Other Part 9 structural items (roofing, cladding, equipment, garages, cottages, logs, change of use)

Roofing items (solar collectors, metal roofing support, GRP roofing, concrete tiles), cladding attachment, grab bars and equipment, HVAC structural movement, garages and carports, cottages, log construction, park model trailers and change of use.

chapters in this guide
13 of 14
chapters in this guide
to read
5 min
to read
code articles cited
25
code articles cited

Last updated

Values this chapter turns on

load a grab bar must resist in any direction
1.3 kN
load a grab bar must resist in any direction
detached garage size allowed on mud sills or slab
55 m²
detached garage size allowed on mud sills or slab
log settlement gap per 300 mm of opening height
13 mm
log settlement gap per 300 mm of opening height
minimum size of a carport column pier
190 x 190 mm
minimum size of a carport column pier

This chapter covers the structural pieces in the later Sections of Part 9. Each is short, so questions tend to be direct lookups. A few involve simple arithmetic, such as a pier size, a log settlement gap or a column height.

Roofing and cladding

Roofing. A solar collector system may sit above roofing that meets 9.26.2.1 OBC Div. B 9.26.1.4.OBC Div. B 9.26.1.4. Solar Collector Systems(1) A solar collector system is permitted to be installed above roofing materials conforming to Sentence 9.26.2.1.(1).. Two roofing types can span between spaced supports instead of sitting on a deck. Each must then be designed for roof loads:

  • sheet metal roofing, for the specified live loads for roofs OBC Div. B 9.26.13.2.OBC Div. B 9.26.13.2. Support(1) Where sheet metal roofing is not supported by roof decking but spans between spaced supports, the panels shall be designed to support the specified live loads for roofs.;
  • glass reinforced polyester panels, for the specified roof loads OBC Div. B 9.26.14.1.OBC Div. B 9.26.14.1. Support(1) Where glass reinforced polyester roofing panels are not supported by roof decking but span between spaced supports, the panels shall be designed to support the specified roof loads..

Concrete roof tiles are installed to the CAN/CSA-A220 Series OBC Div. B 9.26.17.1.OBC Div. B 9.26.17.1. Installation(1) Concrete roof tiles shall be installed according to CAN/CSA-A220 Series, "Concrete Roof Tiles." (See Note A-9.26.17.1.(1)).

Cladding. Cladding is normally fastened to framing, furring or blocking. It may be fastened to the sheathing alone only when the sheathing is thick enough OBC Div. B 9.27.5.1.OBC Div. B 9.27.5.1. Attachment(1) Except as permitted by Sentences (2) to (5), cladding shall be fastened to the framing members or furring members, or to blocking between the framing members. (2) Vertical lumber, stucco lath or reinforcing, vertically applied vinyl siding, vertically applied insulated vinyl siding, and polypropylene siding are…:

Cladding fastened to sheathing only Minimum sheathing
Vertical lumber, stucco lath, vertical vinyl or insulated vinyl, polypropylene 14.3 mm lumber, or 12.5 mm plywood, OSB or waferboard
Vertical metal siding, wood shingles and shakes 14.3 mm lumber, or 7.5 mm plywood, OSB or waferboard

A common trap is to apply the 7.5 mm value to vinyl siding.

Practice this topic

Equipment loads and seismic restraint

Where grab bars are provided, they must resist 1.3 kN applied vertically or horizontally OBC Div. B 9.31.2.3.OBC Div. B 9.31.2.3. Grab Bars(1) When provided, grab bars shall be capable of resisting a load of not less than 1.3 kN applied vertically or horizontally..

In locations where S_a(0.2) from SB-1 Table 3 is greater than 0.55, two kinds of equipment must be secured to the structure:

  • service water heaters, against overturning OBC Div. B 9.31.6.2.OBC Div. B 9.31.6.2. Equipment and Installation(1) Every service water heater and its installation shall conform to Part 7. (2) Reserved (3) Where the building is in a location where the spectral response acceleration, S_a(0.2) , is greater than 0.55, service water heaters shall be secured to the structure to resist overturning. (See Note A-9.31.6.2.(3));
  • heating and air-conditioning equipment with fuel or power connections, against overturning and displacement OBC Div. B 9.33.4.7.OBC Div. B 9.33.4.7. Structural Movement(1) Mechanical systems and equipment shall be designed and installed to accommodate the maximum amount of structural movement provided for in the construction of the building. (2) Where the building is in a location where the spectral acceleration, S_a(0.2) , is greater than 0.55, heating and air-conditioning….

Mechanical systems must also accommodate the structural movement the building is designed for.

Practice this topic

Garages and carports (9.35)

Section 9.35 covers garages and carports serving no more than one dwelling unit OBC Div. B 9.35.1.1.OBC Div. B 9.35.1.1. Application(1) This Section applies to garages and carports serving not more than one dwelling unit.. Foundations follow 9.12 and 9.15, including under the garage door OBC Div. B 9.35.3.1.OBC Div. B 9.35.3.1. Foundation Required(1) Except as permitted in this Subsection, foundations conforming to Sections 9.12. and 9.15. shall be provided for the support of carport and garage super-structures, including that portion beneath garage doors. (2) Detached garages of less than 55 m² floor area and not more than 1 storey in height that are not of….

A detached garage meeting all three of these limits may instead sit on wood mud sills, or on a concrete slab at least 100 mm thick:

  • under 55 m²;
  • one storey;
  • no masonry or masonry veneer.

The same garages are also exempt from foundation drainage where the ground slopes away from them.

Other garage and carport rules:

  • An attached garage in shifting clay should have foundations about as deep as the house. A slab-on-ground needs a construction joint where it meets the house slab OBC Div. B 9.35.3.2.OBC Div. B 9.35.3.2. Protection from Damage Due to Soil Movement(1) In clay-type soils subject to significant movement with a change in soil moisture content, the foundation depth of carports or garages connected to a dwelling unit directly or by a breezeway shall be approximately the same depth as the foundation of the main building. (2) Where slab-on-ground construction is used….
  • Carport column piers rise at least 150 mm above ground. They extend at least 25 mm past the column base on each side, and are never smaller than 190 x 190 mm OBC Div. B 9.35.3.4.OBC Div. B 9.35.3.4. Column Piers(1) Piers for the support of carport columns shall extend not less than 150 mm above ground level. (2) Piers referred to in Sentence (1) shall project not less than 25 mm beyond the base of the column but in no case be less than 190 mm by 190 mm in size..
  • Garage and carport columns follow 9.17, except that 89 x 89 mm wood columns are allowed OBC Div. B 9.35.4.2.OBC Div. B 9.35.4.2. Columns(1) Columns for garages and carports shall conform to Section 9.17., except that 89 mm by 89 mm wood columns may be used..
  • Walls and columns are anchored against wind uplift under 9.23.6. A garage sitting on the ground surface needs ground anchors OBC Div. B 9.35.4.3.OBC Div. B 9.35.4.3. Anchorage(1) Garage or carport walls and columns shall be anchored to the foundation to resist wind uplift in conformance with Subsection 9.23.6., except that where a garage is supported on the surface of the ground, ground anchors shall be provided to resist wind uplift..

Practice this topic

Seasonal recreational buildings and logs (9.37, 9.38)

Cottages must meet Part 9, with some exemptions OBC Div. B 9.37.1.1.OBC Div. B 9.37.1.1. Application(1) This Section applies to buildings of residential occupancy used or intended to be used as seasonal recreational buildings. (2) The buildings described in Sentence (1) shall comply with all the requirements of this Part, except where they are specifically exempted in this Section.. Continuous perimeter foundation walls are not required. Unit masonry columns are limited in height by the least dimension of the column OBC Div. B 9.37.2.2.OBC Div. B 9.37.2.2. Foundations(1) Continuous perimeter foundation walls are not required, but when they are provided, they shall comply with the requirements of this Part. (2) Where unit masonry columns are used, the height of such columns shall not exceed, (a) in the case of hollow masonry units, 4 times the least dimension of the units, (b) in…:

Column Maximum height
Hollow units 4 x least dimension
Solid units, or hollow units filled with concrete 10 x least dimension
Reinforced with four 13 mm bars and filled 18 x least dimension

Taller columns are designed to Part 4. Below-grade foundations and floors-on-ground still need dampproofing under Section 9.13 OBC Div. B 9.37.2.3.OBC Div. B 9.37.2.3. Waterproofing and Dampproofing(1) Where foundations below ground level and concrete floors on ground are used, they shall comply with Section 9.13..

Logs may be used structurally if analysis, tests or experience show they are adequate OBC Div. B 9.38.1.1.OBC Div. B 9.38.1.1. Material Requirements(1) Logs that are sound and free of fractures may be used for foundations, beams, posts and similar members, provided it can be shown by a structural analysis or tests or previous experience that the strength of the member is adequate for its intended purposes.. Logs touching masonry or concrete at or below grade are preservative-treated. Each horizontal log is fastened to its bearer in at least three places, never more than 1,800 mm apart OBC Div. B 9.38.2.3.OBC Div. B 9.38.2.3. Joining Logs(1) Each log in a horizontal position shall be scribed as close as possible to its bearer and fastened to the bearer in at least three places throughout its length, by dowels, continuous machined joints, vertical framing members or interlocking intersections or any combination of these, but in no case shall the…. Horizontal logs shrink, so every opening needs a settlement clearance between the rough buck header and the lintel log. It must be at least 13 mm for each 300 mm of opening height OBC Div. B 9.38.3.2.OBC Div. B 9.38.3.2. Clearance(1) At every opening in a wall made of logs in a horizontal position where shrinkage can occur there shall be a clearance between the rough buck header and the lintel log of not less than 13 mm in width for each 300 mm of height to allow for settlement..

Practice this topic

Park model trailers and change of use

Under Section 9.39 OBC Div. B 9.39.2.1.OBC Div. B 9.39.2.1. General(1) Except as provided in Subsection 9.39.3., a manufactured building used or intended to be used as a seasonal recreational building of residential occupancy is deemed to comply with this Code if it is designed and constructed in conformance with CAN/CSA-Z241 Series, "Park model trailers.", a park model trailer is deemed to comply with the Code if two conditions hold:

  • it is built to CAN/CSA-Z241;
  • it is used as a seasonal recreational building.

Components built off the factory site must still meet the Code. The trailer is supported and anchored to the manufacturer's installation instructions OBC Div. B 9.39.3.3.OBC Div. B 9.39.3.3. Foundations and Anchorage(1) Buildings described in Article 9.39.1.1. shall be supported and anchored in conformance with the manufacturer's installation instructions..

Change of use. Where a change of use occurs, the part of the building affected must be brought up to the listed Part 9 requirements for the new major occupancy OBC Div. B 9.41.2.1.OBC Div. B 9.41.2.1. Change of Use and Compensating Construction(1) Where proposed construction will result in a change of use described in Clauses 9.40.1.1.(1)(a) to (f), additional construction shall be required in order that the building or part of a building subject to the change of use conforms to the requirements of Subsections 9.5.1. and 9.5.3. to 9.5.10., Section 9.6.…. The listed requirements include doors, glass, guards, egress windows, flame spread, plumbing facilities, ventilation and electrical.

The key performance rule is that the building's performance level after construction may not be lower than before. It is evaluated under Part 11. Where it would drop, compensating construction is required under 11.4.3 OBC Div. B 9.41.2.2.OBC Div. B 9.41.2.2. Performance Level Evaluation and Compensating Construction(1) The performance level of a building after construction shall not be less than the performance level of the building prior to construction. (2) For the purposes of Sentence (1), reduction of performance level shall be determined in accordance with Articles 11.4.2.1., 11.4.2.3. and 11.4.2.5. (3) Where the proposed….

Practice this topic

Chapter review

Chapter at a glance

One line per section: the idea to carry into the exam. Then the answers that most often catch candidates out.

Practice this chapter

Questions on Other Part 9 structural items, in the exam format, every answer explained and cited to its article. Sign in to start; a free account gets the free questions.

Code cited in this chapter

Based on the official 2024 Building Code Compendium on ontario.ca.

© King's Printer for Ontario, 2024. Reproduced with permission.

  • OBC Div. B 9.26.1.4. Solar Collector Systems

    (1)A solar collector system is permitted to be installed above roofing materials conforming to Sentence 9.26.2.1.(1).

    Open OBC Div. B 9.26.1.4. in the code viewer
  • OBC Div. B 9.26.13.2. Support

    (1)Where sheet metal roofing is not supported by roof decking but spans between spaced supports, the panels shall be designed to support the specified live loads for roofs.

    Open OBC Div. B 9.26.13.2. in the code viewer
  • OBC Div. B 9.26.14.1. Support

    (1)Where glass reinforced polyester roofing panels are not supported by roof decking but span between spaced supports, the panels shall be designed to support the specified roof loads.

    Open OBC Div. B 9.26.14.1. in the code viewer
  • OBC Div. B 9.26.17.1. Installation

    (1)Concrete roof tiles shall be installed according to CAN/CSA-A220 Series, "Concrete Roof Tiles." (See Note A-9.26.17.1.(1))

    Open OBC Div. B 9.26.17.1. in the code viewer
  • OBC Div. B 9.27.5.1. Attachment

    (1)Except as permitted by Sentences (2) to (5), cladding shall be fastened to the framing members or furring members, or to blocking between the framing members.

    (2)Vertical lumber, stucco lath or reinforcing, vertically applied vinyl siding, vertically applied insulated vinyl siding, and polypropylene siding are permitted to be attached to sheathing only where the sheathing consists of not less than

    (a)14.3 mm lumber,

    (b)12.5 mm plywood, or

    (c)12.5 mm OSB or waferboard.

    (3)Vertically applied metal siding and wood shingles and shakes are permitted to be attached to the sheathing only where the sheathing consists of not less than

    (a)14.3 mm lumber,

    (b)7.5 mm plywood, or

    (c)7.5 mm OSB or waferboard.

    (4)Where wood shingles or shakes are applied to sheathing which is not suitable for attaching the shingles or shakes, the shingles or shakes are permitted to be attached to a wood lath not less than 38 mm by 9.5 mm thick securely nailed to the framing and applied as described in Article 9.27.7.5.

    (5)Cladding, trim and furring members are permitted to be attached to the web fastening strips of flat wall insulating concrete form units using screws in accordance with Sentence 9.27.5.4.(2)

    Open OBC Div. B 9.27.5.1. in the code viewer
  • OBC Div. B 9.31.2.3. Grab Bars

    (1)When provided, grab bars shall be capable of resisting a load of not less than 1.3 kN applied vertically or horizontally.

    Open OBC Div. B 9.31.2.3. in the code viewer
  • OBC Div. B 9.31.6.2. Equipment and Installation

    (1)Every service water heater and its installation shall conform to Part 7.

    (2)Reserved

    (3)Where the building is in a location where the spectral response acceleration, S_a(0.2) , is greater than 0.55, service water heaters shall be secured to the structure to resist overturning. (See Note A-9.31.6.2.(3))

    Open OBC Div. B 9.31.6.2. in the code viewer
  • OBC Div. B 9.33.4.7. Structural Movement

    (1)Mechanical systems and equipment shall be designed and installed to accommodate the maximum amount of structural movement provided for in the construction of the building.

    (2)Where the building is in a location where the spectral acceleration, S_a(0.2) , is greater than 0.55, heating and air-conditioning equipment with fuel or power connections shall be secured to the structure to resist overturning and displacement. (See Note A-9.31.6.2.(3))

    Open OBC Div. B 9.33.4.7. in the code viewer
Show all 25 articles
  • OBC SB-1 Table 3: Seismic Design Data for Selected Locations in Ontario for Part 9 Design

    Table 3: Seismic Design Data for Selected Locations in Ontario for Part 9 Design

    Location | S_a(0.2) for Seismic Design in Part 9

    Ailsa Craig | 0.095

    Ajax | 0.210

    Alexandria | 0.589

    Alliston | 0.111

    Almonte | 0.337

    Armstrong | 0.064

    Arnprior | 0.371

    Atikokan | 0.069

    Attawapiskat | 0.074

    Aurora | 0.138

    Bancroft | 0.151

    Barrie | 0.108

    Barriefield | 0.162

    Beaverton | 0.117

    Belleville | 0.162

    Belmont | 0.116

    Big Trout Lake (Kitchenuhmaykoosib) | 0.054

    CFB Borden | 0.107

    Bracebridge | 0.116

    Bradford | 0.123

    Brampton | 0.168

    Brantford | 0.155

    Brighton | 0.173

    Brockville | 0.259

    Burk's Falls | 0.143

    Burlington | 0.266

    Caledon | 0.168

    Cambridge | 0.141

    Campbellford | 0.144

    Cannington | 0.122

    Carleton Place | 0.302

    Cavan | 0.140

    Centralia | 0.092

    Chapleau | 0.071

    Chatham | 0.112

    Chesley | 0.083

    Clinton | 0.084

    Coboconk | 0.120

    Cobourg | 0.179

    Cochrane | 0.222

    Colborne | 0.176

    Collingwood | 0.096

    Cornwall | 0.587

    Corunna | 0.087

    Deep River | 0.389

    Deseronto | 0.158

    Dorchester | 0.112

    Dorion | 0.059

    Dresden | 0.104

    Dryden | 0.072

    Dundalk | 0.097

    Dunnville | 0.232

    Durham | 0.088

    Dutton | 0.116

    Earlton | 0.182

    Edison | 0.070

    Elliot Lake | 0.074

    Elmvale | 0.101

    Embro | 0.111

    Englehart | 0.175

    Espanola | 0.086

    Exeter | 0.090

    Fenelon Falls | 0.121

    Fergus | 0.115

    Forest | 0.087

    Fort Erie | 0.312

    Fort Erie (Ridgeway) | 0.307

    Fort Frances | 0.064

    Gananoque | 0.180

    Geraldton | 0.057

    Glencoe | 0.107

    Goderich | 0.079

    Gore Bay | 0.071

    Graham | 0.071

    Gravenhurst (Muskoka Airport) | 0.112

    Grimsby | 0.301

    Guelph | 0.133

    Guthrie | 0.109

    Haileybury | 0.219

    Haldimand (Caledonia) | 0.215

    Haldimand (Hagersville) | 0.172

    Haliburton | 0.133

    Halton Hills (Georgetown) | 0.155

    Hamilton | 0.260

    Hanover | 0.085

    Hastings | 0.141

    Hawkesbury | 0.506

    Hearst | 0.073

    Honey Harbour | 0.103

    Hornepayne | 0.063

    Huntsville | 0.129

    Ingersoll | 0.116

    Iroquois Falls | 0.196

    Jellicoe | 0.057

    Kapuskasing | 0.112

    Kemptville | 0.429

    Kenora | 0.064

    Killaloe | 0.264

    Kincardine | 0.076

    Kingston | 0.161

    Kinmount | 0.123

    Kirkland Lake | 0.159

    Kitchener | 0.122

    Lakefield | 0.130

    Lansdowne House | 0.056

    Leamington | 0.114

    Lindsay | 0.126

    Lion's Head | 0.080

    Listowel | 0.093

    London | 0.108

    Lucan | 0.097

    Maitland | 0.282

    Markdale | 0.089

    Markham | 0.182

    Martin | 0.072

    Matheson | 0.160

    Mattawa | 0.446

    Midland | 0.101

    Milton | 0.191

    Milverton | 0.098

    Minden | 0.124

    Mississauga | 0.219

    Mississauga (Lester B. Pearson International Airport) | 0.193

    Mississauga (Port Credit) | 0.247

    Mitchell | 0.093

    Moosonee | 0.081

    Morrisburg | 0.558

    Mount Forest | 0.093

    Nakina | 0.057

    Nanticoke (Jarvis) | 0.156

    Nanticoke (Port Dover) | 0.144

    Napanee | 0.156

    New Liskeard | 0.209

    Newcastle | 0.186

    Newcastle (Bowmanville) | 0.188

    Newmarket | 0.132

    Niagara Falls | 0.321

    North Bay | 0.247

    Norwood | 0.136

    Oakville | 0.260

    Orangeville | 0.115

    Orillia | 0.109

    Oshawa | 0.192

    Ottawa (Metropolitan) | N/A

    Ottawa (City Hall) | 0.439

    Ottawa (Barrhaven) | 0.427

    Ottawa (Kanata) | 0.401

    Ottawa (MacDonald-Cartier Int'l Airport) | 0.446

    Ottawa (Orleans) | 0.474

    Owen Sound | 0.083

    Pagwa River | 0.060

    Paris | 0.141

    Parkhill | 0.092

    Parry Sound | 0.110

    Pelham (Fonthill) | 0.311

    Pembroke | 0.379

    Penetanguishene | 0.101

    Perth | 0.225

    Petawawa | 0.379

    Peterborough | 0.135

    Petrolia | 0.092

    Pickering (Zones 1 to 4) | 0.219

    Picton | 0.159

    Plattsville | 0.119

    Point Alexander | 0.391

    Port Burwell | 0.132

    Port Colborne | 0.298

    Port Elgin | 0.077

    Port Hope | 0.181

    Port Perry | 0.144

    Port Stanley | 0.123

    Prescott | 0.350

    Princeton | 0.129

    Raith | 0.067

    Rayside-Balfour (Chelmsford) | 0.104

    Red Lake | 0.068

    Renfrew | 0.352

    Richmond Hill | 0.163

    Rockland | 0.510

    Sarnia | 0.085

    Sault Ste. Marie | 0.062

    Schreiber | 0.057

    Seaforth | 0.087

    Shelburne | 0.104

    Simcoe | 0.141

    Sioux Lookout | 0.073

    Smiths Falls | 0.256

    Smithville | 0.296

    Smooth Rock Falls | 0.200

    South River | 0.164

    Southampton | 0.077

    St. Catharines | 0.319

    St. Mary's | 0.101

    St. Thomas | 0.117

    Stirling | 0.149

    Stratford | 0.103

    Strathroy | 0.100

    Sturgeon Falls | 0.183

    Sudbury | 0.110

    Sundridge | 0.157

    Tavistock | 0.108

    Temagami | 0.239

    Thamesford | 0.111

    Thedford | 0.089

    Thunder Bay | 0.061

    Tillsonburg | 0.126

    Timmins | 0.125

    Timmins (Porcupine) | 0.140

    Toronto Metropolitan Region | N/A

    Etobicoke | 0.193

    North York | 0.195

    Scarborough | 0.219

    Toronto (City Hall) | 0.249

    Trenton | 0.167

    Trout Creek | 0.186

    Uxbridge | 0.139

    Vaughan (Woodbridge) | 0.167

    Vittoria | 0.139

    Walkerton | 0.083

    Wallaceburg | 0.098

    Waterloo | 0.118

    Watford | 0.095

    Wawa | 0.062

    Welland | 0.308

    West Lorne | 0.118

    Whitby | 0.203

    Whitby (Brooklin) | 0.176

    White River | 0.060

    Wiarton | 0.080

    Windsor | 0.096

    Wingham | 0.083

    Woodstock | 0.118

    Wyoming | 0.090

    Open OBC SB-1 in the code viewer
  • OBC Div. B 9.35.1.1. Application

    (1)This Section applies to garages and carports serving not more than one dwelling unit.

    Open OBC Div. B 9.35.1.1. in the code viewer
  • OBC Div. B 9.35.3.1. Foundation Required

    (1)Except as permitted in this Subsection, foundations conforming to Sections 9.12. and 9.15. shall be provided for the support of carport and garage super-structures, including that portion beneath garage doors.

    (2)Detached garages of less than 55 m² floor area and not more than 1 storey in height that are not of masonry or masonry veneer construction are permitted to be supported on

    (a)wood mud sills, or

    (b)a concrete floor slab having a minimum thickness of not less than 100 mm.

    Open OBC Div. B 9.35.3.1. in the code viewer
  • OBC Div. B 9.35.3.2. Protection from Damage Due to Soil Movement

    (1)In clay-type soils subject to significant movement with a change in soil moisture content, the foundation depth of carports or garages connected to a dwelling unit directly or by a breezeway shall be approximately the same depth as the foundation of the main building.

    (2)Where slab-on-ground construction is used, a construction joint shall be provided between the main building slab and a slab serving an attached garage, breezeway or carport.

    (3)Except as provided in Section 9.12., foundations for attached unheated garages or carports shall be below frost level.

    Open OBC Div. B 9.35.3.2. in the code viewer
  • OBC Div. B 9.35.3.4. Column Piers

    (1)Piers for the support of carport columns shall extend not less than 150 mm above ground level.

    (2)Piers referred to in Sentence (1) shall project not less than 25 mm beyond the base of the column but in no case be less than 190 mm by 190 mm in size.

    Open OBC Div. B 9.35.3.4. in the code viewer
  • OBC Div. B 9.35.4.2. Columns

    (1)Columns for garages and carports shall conform to Section 9.17., except that 89 mm by 89 mm wood columns may be used.

    Open OBC Div. B 9.35.4.2. in the code viewer
  • OBC Div. B 9.35.4.3. Anchorage

    (1)Garage or carport walls and columns shall be anchored to the foundation to resist wind uplift in conformance with Subsection 9.23.6., except that where a garage is supported on the surface of the ground, ground anchors shall be provided to resist wind uplift.

    Open OBC Div. B 9.35.4.3. in the code viewer
  • OBC Div. B 9.37.1.1. Application

    (1)This Section applies to buildings of residential occupancy used or intended to be used as seasonal recreational buildings.

    (2)The buildings described in Sentence (1) shall comply with all the requirements of this Part, except where they are specifically exempted in this Section.

    Open OBC Div. B 9.37.1.1. in the code viewer
  • OBC Div. B 9.37.2.2. Foundations

    (1)Continuous perimeter foundation walls are not required, but when they are provided, they shall comply with the requirements of this Part.

    (2)Where unit masonry columns are used, the height of such columns shall not exceed,

    (a)in the case of hollow masonry units, 4 times the least dimension of the units,

    (b)in the case of solid masonry units or hollow units with voids filled with concrete, 10 times the least dimension of the column, or

    (c)where the column is reinforced with at least four 13 mm diam bars and filled with concrete, 18 times the least dimension of the column.

    (3)Columns in excess of the height limitations of Clauses (2)(a) to (c) shall be designed in accordance with Part 4.

    Open OBC Div. B 9.37.2.2. in the code viewer
  • OBC Div. B 9.37.2.3. Waterproofing and Dampproofing

    (1)Where foundations below ground level and concrete floors on ground are used, they shall comply with Section 9.13.

    Open OBC Div. B 9.37.2.3. in the code viewer
  • OBC Div. B 9.38.1.1. Material Requirements

    (1)Logs that are sound and free of fractures may be used for foundations, beams, posts and similar members, provided it can be shown by a structural analysis or tests or previous experience that the strength of the member is adequate for its intended purposes.

    Open OBC Div. B 9.38.1.1. in the code viewer
  • OBC Div. B 9.38.2.3. Joining Logs

    (1)Each log in a horizontal position shall be scribed as close as possible to its bearer and fastened to the bearer in at least three places throughout its length, by dowels, continuous machined joints, vertical framing members or interlocking intersections or any combination of these, but in no case shall the distance between fastenings exceed 1,800 mm.

    Open OBC Div. B 9.38.2.3. in the code viewer
  • OBC Div. B 9.38.3.2. Clearance

    (1)At every opening in a wall made of logs in a horizontal position where shrinkage can occur there shall be a clearance between the rough buck header and the lintel log of not less than 13 mm in width for each 300 mm of height to allow for settlement.

    Open OBC Div. B 9.38.3.2. in the code viewer
  • OBC Div. B 9.39.2.1. General

    (1)Except as provided in Subsection 9.39.3., a manufactured building used or intended to be used as a seasonal recreational building of residential occupancy is deemed to comply with this Code if it is designed and constructed in conformance with CAN/CSA-Z241 Series, "Park model trailers."

    Open OBC Div. B 9.39.2.1. in the code viewer
  • OBC Div. B 9.39.3.3. Foundations and Anchorage

    (1)Buildings described in Article 9.39.1.1. shall be supported and anchored in conformance with the manufacturer's installation instructions.

    Open OBC Div. B 9.39.3.3. in the code viewer
  • OBC Div. B 9.41.2.1. Change of Use and Compensating Construction

    (1)Where proposed construction will result in a change of use described in Clauses 9.40.1.1.(1)(a) to (f), additional construction shall be required in order that the building or part of a building subject to the change of use conforms to the requirements of Subsections 9.5.1. and 9.5.3. to 9.5.10., Section 9.6., Article 9.7.2.3. Sentences 9.7.5.1.(2) and 9.7.6.2.(1) and (3), Articles 9.8.8.1. and 9.9.10.1., Subsection 9.10.17. and Sections 9.31., 9.32. and 9.34. as they apply to the new major occupancy that the building or part of a building is to support.

    (2)For the purposes of this Article, existing buildings shall be classified as to their construction and occupancy as provided for in Sentence 11.2.1.1.(1).

    Open OBC Div. B 9.41.2.1. in the code viewer
  • OBC Div. B 9.41.2.2. Performance Level Evaluation and Compensating Construction

    (1)The performance level of a building after construction shall not be less than the performance level of the building prior to construction.

    (2)For the purposes of Sentence (1), reduction of performance level shall be determined in accordance with Articles 11.4.2.1., 11.4.2.3. and 11.4.2.5.

    (3)Where the proposed construction would reduce the performance level of an existing building, compensating construction shall be required in conformance with Articles 11.4.3.1., 11.4.3.2., 11.4.3.4. and 11.4.3.6.

    (4)Section 11.5. applies in respect of the requirements of Sentences 11.4.3.4.(1), (3) and (4).

    Open OBC Div. B 9.41.2.2. in the code viewer