Values this chapter turns on
- load a grab bar must resist in any direction
- 1.3 kN
- load a grab bar must resist in any direction
- detached garage size allowed on mud sills or slab
- 55 m²
- detached garage size allowed on mud sills or slab
- log settlement gap per 300 mm of opening height
- 13 mm
- log settlement gap per 300 mm of opening height
- minimum size of a carport column pier
- 190 x 190 mm
- minimum size of a carport column pier
This chapter covers the structural pieces in the later Sections of Part 9. Each is short, so questions tend to be direct lookups. A few involve simple arithmetic, such as a pier size, a log settlement gap or a column height.
Roofing and cladding
Roofing. A solar collector system may sit above roofing that meets 9.26.2.1 OBC Div. B 9.26.1.4.OBC Div. B 9.26.1.4. Solar Collector Systems(1) A solar collector system is permitted to be installed above roofing materials conforming to Sentence 9.26.2.1.(1).. Two roofing types can span between spaced supports instead of sitting on a deck. Each must then be designed for roof loads:
- sheet metal roofing, for the specified live loads for roofs OBC Div. B 9.26.13.2.OBC Div. B 9.26.13.2. Support(1) Where sheet metal roofing is not supported by roof decking but spans between spaced supports, the panels shall be designed to support the specified live loads for roofs.;
- glass reinforced polyester panels, for the specified roof loads OBC Div. B 9.26.14.1.OBC Div. B 9.26.14.1. Support(1) Where glass reinforced polyester roofing panels are not supported by roof decking but span between spaced supports, the panels shall be designed to support the specified roof loads..
Concrete roof tiles are installed to the CAN/CSA-A220 Series OBC Div. B 9.26.17.1.OBC Div. B 9.26.17.1. Installation(1) Concrete roof tiles shall be installed according to CAN/CSA-A220 Series, "Concrete Roof Tiles." (See Note A-9.26.17.1.(1)).
Cladding. Cladding is normally fastened to framing, furring or blocking. It may be fastened to the sheathing alone only when the sheathing is thick enough OBC Div. B 9.27.5.1.OBC Div. B 9.27.5.1. Attachment(1) Except as permitted by Sentences (2) to (5), cladding shall be fastened to the framing members or furring members, or to blocking between the framing members. (2) Vertical lumber, stucco lath or reinforcing, vertically applied vinyl siding, vertically applied insulated vinyl siding, and polypropylene siding are…:
| Cladding fastened to sheathing only | Minimum sheathing |
|---|---|
| Vertical lumber, stucco lath, vertical vinyl or insulated vinyl, polypropylene | 14.3 mm lumber, or 12.5 mm plywood, OSB or waferboard |
| Vertical metal siding, wood shingles and shakes | 14.3 mm lumber, or 7.5 mm plywood, OSB or waferboard |
A common trap is to apply the 7.5 mm value to vinyl siding.
Equipment loads and seismic restraint
Where grab bars are provided, they must resist 1.3 kN applied vertically or horizontally OBC Div. B 9.31.2.3.OBC Div. B 9.31.2.3. Grab Bars(1) When provided, grab bars shall be capable of resisting a load of not less than 1.3 kN applied vertically or horizontally..
In locations where S_a(0.2) from SB-1 Table 3 is greater than 0.55, two kinds of equipment must be secured to the structure:
- service water heaters, against overturning OBC Div. B 9.31.6.2.OBC Div. B 9.31.6.2. Equipment and Installation(1) Every service water heater and its installation shall conform to Part 7. (2) Reserved (3) Where the building is in a location where the spectral response acceleration, S_a(0.2) , is greater than 0.55, service water heaters shall be secured to the structure to resist overturning. (See Note A-9.31.6.2.(3));
- heating and air-conditioning equipment with fuel or power connections, against overturning and displacement OBC Div. B 9.33.4.7.OBC Div. B 9.33.4.7. Structural Movement(1) Mechanical systems and equipment shall be designed and installed to accommodate the maximum amount of structural movement provided for in the construction of the building. (2) Where the building is in a location where the spectral acceleration, S_a(0.2) , is greater than 0.55, heating and air-conditioning….
Mechanical systems must also accommodate the structural movement the building is designed for.
Garages and carports (9.35)
Section 9.35 covers garages and carports serving no more than one dwelling unit OBC Div. B 9.35.1.1.OBC Div. B 9.35.1.1. Application(1) This Section applies to garages and carports serving not more than one dwelling unit.. Foundations follow 9.12 and 9.15, including under the garage door OBC Div. B 9.35.3.1.OBC Div. B 9.35.3.1. Foundation Required(1) Except as permitted in this Subsection, foundations conforming to Sections 9.12. and 9.15. shall be provided for the support of carport and garage super-structures, including that portion beneath garage doors. (2) Detached garages of less than 55 m² floor area and not more than 1 storey in height that are not of….
A detached garage meeting all three of these limits may instead sit on wood mud sills, or on a concrete slab at least 100 mm thick:
- under 55 m²;
- one storey;
- no masonry or masonry veneer.
The same garages are also exempt from foundation drainage where the ground slopes away from them.
Other garage and carport rules:
- An attached garage in shifting clay should have foundations about as deep as the house. A slab-on-ground needs a construction joint where it meets the house slab OBC Div. B 9.35.3.2.OBC Div. B 9.35.3.2. Protection from Damage Due to Soil Movement(1) In clay-type soils subject to significant movement with a change in soil moisture content, the foundation depth of carports or garages connected to a dwelling unit directly or by a breezeway shall be approximately the same depth as the foundation of the main building. (2) Where slab-on-ground construction is used….
- Carport column piers rise at least 150 mm above ground. They extend at least 25 mm past the column base on each side, and are never smaller than 190 x 190 mm OBC Div. B 9.35.3.4.OBC Div. B 9.35.3.4. Column Piers(1) Piers for the support of carport columns shall extend not less than 150 mm above ground level. (2) Piers referred to in Sentence (1) shall project not less than 25 mm beyond the base of the column but in no case be less than 190 mm by 190 mm in size..
- Garage and carport columns follow 9.17, except that 89 x 89 mm wood columns are allowed OBC Div. B 9.35.4.2.OBC Div. B 9.35.4.2. Columns(1) Columns for garages and carports shall conform to Section 9.17., except that 89 mm by 89 mm wood columns may be used..
- Walls and columns are anchored against wind uplift under 9.23.6. A garage sitting on the ground surface needs ground anchors OBC Div. B 9.35.4.3.OBC Div. B 9.35.4.3. Anchorage(1) Garage or carport walls and columns shall be anchored to the foundation to resist wind uplift in conformance with Subsection 9.23.6., except that where a garage is supported on the surface of the ground, ground anchors shall be provided to resist wind uplift..
Seasonal recreational buildings and logs (9.37, 9.38)
Cottages must meet Part 9, with some exemptions OBC Div. B 9.37.1.1.OBC Div. B 9.37.1.1. Application(1) This Section applies to buildings of residential occupancy used or intended to be used as seasonal recreational buildings. (2) The buildings described in Sentence (1) shall comply with all the requirements of this Part, except where they are specifically exempted in this Section.. Continuous perimeter foundation walls are not required. Unit masonry columns are limited in height by the least dimension of the column OBC Div. B 9.37.2.2.OBC Div. B 9.37.2.2. Foundations(1) Continuous perimeter foundation walls are not required, but when they are provided, they shall comply with the requirements of this Part. (2) Where unit masonry columns are used, the height of such columns shall not exceed, (a) in the case of hollow masonry units, 4 times the least dimension of the units, (b) in…:
| Column | Maximum height |
|---|---|
| Hollow units | 4 x least dimension |
| Solid units, or hollow units filled with concrete | 10 x least dimension |
| Reinforced with four 13 mm bars and filled | 18 x least dimension |
Taller columns are designed to Part 4. Below-grade foundations and floors-on-ground still need dampproofing under Section 9.13 OBC Div. B 9.37.2.3.OBC Div. B 9.37.2.3. Waterproofing and Dampproofing(1) Where foundations below ground level and concrete floors on ground are used, they shall comply with Section 9.13..
Logs may be used structurally if analysis, tests or experience show they are adequate OBC Div. B 9.38.1.1.OBC Div. B 9.38.1.1. Material Requirements(1) Logs that are sound and free of fractures may be used for foundations, beams, posts and similar members, provided it can be shown by a structural analysis or tests or previous experience that the strength of the member is adequate for its intended purposes.. Logs touching masonry or concrete at or below grade are preservative-treated. Each horizontal log is fastened to its bearer in at least three places, never more than 1,800 mm apart OBC Div. B 9.38.2.3.OBC Div. B 9.38.2.3. Joining Logs(1) Each log in a horizontal position shall be scribed as close as possible to its bearer and fastened to the bearer in at least three places throughout its length, by dowels, continuous machined joints, vertical framing members or interlocking intersections or any combination of these, but in no case shall the…. Horizontal logs shrink, so every opening needs a settlement clearance between the rough buck header and the lintel log. It must be at least 13 mm for each 300 mm of opening height OBC Div. B 9.38.3.2.OBC Div. B 9.38.3.2. Clearance(1) At every opening in a wall made of logs in a horizontal position where shrinkage can occur there shall be a clearance between the rough buck header and the lintel log of not less than 13 mm in width for each 300 mm of height to allow for settlement..
Park model trailers and change of use
Under Section 9.39 OBC Div. B 9.39.2.1.OBC Div. B 9.39.2.1. General(1) Except as provided in Subsection 9.39.3., a manufactured building used or intended to be used as a seasonal recreational building of residential occupancy is deemed to comply with this Code if it is designed and constructed in conformance with CAN/CSA-Z241 Series, "Park model trailers.", a park model trailer is deemed to comply with the Code if two conditions hold:
- it is built to CAN/CSA-Z241;
- it is used as a seasonal recreational building.
Components built off the factory site must still meet the Code. The trailer is supported and anchored to the manufacturer's installation instructions OBC Div. B 9.39.3.3.OBC Div. B 9.39.3.3. Foundations and Anchorage(1) Buildings described in Article 9.39.1.1. shall be supported and anchored in conformance with the manufacturer's installation instructions..
Change of use. Where a change of use occurs, the part of the building affected must be brought up to the listed Part 9 requirements for the new major occupancy OBC Div. B 9.41.2.1.OBC Div. B 9.41.2.1. Change of Use and Compensating Construction(1) Where proposed construction will result in a change of use described in Clauses 9.40.1.1.(1)(a) to (f), additional construction shall be required in order that the building or part of a building subject to the change of use conforms to the requirements of Subsections 9.5.1. and 9.5.3. to 9.5.10., Section 9.6.…. The listed requirements include doors, glass, guards, egress windows, flame spread, plumbing facilities, ventilation and electrical.
The key performance rule is that the building's performance level after construction may not be lower than before. It is evaluated under Part 11. Where it would drop, compensating construction is required under 11.4.3 OBC Div. B 9.41.2.2.OBC Div. B 9.41.2.2. Performance Level Evaluation and Compensating Construction(1) The performance level of a building after construction shall not be less than the performance level of the building prior to construction. (2) For the purposes of Sentence (1), reduction of performance level shall be determined in accordance with Articles 11.4.2.1., 11.4.2.3. and 11.4.2.5. (3) Where the proposed….
Chapter review
Chapter at a glance
One line per section: the idea to carry into the exam. Then the answers that most often catch candidates out.
- Roofing and cladding
Concrete roof tiles are installed to the CAN/CSA-A220 Series.
- Equipment loads and seismic restraint
Where grab bars are provided, they must resist 1.3 kN applied vertically or horizontally.
- Garages and carports (9.35)
Section 9.35 covers garages and carports serving no more than one dwelling unit.
- Seasonal recreational buildings and logs (9.37, 9.38)
Cottages must meet Part 9, with some exemptions.
- Park model trailers and change of use
Components built off the factory site must still meet the Code.
Practice this chapter
Questions on Other Part 9 structural items, in the exam format, every answer explained and cited to its article. Sign in to start; a free account gets the free questions.
Code cited in this chapter
Based on the official 2024 Building Code Compendium on ontario.ca.
© King's Printer for Ontario, 2024. Reproduced with permission.
OBC Div. B 9.26.1.4. Solar Collector Systems
Open OBC Div. B 9.26.1.4. in the code viewer(1)A solar collector system is permitted to be installed above roofing materials conforming to Sentence 9.26.2.1.(1).
OBC Div. B 9.26.13.2. Support
Open OBC Div. B 9.26.13.2. in the code viewer(1)Where sheet metal roofing is not supported by roof decking but spans between spaced supports, the panels shall be designed to support the specified live loads for roofs.
OBC Div. B 9.26.14.1. Support
Open OBC Div. B 9.26.14.1. in the code viewer(1)Where glass reinforced polyester roofing panels are not supported by roof decking but span between spaced supports, the panels shall be designed to support the specified roof loads.
OBC Div. B 9.26.17.1. Installation
Open OBC Div. B 9.26.17.1. in the code viewer(1)Concrete roof tiles shall be installed according to CAN/CSA-A220 Series, "Concrete Roof Tiles." (See Note A-9.26.17.1.(1))
OBC Div. B 9.27.5.1. Attachment
Open OBC Div. B 9.27.5.1. in the code viewer(1)Except as permitted by Sentences (2) to (5), cladding shall be fastened to the framing members or furring members, or to blocking between the framing members.
(2)Vertical lumber, stucco lath or reinforcing, vertically applied vinyl siding, vertically applied insulated vinyl siding, and polypropylene siding are permitted to be attached to sheathing only where the sheathing consists of not less than
(a)14.3 mm lumber,
(b)12.5 mm plywood, or
(c)12.5 mm OSB or waferboard.
(3)Vertically applied metal siding and wood shingles and shakes are permitted to be attached to the sheathing only where the sheathing consists of not less than
(a)14.3 mm lumber,
(b)7.5 mm plywood, or
(c)7.5 mm OSB or waferboard.
(4)Where wood shingles or shakes are applied to sheathing which is not suitable for attaching the shingles or shakes, the shingles or shakes are permitted to be attached to a wood lath not less than 38 mm by 9.5 mm thick securely nailed to the framing and applied as described in Article 9.27.7.5.
(5)Cladding, trim and furring members are permitted to be attached to the web fastening strips of flat wall insulating concrete form units using screws in accordance with Sentence 9.27.5.4.(2)
OBC Div. B 9.31.2.3. Grab Bars
Open OBC Div. B 9.31.2.3. in the code viewer(1)When provided, grab bars shall be capable of resisting a load of not less than 1.3 kN applied vertically or horizontally.
OBC Div. B 9.31.6.2. Equipment and Installation
Open OBC Div. B 9.31.6.2. in the code viewer(1)Every service water heater and its installation shall conform to Part 7.
(2)Reserved
(3)Where the building is in a location where the spectral response acceleration, S_a(0.2) , is greater than 0.55, service water heaters shall be secured to the structure to resist overturning. (See Note A-9.31.6.2.(3))
OBC Div. B 9.33.4.7. Structural Movement
Open OBC Div. B 9.33.4.7. in the code viewer(1)Mechanical systems and equipment shall be designed and installed to accommodate the maximum amount of structural movement provided for in the construction of the building.
(2)Where the building is in a location where the spectral acceleration, S_a(0.2) , is greater than 0.55, heating and air-conditioning equipment with fuel or power connections shall be secured to the structure to resist overturning and displacement. (See Note A-9.31.6.2.(3))
Show all 25 articles
OBC SB-1 Table 3: Seismic Design Data for Selected Locations in Ontario for Part 9 Design
Open OBC SB-1 in the code viewerTable 3: Seismic Design Data for Selected Locations in Ontario for Part 9 Design
Location | S_a(0.2) for Seismic Design in Part 9
Ailsa Craig | 0.095
Ajax | 0.210
Alexandria | 0.589
Alliston | 0.111
Almonte | 0.337
Armstrong | 0.064
Arnprior | 0.371
Atikokan | 0.069
Attawapiskat | 0.074
Aurora | 0.138
Bancroft | 0.151
Barrie | 0.108
Barriefield | 0.162
Beaverton | 0.117
Belleville | 0.162
Belmont | 0.116
Big Trout Lake (Kitchenuhmaykoosib) | 0.054
CFB Borden | 0.107
Bracebridge | 0.116
Bradford | 0.123
Brampton | 0.168
Brantford | 0.155
Brighton | 0.173
Brockville | 0.259
Burk's Falls | 0.143
Burlington | 0.266
Caledon | 0.168
Cambridge | 0.141
Campbellford | 0.144
Cannington | 0.122
Carleton Place | 0.302
Cavan | 0.140
Centralia | 0.092
Chapleau | 0.071
Chatham | 0.112
Chesley | 0.083
Clinton | 0.084
Coboconk | 0.120
Cobourg | 0.179
Cochrane | 0.222
Colborne | 0.176
Collingwood | 0.096
Cornwall | 0.587
Corunna | 0.087
Deep River | 0.389
Deseronto | 0.158
Dorchester | 0.112
Dorion | 0.059
Dresden | 0.104
Dryden | 0.072
Dundalk | 0.097
Dunnville | 0.232
Durham | 0.088
Dutton | 0.116
Earlton | 0.182
Edison | 0.070
Elliot Lake | 0.074
Elmvale | 0.101
Embro | 0.111
Englehart | 0.175
Espanola | 0.086
Exeter | 0.090
Fenelon Falls | 0.121
Fergus | 0.115
Forest | 0.087
Fort Erie | 0.312
Fort Erie (Ridgeway) | 0.307
Fort Frances | 0.064
Gananoque | 0.180
Geraldton | 0.057
Glencoe | 0.107
Goderich | 0.079
Gore Bay | 0.071
Graham | 0.071
Gravenhurst (Muskoka Airport) | 0.112
Grimsby | 0.301
Guelph | 0.133
Guthrie | 0.109
Haileybury | 0.219
Haldimand (Caledonia) | 0.215
Haldimand (Hagersville) | 0.172
Haliburton | 0.133
Halton Hills (Georgetown) | 0.155
Hamilton | 0.260
Hanover | 0.085
Hastings | 0.141
Hawkesbury | 0.506
Hearst | 0.073
Honey Harbour | 0.103
Hornepayne | 0.063
Huntsville | 0.129
Ingersoll | 0.116
Iroquois Falls | 0.196
Jellicoe | 0.057
Kapuskasing | 0.112
Kemptville | 0.429
Kenora | 0.064
Killaloe | 0.264
Kincardine | 0.076
Kingston | 0.161
Kinmount | 0.123
Kirkland Lake | 0.159
Kitchener | 0.122
Lakefield | 0.130
Lansdowne House | 0.056
Leamington | 0.114
Lindsay | 0.126
Lion's Head | 0.080
Listowel | 0.093
London | 0.108
Lucan | 0.097
Maitland | 0.282
Markdale | 0.089
Markham | 0.182
Martin | 0.072
Matheson | 0.160
Mattawa | 0.446
Midland | 0.101
Milton | 0.191
Milverton | 0.098
Minden | 0.124
Mississauga | 0.219
Mississauga (Lester B. Pearson International Airport) | 0.193
Mississauga (Port Credit) | 0.247
Mitchell | 0.093
Moosonee | 0.081
Morrisburg | 0.558
Mount Forest | 0.093
Nakina | 0.057
Nanticoke (Jarvis) | 0.156
Nanticoke (Port Dover) | 0.144
Napanee | 0.156
New Liskeard | 0.209
Newcastle | 0.186
Newcastle (Bowmanville) | 0.188
Newmarket | 0.132
Niagara Falls | 0.321
North Bay | 0.247
Norwood | 0.136
Oakville | 0.260
Orangeville | 0.115
Orillia | 0.109
Oshawa | 0.192
Ottawa (Metropolitan) | N/A
Ottawa (City Hall) | 0.439
Ottawa (Barrhaven) | 0.427
Ottawa (Kanata) | 0.401
Ottawa (MacDonald-Cartier Int'l Airport) | 0.446
Ottawa (Orleans) | 0.474
Owen Sound | 0.083
Pagwa River | 0.060
Paris | 0.141
Parkhill | 0.092
Parry Sound | 0.110
Pelham (Fonthill) | 0.311
Pembroke | 0.379
Penetanguishene | 0.101
Perth | 0.225
Petawawa | 0.379
Peterborough | 0.135
Petrolia | 0.092
Pickering (Zones 1 to 4) | 0.219
Picton | 0.159
Plattsville | 0.119
Point Alexander | 0.391
Port Burwell | 0.132
Port Colborne | 0.298
Port Elgin | 0.077
Port Hope | 0.181
Port Perry | 0.144
Port Stanley | 0.123
Prescott | 0.350
Princeton | 0.129
Raith | 0.067
Rayside-Balfour (Chelmsford) | 0.104
Red Lake | 0.068
Renfrew | 0.352
Richmond Hill | 0.163
Rockland | 0.510
Sarnia | 0.085
Sault Ste. Marie | 0.062
Schreiber | 0.057
Seaforth | 0.087
Shelburne | 0.104
Simcoe | 0.141
Sioux Lookout | 0.073
Smiths Falls | 0.256
Smithville | 0.296
Smooth Rock Falls | 0.200
South River | 0.164
Southampton | 0.077
St. Catharines | 0.319
St. Mary's | 0.101
St. Thomas | 0.117
Stirling | 0.149
Stratford | 0.103
Strathroy | 0.100
Sturgeon Falls | 0.183
Sudbury | 0.110
Sundridge | 0.157
Tavistock | 0.108
Temagami | 0.239
Thamesford | 0.111
Thedford | 0.089
Thunder Bay | 0.061
Tillsonburg | 0.126
Timmins | 0.125
Timmins (Porcupine) | 0.140
Toronto Metropolitan Region | N/A
Etobicoke | 0.193
North York | 0.195
Scarborough | 0.219
Toronto (City Hall) | 0.249
Trenton | 0.167
Trout Creek | 0.186
Uxbridge | 0.139
Vaughan (Woodbridge) | 0.167
Vittoria | 0.139
Walkerton | 0.083
Wallaceburg | 0.098
Waterloo | 0.118
Watford | 0.095
Wawa | 0.062
Welland | 0.308
West Lorne | 0.118
Whitby | 0.203
Whitby (Brooklin) | 0.176
White River | 0.060
Wiarton | 0.080
Windsor | 0.096
Wingham | 0.083
Woodstock | 0.118
Wyoming | 0.090
OBC Div. B 9.35.1.1. Application
Open OBC Div. B 9.35.1.1. in the code viewer(1)This Section applies to garages and carports serving not more than one dwelling unit.
OBC Div. B 9.35.3.1. Foundation Required
Open OBC Div. B 9.35.3.1. in the code viewer(1)Except as permitted in this Subsection, foundations conforming to Sections 9.12. and 9.15. shall be provided for the support of carport and garage super-structures, including that portion beneath garage doors.
(2)Detached garages of less than 55 m² floor area and not more than 1 storey in height that are not of masonry or masonry veneer construction are permitted to be supported on
(a)wood mud sills, or
(b)a concrete floor slab having a minimum thickness of not less than 100 mm.
OBC Div. B 9.35.3.2. Protection from Damage Due to Soil Movement
Open OBC Div. B 9.35.3.2. in the code viewer(1)In clay-type soils subject to significant movement with a change in soil moisture content, the foundation depth of carports or garages connected to a dwelling unit directly or by a breezeway shall be approximately the same depth as the foundation of the main building.
(2)Where slab-on-ground construction is used, a construction joint shall be provided between the main building slab and a slab serving an attached garage, breezeway or carport.
(3)Except as provided in Section 9.12., foundations for attached unheated garages or carports shall be below frost level.
OBC Div. B 9.35.3.4. Column Piers
Open OBC Div. B 9.35.3.4. in the code viewer(1)Piers for the support of carport columns shall extend not less than 150 mm above ground level.
(2)Piers referred to in Sentence (1) shall project not less than 25 mm beyond the base of the column but in no case be less than 190 mm by 190 mm in size.
OBC Div. B 9.35.4.2. Columns
Open OBC Div. B 9.35.4.2. in the code viewer(1)Columns for garages and carports shall conform to Section 9.17., except that 89 mm by 89 mm wood columns may be used.
OBC Div. B 9.35.4.3. Anchorage
Open OBC Div. B 9.35.4.3. in the code viewer(1)Garage or carport walls and columns shall be anchored to the foundation to resist wind uplift in conformance with Subsection 9.23.6., except that where a garage is supported on the surface of the ground, ground anchors shall be provided to resist wind uplift.
OBC Div. B 9.37.1.1. Application
Open OBC Div. B 9.37.1.1. in the code viewer(1)This Section applies to buildings of residential occupancy used or intended to be used as seasonal recreational buildings.
(2)The buildings described in Sentence (1) shall comply with all the requirements of this Part, except where they are specifically exempted in this Section.
OBC Div. B 9.37.2.2. Foundations
Open OBC Div. B 9.37.2.2. in the code viewer(1)Continuous perimeter foundation walls are not required, but when they are provided, they shall comply with the requirements of this Part.
(2)Where unit masonry columns are used, the height of such columns shall not exceed,
(a)in the case of hollow masonry units, 4 times the least dimension of the units,
(b)in the case of solid masonry units or hollow units with voids filled with concrete, 10 times the least dimension of the column, or
(c)where the column is reinforced with at least four 13 mm diam bars and filled with concrete, 18 times the least dimension of the column.
(3)Columns in excess of the height limitations of Clauses (2)(a) to (c) shall be designed in accordance with Part 4.
OBC Div. B 9.37.2.3. Waterproofing and Dampproofing
Open OBC Div. B 9.37.2.3. in the code viewer(1)Where foundations below ground level and concrete floors on ground are used, they shall comply with Section 9.13.
OBC Div. B 9.38.1.1. Material Requirements
Open OBC Div. B 9.38.1.1. in the code viewer(1)Logs that are sound and free of fractures may be used for foundations, beams, posts and similar members, provided it can be shown by a structural analysis or tests or previous experience that the strength of the member is adequate for its intended purposes.
OBC Div. B 9.38.2.3. Joining Logs
Open OBC Div. B 9.38.2.3. in the code viewer(1)Each log in a horizontal position shall be scribed as close as possible to its bearer and fastened to the bearer in at least three places throughout its length, by dowels, continuous machined joints, vertical framing members or interlocking intersections or any combination of these, but in no case shall the distance between fastenings exceed 1,800 mm.
OBC Div. B 9.38.3.2. Clearance
Open OBC Div. B 9.38.3.2. in the code viewer(1)At every opening in a wall made of logs in a horizontal position where shrinkage can occur there shall be a clearance between the rough buck header and the lintel log of not less than 13 mm in width for each 300 mm of height to allow for settlement.
OBC Div. B 9.39.2.1. General
Open OBC Div. B 9.39.2.1. in the code viewer(1)Except as provided in Subsection 9.39.3., a manufactured building used or intended to be used as a seasonal recreational building of residential occupancy is deemed to comply with this Code if it is designed and constructed in conformance with CAN/CSA-Z241 Series, "Park model trailers."
OBC Div. B 9.39.3.3. Foundations and Anchorage
Open OBC Div. B 9.39.3.3. in the code viewer(1)Buildings described in Article 9.39.1.1. shall be supported and anchored in conformance with the manufacturer's installation instructions.
OBC Div. B 9.41.2.1. Change of Use and Compensating Construction
Open OBC Div. B 9.41.2.1. in the code viewer(1)Where proposed construction will result in a change of use described in Clauses 9.40.1.1.(1)(a) to (f), additional construction shall be required in order that the building or part of a building subject to the change of use conforms to the requirements of Subsections 9.5.1. and 9.5.3. to 9.5.10., Section 9.6., Article 9.7.2.3. Sentences 9.7.5.1.(2) and 9.7.6.2.(1) and (3), Articles 9.8.8.1. and 9.9.10.1., Subsection 9.10.17. and Sections 9.31., 9.32. and 9.34. as they apply to the new major occupancy that the building or part of a building is to support.
(2)For the purposes of this Article, existing buildings shall be classified as to their construction and occupancy as provided for in Sentence 11.2.1.1.(1).
OBC Div. B 9.41.2.2. Performance Level Evaluation and Compensating Construction
Open OBC Div. B 9.41.2.2. in the code viewer(1)The performance level of a building after construction shall not be less than the performance level of the building prior to construction.
(2)For the purposes of Sentence (1), reduction of performance level shall be determined in accordance with Articles 11.4.2.1., 11.4.2.3. and 11.4.2.5.
(3)Where the proposed construction would reduce the performance level of an existing building, compensating construction shall be required in conformance with Articles 11.4.3.1., 11.4.3.2., 11.4.3.4. and 11.4.3.6.
(4)Section 11.5. applies in respect of the requirements of Sentences 11.4.3.4.(1), (3) and (4).