In the 2024 Ontario Building Code, a deck serving a single house must be designed for the specified roof snow load or 1.9 kPa, whichever is greater (OBC Div. B 9.4.2.3.OBC Div. B 9.4.2.3. Platforms Subject to Snow and Occupancy Loads(1) Balconies, decks and other accessible exterior platforms intended for an occupancy and subject to snow loads shall be designed to carry the specified roof snow load or 1.9 kPa, whichever is greater, where the platform, or each segregated area of the platform, serves a single dwelling unit. (See Note A-9.4.2.3.(1))), and its footings must generally reach the depths in Table 9.12.2.2, unless it qualifies as a small freestanding deck of not more than 55 m² with joists not more than 600 mm above grade (OBC Div. B 9.12.2.2.OBC Div. B 9.12.2.2. Minimum Depth of Foundations(1) Except as provided in Sentences (4) to (7), the minimum depth of foundations below finished ground level shall conform to Table 9.12.2.2. (2) Where a foundation is insulated in a manner that will reduce the heat flow to the soil beneath the footings, the foundation depth shall conform to that required for…). Guards, stairs, spans and post anchorage each have their own articles, covered below.
There is no single "deck section" in the code. The rules are spread across Part 9 of Division B, and the permit rules are in the Building Code Act and Division C. This page pulls them together in plain language. Municipal zoning bylaws (setbacks, lot coverage) and permit conditions often add requirements, so confirm with your building department before you dig.
Deck rules at a glance
| Topic | Key rule | Article |
|---|---|---|
| Design load | greater of roof snow load or 1.9 kPa | 9.4.2.3.(1) |
| Footing depth | per Table 9.12.2.2 (soil and drainage) | 9.12.2.2.(1) |
| Small deck exemption from footing depth | 1 storey, 55 m² max, joists 600 mm max above ground, no roof, not attached (one exception) | 9.12.2.2.(7) |
| Posts and columns | Section 9.17 covers up to 2 deck levels, joists bearing up to 5 m | 9.17.1.1.(1)(b) |
| Post anchorage | anchor to resist uplift and lateral movement, small deck exemption | 9.23.6.2. |
| Joist spans | Span Tables 9.23.4.2.-A and -B | 9.23.4.2.(1) |
| Beam spans | Span Tables 9.23.4.2.-H to -K | 9.23.4.2.(3) |
| Beam end bearing | 89 mm unless the span table notes say otherwise | 9.23.8.1. |
| Wood near the ground | pressure-treated where clearance is under 150 mm | 9.3.2.9.(3) |
| Guards | over 600 mm drop; 900 mm or 1,070 mm high | 9.8.8.1., 9.8.8.3. |
This is our own summary. Read each article in full before relying on it.
Loads
9.4.2.3.(1)OBC Div. B 9.4.2.3. Platforms Subject to Snow and Occupancy Loads(1) Balconies, decks and other accessible exterior platforms intended for an occupancy and subject to snow loads shall be designed to carry the specified roof snow load or 1.9 kPa, whichever is greater, where the platform, or each segregated area of the platform, serves a single dwelling unit. (See Note A-9.4.2.3.(1)) says balconies, decks and other accessible exterior platforms that serve a single dwelling unit and are exposed to snow must carry the specified roof snow load or 1.9 kPa, whichever is greater. Snow loads come from the formula in 9.4.2.2.OBC Div. B 9.4.2.2. Specified Snow Loads(1) Except as provided in Sentences (2) and (4), specified snow loads shall be not less than those calculated using the following formula: S = C_bS_s + S_r where S = specified snow load, C_b = basic snow load roof factor, which is 0.45 where the entire width of a roof does not exceed 4.3 m and 0.55 for all other…, using ground snow and rain loads for your location from Supplementary Standard SB-1. In snowy parts of Ontario, the snow load, not the 1.9 kPa minimum, can govern.
Footings and foundations
Depth. 9.12.2.2.OBC Div. B 9.12.2.2. Minimum Depth of Foundations(1) Except as provided in Sentences (4) to (7), the minimum depth of foundations below finished ground level shall conform to Table 9.12.2.2. (2) Where a foundation is insulated in a manner that will reduce the heat flow to the soil beneath the footings, the foundation depth shall conform to that required for… sends you to Table 9.12.2.2.OBC Div. B Table 9.12.2.2. Minimum Depths of Foundations — Forming Part of Sentence 9.12.2.2.(1)Table 9.12.2.2 — Minimum Depths of Foundations — Forming Part of Sentence 9.12.2.2.(1) Forming Part of Sentence 9.12.2.2.(1) Type of Soil | Min Depth of Foundation Containing Heated Basement or Crawl Space[1] With Good Soil Drainage | Min Depth of Foundation Containing Heated Basement or Crawl Space[1] With Poor Soil…, which sets minimum depths by soil type and drainage. A deck footing is a foundation "containing no heated space." For clay or soils not clearly defined, that means at least 1.2 m and not less than the depth of frost penetration. Rock has no limit, and neither do coarse-grained soils with good drainage. Silt needs footings below the depth of frost penetration. Lesser depths are allowed where local experience or a design shows they are satisfactory.
The small deck exemption. The depth table does not apply to a deck that is not more than 1 storey, not more than 55 m² in area, has not more than 600 mm from finished ground to the underside of the joists, supports no roof, and is not attached to another structure, unless it can be shown that differential movement will not harm that structure (9.12.2.2.(7)OBC Div. B 9.12.2.2. Minimum Depth of Foundations(1) Except as provided in Sentences (4) to (7), the minimum depth of foundations below finished ground level shall conform to Table 9.12.2.2. (2) Where a foundation is insulated in a manner that will reduce the heat flow to the soil beneath the footings, the foundation depth shall conform to that required for…). This is the clause behind low, floating decks.
Size. Footing widths and column footing areas are in 9.15.3.4.OBC Div. B 9.15.3.4. Basic Footing Widths and Areas(1) Except as provided in Sentences (2) and (3) and in Articles 9.15.3.5. to 9.15.3.7., the minimum footing width or area shall comply with Table 9.15.3.4. (2) Where the supported joist span exceeds 4.9 m in buildings with light wood-frame walls, floors and roofs, strip footing widths shall be determined according to… and its table, based on the number of floors supported and the column spacing. Ask your building department which values it expects for deck piers.
Posts, beams and joists
Posts. Section 9.17 covers columns supporting beams that carry not more than 2 levels of wood-frame decks (or 1 level plus a roof), where the joists bearing on the beam are not more than 5 m long, the snow plus occupancy load does not exceed 4.8 kPa, and the deck serves a single residential suite (9.17.1.1.OBC Div. B 9.17.1.1. Application(1) This Section applies to columns used to support (a) beams carrying loads from not more than 2 wood-frame floors where (i) the supported length of joists bearing on such beams does not exceed 5 m, and (ii) the live load on any floor does not exceed 2.4 kPa, (See Table 4.1.5.3.) (b) beams or header joists carrying…). Outside those limits, Part 4 design is required. Columns must be fastened to what they support and braced against racking, except posts not more than 600 mm long under a deck with no superstructure (9.17.2.2.OBC Div. B 9.17.2.2. Lateral Support(1) Columns shall be securely fastened to the supported member to reduce the likelihood of lateral differential movement between the column and the supported member. (See also Article 9.23.6.2.) (2) Except as permitted by Sentence (3), columns shall be laterally supported to resist racking (a) directly, or (b) by…).
Anchorage. Exterior posts generally must be anchored to resist uplift and lateral movement. Where deck posts are on a platform with not more than 600 mm from ground to the underside of the joists, the posts must be anchored to the foundation, or the joists or beams anchored to the ground, to resist uplift and lateral movement. A small, freestanding, roofless, single-storey deck of not more than 55 m² is exempt (9.23.6.2.OBC Div. B 9.23.6.2. Anchorage of Columns and Posts(1) Except as provided in Sentences (2) and (3), exterior columns and posts shall be anchored to resist uplift and lateral movement. (2) Except as provided in Sentence (3), where columns or posts support balconies, decks, verandas and other exterior platforms, and the distance from finished ground to the underside of…).
Spans. Joist spans come from Span Tables 9.23.4.2.-A and -B and beam spans from Tables 9.23.4.2.-H to -K (9.23.4.2.OBC Div. B 9.23.4.2. Spans for Joists, Rafters and Beams(1) Except as required in Sentence (2) and Article 9.23.14.10., spans for wood joists and rafters shall conform to the spans shown in Span Tables 9.23.4.2.-A to 9.23.4.2-G for the uniform live loads shown in the Tables. (See Article 9.4.2.2.) (2) Spans for floor joists that are not selected from Span Tables…). Each table is read by species group, grade, member size and spacing (or, for beams, supported length). The tables apply only to floors carrying residential-level loads (9.23.4.1.OBC Div. B 9.23.4.1. Application(1) Spans provided in this Subsection for joists, beams and lintels supporting floors shall apply only where (a) the floors serve residential areas as described in Table 4.1.5.3., or (b) the uniformly distributed live load on the floors does not exceed that specified for residential areas as described in Table…), so if the snow load at your site pushes the deck load above that, the tables alone do not answer the question and a design under Part 4 or engineering guidance is needed (9.4.1.1.OBC Div. B 9.4.1.1. General(1) Subject to the application limitations defined elsewhere in this Part, structural members and their connections shall (a) conform to requirements provided elsewhere in this Part, (b) be designed according to good engineering practice such as provided in the CWC 2014, "Engineering Guide for Wood Frame…).
Bearing and connections. Beams need at least 89 mm of end bearing unless the span table notes say otherwise (9.23.8.1.OBC Div. B 9.23.8.1. Bearing for Beams(1) Beams shall have even and level bearing and the bearing at end supports shall be not less than 89 mm long, except as stated in the notes to Span Tables 9.23.4.2.-H to 9.23.4.2.-K. .), and joists at least 38 mm (9.23.9.1.OBC Div. B 9.23.9.1. End Bearing for Joists(1) Except when supported on ribbon boards, floor joists shall have not less than 38 mm length of end bearing. (2) Ribbon boards referred to in Sentence (1) shall be not less than 19 mm by 89 mm lumber let into the studs.). Joists framed into the side of a wood beam sit on joist hangers or ledger strips of the sizes in 9.23.9.2.OBC Div. B 9.23.9.2. Joists Supported by Beams(1) Floor joists may be supported on the tops of beams or may be framed into the sides of beams. (2) When framed into the side of a wood beam, joists referred to in Sentence (1) shall be supported on (a) joist hangers or other acceptable mechanical connectors, or (b) not less than 38 mm by 64 mm ledger strips nailed….
Protecting the wood
Structural wood less than 150 mm above finished ground must be pressure-treated with a preservative (9.3.2.9.(3)OBC Div. B 9.3.2.9. Termite and Decay Protection(1) In localities where termites are known to occur, (a) clearance between structural wood elements and the finished ground level directly below them shall be not less than 450 mm and, except as provided in Sentence (2), all sides of the supporting elements shall be visible to permit inspection, or (b) structural wood…). The same article sets the CSA O80 use categories: for example UC3.2 for exterior above-ground wood and UC4.1 for ground contact, with treated wood marked to show its category. Where termites are known to occur, extra rules apply.
Guards and stairs
A deck more than 600 mm above the ground within 1.2 m of its edge needs a guard (9.8.8.1.OBC Div. B 9.8.8.1. Required Guards(1) Except as provided in Sentence (2) and except at the leading edge at the top of a flight, every surface to which access is provided, including but not limited to flights of steps and ramps, exterior landings, porches, balconies, mezzanines, galleries and raised walkways, shall be protected by a guard on each side…): 900 mm high where the deck is not more than 1,800 mm above finished ground, 1,070 mm above that (9.8.8.3.OBC Div. B 9.8.8.3. Height of Guards(1) Except as provided in Sentences (2) to (3.1), all guards shall be not less than 1,070 mm high. (2) All guards within dwelling units or within houses with a secondary suite including their common spaces shall be not less than 900 mm high. (3) Exterior guards serving not more than one dwelling unit or a house with a…). Wood guards built to SB-7 are deemed to meet the load requirements (9.8.8.2.OBC Div. B 9.8.8.2. Loads on Guards(1) Except as provided in Sentences (2), (3), (5) and (6), guards shall be designed to resist the specified loads prescribed in Table 9.8.8.2. (2) The size of the opening between any two adjacent vertical elements within a guard shall not exceed the limits required by Sentence 9.8.8.5.(1) when each of these elements…). Deck stairs follow the private stair rules in Table 9.8.4.1.OBC Div. B Table 9.8.4.1. Rise for Rectangular Treads, Tapered Treads and Winders and Run for Rectangular Treads — Forming Part of Sentences 9.8.4.1.(1) and 9.8.4.2.(1)Table 9.8.4.1 — Rise for Rectangular Treads, Tapered Treads and Winders and Run for Rectangular Treads — Forming Part of Sentences 9.8.4.1.(1) and 9.8.4.2.(1) Stair Type | Max. Rise, mm, for All Steps | Min. Rise, mm, for All Steps | Max. Run, mm, for Rectangular Treads | Min. Run, mm, for Rectangular Treads Private…, and need a handrail once they have more than 3 risers (9.8.7.1.OBC Div. B 9.8.7.1. Required Handrails(1) Except as provided in Sentences (2) to (4), handrails shall be installed on stairs and ramps in conformance with Table 9.8.7.1. (2) Where a stair or ramp is required to be at least 2,200 mm wide due to the occupant load, a handrail shall be installed such that no position on the stair or ramp is more than 825 mm…). See deck railing height.
Permits
The Building Code Act, 1992 says no one may construct a building without a permit from the chief building official (BCA s. 8BCA s. 8 Building permits(1) No person shall construct or demolish a building or cause a building to be constructed or demolished unless a permit has been issued therefor by the chief building official. (1.1) An application for a permit to construct or demolish a building may be made by a person specified by regulation and the prescribed form…). The Act defines a building to include a structure occupying more than 10 m² that consists of a wall, roof or floor, or a structural system serving that function (BCA s. 1(1)BCA s. 1 building“building” means, (a) a structure occupying an area greater than ten square metres consisting of a wall, roof and floor or any of them or a structural system serving the function thereof including all plumbing, works, fixtures and service systems appurtenant thereto, (b) a structure occupying an area of ten square…). The exemptions in Div. C 1.3.1.1.OBC Div. C 1.3.1.1. Requirement for Permits(1) A person is exempt from the requirement to obtain a permit under section 8 of the Act, (a) for the demolition of a farm building located on a farm, (b) subject to Sentence (2), for the construction or demolition of a building in territory without municipal organization, or (c) for the construction of a Class 1… cover things like tents and small sheds, not decks. Municipalities apply these rules, and many publish deck permit guides, so check with yours.
Common mistakes
- Using the floating deck exemption on an attached deck without showing differential movement will not harm the house.
- Picking spans from the wrong table (ceiling or roof joists instead of floor joists).
- Forgetting snow load in heavy-snow areas.
- Ignoring zoning setbacks, which come from the municipal bylaw, not the Building Code.
- Untreated or wrong-category lumber near the ground.
How to look it up yourself
In Division B, Part 9, search the 2024 Compendium for "decks and other accessible exterior platforms" (it appears in 9.4.2.3., 9.12.2.2. and 9.17.1.1.), "Minimum Depth of Foundations", "Anchorage of Columns and Posts" and "Maximum Spans for Floor Joists". For permits, search the Act for "No person shall construct or demolish a building".
Decks pull together structure, foundations and guards, all of which are on the House exam syllabus. Read the free House exam study guide and try the free practice quiz on that page.
Based on the official 2024 Building Code Compendium on ontario.ca.
© King's Printer for Ontario, 2024. Reproduced with permission.