Building Structural study guideStructure

Earthquake load and effects (4.1.8)

Seismic design: site classes, spectral response, seismic force resisting systems, equivalent static force procedure, irregularities and elements of structures and non-structural components.

chapters in this guide
5 of 14
chapters in this guide
to read
6 min
to read
code articles cited
18
code articles cited

Last updated

Values this chapter turns on

seismic hazard probability of exceedance in 50 years
2%
seismic hazard probability of exceedance in 50 years
interstorey drift limit, most buildings, of h_s
2.5%
interstorey drift limit, most buildings, of h_s
interstorey drift limit, post-disaster, of h_s
1%
interstorey drift limit, post-disaster, of h_s
storey weight over a neighbour that is irregular
150%
storey weight over a neighbour that is irregular

Subsection 4.1.8 is the longest piece of Part 4. The exam does not expect you to run a full seismic design. It does expect you to find the right table value and to do short calculations. You will need the importance factor, the site designation, the seismic category, R_d and R_o, the period, the base shear with its limits, the drift limits and the force on components.

Where the hazard values come from

For Part 4, SB-1 points to the 2020 National Building Code of Canada Seismic Hazard Tool. It gives spectral accelerations S_a(T, X) at 0.2, 0.5, 1.0, 2.0, 5.0 and 10.0 s, at a 2% probability of exceedance in 50 years SB-1 Seismic Data for Part 4OBC SB-1 Seismic Data for Part 4The seismic hazard values to be used for the design of buildings under Part 4 can be obtained from the 2020 National Building Code of Canada Seismic Hazard Tool (https://doi.org/10.23687/b1bd3cf0-0672-47f4-8bfa-290ae75fde9b), which provides seismic hazard values for any site in Canada defined by latitude, longitude…. SB-1 Table 3 lists S_a(0.2) values for selected towns, but those are only for Part 9 prescriptive design SB-1 Table 3OBC SB-1 Table 3: Seismic Design Data for Selected Locations in Ontario for Part 9 DesignTable 3: Seismic Design Data for Selected Locations in Ontario for Part 9 Design Location | S_a(0.2) for Seismic Design in Part 9 Ailsa Craig | 0.095 Ajax | 0.210 Alexandria | 0.589 Alliston | 0.111 Almonte | 0.337 Armstrong | 0.064 Arnprior | 0.371 Atikokan | 0.069 Attawapiskat | 0.074 Aurora | 0.138 Bancroft | 0.151….

Practice this topic

Site designation

The site designation X comes from the measured average shear wave velocity in the top 30 m (V_s30), when it is available OBC Div. B 4.1.8.4.OBC Div. B 4.1.8.4. Site Properties(1) For site designation X, as determined in accordance with Sentence (2) or (3), the peak ground acceleration, PGA(X), the peak ground velocity, PGV(X), and the 5%-damped spectral acceleration values, S_a(T,X) , at periods T of 0.2 s, 0.5 s, 1.0 s, 2.0 s, 5.0 s and 10.0 s shall (a) except as provided in Sentence (4)…. Without measured V_s30, you use the Site Class from Table 4.1.8.4.-B, based on N̄60 or s̄u OBC Div. B Table 4.1.8.4.-BOBC Div. B Table 4.1.8.4-B. Ground Profile CharacteristicsTable 4.1.8.4.-B — Ground Profile Characteristics Forming Part of Sentence 4.1.8.4.(3) Site Class, S | Ground Profile | Average Shear Wave Velocity in Top 30 m, V_s30, in m/s[1] | Average Standard Penetration Resistance in Top 30 m, N̄₆₀, in Blows per 0.3 m | Average Undrained Shear Strength in Top 30 m, s̄_u, in kPa…:

Site Class Ground N̄60 s̄u (kPa)
C Very dense soil and soft rock over 50 over 100
D Stiff soil over 15 to 50 over 50 to 100
E Soft soil over 10 to 15 over 40 to 50
F Other soils 10 or less 40 or less

Some ground profiles go straight to X_F whatever the numbers say. These include liquefiable soil, quick or sensitive clay, more than 3 m of peat, more than 8 m of highly plastic soil, or more than 30 m of soft to medium-stiff clay. X_F needs a site-specific geotechnical evaluation.

The design spectrum S(T) comes from Table 4.1.8.4.-COBC Div. B Table 4.1.8.4-C. Design Spectral AccelerationTable 4.1.8.4.-C — Design Spectral Acceleration Forming Part of Sentence 4.1.8.4.(6) T (period, s) | Design Spectral Acceleration, S(T) ≤ 0.2 | S_a(0.2,X) or S_a(0.5,X), whichever is greater 0.5 | S_a(0.5,X) 1.0 | S_a(1.0,X) 2.0 | S_a(2.0,X) 5.0 | S_a(5.0,X) 10.0 | S_a(10.0,X). For short periods, S(0.2) is the greater of S_a(0.2, X) and S_a(0.5, X).

Practice this topic

Importance factor and seismic category

I_E is 0.8, 1.0, 1.3 and 1.5 for Low, Normal, High and Post-disaster OBC Div. B Table 4.1.8.5.-AOBC Div. B Table 4.1.8.5-A. Importance Factor for Earthquake Loads and Effects, I_ETable 4.1.8.5.-A — Importance Factor for Earthquake Loads and Effects, I_E Forming Part of Sentence 4.1.8.5.(1) Importance Category | ULS | SLS[1] Low | 0.8 | [2] Normal | 1.0 | [2] High | 1.3 | [2] Post-disaster | 1.5 | [2] Notes to Table 4.1.8.5.-A: (1) See Article 4.1.8.13. (2) See Appendix A.. Note that these differ from the snow and wind factors (1.15 and 1.25 at the top end).

The seismic category comes from I_E S(0.2) and I_E S(1.0), whichever gives the more severe result OBC Div. B Table 4.1.8.5.-BOBC Div. B Table 4.1.8.5-B. Seismic Categories for BuildingsTable 4.1.8.5.-B — Seismic Categories for Buildings Forming Part of Sentence 4.1.8.5.(2) Seismic Category | I_ES(0.2) | I_ES(1.0) SC1 | I_ES(0.2) < 0.2 | I_ES(1.0) < 0.1 SC2 | 0.2 ≤ I_ES(0.2) < 0.35 | 0.1 ≤ I_ES(1.0) < 0.2 SC3 | 0.35 ≤ I_ES(0.2) ≤ 0.75 | 0.2 ≤ I_ES(1.0) ≤ 0.3 SC4 | I_ES(0.2) > 0.75 | I_ES(1.0) > 0.3…:

Category I_E S(0.2) I_E S(1.0)
SC1 under 0.2 under 0.1
SC2 0.2 to under 0.35 0.1 to under 0.2
SC3 0.35 to 0.75 0.2 to 0.3
SC4 over 0.75 over 0.3

Practice this topic

Low-hazard shortcut (4.1.8.1)

Much of Ontario has low seismic hazard. Where I_E F_s S_a(0.2, X450) is under 0.16 and I_E F_s S_a(2.0, X450) is under 0.03, Sentences 4.1.8.1.(3) to (15) give a simpler method OBC Div. B 4.1.8.1.OBC Div. B 4.1.8.1. Analysis(1) Except as permitted in Sentence (2), the deflections and specified loading due to earthquake motions shall be determined according to the requirements of Articles 4.1.8.2. to 4.1.8.23. (2) Where I_EF_sS_a(0.2,X_450) and I_EF_sS_a(2.0,X_450) are less than 0.16 and 0.03 respectively, the deflections and specified…. F_s is 1.0 for rock (N̄60 over 50), 1.6 for N̄60 of 15 to 50, and 2.8 otherwise. The simple method uses V_s = F_s S_a(T_s) I_E W / R_s, with R_s = 1.5 in most cases. An unreinforced masonry SFRS is not allowed where I_E is over 1.0 or the height is 30 m or more.

Practice this topic

SFRS, irregularities and restrictions

The SFRS must resist 100% of the earthquake load. Stiff elements that are not part of it, such as masonry infill, must be separated from the structure or made part of the SFRS OBC Div. B 4.1.8.3.OBC Div. B 4.1.8.3. General Requirements(1) The building shall be designed to meet the requirements of this Subsection and of the design standards referenced in Section 4.3. (2) Structures shall be designed with a clearly defined load path, or paths, that will transfer the inertial forces generated in an earthquake to the supporting ground. (3) The….

Table 4.1.8.6.OBC Div. B Table 4.1.8.6. Structural IrregularitiesTable 4.1.8.6. — Structural Irregularities Forming Part of Sentences .(1)4.1.8.6 and (3), Clause 4.1.8.7.(1)(c) and Article 4.1.8.10. Type | Irregularity Type and Definition | Notes 1 | Vertical Stiffness Irregularity For concrete and masonry shear walls, vertical stiffness irregularity shall be considered to exist… lists ten irregularity types. The thresholds you are most likely to be asked:

  • Type 1, vertical stiffness: one storey's drift ratio is more than 130% of an adjacent storey's. For concrete or masonry walls, it is stiffness under 70% of an adjacent storey or 80% of the three-storey average.
  • Type 2, weight: one storey weighs more than 150% of an adjacent storey. A lighter roof does not count.
  • Type 3, vertical geometric: the SFRS dimension in one storey is more than 130% of an adjacent storey's.
  • Type 6, weak storey: the storey shear strength is less than the storey above.
  • Type 7, torsional sensitivity: the ratio B exceeds 1.7.

R_d (ductility) and R_o (overstrength), with height limits per seismic category, come from Table 4.1.8.9.OBC Div. B Table 4.1.8.9. Steel Structures Designed and Detailed According to CSA S16[3][4]Table 4.1.8.9. — Steel Structures Designed and Detailed According to CSA S16[3][4] Forming Part of Sentences 4.1.8.9.(1) and (5) Type of SFRS | R_d | R_o | Restrictions[2] — Seismic Category: SC1 | Restrictions[2] — Seismic Category: SC2 | Restrictions[2] — Seismic Category: SC3 | Restrictions[2] — Seismic Category…. For example, a steel ductile moment-resisting frame has R_d = 5.0 and R_o = 1.5. In the table, NL means not limited, NP means not permitted, and a number is a height limit in metres OBC Div. B 4.1.8.9.OBC Div. B 4.1.8.9. Force Reduction Factors, System Overstrength Factors, and General Restrictions(1) Except as provided in Articles 4.1.8.20. and 4.1.8.22., the values of R_d and R_o and the corresponding system restrictions shall conform to Table 4.1.8.9. and the requirements of this Subsection. (2) When a particular value of R_d is required by this Article, the corresponding R_o shall be used. (3) For…. In buildings with mixed systems, use the lowest R_dR_o.

Post-disaster buildings need R_d of at least 2.0 and may not have a weak storey. High Importance buildings need R_d of 2.0 in SC4 and 1.5 otherwise OBC Div. B 4.1.8.10.OBC Div. B 4.1.8.10. Additional System Restrictions(1) Except as required by Clause (2)(b), structures with a Type 6 irregularity, Discontinuity in Capacity Weak Storey, as described in Table 4.1.8.6., are not permitted unless the Seismic Category is SC1 and the forces used for design of the SFRS are multiplied by R_dR_o . (2) Post-disaster buildings shall (a) not….

Practice this topic

Equivalent static force procedure

Dynamic analysis is the default. The equivalent static force procedure may be used in three cases: in SC1 or SC2; for regular structures under 60 m with T_a under 2 s; or for certain irregular structures under 20 m with T_a under 0.5 s OBC Div. B 4.1.8.7.OBC Div. B 4.1.8.7. Methods of Analysis(1) Analysis for earthquake actions shall be carried out in accordance with the Dynamic Analysis Procedure described in Article 4.1.8.12. (See Note A-4.1.8.7.(1)), except that the Equivalent Static Force Procedure described in Article 4.1.8.11. may be used for structures that meet any of the following criteria: (a)….

The base shear is V = S(T_a) M_v I_E W / (R_d R_o) OBC Div. B 4.1.8.11.OBC Div. B 4.1.8.11. Equivalent Static Force Procedure for Structures Satisfying the Conditions of Article 4.1.8.7.(1) The static loading due to earthquake motion shall be determined according to the procedures given in this Article. (2) Except as provided in Sentence (12), the specified lateral earthquake force, V, shall be calculated using the following formula: V = S(T_a)M_vI_EW/(R_dR_o) except, (a) for walls, coupled walls and…. Its limits are:

  • Minimum: V must be at least S(4.0) for walls, or S(2.0) for frames and other systems, in place of S(T_a).
  • Cap: for sites other than X_F with R_d of 1.5 or more, V need not exceed the larger of (2/3)S(0.2) I_E W/(R_d R_o) and S(0.5) I_E W/(R_d R_o).

Period T_a:

System T_a (h_n in m)
Steel moment frame 0.085 h_n^(3/4)
Concrete moment frame 0.075 h_n^(3/4)
Other moment frames 0.1 N
Braced frame 0.025 h_n
Shear walls and other 0.05 h_n^(3/4)
  • Formula: 0.60 x 10,000 / 2.6 = 2,308 kN.
  • Cap: the larger of (2/3)(0.60) x 10,000 / 2.6 = 1,538 kN and 0.35 x 10,000 / 2.6 = 1,346 kN, so 1,538 kN.
  • Design V = 1,538 kN.

Practice this topic

Drift

Deflections from the elastic analysis are multiplied by R_dR_o/I_E. The interstorey drift limit is 0.01 h_s for post-disaster buildings, 0.02 h_s for High Importance buildings and 0.025 h_s for all others OBC Div. B 4.1.8.13.OBC Div. B 4.1.8.13. Deflections and Drift Limits(1) Except as provided in Sentences (5) and (6), lateral deflections of a structure shall be calculated in accordance with the loads and requirements defined in this Subsection. (2) Lateral deflections obtained from a linear elastic analysis using the methods given in Articles 4.1.8.11. and 4.1.8.12. and incorporating…. Do not confuse these with the 1/500 wind drift limit in 4.1.3.5.

Practice this topic

Elements and non-structural components

Components in Table 4.1.8.18 are designed for V_p = 0.3 S(0.2) I_E S_p W_p, where S_p = C_p A_r A_x / R_p. S_p is limited to between 0.7 and 4.0, and A_x = 1 + 2h_x/h_n OBC Div. B 4.1.8.18.OBC Div. B 4.1.8.18. Elements of Structures, Non-Structural Components and Equipment(1) Except as provided in Sentences (2), (7) and (16), elements and components of buildings described in Table 4.1.8.18. and their connections to the structure shall be designed to accommodate the building deflections calculated in accordance with Article 4.1.8.13. and the element or component deflections calculated…. In buildings in SC1 or SC2, other than post-disaster, isolated or damped buildings, Categories 6 to 22 are exempt. Non-ductile connections, such as adhesives or power-actuated fasteners, take R_p = 1.0. Friction from gravity may not be counted on to resist earthquake forces.

  • S_p = 1.0 x 2.5 x 3 / 2.5 = 3.0, which is within the limits.
  • With S(0.2) = 0.40, I_E = 1.0 and W_p = 10 kN: V_p = 0.3 x 0.40 x 1.0 x 3.0 x 10 = 3.6 kN.

Practice this topic

Chapter review

Chapter at a glance

One line per section: the idea to carry into the exam. Then the answers that most often catch candidates out.

Practice this chapter

Questions on Earthquake load and effects (4.1.8), in the exam format, every answer explained and cited to its article. Sign in to start; a free account gets the free questions.

Code cited in this chapter

Based on the official 2024 Building Code Compendium on ontario.ca.

© King's Printer for Ontario, 2024. Reproduced with permission.

  • OBC SB-1 Seismic Data for Part 4

    The seismic hazard values to be used for the design of buildings under Part 4 can be obtained from the 2020 National Building Code of Canada Seismic Hazard Tool (https://doi.org/10.23687/b1bd3cf0-0672-47f4-8bfa-290ae75fde9b), which provides seismic hazard values for any site in Canada defined by latitude, longitude and site designation. The seismic hazard values used for the design of buildings under Part 4 must correspond to the applicable probability of exceedance stated in Subsection 4.1.8. The tool also provides seismic hazard values at additional probabilities and periods.

    Seismic hazard values can be appreciably different for localities across a large locale. Therefore, applying the same seismic hazard value to a large geographic area could result in buildings being over-designed or under-designed. Given the large number of data points in Ontario, listing every locality in a table is not practical. For archival purposes, the seismic hazard values of locations for specific latitudes and longitudes are reproduced from the 2020 National Building Code of Canada Seismic Hazard Tool on NPARC at https://doi.org/10.4224/nqzr-dz38. The digital properties of the NPARC website are more suited for a static, archival data set. As such, Figure A-1.1.3.1.(4) for Division B identifies the NPARC website as the primary data set for the specified latitude and longitudes.

    The parameters used to represent seismic hazard for specific geographical locations are the 5%-damped horizontal spectral acceleration for periods of 0.2 s, 0.5 s, 1.0 s, 2.0 s, 5.0 s and 10.0 s, the horizontal peak ground acceleration (PGA) and the horizontal peak ground velocity (PGV) corresponding to a 2% probability of being exceeded in 50 years. The six spectral acceleration parameters are deemed sufficient to define spectra closely matching the shape of the uniform hazard spectra (UHS) for design purposes. Spectral acceleration values for additional periods are provided for use in the selection of ground motion time histories. Spectral acceleration values for additional probabilities of exceedance are also provided.

    The seismic hazard values are mean values based on a statistical analysis of the earthquakes that have been experienced in Ontario and adjacent regions.(11) They were updated for the 2024 edition of the Building Code by slightly revising the seismic source zones(12) to match new information, revising the ground motion models (GMMs),(13) and using a probabilistic model to combine all inputs.

    In addition, the method of determining seismic hazard values for different site designations has changed. For the 2012 Building Code, the seismic hazard values were calculated for reference Site Class C, and the values for other site designations were determined by applying a site coefficient to the calculated values. For the 2024 Building Code, the seismic hazard values for each site designation were calculated directly.

    For almost all locations, the revised GMMs are the most significant reason for changes in the seismic hazard values from the 2012 Building Code. In general, the estimated seismic hazard has increased across Ontario.

    Further details regarding the representation of seismic hazard can be found in the Commentary entitled Design for Seismic Effects in the "Structural Commentaries (User's Guide – NBC 2020: Part 4 of Division B)".

    Open OBC SB-1 in the code viewer
  • OBC SB-1 Table 3: Seismic Design Data for Selected Locations in Ontario for Part 9 Design

    Table 3: Seismic Design Data for Selected Locations in Ontario for Part 9 Design

    Location | S_a(0.2) for Seismic Design in Part 9

    Ailsa Craig | 0.095

    Ajax | 0.210

    Alexandria | 0.589

    Alliston | 0.111

    Almonte | 0.337

    Armstrong | 0.064

    Arnprior | 0.371

    Atikokan | 0.069

    Attawapiskat | 0.074

    Aurora | 0.138

    Bancroft | 0.151

    Barrie | 0.108

    Barriefield | 0.162

    Beaverton | 0.117

    Belleville | 0.162

    Belmont | 0.116

    Big Trout Lake (Kitchenuhmaykoosib) | 0.054

    CFB Borden | 0.107

    Bracebridge | 0.116

    Bradford | 0.123

    Brampton | 0.168

    Brantford | 0.155

    Brighton | 0.173

    Brockville | 0.259

    Burk's Falls | 0.143

    Burlington | 0.266

    Caledon | 0.168

    Cambridge | 0.141

    Campbellford | 0.144

    Cannington | 0.122

    Carleton Place | 0.302

    Cavan | 0.140

    Centralia | 0.092

    Chapleau | 0.071

    Chatham | 0.112

    Chesley | 0.083

    Clinton | 0.084

    Coboconk | 0.120

    Cobourg | 0.179

    Cochrane | 0.222

    Colborne | 0.176

    Collingwood | 0.096

    Cornwall | 0.587

    Corunna | 0.087

    Deep River | 0.389

    Deseronto | 0.158

    Dorchester | 0.112

    Dorion | 0.059

    Dresden | 0.104

    Dryden | 0.072

    Dundalk | 0.097

    Dunnville | 0.232

    Durham | 0.088

    Dutton | 0.116

    Earlton | 0.182

    Edison | 0.070

    Elliot Lake | 0.074

    Elmvale | 0.101

    Embro | 0.111

    Englehart | 0.175

    Espanola | 0.086

    Exeter | 0.090

    Fenelon Falls | 0.121

    Fergus | 0.115

    Forest | 0.087

    Fort Erie | 0.312

    Fort Erie (Ridgeway) | 0.307

    Fort Frances | 0.064

    Gananoque | 0.180

    Geraldton | 0.057

    Glencoe | 0.107

    Goderich | 0.079

    Gore Bay | 0.071

    Graham | 0.071

    Gravenhurst (Muskoka Airport) | 0.112

    Grimsby | 0.301

    Guelph | 0.133

    Guthrie | 0.109

    Haileybury | 0.219

    Haldimand (Caledonia) | 0.215

    Haldimand (Hagersville) | 0.172

    Haliburton | 0.133

    Halton Hills (Georgetown) | 0.155

    Hamilton | 0.260

    Hanover | 0.085

    Hastings | 0.141

    Hawkesbury | 0.506

    Hearst | 0.073

    Honey Harbour | 0.103

    Hornepayne | 0.063

    Huntsville | 0.129

    Ingersoll | 0.116

    Iroquois Falls | 0.196

    Jellicoe | 0.057

    Kapuskasing | 0.112

    Kemptville | 0.429

    Kenora | 0.064

    Killaloe | 0.264

    Kincardine | 0.076

    Kingston | 0.161

    Kinmount | 0.123

    Kirkland Lake | 0.159

    Kitchener | 0.122

    Lakefield | 0.130

    Lansdowne House | 0.056

    Leamington | 0.114

    Lindsay | 0.126

    Lion's Head | 0.080

    Listowel | 0.093

    London | 0.108

    Lucan | 0.097

    Maitland | 0.282

    Markdale | 0.089

    Markham | 0.182

    Martin | 0.072

    Matheson | 0.160

    Mattawa | 0.446

    Midland | 0.101

    Milton | 0.191

    Milverton | 0.098

    Minden | 0.124

    Mississauga | 0.219

    Mississauga (Lester B. Pearson International Airport) | 0.193

    Mississauga (Port Credit) | 0.247

    Mitchell | 0.093

    Moosonee | 0.081

    Morrisburg | 0.558

    Mount Forest | 0.093

    Nakina | 0.057

    Nanticoke (Jarvis) | 0.156

    Nanticoke (Port Dover) | 0.144

    Napanee | 0.156

    New Liskeard | 0.209

    Newcastle | 0.186

    Newcastle (Bowmanville) | 0.188

    Newmarket | 0.132

    Niagara Falls | 0.321

    North Bay | 0.247

    Norwood | 0.136

    Oakville | 0.260

    Orangeville | 0.115

    Orillia | 0.109

    Oshawa | 0.192

    Ottawa (Metropolitan) | N/A

    Ottawa (City Hall) | 0.439

    Ottawa (Barrhaven) | 0.427

    Ottawa (Kanata) | 0.401

    Ottawa (MacDonald-Cartier Int'l Airport) | 0.446

    Ottawa (Orleans) | 0.474

    Owen Sound | 0.083

    Pagwa River | 0.060

    Paris | 0.141

    Parkhill | 0.092

    Parry Sound | 0.110

    Pelham (Fonthill) | 0.311

    Pembroke | 0.379

    Penetanguishene | 0.101

    Perth | 0.225

    Petawawa | 0.379

    Peterborough | 0.135

    Petrolia | 0.092

    Pickering (Zones 1 to 4) | 0.219

    Picton | 0.159

    Plattsville | 0.119

    Point Alexander | 0.391

    Port Burwell | 0.132

    Port Colborne | 0.298

    Port Elgin | 0.077

    Port Hope | 0.181

    Port Perry | 0.144

    Port Stanley | 0.123

    Prescott | 0.350

    Princeton | 0.129

    Raith | 0.067

    Rayside-Balfour (Chelmsford) | 0.104

    Red Lake | 0.068

    Renfrew | 0.352

    Richmond Hill | 0.163

    Rockland | 0.510

    Sarnia | 0.085

    Sault Ste. Marie | 0.062

    Schreiber | 0.057

    Seaforth | 0.087

    Shelburne | 0.104

    Simcoe | 0.141

    Sioux Lookout | 0.073

    Smiths Falls | 0.256

    Smithville | 0.296

    Smooth Rock Falls | 0.200

    South River | 0.164

    Southampton | 0.077

    St. Catharines | 0.319

    St. Mary's | 0.101

    St. Thomas | 0.117

    Stirling | 0.149

    Stratford | 0.103

    Strathroy | 0.100

    Sturgeon Falls | 0.183

    Sudbury | 0.110

    Sundridge | 0.157

    Tavistock | 0.108

    Temagami | 0.239

    Thamesford | 0.111

    Thedford | 0.089

    Thunder Bay | 0.061

    Tillsonburg | 0.126

    Timmins | 0.125

    Timmins (Porcupine) | 0.140

    Toronto Metropolitan Region | N/A

    Etobicoke | 0.193

    North York | 0.195

    Scarborough | 0.219

    Toronto (City Hall) | 0.249

    Trenton | 0.167

    Trout Creek | 0.186

    Uxbridge | 0.139

    Vaughan (Woodbridge) | 0.167

    Vittoria | 0.139

    Walkerton | 0.083

    Wallaceburg | 0.098

    Waterloo | 0.118

    Watford | 0.095

    Wawa | 0.062

    Welland | 0.308

    West Lorne | 0.118

    Whitby | 0.203

    Whitby (Brooklin) | 0.176

    White River | 0.060

    Wiarton | 0.080

    Windsor | 0.096

    Wingham | 0.083

    Woodstock | 0.118

    Wyoming | 0.090

    Open OBC SB-1 in the code viewer
  • OBC Div. B 4.1.8.4. Site Properties

    (1)For site designation X, as determined in accordance with Sentence (2) or (3), the peak ground acceleration, PGA(X), the peak ground velocity, PGV(X), and the 5%-damped spectral acceleration values, S_a(T,X) , at periods T of 0.2 s, 0.5 s, 1.0 s, 2.0 s, 5.0 s and 10.0 s shall

    (a)except as provided in Sentence (4), be determined in accordance with Subsection 1.1.3., and

    (b)except as provided in Article 4.1.8.23., correspond to a 2% probability of exceedance in 50 years.

    (2)Except as provided in Sentence (3), the site designation referred to in Sentence (1) shall be determined using the average shear wave velocity, V_s30 , calculated from in situ measurements of shear wave velocity, as follows:

    (a)for the ground profiles described in Table 4.1.8.4.-A, the site designation shall be determined in accordance with the Table, and

    (b)for all other ground profiles, the site designation shall be X_V , where V is the value of V_s30 . (See Note A-4.1.8.4.(2) and (3))

    (3)Where Vs_30 calculated from in situ measurements is not available, the site designation referred to in Sentence (1) shall be X_S , where S is the Site Class determined using the energy-corrected average standard penetration resistance, N¯_60 , or the average undrained shear strength, s¯_u , in accordance with Table 4.1.8.4.-B, N¯_60 and s¯_u being calculated based on rational analysis. (See Notes A-4.1.8.4.(3) and A-4.1.8.4.(2) and (3))

    (4)Site-specific geotechnical evaluation is required to determine the values of PGA(X_F) , PGV(X_F) and S_a(T,X_F) for site designation X_F .

    (5)Where structures on liquefiable soils have a fundamental lateral period, T_a , of 0.5 s or less, the site designation X and the corresponding values of S_a(T,X) and PGA(X) are permitted to be determined in accordance with Sentence (1) by assuming that the soils are not liquefiable.

    (6)The design spectral acceleration, S(T), shall be determined in accordance with Table 4.1.8.4.-C, using log-log or linear interpolation for intermediate values of T. (See Note A-4.1.8.4.(6))

    (7)Where required for the application of a standard referenced in this Subsection, the acceleration-based site coefficient, F_a , for site designation X shall be taken as S(0.2)/S_a(0.2,X_450) and the velocity-based site coefficient, F_v , for site designation X shall be taken as S(1.0)/S_a(1.0,X_450) .

    Open OBC Div. B 4.1.8.4. in the code viewer
  • OBC Div. B Table 4.1.8.4-B. Ground Profile Characteristics

    Table 4.1.8.4.-B — Ground Profile Characteristics Forming Part of Sentence 4.1.8.4.(3) Site Class, S | Ground Profile | Average Shear Wave Velocity in Top 30 m, V_s30, in m/s[1] | Average Standard Penetration Resistance in Top 30 m, N̄₆₀, in Blows per 0.3 m | Average Undrained Shear Strength in Top 30 m, s̄_u, in kPa A | Hard rock[2] | V_s30 > 1 500 | N/A | N/A B | Rock[2] | 760 < V_s30 ≤ 1 500 | N/A | N/A C | Very dense soil and soft rock | 360 < V_s30 ≤ 760 | N̄₆₀ > 50 | s̄_u > 100 D | Stiff soil | 180 < V_s30 ≤ 360 | 15 < N̄₆₀ ≤ 50 | 50 < s̄_u ≤ 100 E[4] | Soft soil | 140 < V_s30 ≤ 180 | 10 < N̄₆₀ ≤ 15 | 40 < s̄_u ≤ 50 F[5] | Other soils[3] | V_s30 ≤ 140 | N̄₆₀ ≤ 10 | s̄_u ≤ 40 Notes to Table 4.1.8.4.-B: (1) See Note A-4.1.8.4. (2) and (3). (2) Site designations X_A and X_B, corresponding to Site Classes A and B, are not to be used in cases where the ground profile contains more than 3 m of softer materials between rock and the underside of footing or mat foundations. The appropriate site designation for such cases is X₇₆₀. (3) Site-specific geotechnical evaluation is required. (4) Site Class E includes any ground profile other than Site Class F that contains more than 3 m of soil with all the following characteristics: - plasticity index, PI > 20, - moisture content, w ≥ 40%, and - undrained shear strength, s_u < 25 kPa. (5) Site Class F includes any ground profile that contains: - liquefiable soil, quick and highly sensitive clay, collapsible weakly cemented soil, or other soil susceptible to failure or collapse under seismic loading, - more than 3 m of peat and/or highly organic clay, - more than 8 m of highly plastic soil with PI > 75, or - more than 30 m of soft to medium-stiff clay.

    Open OBC Div. B Table 4.1.8.4-B. in the code viewer
  • OBC Div. B Table 4.1.8.4-C. Design Spectral Acceleration

    Table 4.1.8.4.-C — Design Spectral Acceleration Forming Part of Sentence 4.1.8.4.(6) T (period, s) | Design Spectral Acceleration, S(T) ≤ 0.2 | S_a(0.2,X) or S_a(0.5,X), whichever is greater 0.5 | S_a(0.5,X) 1.0 | S_a(1.0,X) 2.0 | S_a(2.0,X) 5.0 | S_a(5.0,X) 10.0 | S_a(10.0,X)

    Open OBC Div. B Table 4.1.8.4-C. in the code viewer
  • OBC Div. B Table 4.1.8.5-A. Importance Factor for Earthquake Loads and Effects, I_E

    Table 4.1.8.5.-A — Importance Factor for Earthquake Loads and Effects, I_E Forming Part of Sentence 4.1.8.5.(1) Importance Category | ULS | SLS[1] Low | 0.8 | [2] Normal | 1.0 | [2] High | 1.3 | [2] Post-disaster | 1.5 | [2] Notes to Table 4.1.8.5.-A: (1) See Article 4.1.8.13. (2) See Appendix A.

    Open OBC Div. B Table 4.1.8.5-A. in the code viewer
  • OBC Div. B Table 4.1.8.5-B. Seismic Categories for Buildings

    Table 4.1.8.5.-B — Seismic Categories for Buildings Forming Part of Sentence 4.1.8.5.(2) Seismic Category | I_ES(0.2) | I_ES(1.0) SC1 | I_ES(0.2) < 0.2 | I_ES(1.0) < 0.1 SC2 | 0.2 ≤ I_ES(0.2) < 0.35 | 0.1 ≤ I_ES(1.0) < 0.2 SC3 | 0.35 ≤ I_ES(0.2) ≤ 0.75 | 0.2 ≤ I_ES(1.0) ≤ 0.3 SC4 | I_ES(0.2) > 0.75 | I_ES(1.0) > 0.3 Notes to Table 4.1.8.5.-B: (1) The Seismic Category of a building shall be taken as the more severe of the categories determined on the basis of linS(0.2) and linS(1.0) , irrespective of the fundamental lateral period of the building, T_a .

    Open OBC Div. B Table 4.1.8.5-B. in the code viewer
  • OBC Div. B 4.1.8.1. Analysis

    (1)Except as permitted in Sentence (2), the deflections and specified loading due to earthquake motions shall be determined according to the requirements of Articles 4.1.8.2. to 4.1.8.23.

    (2)Where I_EF_sS_a(0.2,X_450) and I_EF_sS_a(2.0,X_450) are less than 0.16 and 0.03 respectively, the deflections and specified loading due to earthquake motions are permitted to be determined in accordance with Sentences (3) to (15), where

    (a)I_E is the earthquake importance factor and has a value of 0.8, 1.0, 1.3 and 1.5 for buildings in the Low, Normal, High and Post-disaster Importance Categories respectively,

    (b)F_s is the site coefficient based on the average N¯_60 or s¯_u , as defined in Article 4.1.8.2., for the top 30 m of soil below the footings, pile caps or mat foundations and has a value of

    (i)1.0 for rock sites or when N¯_60 > 50 or s¯_u > 100 kPa,

    (ii)1.6 when 15 ≤ N¯_60 ≤ 50 or 50 kPa ≤ s¯_u ≤ 100 kPa , and

    (iii)2.8 for all other cases, and

    (c)S_a(T, X₄₅₀) is the 5%-damped spectral acceleration value at period T for site designation X₄₅₀, as defined in Article 4.1.8.2., determined in accordance with Subsection 1.1.3. and corresponding to a 2% probability of exceedance in 50 years.

    (3)The structure shall have a clearly defined

    (a)seismic force resisting system (SFRS) to resist the earthquake loads and their effects, and

    (b)load path (or paths) that will transfer the inertial forces generated in an earthquake to the supporting ground.

    (4)An unreinforced masonry SFRS shall not be permitted where

    (a)I_E is greater than 1.0, or

    (b)the height above grade is greater than or equal to 30 m.

    (5)The height above grade of an SFRS designed in accordance with CSA S136, "North American Specification for the Design of Cold-Formed Steel Structural Members (using the Appendix B provisions applicable to Canada)," shall be less than 15 m.

    (6)Earthquake forces shall be assumed to act horizontally and independently about any two orthogonal axes.

    (7)The specified lateral earthquake force, V_s , at the base of the structure in the direction under consideration shall be calculated as follows:

    V_s = F_sS_a(T_s,X_450)I_EW/R_s

    where

    S_a(T,X_450) = value of S_a(T,X_450) determined by linear interpolation between the values of S_a(0.2,X_450),S_a(0.5,X_450) and S_a(1.0,X_450),

    = S_a(0.2,X_450) for T_s ≤ 0.2 s, and

    = S_a(1.0,X_450) for T_s ≥ 1.0 s,

    W = sumofW_i over the height of the building, where W_i is defined in Article 4.1.8.2., and

    R_s = 1.5 , except R_s = 1.0 for structures where the storey strength is less than that in the storey above and for an unreinforced masonry SFRS,

    where

    T_s = fundamental lateral period of vibration of the building, as defined in Article 4.1.8.2.,

    = 0.085(h_n)3/4 for steel moment frames,

    = 0.075(h_n)^(3/4) for concrete moment frames,

    = 0.1N for other moment frames,

    = 0.025h_n for braced frames, and

    = 0.05(h_n)^(3/4) for shear walls and other structures,

    where

    h_n = height, in m, above the base to level n, as defined in Article 4.1.8.2., and

    N = total number of storeys above exterior grade to level n, as defined in Article 4.1.8.2.,

    except that, in cases where R_s = 1.5 , V_s need not be greater than F_sS_a(0.5,X_450)I_EW/R_s .

    (8)The total lateral earthquake design force, V_s , shall be distributed over the height of the building in accordance with the following formula:

    F_x = V_sW_xh_x/(∑_(i = 1)^nw_ih_i)

    where

    F_x = force applied through the centre of mass at level x,

    W_x,W_i = portion of W that is located at or is assigned to level x or i respectively, and

    h_x , h_i = height, in m, above the base to level x or i respectively, as defined in Article 4.1.8.2.

    (9)Accidental torsional effects applied concurrently with F_x shall be considered by applying torsional moments about the vertical axis at each level for each of the following cases considered separately:

    (a)+ 0.1D_nxF_x , and

    (b)- 0.1D_nxF_x .

    (10)Deflections obtained from a linear analysis shall include the effects of torsion and be multiplied by R_s/I_E to get realistic values of expected deflections.

    (11)The deflections referred to in Sentence (10) shall be used to calculate the largest interstorey deflection, which shall not exceed

    (a)0.01 h_s for post-disaster buildings,

    (b)0.02 h_s for High Importance Category buildings, and

    (c)0.025h_s for all other buildings,

    where h_s is the interstorey height as defined in Article 4.1.8.2.

    (12)When earthquake forces are calculated using R_s = 1.5 , the following elements in the SFRS shall have their design forces due to earthquake effects increased by 33%:

    (a)diaphragms and their chords, connections, struts and collectors,

    (b)tie downs in wood or drywall shear walls,

    (c)connections and anchor bolts in steel- and wood-braced frames,

    (d)connections in precast concrete, and

    (e)connections in steel moment frames.

    (13)Except as provided in Sentence (14), where cantilever parapet walls, other cantilever walls, exterior ornamentation and appendages, towers, chimneys or penthouses are connected to or form part of a building, they shall be designed, along with their connections, for a lateral force, V_sp , distributed according to the distribution of mass of the element and acting in the lateral direction that results in the most critical loading for design using the following equation:

    V_sp = 0.9S_a(0.2,X_450)F_sI_EW_p

    where

    W_p = weight of a portion of a structure as defined in Article 4.1.8.2.

    (14)The value of V_sp shall be doubled for unreinforced masonry elements.

    (15)Structures designed in accordance with this Article need not comply with the seismic requirements stated in the applicable design standard referenced in Section 4.3.

    Open OBC Div. B 4.1.8.1. in the code viewer
Show all 18 articles
  • OBC Div. B 4.1.8.3. General Requirements

    (1)The building shall be designed to meet the requirements of this Subsection and of the design standards referenced in Section 4.3.

    (2)Structures shall be designed with a clearly defined load path, or paths, that will transfer the inertial forces generated in an earthquake to the supporting ground.

    (3)The structure shall have a clearly defined SFRS, as defined in Article 4.1.8.2.

    (4)The SFRS shall be designed to resist 100% of the earthquake loads and their effects. (See Note A-4.1.8.3.(4))

    (5)All structural framing elements not considered to be part of the SFRS must be investigated and shown to behave elastically or to have sufficient non-linear capacity to support their gravity loads while undergoing earthquake-induced deformations calculated from the deflections determined in Article 4.1.8.13.

    (6)Stiff elements that are not considered part of the SFRS, such as concrete, masonry, brick or precast walls or panels, shall be

    (a)separated from all structural elements of the building such that no interaction takes place as the building undergoes deflections due to earthquake effects as calculated in this Subsection, or

    (b)made part of the SFRS and satisfy the requirements of this Subsection. (See Note A-4.1.8.3.(6))

    (7)Stiffness imparted to the structure from elements not part of the SFRS, other than those described in Sentence (6), shall not be used to resist earthquake deflections but shall be accounted for

    (a)in calculating the period of the structure for determining forces if the added stiffness decreases the fundamental lateral period by more than 15%,

    (b)in determining the irregularity of the structure, except the additional stiffness shall not be used to make an irregular SFRS regular or to reduce the effects of torsion, and (See Note A-4.1.8.3.(7)(b) and

    (c)

    (c) in designing the SFRS if inclusion of the elements not part of the SFRS in the analysis has an adverse effect on the SFRS. (See Note A-4.1.8.3.(7)(b) and (c))

    (8)Structural modeling shall be representative of the magnitude and spatial distribution of the mass of the building and of the stiffness of all elements of the SFRS, including stiff elements that are not separated in accordance with Sentence 4.1.8.3.(6), and shall account for

    (a)the effect of cracked sections in reinforced concrete and reinforced masonry elements,

    (b)the effect of the finite size of members and joints,

    (c)sway effects arising from the interaction of gravity loads with the displaced configuration of the structure, and

    (d)other effects that influence the lateral stiffness of the building.

    (See Note A-4.1.8.3.(8))

    Open OBC Div. B 4.1.8.3. in the code viewer
  • OBC Div. B Table 4.1.8.6. Structural Irregularities

    Table 4.1.8.6. — Structural Irregularities Forming Part of Sentences .(1)4.1.8.6 and (3), Clause 4.1.8.7.(1)(c) and Article 4.1.8.10. Type | Irregularity Type and Definition | Notes 1 | Vertical Stiffness Irregularity For concrete and masonry shear walls, vertical stiffness irregularity shall be considered to exist where the lateral stiffness of the SFRS in any storey is less than 70% of the stiffness in an adjacent storey, or less than 80% of the average stiffness in the three storeys above or below. For all other types of SFRS, vertical stiffness irregularity shall be considered to exist where the interstorey deflection under lateral earthquake forces divided by the interstorey height, h_s, of any storey is greater than 130% of that of an adjacent storey. | [3][4][5] 2 | Weight (mass) Irregularity Weight irregularity shall be considered to exist where the weight, W_i, of any storey is more than 150% of the weight of an adjacent storey. A roof that is lighter than the floor below need not be considered. | [3] 3 | Vertical Geometric Irregularity Vertical geometric irregularity shall be considered to exist where the horizontal dimension of the SFRS in any storey is more than 130% of that in an adjacent storey. | [3][4][6] 4 | In-Plane Discontinuity in Vertical Lateral-Force-Resisting Element Except for braced frames and moment-resisting frames, an in-plane discontinuity shall be considered to exist where there is an offset of a lateral-force-resisting element of the SFRS or a reduction in lateral stiffness of the resisting element in the storey below. | [3][4][6] 5 | Out-of-Plane Offsets Discontinuities in a lateral force path, such as out-of-plane offsets of the vertical elements of the SFRS. | [3][4][6] 6 | Discontinuity in Capacity – Weak Storey A weak storey is one in which the storey shear strength is less than that in the storey above. The storey shear strength is the total strength of all seismic-resisting elements of the SFRS sharing the storey shear for the direction under consideration. | [3][4] 7 | Torsional Sensitivity (to be considered when diaphragms are not flexible) Torsional sensitivity shall be considered to exist when the ratio B calculated according to Sentence 4.1.8.11.(10) exceeds 1.7. | [3][4][7] 8 | Non-orthogonal Systems A non-orthogonal system irregularity shall be considered to exist when the SFRS is not oriented along a set of orthogonal axes. | [3][8] 9 | Gravity-Induced Lateral Demand Irregularity Gravity-induced lateral demand irregularity on the SFRS shall be considered to exist where the ratio α calculated in accordance with Sentence 4.1.8.10.(7) exceeds 0.1 for an SFRS with self-centering characteristics and 0.03 for other systems. | [3][4][8] 10 | Sloped Column Irregularity Sloped column irregularity shall be considered to exist where a vertical member that is inclined more than 2° from the vertical supports a portion of the weight of the building in axial compression. | [4] Notes to Table 4.1.8.6.: (1) One-storey penthouses with a weight of less than 10% of the level below need not be considered in the application of this Table. (2) See Note A-Table 4.1.8.6. (3) See Article 4.1.8.7. (4) See Article 4.1.8.10. (5) Increased stiffness in storeys below grade need not be considered in the determination of vertical stiffness irregularity. (6) See Article 4.1.8.15. (7) See Sentences 4.1.8.11.(10) and (11), and 4.1.8.12.(4). (8) See Article 4.1.8.8.

    Open OBC Div. B Table 4.1.8.6. in the code viewer
  • OBC Div. B Table 4.1.8.9. Steel Structures Designed and Detailed According to CSA S16[3][4]

    Table 4.1.8.9. — Steel Structures Designed and Detailed According to CSA S16[3][4] Forming Part of Sentences 4.1.8.9.(1) and (5) Type of SFRS | R_d | R_o | Restrictions[2] — Seismic Category: SC1 | Restrictions[2] — Seismic Category: SC2 | Restrictions[2] — Seismic Category: SC3 | Restrictions[2] — Seismic Category: SC4 Ductile moment-resisting frames | 5.0 | 1.5 | NL | NL | NL | NL Moderately ductile moment-resisting frames | 3.5 | 1.5 | NL | NL | NL | NL Limited ductility moment-resisting frames | 2.0 | 1.3 | NL | NL | 60 | 30 Moderately ductile truss moment-resisting frames | 3.5 | 1.6 | NL | NL | 50 | 30 Moderately ductile concentrically braced frames Tension-compression braces | 3.0 | 1.3 | NL | NL | 40 | 40 Moderately ductile concentrically braced frames Tension only braces | 3.0 | 1.3 | NL | NL | 20 | 20 Limited ductility concentrically braced frames Tension-compression braces | 2.0 | 1.3 | NL | NL | 60 | 60 Limited ductility concentrically braced frames Tension only braces | 2.0 | 1.3 | NL | NL | 40 | 40 Ductile buckling-restrained braced frames | 4.0 | 1.2 | NL | NL | 40 | 40 Ductile eccentrically braced frames | 4.0 | 1.5 | NL | NL | NL | NL Ductile plate walls | 5.0 | 1.6 | NL | NL | NL | NL Moderately ductile plate walls | 3.5 | 1.3 | NL | NL | 40 | 40 Limited ductility plate walls | 2.0 | 1.5 | NL | NL | 60 | 60 Conventional construction of moment-resisting frames, braced frames or plate walls Assembly occupancies | 1.5 | 1.3 | NL | NL | 15 | 15 Conventional construction of moment-resisting frames, braced frames or plate walls Other occupancies | 1.5 | 1.3 | NL | NL | 60 | 40 Other steel SFRS(s) not defined above | 1.0 | 1.0 | 15 | 15 | NP | NP Table 4.1.8.9. (continued) — Concrete Structures Designed and Detailed According to CSA A23.3 Type of SFRS | R_d | R_o | Restrictions[2] — Seismic Category: SC1 | Restrictions[2] — Seismic Category: SC2 | Restrictions[2] — Seismic Category: SC3 | Restrictions[2] — Seismic Category: SC4 Ductile moment-resisting frames | 4.0 | 1.7 | NL | NL | NL | NL Moderately ductile moment-resisting frames | 2.5 | 1.4 | NL | NL | 60 | 40 Ductile coupled walls | 4.0 | 1.7 | NL | NL | NL | NL Moderately ductile coupled walls | 2.5 | 1.4 | NL | NL | NL | 60 Ductile partially coupled walls | 3.5 | 1.7 | NL | NL | NL | NL Moderately ductile partially coupled walls | 2.0 | 1.4 | NL | NL | NL | 60 Ductile shear walls | 3.5 | 1.6 | NL | NL | NL | NL Moderately ductile shear walls | 2.0 | 1.4 | NL | NL | NL | 60 Conventional construction Moment-resisting frames | 1.5 | 1.3 | NL | NL | 20 | 10[5][6] Conventional construction Shear walls | 1.5 | 1.3 | NL | NL | 40 | 30 Conventional construction Two-way slabs without beams | 1.3 | 1.3 | 20 | 15 | NP | NP Tilt-up Construction Moderately ductile walls and frames | 2.0 | 1.3 | 30 | 25 | 25 | 25 Tilt-up Construction Limited ductility walls and frames | 1.5 | 1.3 | 30 | 25 | 20 | 20[7] Tilt-up Construction Conventional walls and frames | 1.3 | 1.3 | 25 | 20 | NP | NP Other concrete SFRS(s) not listed above | 1.0 | 1.0 | 15 | 15 | NP | NP Table 4.1.8.9. (continued) — Timber Structures Designed and Detailed According to CSA O86 Type of SFRS | R_d | R_o | Restrictions[2] — Seismic Category: SC1 | Restrictions[2] — Seismic Category: SC2 | Restrictions[2] — Seismic Category: SC3 | Restrictions[2] — Seismic Category: SC4 Shear walls Nailed shear walls: wood-based panel | 3.0 | 1.7 | NL | NL | 30 | 20 Shear walls Shear walls: wood-based and gypsum panels in combination | 2.0 | 1.7 | NL | NL | 20 | 20 Moderately ductile cross-laminated timber shear walls: platform-type construction | 2.0 | 1.5 | 30 | 30 | 30 | 20 Limited ductility cross-laminated timber shear walls: platform-type construction | 1.0 | 1.3 | 30 | 30 | 30 | 20 Braced or moment-resisting frames with ductile connections Moderately ductile | 2.0 | 1.5 | NL | NL | 20 | 20 Braced or moment-resisting frames with ductile connections Limited ductility | 1.5 | 1.5 | NL | NL | 15 | 15 Other wood- or gypsum-based SFRS(s) not listed above | 1.0 | 1.0 | 15 | 15 | NP | NP Table 4.1.8.9. (continued) — Masonry Structures Designed and Detailed According to CSA S304 Type of SFRS | R_d | R_o | Restrictions[2] — Seismic Category: SC1 | Restrictions[2] — Seismic Category: SC2 | Restrictions[2] — Seismic Category: SC3 | Restrictions[2] — Seismic Category: SC4 Ductile shear walls | 3.0 | 1.5 | NL | NL | 60 | 40 Moderately ductile shear walls | 2.0 | 1.5 | NL | NL | 60 | 40 Conventional construction Shear walls | 1.5 | 1.5 | NL | 60 | 30 | 15 Conventional construction Moment-resisting frames | 1.5 | 1.5 | NL | 30 | NP | NP Unreinforced masonry | 1.0 | 1.0 | 30 | 15 | NP | NP Other masonry SFRS(s) not listed above | 1.0 | 1.0 | 15 | NP | NP | NP Table 4.1.8.9. (continued) — Cold-Formed Steel Structures Designed and Detailed According to CSA S136 Type of SFRS | R_d | R_o | Restrictions[2] — Seismic Category: SC1 | Restrictions[2] — Seismic Category: SC2 | Restrictions[2] — Seismic Category: SC3 | Restrictions[2] — Seismic Category: SC4 Shear walls Screw-connected shear walls - wood-based panels | 2.5 | 1.7 | 20 | 20 | 20 | 20 Shear walls Screw-connected shear walls - wood-based and gypsum panels in combination | 1.5 | 1.7 | 20 | 20 | 20 | 20 Diagonal strap concentrically braced walls Limited ductility | 1.9 | 1.3 | 20 | 20 | 20 | 20 Diagonal strap concentrically braced walls Conventional construction | 1.2 | 1.3 | 15 | 15 | NP | NP Other cold-formed SFRSs not listed above | 1.0 | 1.0 | 15 | 15 | NP | NP Notes to Table 4.1.8.9.: (1) See Article 4.1.8.10. (2) NP = system is not permitted. NL = system is permitted and not limited in height as an SFRS. Numbers in this Table are maximum height limits above grade, in m. Height may be limited in other Parts of the Code. The most stringent requirement governs. (3) Higher design force levels are prescribed in CSA S16 for some heights of buildings. (4) See Note A-Table 4.1.8.9. (5) Frames are limited to a maximum of 2 storeys. (6) The maximum height limit is permitted to be increased to 15 m where I_ES(1.0) ≤ 0.3 . (7) Frames are limited to a maximum of 3 storeys.

    Open OBC Div. B Table 4.1.8.9. in the code viewer
  • OBC Div. B 4.1.8.9. Force Reduction Factors, System Overstrength Factors, and General Restrictions

    (1)Except as provided in Articles 4.1.8.20. and 4.1.8.22., the values of R_d and R_o and the corresponding system restrictions shall conform to Table 4.1.8.9. and the requirements of this Subsection.

    (2)When a particular value of R_d is required by this Article, the corresponding R_o shall be used.

    (3)For combinations of different types of SFRS acting in the same direction in the same storey, R_dR_o shall be taken as the lowest value of R_dR_o corresponding to these systems.

    (4)For vertical variations of R_dR_o , excluding rooftop structures not exceeding two storeys in height whose weight is less than the greater of 10% of W and 30% of W_i of the level below, the value of R_dR_o used in the design of any storey shall be less than or equal to the lowest value of R_dR_o used in the given direction for the storeys above, and the requirements of Sentence 4.1.8.15.(6) must be satisfied. (See Note A-4.1.8.9.(4))

    (5)If it can be demonstrated through testing, research and analysis that the seismic performance of a structural system is at least equivalent to one of the types of SFRS defined in Table 4.1.8.9., then such a structural system will qualify for values of R_d and R_o corresponding to the equivalent type in that Table. (See Note A-4.1.8.9.(5))

    Open OBC Div. B 4.1.8.9. in the code viewer
  • OBC Div. B 4.1.8.10. Additional System Restrictions

    (1)Except as required by Clause (2)(b), structures with a Type 6 irregularity, Discontinuity in Capacity Weak Storey, as described in Table 4.1.8.6., are not permitted unless the Seismic Category is SC1 and the forces used for design of the SFRS are multiplied by R_dR_o .

    (2)Post-disaster buildings shall

    (a)not have Type 1, 3, 4, 5, 7, 9 or 10 irregularities as described in Table 4.1.8.6., where the Seismic Category is SC3 or SC4.

    (b)not have a Type 6 irregularity as described in Table 4.1.8.6.,

    (c)have an SFRS with an R_d of 2.0 or greater,

    (d)where they are constructed with concrete or masonry shear walls, have no storey with a lateral stiffness that is less than that of the storey above it, and

    (e)where they are constructed with other types of SFRS, have no storey for which the interstorey deflection under lateral earthquake forces divided by the interstorey height, h_s, is greater than that of the storey above it.

    (3)High Importance Category buildings shall

    (a)not have Type 1, 3, 4, 5, 7, 9 or 10 irregularities as described in Table 4.1.8.6., where the Seismic Category is SC4,

    (b)not have a Type 6 irregularity as described in Table 4.1.8.6.,

    (c)have an SFRS with an R_d of at least

    (i)2.0 where the Seismic Category is SC4, and

    (ii)1.5 otherwise,

    (d)where they are constructed with concrete or masonry shear walls, have no storey with a lateral stiffness that is less than that of the storey above it, and

    (e)where they are constructed with other types of SFRS, have no storey for which the interstorey deflection under lateral earthquake forces divided by the interstorey height, h_s, is greater than that of the storey above it.

    (4)Where the fundamental lateral period, T_a , is greater than or equal to 1.0 s and I_ES(1.0) is greater than 0.25, shear walls that are other than wood-based and form part of the SFRS shall be continuous from their top to the foundation and shall not have Type 4 or 5 irregularities as described in Table 4.1.8.6.

    (5)For buildings in Seismic Category SC3 or SC4 that are constructed with more than 4 storeys of continuous wood construction, timber SFRSs consisting of shear walls with wood-based panels or of braced or moment-resisting frames as defined in Table 4.1.8.9. within the continuous wood construction shall not have Type 4 or 5 irregularities as described in Table 4.1.8.6. (See Note A-4.1.8.10.(5) and (6))

    (6)For buildings in Seismic Category SC3 or SC4 that are constructed with more than 4 storeys of continuous wood construction, timber SFRSs consisting of moderately ductile or limited ductility cross-laminated timber shear walls, platform-type construction, as defined in Table 4.1.8.9. within the continuous wood construction shall not have Type 4, 5, 6, 8, 9 or 10 irregularities as described in Table 4.1.8.6. (See Note A-4.1.8.10.(5) and (6))

    (7)The ratio α for a Type 9 irregularity as described in Table 4.1.8.6. shall be determined independently for each orthogonal direction using the following equation:

    α = Q_G/Q_y

    where

    Q_G = gravity-induced lateral demand on the SFRS at the critical level of the yielding system, and

    Q_y = the resistance of the yielding mechanism required to resist the earthquake loads, which need not be taken as less than R_o multiplied by the specified lateral earthquake force as determined in Article 4.1.8.11. or 4.1.8.12., as appropriate.

    (See Note A-4.1.8.10.(7))

    (8)For buildings with a Type 9 irregularity as described in Table 4.1.8.6. and where I_ES(0.2) is equal to or greater than 0.5, deflections determined in accordance with Article 4.1.8.13. shall be multiplied by 1.2.

    (9)For buildings where the value of α , as determined in accordance with Sentence (7), exceeds twice the appropriate limit specified in Table 4.1.8.6. for a Type 9 irregularity and where I_ES(0.2) is equal to or greater than 0.5, a Non-linear Dynamic Analysis of the structure shall be carried out in accordance with Article 4.1.8.12. and the following criteria:

    (a)the analysis shall account for the effects of the vertical response of the building mass,

    (b)the analysis shall account for the effects of the vertical response of building components that undergo a vertical displacement when displaced laterally,

    (c)the analysis shall use vertical ground motion time histories that are compatible with horizontal ground motion time histories scaled to the target response spectrum and that are applied concurrently with the horizontal ground motion time histories.

    (d)the largest interstorey deflection at any level of the building as determined from the analysis shall not be greater than 60% of the appropriate limit stated in Sentence 4.1.8.13.(3), and

    (e)the results of an analysis using the ground motion time histories in Clause (c) multiplied by 1.5 shall satisfy the non-linear acceptance criteria. (See Note A-4.1.8.10.(9))

    (10)The design of buildings in Seismic Category SC3 or SC4 with a Type 10 irregularity as described in Table 4.1.8.6. shall satisfy the following requirements:

    (a)the structure shall be designed to resist the additional earthquake forces due to the vertical accelerations of the mass supported by inclined vertical members, and (See Note A-4.1.8.10.(10)(a))

    (b)the effects of the horizontal and vertical movements of inclined vertical members, while undergoing earthquakeinduced deformations, on the floor systems they support shall be considered in the design of the building and accounted for in the application of Sentence 4.1.8.3.(5).

    Open OBC Div. B 4.1.8.10. in the code viewer
  • OBC Div. B 4.1.8.7. Methods of Analysis

    (1)Analysis for earthquake actions shall be carried out in accordance with the Dynamic Analysis Procedure described in Article 4.1.8.12. (See Note A-4.1.8.7.(1)), except that the Equivalent Static Force Procedure described in Article 4.1.8.11. may be used for structures that meet any of the following criteria:

    (a)where the Seismic Category is SC1 or SC2,

    (b)regular structures that are less than 60 m in height and have a fundamental lateral period, T_a, less than 2 s in each of two orthogonal directions as defined in Article 4.1.8.8., or

    (c)structures with a structural irregularity of Type 2, 3, 4, 5, 6 or 8 as defined in Table 4.1.8.6. that are less than 20 m in height and have a fundamental lateral period, T_a, less than 0.5 s in each of two orthogonal directions as defined in Article 4.1.8.8.

    Open OBC Div. B 4.1.8.7. in the code viewer
  • OBC Div. B 4.1.8.11. Equivalent Static Force Procedure for Structures Satisfying the Conditions of Article 4.1.8.7.

    (1)The static loading due to earthquake motion shall be determined according to the procedures given in this Article.

    (2)Except as provided in Sentence (12), the specified lateral earthquake force, V, shall be calculated using the following formula:

    V = S(T_a)M_vI_EW/(R_dR_o)

    except,

    (a)for walls, coupled walls and wall-frame systems, V shall not be less than,

    S(4.0)M_vI_EW/(R_dR_o)

    (b)for moment-resisting frames, braced frames and other systems, V shall not be less than,

    S(2.0)M_vI_EW/(R_dR_o)

    , and

    (c)for buildings located on a site designated as other than X_F and having an SFRS with an R_d equal to or greater than 1.5, V need not be greater than the larger of

    (2/3)S(0.2)I_EW/(R_dR_o)

    , and

    S(0.5)I_EW/(R_dR_o)

    (3)Except as provided in Sentence (4), the fundamental lateral period, T_a, in the direction under consideration in Sentence (2) shall be determined as:

    (a)for moment-resisting frames that resist 100% of the lateral earthquake forces and where the frame is not enclosed by or adjoined by more rigid elements that would tend to prevent the frame from resisting lateral forces, and where h_n is in metres:

    (i)0.085(h_n)3/4 for steel moment frames,

    (ii)0.075(h_n)^(3/4) for concrete moment frames, or

    (iii)0.1N for other moment frames,

    (b)0.025 h_n for braced frames,

    (c)0.05(h_n)^(3/4) for shear wall and other structures, or

    (d)other established methods of mechanics using a structural model that complies with the requirements of Sentence 4.1.8.3.(8), except that

    (i)for moment-resisting frames, T_a shall not be taken as greater than 1.5 times that determined in Clause (a),

    (ii)for braced frames, T_a shall not be taken as greater than 2.0 times that determined in Clause (b),

    (iii)for shear wall structures, T_a shall not be taken as greater than 2.0 times that determined in Clause (c),

    (iv)for other structures, Ta shall not be taken as greater than that determined in Clause (c), and

    (v)for the purpose of calculating the deflections, the period without the upper limit specified in Subclauses (d)(i) to (d)(iv) may be used, except that, for walls, coupled walls and wall-frame systems, T_a shall not exceed 4.0 s, and for moment-resisting frames, braced frames, and other systems, T_a shall not exceed 2.0 s. (See Note A-4.1.8.11.(3))

    (4)For single-storey buildings with steel deck or wood roof diaphragms, the fundamental lateral period, T_a , in the direction under consideration is permitted to be taken as,

    (a)0.05(h_n)^(3/4) + 0.004L for shear walls,

    (b)0.035h_n + 0.004L for steel moment frames and steel braced frames, or

    (c)the value obtained from methods of mechanics using a structural model that complies with the requirements of Sentence 4.1.8.3.(8), except that Ta shall not be greater than 1.5 times the value determined in Clause (a) or (b), as applicable,

    where L is the shortest length of the diaphragm, in m, between adjacent vertical elements of the SFRS in the direction perpendicular to the direction under consideration.

    (5)The weight, W, of the building shall be calculated using the following formula:

    W = ∑_(i = 1)^nW_i

    (6)The higher mode factor, M_(ν) , and its associated base overturning moment reduction factor, J, shall conform to Table 4.1.8.11.

    (7)The specified lateral earthquake force, V, shall be distributed such that

    (a)a portion, F_t, is concentrated at the top of the building, where F_t is equal to 0.07T_aV but need not exceed 0.25 V and may be considered as zero where the fundamental lateral period, T_a, does not exceed 0.7 s, and

    (b)the remainder, V - F_t , is distributed along the height of the building, including the top level, in accordance with the following formula:

    F_x = (V - F_t)W_xh_x/(∑_(i = 1)^nW_ih_i)

    (8)The structure shall be designed to resist overturning effects caused by the earthquake forces determined in Sentence (7) and the overturning moment at level x, M_x , shall be determined using the following equation:

    M_x = J_x∑_(i = x)^nF_i (h_i - h_x)

    where

    J_x = 1.0 for h_x ≥ 0.6h_n , and

    J_x = J + (1 - J)(h_x/0.6h_n) for h_x , < 0.6h_n

    where

    J = base overturning moment reduction factor conforming to Table 4.1.8.11.

    (9)Torsional effects that are concurrent with the effects of the forces determined in Sentence (7) and are caused by the simultaneous actions of the following torsional moments shall be considered in the design of the structure according to Sentence (11):

    (a)torsional moments introduced by eccentricity between the centres of mass and resistance and their dynamic amplification, and

    (b)torsional moments due to accidental eccentricities.

    (10)Torsional sensitivity shall be determined by calculating the ratio B_x for each level x according to the following equation for each orthogonal direction determined independently:

    B_x = δ_max / δ_ave

    where

    B = maximum of all values of B_x in both orthogonal directions, except that the B_x for one-storey penthouses with a weight less than 10% of the level below need not be considered,

    δ_max = maximum storey displacement at the extreme points of the structure at level x in the direction of the earthquake induced by the forces determined in Sentence (7) acting at distances ± 0.10 D_nx from the centres of mass at each floor, and

    δ_ave = average of the displacements at the extreme points of the structure at level x produced by the forces determined in Sentence (7).

    (11)Torsional effects shall be accounted for as follows:

    (a)for a building with B ≤ 1.7 or in Seismic Category SC1 or SC2, by applying torsional moments about a vertical axis at each level throughout the building, derived for each of the following load cases considered separately:

    (i)T_x = F_x(e_x + 0.10D_nx) , and

    (ii)T_x = F_x(e_x − 0.10D_nx)

    (b)for a building with B > 1.7 in Seismic Category SC3 or SC4, by a Dynamic Analysis Procedure as specified in Article 4.1.8.12.

    where F_x is determined in accordance with Sentence (7) and where each element of the building is designed for the most severe effect of the above load cases.

    (12)Where the fundamental lateral period, T_a, is determined in accordance with Clause (3)(d) and the building is constructed with more than 4 storeys of continuous wood construction and has a timber SFRS consisting of shear walls with wood-based panels or of braced or moment-resisting frames as defined in Table 4.1.8.9., the specified lateral earthquake force, V, as determined in Sentence (2) shall be multiplied by 1.2 but need not exceed the value determined by using Clause (2)(c). (See Note A-4.1.8.10.(5) and (6))

    Open OBC Div. B 4.1.8.11. in the code viewer
  • OBC Div. B 4.1.8.13. Deflections and Drift Limits

    (1)Except as provided in Sentences (5) and (6), lateral deflections of a structure shall be calculated in accordance with the loads and requirements defined in this Subsection.

    (2)Lateral deflections obtained from a linear elastic analysis using the methods given in Articles 4.1.8.11. and 4.1.8.12. and incorporating the effects of torsion, including accidental torsional moments, shall be multiplied by R_dR_o/I_E and increased as required in Sentences 4.1.8.10.(8) and 4.1.8.16.(1) to give realistic values of anticipated deflections.

    (3)Based on the lateral deflections calculated in Sentences (2), (5) and (6), the largest interstorey deflection at any level shall be limited to 0.01 h_s for post-disaster buildings, 0.02 h_s for High Importance Category buildings, and 0.025 h_s for all other buildings.

    (4)The deflections calculated in Sentence (2) shall be used to account for sway effects as required by Sentence 4.1.3.2.(12). (See Note A-4.1.8.13.(4))

    (5)The lateral deflections of a seismically isolated structure shall be calculated in accordance with Article 4.1.8.20.

    (6)The lateral deflections of a structure with supplemental energy dissipation shall be calculated in accordance with Article 4.1.8.22.

    Open OBC Div. B 4.1.8.13. in the code viewer
  • OBC Div. B 4.1.8.18. Elements of Structures, Non-Structural Components and Equipment

    (1)Except as provided in Sentences (2), (7) and (16), elements and components of buildings described in Table 4.1.8.18. and their connections to the structure shall be designed to accommodate the building deflections calculated in accordance with Article 4.1.8.13. and the element or component deflections calculated in accordance with Sentence (9), and shall be designed for a specified lateral earthquake force, V_p , distributed according to the distribution of mass:

    V_rmp = 0.3S(0.2)I_rmES_rmpW_rmp

    where

    S(0.2) = design spectral acceleration value at a period of 0.2 s, as defined in Sentence 4.1.8.4.(6),

    I_E = earthquake importance factor for the building, as defined in Article 4.1.8.5.,

    S_p = C_pA_rA_x/R_p (the maximum value of S_p shall be taken as 4.0 and the minimum value of S_p shall be as 0.7), where

    C_p = element or component factor from Table 4.1.8.18.,

    A_r = element or component force amplification factor from Table 4.1.8.18.,

    A_x = height factor (1 + 2h_x/h_n),

    R_p = element or component response modification factor from Table 4.1.8.18., and

    W_p = weight of the component or element.

    (2)For buildings in Seismic Category SC1 or SC2, other than post-disaster buildings, seismically isolated buildings, and buildings with supplemental energy dissipation systems, the requirements of Sentence (1) need not apply to Categories 6 through 22 of Table 4.1.8.18.

    (3)For the purpose of applying Sentence (1) for Categories 11 and 12 of Table 4.1.8.18., elements or components shall be assumed to be flexible or flexibly connected unless it can be shown that the fundamental period of the element or component and its connection is less than or equal to 0.06 s, in which case the element or component is classified as being rigid and rigidly connected.

    (4)The weight of access floors shall include the dead load of the access floor and the weight of permanent equipment, which shall not be taken as less than 25% of the floor live load.

    (5)When the mass of a tank plus its contents or the mass of a flexible or flexibly connected piece of machinery, fixture or equipment is greater than 10% of the mass of the supporting floor, the lateral forces shall be determined by rational analysis.

    (6)Forces shall be applied in the horizontal direction that results in the most critical loading for design, except for Category 6 of Table 4.1.8.18., where the forces shall be applied up and down vertically.

    (7)Connections to the structure of elements and components listed in Table 4.1.8.18. shall be designed to support the component or element for gravity loads, shall conform to the requirements of Sentence (1), and shall also satisfy these additional requirements:

    (a)except as provided in Sentence (17), friction due to gravity loads shall not be considered to provide resistance to earthquake forces,

    (b)R_p for non-ductile connections, such as adhesives or power-actuated fasteners, shall be taken as 1.0,

    (c)R_p for shallow post-installed mechanical, post-installed adhesive, and cast-in-place anchors in concrete shall be 1.5, where shallow anchors are those with a ratio of embedment length to diameter of less than 8,

    (d)post-installed mechanical, drop-in and adhesive anchors in concrete shall be pre-qualified for seismic applications by cyclic load testing in accordance with

    (i)CSA A23.3, "Design of concrete structures," and

    (ii)ACI 355.2, "Qualification of Post-Installed Mechanical Anchors in Concrete (ACI 355.2-19) and Commentary," or ACI 355.4, "Qualification of Post-Installed Adhesive Anchors in Concrete (ACI 355.4-19) and Commentary," as applicable,

    (e)post-installed mechanical and adhesive anchors in masonry and post-installed mechanical anchors in structural steel shall be pre-qualified for seismic applications by cyclic tension load testing, (See Note A-4.1.8.18.(7)(e))

    (f)power-actuated fasteners shall not be used for cyclic tension loads,

    (g)connections for non-structural elements or components of Category 1, 2 or 3 of Table 4.1.8.18. attached to the side of a building and above the first level above grade shall satisfy the following requirements:

    (h)for connections where the body of the connection is ductile, the body shall be designed for values of C_p , A_r and R_p given in Table 4.1.8.18., and all of the other parts of the connection, such as anchors, welds, bolts and inserts, shall be capable of developing 2.0 times the nominal yield resistance of the body of the connection, and

    (i)connections where the body of the connection is not ductile shall be designed for values of C_p = 2.0 , R_p = 1.0 and A_r given in Table 4.1.8.18., and

    (j)a ductile connection is one where the body of the connection is capable of dissipating energy through cyclic inelastic behaviour.

    (8)Floors and roofs acting as diaphragms shall satisfy the requirements for diaphragms stated in Article 4.1.8.15.

    (9)Lateral deflections of elements or components shall be based on the loads defined in Sentence (1) and lateral deflections obtained from an elastic analysis shall be multiplied by R_p/I_E to give realistic values of the anticipated deflections.

    (10)The elements or components shall be designed so as not to transfer to the structure any forces unaccounted for in the design, and rigid elements such as walls or panels shall satisfy the requirements of Sentence 4.1.8.3.(6).

    (11)Seismic restraint for suspended equipment, pipes, ducts, electrical cable trays, etc. shall be designed to meet the force and displacement requirements of this Article and be constructed in a manner that will not subject hanger rods to bending.

    (12)Isolated suspended equipment and components, such as pendent lights, may be designed as a pendulum system provided that adequate chains or cables capable of supporting 2.0 times the weight of the suspended component are provided and the deflection requirements of Sentence (10) are satisfied.

    (13)Free-standing steel pallet storage racks are permitted to be designed to resist earthquake effects using rational analysis, provided the design achieves the minimum performance level required by Subsection 4.1.8. (See Note A-4.1.8.18.(13) and 4.4.3.1.(1).)

    (14)Except as provided in Sentence (15), the relative displacement of glass in glazing systems, D_fallout , shall be equal to the greater of

    (a)D_fallout ≥ 1.25I_ED_p , where

    D_fallout = relative displacement at which glass fallout occurs, and

    D_p = relative earthquake displacement that the component must be designed to accommodate, calculated in accordance with Article 4.1.8.13. and applied over the height of the glass component, or

    (b)13 mm.

    (See Note A-4.1.8.18.(14) and (15))

    (15)Glass need not comply with Sentence (14), provided at least one of the following conditions is met:

    (a)the Seismic Category is SC1 or SC2,

    (b)the glass has sufficient clearance from its frame such that D_clear ≥ 1.25D_p calculated as follows:

    D_clear = 2C_1(1 + h_pC_2/(b_pC_1))

    where

    D_clear = relative horizontal displacement measured over the height of the glass panel, which causes initial glass-to-frame contact,

    C₁ = average of the clearances on both sides between the vertical glass edges and the frame,

    h_p = height of the rectangular glass panel,

    C_2 = averages of the top and bottom clearances between the horizontal glass edges and the frame, and

    b_p = width of the rectangular glass panel,

    (c)the glass is fully tempered, monolithic, installed in a non-post-disaster building, and no part of the glass is located more than 3 m above a walking surface, or

    (d)the glass is annealed or heat-strengthened laminated glass in a single thickness with an interlayer no less than 0.76 mm and captured mechanically in a wall system glazing pocket with the perimeter secured to the frame by a wet, glazed, gunable, curing, elastomeric sealant perimeter bead of 13 mm minimum glass contact width.

    (See Note A-4.1.8.18.(14) and (15))

    (16)For structures with supplemental energy dissipation, elements and components of buildings described in Table 4.1.8.18. and their connections to the structure shall be designed for a specified lateral earthquake force, V_p , determined at each floor level as follows:

    V_p = S_sedI_E(C_pA_r/R_p)W_p

    where

    S_sed = peak spectral acceleration, S_a(T,X) , in the period range of T=0 s to T=0.5 s determined from the mean 5%-damped floor spectral acceleration values by averaging the individual 5%-damped floor response spectra at the centroid of the floor area at that floor level determined using Non-linear Dynamic Analysis, and

    I_E,C_p,A_r,R_p,W_p = as defined in Sentence (1).

    (See Note A-4.1.8.18.(16))

    (17)For a ballasted array of interconnected solar panels mounted on a roof, where I_ES(0.2) is less than or equal to 1.0, friction due to gravity loads is permitted to be considered to provide resistance to seismic forces, provided

    (a)the roof is not normally occupied,

    (b)the roof is surrounded by a parapet extending from the roof surface to not less than the greater of

    (i)150 mm above the centre of mass of the array, and

    (ii)400 mm above the roof surface,

    (c)the height of the centre of mass of the array above the roof surface is less than the lesser of

    (i)900 mm, and

    (ii)one half of the smallest plan dimension of the supporting base of the array,

    (d)the roof slope at the location of the array is less than or equal to 3°,

    (e)the factored friction resistance calculated using the kinetic friction coefficient determined in accordance with Sentence (18) and a resistance factor of 0.7 is greater than or equal to the specified lateral earthquake force, V_p , on the array determined in accordance with Sentence (1) using values of A_r = 1.0 , A_x = 3.0 , C_p = 1.0 , and R_p = 1.25 ,

    (f)the minimum clearance between the array and other arrays or fixed objects is the greater of

    (i)225 mm, and

    (ii)1500(I_ES(0.2) - 0.4)2 , in mm, and

    (g)the minimum clearance between the array and the roof parapet is the greater of

    (i)450 mm, and

    (ii)3 000(I_ES(0.2) - 0.4)^2 , in mm.

    (18)For the purpose of Clause (17)(e), the kinetic friction coefficient shall be determined in accordance with ASTM G115, "Standard Guide for Measuring and Reporting Friction Coefficients," through experimental testing that

    (a)is carried out by an accredited laboratory on a full-scale array or a prototype of the array,

    (b)models the interface between the supporting base of the array and the roof surface, and

    (c)accounts for the adverse effects of anticipated climatic conditions on the friction resistance.

    (See Note A-4.1.8.18.(18))

    Open OBC Div. B 4.1.8.18. in the code viewer
  • OBC Div. B Table 4.1.8.18. Architectural and Structural Components

    Table 4.1.8.18. — Architectural and Structural Components Category | Part or Portion of Building | C_p | A_r | R_p 1 | All exterior and interior walls, and cladding panels, except those in Category 2 or 3 | 1.00 | 1.00 | 2.50 2 | Cantilever parapet and other cantilever walls, including cantilever cladding panels, except retaining walls | 1.00 | 2.50 | 2.50 3 | Exterior and interior ornamentations and appendages | 1.00 | 2.50 | 2.50 4 | Floors and roofs acting as diaphragms[2] | --- | --- | --- 5 | Towers, chimneys, smokestacks and penthouses when connected to or forming part of a building | 1.00 | 2.50 | 2.50 6 | Horizontally cantilevered floors, balconies, beams, etc. | 1.00 | 1.00 | 2.50 7 | Suspended ceilings, light fixtures and other attachments to ceilings with independent vertical support | 1.00 | 1.00 | 2.50 8 | Masonry veneer connections | 1.00 | 1.00 | 1.50 9 | Access floors | 1.00 | 1.00 | 2.50 10 | Masonry or concrete fences more than 1.8 m tall | 1.00 | 1.00 | 2.50 Table 4.1.8.18. (continued) — Mechanical and Electrical Components Category | Part or Portion of Building | C_p | A_r | R_p 11 | Machinery, fixtures, equipment and tanks (including contents) that are rigid and rigidly connected | 1.00 | 1.00 | 1.25 11 | that are flexible or flexibly connected | 1.00 | 2.50 | 2.50 12 | Machinery, fixtures, equipment and tanks (including contents) containing toxic or explosive materials, materials having a flash point below 38°C or firefighting fluids that are rigid and rigidly connected | 1.50 | 1.00 | 1.25 12 | that are flexible or flexibly connected | 1.50 | 2.50 | 2.50 13 | Flat bottom tanks (including contents) attached directly to a floor at or below grade within a building | 0.70 | 1.00 | 2.50 14 | Flat bottom tanks (including contents) attached directly to a floor at or below grade within a building containing toxic or explosive materials, materials having a flash point below 38°C or firefighting fluids | 1.00 | 1.00 | 2.50 15 | Pipes, ducts (including contents) | 1.00 | 1.00 | 3.00 16 | Pipes, ducts (including contents) containing toxic or explosive materials | 1.50 | 1.00 | 3.00 17 | Electrical cable trays, bus ducts, conduits | 1.00 | 2.50 | 5.00 Table 4.1.8.18. (continued) — Other System Components Category | Part or Portion of Building | C_p | A_r | R_p 18 | Rigid components with ductile material and connections | 1.00 | 1.00 | 2.50 19 | Rigid components with non-ductile material or connections | 1.00 | 1.00 | 1.00 20 | Flexible components with ductile material and connections | 1.00 | 2.50 | 2.50 21 | Flexible components with non-ductile material or connections | 1.00 | 2.50 | 1.00 22 | Elevators and escalators[3]: machinery and equipment | As per Category 11 | As per Category 11 | As per Category 11 22 | elevator rails | 1.00 | 1.00 | 2.50 23 | Floor-mounted steel pallet storage racks[4] | 1.00 | 2.50 | 2.50 24 | Floor-mounted steel pallet storage racks on which are stored toxic or explosive materials or materials having a flash point below 38°C[4] | 1.50 | 2.50 | 2.50 Notes to Table 4.1.8.18.: (1) See Note A-Table 4.1.8.18. (2) See Sentence (8). (3) See also ASME A17.1 / CSA B44, "Safety Code for Elevators and Escalators." (4) See Sentence (13) and Note A-Table 4.1.8.18.

    Open OBC Div. B Table 4.1.8.18. in the code viewer