less than 1 kPa.

    (3)Bow string, arch or semi-circular roof trusses having an unsupported span greater than 6 m shall be designed in conformance with the snow load requirements in Subsection 4.1.6.

    (4)Where the height of a roof step at the intersection of an upper level roof and a lower level roof is greater than 2 m, and the upper level roof has a slope less than 1 in 6 and an area greater than 600 m², the specified snow load on the lower level roof shall be

    (a)for distances from the roof step that are less than or equal to the drift length, x_d , calculated in accordance with Sentence (5), not less than 1.5 times the specified snow load, S, calculated using the formula in Sentence (1) with C_b equal to 0.55, and

    (b)for distances from the roof step that are greater than the drift length, x_d , calculated in accordance with Sentence (5), as specified in Sentence (1).

    (5)For the purposes of Sentence (4), the drift length, x_d , in m, shall be calculated as follows:

    x_rmd = 5(h - (0.55S_rms)/(γ))

    where

    h = height of the roof step, in m, and

    γ = specific weight of snow as specified in Clause 9.4.2.1.(1)(f).

    Open OBC Div. B 9.4.2.2. in the code viewer
Show all 34 articles
  • OBC Div. B 9.4.2.3. Platforms Subject to Snow and Occupancy Loads

    (1)Balconies, decks and other accessible exterior platforms intended for an occupancy and subject to snow loads shall be designed to carry the specified roof snow load or 1.9 kPa, whichever is greater, where the platform, or each segregated area of the platform, serves a single dwelling unit. (See Note A-9.4.2.3.(1))

    Open OBC Div. B 9.4.2.3. in the code viewer
  • OBC Div. B 9.4.2.4. Attics and Roof Spaces

    (1)Ceiling joists or truss bottom chords in residential attic or roof spaces having limited accessibility that precludes the storage of equipment or material shall be designed for a total specified load of not less than 0.35 kPa, where the total specified load is the sum of the specified dead load plus the specified live load of the ceiling. (See Note A-9.4.2.4.(1))

    Open OBC Div. B 9.4.2.4. in the code viewer
  • OBC Div. B Table 9.4.3.1. Maximum Deflections — Forming Part of Sentence 9.4.3.1.(1)

    Table 9.4.3.1 — Maximum Deflections — Forming Part of Sentence 9.4.3.1.(1) Structural Members | Type of Ceiling Supported | Max. Allowable Deflection as an Expressed Ratio of the Clear Span Roof rafters, roof joists and roof beams | No ceiling | 1/180 Roof rafters, roof joists and roof beams | Other than plaster or gypsum board | 1/240 Roof rafters, roof joists and roof beams | Plaster or gypsum board | 1/360 Ceiling joists | Other than plaster or gypsum board | 1/240 Ceiling joists | Plaster or gypsum board | 1/360 Floor beams, floor joists and floor decking | All cases | 1/360 Beams, joists and decking for balconies, decks and other accessible exterior platforms | Serving a single dwelling unit | 1/240 Beams, joists and decking for balconies, decks and other accessible exterior platforms | Other | 1/360

    Open OBC Div. B Table 9.4.3.1. in the code viewer
  • OBC Div. B 9.4.3.1. Deflections

    (1)The maximum deflection of structural members shall conform to Table 9.4.3.1.

    (2)Dead loads need not be considered in computing deflections referred to in Sentence (1).

    Open OBC Div. B 9.4.3.1. in the code viewer
  • OBC Div. B Table 9.4.4.1. Allowable Bearing Pressure for Soil or Rock — Forming Part of Sentence 9.4.4.1.(1)

    Table 9.4.4.1 — Allowable Bearing Pressure for Soil or Rock — Forming Part of Sentence 9.4.4.1.(1) Type and Condition of Soil or Rock | Maximum Allowable Bearing Pressure, kPa Dense or compact sand or gravel[1] | 150 Loose sand or gravel[1] | 50 Dense or compact silt[1] | 100 Stiff clay[1] | 150 Firm clay[1] | 75 Soft clay[1] | 40 Till | 200 Clay shale | 300 Sound rock | 500 Notes to Table 9.4.4.1.: (1) See Note A-Table 9.4.1.1.

    Open OBC Div. B Table 9.4.4.1. in the code viewer
  • OBC Div. B 9.4.4.3. High Water Table

    (1)Where a foundation bears on gravel, sand or silt, and the water table is within a distance below the bearing surface equal to the width of the foundation, the allowable bearing pressure shall be 50% of that determined in Article 9.4.4.1.

    Open OBC Div. B 9.4.4.3. in the code viewer
  • OBC Div. B 9.4.4.1. Allowable Bearing Pressures

    (1)Footing sizes for shallow foundations shall be

    (a)determined in accordance with Section 9.15., or

    (b)designed in accordance with Section 4.2. using,

    (i)the maximum allowable bearing pressures in Table 9.4.4.1., or

    (ii)allowable bearing pressures determined from subsurface investigation.

    (2)The design procedures described in Section 4.2. are permitted to be used in lieu of the design procedures in this Subsection.

    (3)The design procedures described in Section 4.2. shall be used where,

    (a)deep foundations are used,

    (b)the footing size falls outside the scope of this Section, or

    (c)the foundation is constructed on peat, filled ground or on sensitive clays as described in Article 9.15.1.1.

    Open OBC Div. B 9.4.4.1. in the code viewer
  • OBC Div. B 9.12.2.1. Excavation to Undisturbed Soil

    (1)Excavations for foundations shall extend to undisturbed soil.

    Open OBC Div. B 9.12.2.1. in the code viewer
  • OBC Div. B Table 9.12.2.2. Minimum Depths of Foundations — Forming Part of Sentence 9.12.2.2.(1)

    Table 9.12.2.2 — Minimum Depths of Foundations — Forming Part of Sentence 9.12.2.2.(1) Forming Part of Sentence 9.12.2.2.(1) Type of Soil | Min Depth of Foundation Containing Heated Basement or Crawl Space[1] With Good Soil Drainage | Min Depth of Foundation Containing Heated Basement or Crawl Space[1] With Poor Soil Drainage | Min Depth of Foundation Containing No Heated Space[2] With Good Soil Drainage | Min Depth of Foundation Containing No Heated Space[2] With Poor Soil Drainage Rock | No limit | No limit | No limit | No limit Coarse grained soils | No limit | No limit | No limit | Below the depth of frost penetration Silt | No limit | No limit | Below the depth of frost penetration | Below the depth of frost penetration Clay or soils not clearly defined[4] | 1.2 m[3] | 1.2 m | 1.2 m but not less than the depth of frost penetration[3] | 1.2 m but not less than the depth of frost penetration Notes to Table 9.12.2.2.: (1) Foundation not insulated to reduce heat loss through the footings. (2) Including foundations insulated to reduce heat loss through the footings. (3) Good soil drainage to not less than the depth of frost penetration. (4) See Note A-Table 9.12.2.2.

    Open OBC Div. B Table 9.12.2.2. in the code viewer
  • OBC Div. B 9.12.2.2. Minimum Depth of Foundations

    (1)Except as provided in Sentences (4) to (7), the minimum depth of foundations below finished ground level shall conform to Table 9.12.2.2.

    (2)Where a foundation is insulated in a manner that will reduce the heat flow to the soil beneath the footings, the foundation depth shall conform to that required for foundations containing no heated space. (See Note A-9.12.2.2.(2))

    (3)The minimum depth of foundations for exterior concrete steps with more than 2 risers shall conform to Sentences (1), (2) and (5).

    (4)Concrete steps with 1 and 2 risers are permitted to be laid on ground level.

    (5)The foundation depths required in Sentence (1) are permitted to be decreased where experience with local soil conditions shows that lesser depths are satisfactory, or where the foundation is designed for lesser depths.

    (6)The foundation depths required in Sentence (1) do not apply to foundations for

    (a)buildings

    (i)that are not of masonry or masonry veneer construction, and

    (ii)whose superstructure conforms with the requirements of the deformation resistance test in CSA Z240.2.1, "Structural requirements for manufactured homes," or

    (b)accessory buildings

    (i)that are not of masonry or masonry veneer construction,

    (ii)not more than 1 storey in building height,

    (iii)not more than 55 m² in building area, and

    (iv)where the distance from finished ground to the underside of the floor joists is not more than 600 mm.

    (7)The foundation depths required by Sentence (1) do not apply to foundations for decks and other accessible exterior platforms

    (a)of not more than 1 storey,

    (b)not more than 55 m² in area,

    (c)where the distance from finished ground to the underside of the floor joists is not more than 600 mm,

    (d)not supporting a roof, and

    (e)not attached to another structure, unless it can be demonstrated that differential movement will not adversely affect the performance of that structure.

    Open OBC Div. B 9.12.2.2. in the code viewer
  • OBC Div. B 9.12.3.3. Deleterious Debris and Boulders

    (1)Backfill that is within 600 mm of the foundation shall be free of deleterious debris and boulders larger than 250 mm diam. (See Note A-9.12.3.3.(1))

    (2)Except as permitted in Sentence (3), backfill shall not contain pyritic material or material that is susceptible to ice lensing in concentrations that will damage the building to a degree that would adversely affect its stability or the performance of assemblies separating dissimilar environments. (See Note A-9.4.4.4.(1))

    (3)Backfill with material of any concentration that is susceptible to ice lensing is permitted where foundation walls are

    (a)cast-in-place concrete,

    (b)concrete block insulated on the exterior, or

    (c)concrete block protected from the backfill by a material that serves as a slip plane.

    (See Note A-9.4.4.4.(1))

    Open OBC Div. B 9.12.3.3. in the code viewer
  • OBC Div. B 9.15.1.1. General

    (1)Except as provided in Articles 9.15.1.2. and 9.15.1.3., this Section applies to

    (a)concrete or unit masonry foundation walls and concrete footings not subject to surcharge

    (i)on stable soils with an allowable bearing pressure of 75 kPa or greater, and

    (ii)for buildings of wood-frame or masonry construction,

    (b)wood-frame foundation walls and wood or concrete footings not subject to surcharge

    (i)on stable soils with an allowable bearing pressure of 75 kPa or greater, and

    (ii)for buildings of wood-frame construction, and

    (c)flat insulating concrete form foundation walls and concrete footings not subject to surcharge (See Note A-9.15.1.1.(1) (c) and 9.20.1.1.(1)(b))

    (i)on stable soils with an allowable bearing pressure of 75 kPa or greater, and

    (ii)for buildings of light-frame or flat insulating concrete form construction that are not more than 2 storeys in building height, with a maximum floor-to-floor height of 3 m.

    (2)Foundations for applications other than as described in Sentence (1) shall be designed in accordance with Section 9.4.

    (3)Where a foundation is erected on filled ground, peat or sensitive clay, the footing sizes shall be designed in conformance with Section 4.2.

    (4)For the purpose of Sentence (3), sensitive clay means the grain size of the majority of the particles is smaller than 0.002 mm, including leda clay.

    Open OBC Div. B 9.15.1.1. in the code viewer
  • OBC Div. B 9.15.3.3. Application of Footing Width and Area Requirements

    (1)Except as provided in Sentence 9.15.3.4.(2), the minimum footing width or area requirements provided in Articles 9.15.3.4. to 9.15.3.7. shall apply to footings, where

    (a)the footings support

    (i)foundation walls of masonry, concrete, or flat insulating concrete form walls,

    (ii)above ground walls of masonry, flat insulating concrete form walls or light wood-frame construction, and

    (iii)floors and roofs of light wood-frame construction,

    (b)the span of supported joists does not exceed 4.9 m, and

    (c)the specified live load on any floor supported by the footing does not exceed 2.4 kPa. (See Table 4.1.5.3.)

    (2)Except as provided in Sentence 9.15.3.4.(2), where the span of the supported joists exceeds 4.9 m, footings shall be designed in accordance with Section 4.2.

    (3)Where the specified live load exceeds 2.4 kPa footings shall be designed in accordance with Section 4.2.

    Open OBC Div. B 9.15.3.3. in the code viewer
  • OBC Div. B Table 9.15.3.4. Minimum Footing Sizes — Forming Part of Sentence 9.15.3.4.(1)

    Table 9.15.3.4 — Minimum Footing Sizes — Forming Part of Sentence 9.15.3.4.(1) Forming Part of Sentence 9.15.3.4.(1) Number of Floors Supported | Minimum Width of Strip Footings Supporting Exterior Walls[2], mm | Minimum Width of Strip Footings Supporting Interior Walls[3], mm | Minimum Footing Area for Columns Spaced 3 m o.c.[1], m² 1 | 250 | 200 | 0.40 2 | 350 | 350 | 0.75 3 | 450 | 500 | 1.0 Notes to Table 9.15.3.4.: (1) See Sentence 9.15.3.7.(1). (2) See Sentences 9.15.3.5.(1). (3) See Sentence 9.15.3.6.(1).

    Open OBC Div. B Table 9.15.3.4. in the code viewer
  • OBC Div. B 9.15.3.5. Adjustments to Footing Widths for Exterior Walls

    (1)The strip footing widths for exterior walls shown in Table 9.15.3.4. shall be increased by

    (a)65 mm for each storey of masonry veneer over wood-frame construction supported by the foundation wall,

    (b)130 mm for each storey of masonry construction supported by the foundation wall, and

    (c)150 mm for each storey of flat insulating concrete form wall construction supported by the foundation wall.

    Open OBC Div. B 9.15.3.5. in the code viewer
  • OBC Div. B 9.15.3.4. Basic Footing Widths and Areas

    (1)Except as provided in Sentences (2) and (3) and in Articles 9.15.3.5. to 9.15.3.7., the minimum footing width or area shall comply with Table 9.15.3.4.

    (2)Where the supported joist span exceeds 4.9 m in buildings with light wood-frame walls, floors and roofs, strip footing widths shall be determined according to

    (a)Section 4.2., or

    (b)the following formula:

    W = w × [∑sjs/(storeys × 4.9)]

    where

    W = minimum footing width,

    w = minimum width of footings supporting joists not exceeding 4.9 m, as defined by Table 9.15.3.4.,

    ∑ sjs = sum of the supported joist spans on each storey bearing on an exterior wall whose load is transferred to the footing, or sum of half of the supported joist spans on each storey bearing on both sides of an interior wall whose load is transferred to the footing, and

    storeys = number of storeys supported by the footing. (See Note A-9.15.3.4.(2))

    (3)Where a foundation rests on gravel, sand or silt in which the water table level is less than the width of the footings below the bearing surface,

    (a)the footing width for walls shall be not less than twice the width required by Sentences (1) and (2), and Articles 9.15.3.5. and 9.15.3.6., and

    (b)the footing area for columns shall be not less than twice the area required by Sentences (1) and (2) and Article 9.15.3.7.

    Open OBC Div. B 9.15.3.4. in the code viewer
  • OBC Div. B 9.15.3.8. Footing Thickness

    (1)Footing thickness shall be not less than the greater of

    (a)100 mm, or

    (b)the width of the projection of the footing beyond the supported element.

    Open OBC Div. B 9.15.3.8. in the code viewer
  • OBC Div. B Table 9.15.4.2-A. Maximum Height of Finish Ground Above Basement Floor or Crawl Space Ground Cover, m

    Table 9.15.4.2.-A. — Maximum Height of Finish Ground Above Basement Floor or Crawl Space Ground Cover, m Forming Part of Sentence 9.15.4.2.(1) Solid concrete and concrete core in flat wall insulating concrete forms[3], 15 MPa min. strength Minimum Thickness of Concrete or Concrete Block, mm | Maximum Height of Finish Ground Above Basement Floor or Crawl Space Ground Cover, m (Height of Foundation Wall Laterally Unsupported at the Top[1][2] ≤ 3.0 m) | Maximum Height of Finish Ground Above Basement Floor or Crawl Space Ground Cover, m (Height of Foundation Wall Laterally Supported at the Top[1][2] ≤ 2.5 m) | Maximum Height of Finish Ground Above Basement Floor or Crawl Space Ground Cover, m (Height of Foundation Wall Laterally Supported at the Top[1][2] > 2.5 m and ≤ 2.75 m) | Maximum Height of Finish Ground Above Basement Floor or Crawl Space Ground Cover, m (Height of Foundation Wall Laterally Supported at the Top[1][2] > 2.75 m and ≤ 3.0 m) 150 | 0.8 | 1.5 | 1.5 | 1.4 200 | 1.2 | 2.15 | 2.15 | 2.1 250 | 1.4 | 2.3 | 2.6 | 2.5 300 | 1.5 | 2.3 | 2.6 | 2.85 Solid concrete and concrete core in flat wall insulating concrete forms[3], 20 MPa min. strength Table 9.15.4.2.-A. — Maximum Height of Finish Ground Above Basement Floor or Crawl Space Ground Cover, m Minimum Thickness of Concrete or Concrete Block, mm | Maximum Height of Finish Ground Above Basement Floor or Crawl Space Ground Cover, m (Height of Foundation Wall Laterally Unsupported at the Top[1][2] ≤ 3.0 m) | Maximum Height of Finish Ground Above Basement Floor or Crawl Space Ground Cover, m (Height of Foundation Wall Laterally Supported at the Top[1][2] ≤ 2.5 m) | Maximum Height of Finish Ground Above Basement Floor or Crawl Space Ground Cover, m (Height of Foundation Wall Laterally Supported at the Top[1][2] > 2.5 m and ≤ 2.75 m) | Maximum Height of Finish Ground Above Basement Floor or Crawl Space Ground Cover, m (Height of Foundation Wall Laterally Supported at the Top[1][2] > 2.75 m and ≤ 3.0 m) 150 | 0.8 | 1.8 | 1.6 | 1.6 200 | 1.2 | 2.3 | 2.3 | 2.2 250 | 1.4 | 2.3 | 2.6 | 2.85 300 | 1.5 | 2.3 | 2.6 | 2.85 Unreinforced concrete block Table 9.15.4.2.-A. — Maximum Height of Finish Ground Above Basement Floor or Crawl Space Ground Cover, m Minimum Thickness of Concrete or Concrete Block, mm | Maximum Height of Finish Ground Above Basement Floor or Crawl Space Ground Cover, m (Height of Foundation Wall Laterally Unsupported at the Top[1][2] ≤ 3.0 m) | Maximum Height of Finish Ground Above Basement Floor or Crawl Space Ground Cover, m (Height of Foundation Wall Laterally Supported at the Top[1][2] ≤ 2.5 m) | Maximum Height of Finish Ground Above Basement Floor or Crawl Space Ground Cover, m (Height of Foundation Wall Laterally Supported at the Top[1][2] > 2.5 m and ≤ 2.75 m) | Maximum Height of Finish Ground Above Basement Floor or Crawl Space Ground Cover, m (Height of Foundation Wall Laterally Supported at the Top[1][2] > 2.75 m and ≤ 3.0 m) 140 | 0.6 | 0.8 | N/A | N/A 190 | 0.9 | 1.2 | [4] | [4] 240 | 1.2 | 1.8 | [4] | [4] 290 | 1.4 | 2.2 | N/A | N/A Notes to Table 9.15.4.2.-A: (1) See Article 9.15.4.3. (2) See Article 9.15.4.6. (3) See Note A-Table 9.15.4.2.-A. (4) See Table 9.15.4.2.-B.

    Open OBC Div. B Table 9.15.4.2-A. in the code viewer
  • OBC Div. B 9.15.4.3. Foundation Walls Considered to be Laterally Supported at the Top

    (1)Sentences (2) to (4) pertain to lateral support for walls described in Sentence 9.15.4.2.(1).

    (2)Foundation walls shall be considered to be laterally supported at the top if

    (a)such walls support a solid masonry superstructure or flat insulating concrete form wall,

    (b)the floor joists are embedded in the top of the foundation walls,

    (c)the floor system is anchored to the top of the foundation walls with anchor bolts, in which case the joists may run either parallel or perpendicular to the foundation walls, or

    (d)they extend from the footing to no more than 300 mm above the finished ground level and are backfilled on both sides such that the difference in elevation between the finished ground levels on either side of the wall is no more than 150 mm.

    (3)Unless the wall around an opening is reinforced to withstand earth pressure, the portion of the foundation wall beneath an opening shall be considered laterally unsupported if

    (a)the opening is more than 1.2 m wide, or

    (b)the total width of the openings in the foundation wall constitutes more than 25% of the length of the wall.

    (4)For the purposes of Sentence (3), the combined width of the openings shall be considered as a single opening if the average width is greater than the width of solid wall between them.

    (5)Flat insulating concrete form foundation walls shall be considered to be laterally supported at the top if the floor joists are installed according to Article 9.20.17.5.

    Open OBC Div. B 9.15.4.3. in the code viewer
  • OBC Div. B 9.15.4.6. Extension Above Ground Level

    (1)Exterior foundation walls shall extend not less than 150 mm above finished ground level.

    Open OBC Div. B 9.15.4.6. in the code viewer
  • OBC Div. B 9.15.5.2. Support of Beams

    (1)Not less than a 190 mm depth of solid masonry shall be provided beneath beams supported on masonry.

    (2)Where the beam referred to in Sentence (1) is supported below the top of the foundation walls, the ends of such beams shall be protected from the weather.

    Open OBC Div. B 9.15.5.2. in the code viewer
  • OBC Div. B 9.16.1.2. Structural Floor Slabs

    (1)Floors-on-ground that support loads from the superstructure shall be designed in conformance with Part 4.

    Open OBC Div. B 9.16.1.2. in the code viewer
  • OBC Div. B 9.16.3.2. Hydrostatic Pressure

    (1)Where groundwater levels may cause hydrostatic pressure beneath a floor-on-ground, the floor-on-ground shall be

    (a)a poured concrete slab, and

    (b)designed to resist such pressures.

    Open OBC Div. B 9.16.3.2. in the code viewer
  • OBC Div. B 9.16.5.1. Wood-Frame Floors

    (1)Floors-on-ground constructed of wood shall conform to CSA S406, "Specification of permanent wood foundations for housing and small buildings."

    Open OBC Div. B 9.16.5.1. in the code viewer
  • OBC Div. B 9.40.1.1. Application

    (1)This Section applies to

    (a)reinforced concrete slabs that are suspended over cold rooms in basements, and are supported by foundation walls along the perimeter of the slab with no additional interior supports, and

    (b)slabs in which the clear span between supporting walls is not more than 2.5 m along the shortest dimension of the slab.

    (2)Slabs for conditions other than described in Sentence (1) shall be designed in accordance with Part 4.

    (3)This Section does not apply to reinforced concrete slabs intended to support motor vehicles.

    Open OBC Div. B 9.40.1.1. in the code viewer
  • OBC Div. B 9.40.1.4. Slab Construction

    (1)Concrete shall be cast against formwork in accordance with CSA A23.1, "Concrete materials and methods of concrete construction."

    (2)The slab shall be not less than 125 mm thick.

    (3)The slab shall be reinforced with 10 M bars spaced not more than 200 mm o.c. in each direction, with 30 mm clear cover from the bottom of the slab to the first layer of bars, and the second layer of bars laid directly on top of the lower layer in the opposite direction.

    (4)The slab shall bear not less than 75 mm on the supporting foundation walls and be anchored to the walls with 600mm × 600mm 10 M bent dowels spaced at not more than 600 mm o.c.

    (5)Exposed slabs shall be sloped to effectively shed water away from the exterior wall.

    Open OBC Div. B 9.40.1.4. in the code viewer