House study guideHouses and Part 9

Rooms and spaces, glass, windows and doors

Room areas and ceiling heights, bedrooms, bathrooms, hallways and doorways, glass, and required windows, doors and skylights.

chapters in this guide
4 of 15
chapters in this guide
to read
5 min
to read
code articles cited
25
code articles cited

Last updated

Values this chapter turns on

master bedroom, or 8.8 m² with built-ins
9.8 m²
master bedroom, or 8.8 m² with built-ins
min doorway width, bathroom
610 mm
min doorway width, bathroom
min hallway width in a dwelling unit
860 mm
min hallway width in a dwelling unit
min glass area, living and dining rooms
10%
min glass area, living and dining rooms

Sections 9.5, 9.6 and 9.7 control the size of rooms and openings in a house: ceiling heights, minimum room areas, hallway and door widths, glass sizes, window glass areas, and how windows and doors resist weather and forced entry. Most questions are lookups with a number, or small calculations such as "what glass area does this bedroom need?".

Ceiling heights and room areas

Section 9.5 applies to dwelling units used year-round as a principal residence (OBC Div. B 9.5.1.0A.OBC Div. B 9.5.1.0A. Application(1) Except as otherwise specified in this Part, this Section applies only to dwelling units that are intended for use on a continuing or year-round basis as the principal residence of the occupant.). Areas and heights are measured between finished surfaces (OBC Div. B 9.5.1.1.OBC Div. B 9.5.1.1. Method of Measurement(1) Except as otherwise specified in this Part, the areas, dimensions and heights of rooms or spaces shall be measured between finished wall surfaces and between finished floor and ceiling surfaces.), and minimum floor areas exclude closets and built-in bedroom cabinets unless stated (OBC Div. B 9.5.1.1A.OBC Div. B 9.5.1.1A. Floor Areas(1) Minimum floor areas specified in this Section do not include closets or built-in bedroom cabinets unless otherwise indicated.).

Combination rooms. Two areas count as one room when the opening between them is the larger of 3 m² or 40% of the wall on the dependent side. The opening cannot contain doors or windows, and a bedroom needs direct passage (OBC Div. B 9.5.1.2.OBC Div. B 9.5.1.2. Combination Rooms(1) Two or more areas may be considered as a combination room if the opening between the areas occupies the larger of 3 m² or 40% or more of the wall measured on the side of the dependent area. (2) Where the dependent area is a bedroom, direct passage shall be provided between the two areas. (3) The opening required…).

Ceiling heights follow Table 9.5.3.1. (OBC Div. B 9.5.3.1.OBC Div. B 9.5.3.1. Ceiling Heights of Rooms or Spaces(1) Except as provided in Sentences (2) and (3), the ceiling heights and clear heights in rooms or spaces in residential occupancies and live/work units shall conform to Table 9.5.3.1. (2) Ceiling heights in secondary suites shall be not less than 1.95 m. (3) Clear heights under beams and ducting in secondary suites…). In our words:

Space Minimum
Living, dining, kitchen 2,300 mm over 75% of required area, 2,100 mm clear at any point
Bedroom 2,300 mm over 50% of required area, or 2,100 mm over all of it; floor under 1,400 mm clear does not count
Basement space 2,100 mm over 75% of the basement; 1,950 mm under beams and ducts
Bathroom, laundry above grade 2,100 mm where a person would stand
Halls, vestibules, other finished rooms 2,100 mm
Secondary suite 1.95 m ceiling, 1.85 m under beams and ducts

A storage garage needs 2 m clear height (OBC Div. B 9.5.3.3.OBC Div. B 9.5.3.3. Storage Garages(1) The clear height in a storage garage shall be not less than 2 m.).

Room areas come from Subsections 9.5.3A. to 9.5.3E.:

Room Minimum area
Living area 13.5 m² (11 m² when combined with kitchen and dining in a unit for not more than two people)
Dining space combined with other space 3.25 m²
Separate dining room 7 m²
Kitchen 4.2 m² (3.7 m² for a unit for not more than two people)
Master bedroom (one per unit) 9.8 m², or 8.8 m² with built-in cabinets
Other bedrooms 7 m², or 6 m² with built-in cabinets
Bedroom space in combination 4.2 m²
Bachelor unit, all spaces combined (not more than two people) 13.5 m²

Smaller areas are allowed when it can be shown they suit the intended use, for example with built-in furniture (OBC Div. B 9.5.1.3.OBC Div. B 9.5.1.3. Lesser Areas and Dimensions(1) Areas of rooms and spaces are permitted to be less than required in this Section provided it can be shown that the rooms and spaces are adequate for their intended use, such as by the provision of built-in furniture to compensate for reduced sizes.). Every dwelling unit needs an enclosed space big enough for a water closet, lavatory and tub or shower, and a door on every room with a water closet (OBC Div. B 9.5.3F.2.OBC Div. B 9.5.3F.2. Doors to Rooms Containing Water Closets(1) A door shall be provided to each room containing a water closet within a dwelling unit.).

Practice this topic

Hallways and doorway sizes

Hallways inside a dwelling unit are at least 860 mm wide. They may drop to 710 mm where only bedrooms and bathrooms are at the far end and a second exit is provided near that end or in each bedroom (OBC Div. B 9.5.4.1.OBC Div. B 9.5.4.1. Hallway Width(1) The unobstructed width of a hallway within a dwelling unit shall be not less than 860 mm, except that the hallway width is permitted to be 710 mm where (a) there are only bedrooms and bathrooms at the end of the hallway furthest from the living area, and (b) a second exit is provided (i) in the hallway near the…).

Door openings follow Table 9.5.5.1. (OBC Div. B 9.5.5.1.OBC Div. B 9.5.5.1. Doorway Opening Sizes(1) Except as provided in Sentence (2) and Articles 9.5.5.3., 9.9.6.2. and 9.9.6.3., doorway openings within dwelling units and within houses with a secondary suite including their common spaces shall be designed to accommodate at least the door sizes given in Table 9.5.5.1. for swing-type and folding doors. (2)…). All heights are 1,980 mm.

Doorway Min. width
Required entrance to the unit, vestibule, stairs to a finished level, the line of passage to the basement, utility rooms 810 mm
Walk-in closet, bathroom, water-closet room, shower room, rooms off a 710 mm hallway 610 mm
Other rooms, exterior balconies 760 mm

Inside a secondary suite, doors may be 1,890 mm high where the 1.95 m ceiling rule is used.

Practice this topic

Glass

Section 9.6 covers glass in interior doors and windows, closets, site-built exterior windows, doors and skylights, shower and tub enclosures, and glazed panels (OBC Div. B 9.6.1.1.OBC Div. B 9.6.1.1. Application(1) This Section applies to (a) glass in (i) interior doors and interior windows and their sidelights, (ii) clothes closets. (iii) site-built exterior windows, doors and skylights, (iv) shower or bathtub enclosures, (v) glazed panels and partitions, and (b) the protection of glass.). Mirrored doors may only be used on clothes closets (OBC Div. B 9.6.1.2.OBC Div. B 9.6.1.2. Material Standards for Glass(1) Glass shall conform to (a) CAN/CGSB-12.1, "Safety Glazing," (b) CAN/CGSB-12.2-M, "Flat, Clear Sheet Glass," (c) CAN/CGSB-12.3-M, "Flat, Clear Float Glass," (d) CAN/CGSB-12.4-M, "Heat Absorbing Glass," (e) CAN/CGSB-12.8, "Insulating glass units," (f) CAN/CGSB-12.9, "Spandrel glass," (g) CAN/CGSB-12.10-M, "Glass…).

Window pane sizes come from Tables 9.6.1.3.-A to -F (based on the SB-1 hourly wind pressure) and door glass from Table 9.6.1.3.-G (OBC Div. B 9.6.1.3.OBC Div. B 9.6.1.3. Structural Sufficiency of Glass(1) Except as provided in Sentence (2), glass shall be designed in conformance with Article 4.3.6.1. (2) Where the building has an essentially uniform distribution of paths for air leakage, including operable openings, but no large openings that would permit wind gusts to rapidly enter the building and the building is…). To read Table -G, pick the glass thickness row and the glass type column. For example, 4 mm fully tempered door glass may be up to 4.00 m², while 4 mm annealed is limited to 1.00 m² (Table 9.6.1.3.-GOBC Div. B Table 9.6.1.3-G. Maximum Glass Area, m²[1]Table 9.6.1.3.-G. — Maximum Glass Area, m²[1] Forming Part of Sentence 9.6.1.3.(3) Glass Thickness, mm | Type of Glass: Annealed | Type of Glass: Annealed, Multiple-Glazed, Factory-Sealed Units | Type of Glass: Laminated | Type of Glass: Wired | Type of Glass: Heat-Strengthened | Type of Glass: Fully Tempered | Type…).

Safety glazing (tempered or laminated, or wired glass) is required for sidelights over 500 mm wide that could be mistaken for doors, storm door glass and sliding door glass at dwelling unit entrances (OBC Div. B 9.6.1.4.(1)OBC Div. B 9.6.1.4. Types of Glass and Protection of Glass(1) Glass sidelights greater than 500 mm wide that could be mistaken for doors, glass in storm doors and glass in sliding doors within or at every entrance to a dwelling unit and in public areas shall be (a) safety glazing of the tempered or laminated type conforming to CAN/CGSB-12.1, "Safety Glazing," or (b) wired…). Other entrance door glass needs it when the pane exceeds 0.5 m² and extends to within 900 mm of the bottom of the door. Shower and tub enclosure glazing must be Class A safety glazing.

Practice this topic

Windows, doors and skylights

Section 9.7 covers windows, doors and skylights between conditioned space and unconditioned space or the outdoors, plus main entrance doors (OBC Div. B 9.7.1.1.OBC Div. B 9.7.1.1. Application(1) This Section applies to (a) windows, doors and skylights separating conditioned space from unconditioned space or the exterior, and (b) main entrance doors. (2) For the purpose of this Section, the term "skylight" refers to unit skylights, roof windows and tubular daylighting devices. (3) For the purpose of this…). Each dwelling unit entrance needs a door, and the main entrance door needs a door viewer, glazing, or a sidelight (OBC Div. B 9.7.2.1.OBC Div. B 9.7.2.1. Entrance Doors(1) A door shall be provided at each entrance to a dwelling unit. (2) Main entrance doors to dwelling units shall be provided with (a) a door viewer or transparent glazing in the door, or (b) a sidelight.).

Minimum glass areas follow Table 9.7.2.3. (OBC Div. B 9.7.2.3.OBC Div. B 9.7.2.3. Minimum Window Areas(1) Except as required in Article 9.9.10.1. and Sentence (3), the minimum window glass areas for rooms in buildings of residential occupancy or rooms that are used for sleeping shall conform to Table 9.7.2.3. (2) The unobstructed glass area of a door or skylight is considered equivalent to that of a window. (3) Work…). Door and skylight glass counts as window glass, and in a combination room the stricter requirement governs.

Room No electric lighting With electric lighting
Living and dining rooms 10% of area served 10%
Bedrooms and other finished rooms 5% 5%
Kitchen 10% not required
Laundry, basement rec room, unfinished basement 4% not required
Water-closet room 0.37 m² not required

Performance. Windows, doors and skylights must resist precipitation, wind loads, air leakage, insects and vermin, forced entry where required, and be easily operable (OBC Div. B 9.7.3.1.OBC Div. B 9.7.3.1. General Performance Criteria(1) Except as provided in Sentences (2) to (4), windows, doors and skylights and their components separating conditioned space from unconditioned space or the exterior shall be designed, constructed and installed so that, when in the closed position, they (a) resist the ingress of precipitation into interior space…). Metal frames need a thermal break, with exceptions for vehicle doors, storm units and fire-rated units (OBC Div. B 9.7.3.3.OBC Div. B 9.7.3.3. Thermal Characteristics of Windows, Doors and Skylights(1) Metal frames and sash of windows, doors and skylights shall incorporate a thermal break. (2) Windows and doors described in Sentence (1) do not require a thermal break where they are installed as (a) vehicular access doors, (b) storm windows and doors, or (c) windows and doors that are required to have a…). Where the January design temperature is between -15°C and -30°C, windows and doors have a maximum U-value of 2.0 W/m²K (skylights 3.0); colder than -30°C, 1.7 (skylights 2.7) (Table 9.7.3.3.OBC Div. B Table 9.7.3.3. Maximum U-value or Minimum Temperature Index (I) for Windows, Doors and Skylights[1][2][3]Table 9.7.3.3. — Maximum U-value or Minimum Temperature Index (I) for Windows, Doors and Skylights[1][2][3] Forming Part of Sentence 9.7.3.3.(3) Component | max. U-value, W/m²K (2.5% January Design Temperature: Between −15°C and −30°C) | min. I (2.5% January Design Temperature: Between −15°C and −30°C) | max. U-value…). Manufactured units meet the NAFS standard and the Canadian Supplement, with a minimum Performance Class R (OBC Div. B 9.7.4.3.OBC Div. B 9.7.4.3. Performance Requirements(1) Performance grades for windows, doors and skylights shall be selected according to CSA A440S1, "Canadian Supplement to AAMA/WDMA/CSA 101/I.S.2/A440-17, North American Fenestration Standard/Specification for windows, doors, and skylights" so as to be appropriate for the conditions and geographic location in which…).

Forced entry. For swinging entrance doors to dwelling units and doors to attached garages (OBC Div. B 9.7.5.2.OBC Div. B 9.7.5.2. Resistance to Forced Entry for Doors(1) Except for exterior doors to garages and to other ancillary spaces, this Article applies to (a) swinging entrance doors to dwelling units, (b) swinging doors between dwelling units and attached garages or other ancillary spaces, and (c) swinging doors that provide access directly or indirectly from a storage…):

Item Requirement
Wood door solid core or stile-and-rail, at least 45 mm thick
Deadbolt cylinder with at least 5 pins, bolt throw at least 25 mm
Inactive leaf top and bottom bolts with at least 15 mm engagement
Hinge screws in wood frames at least 2 per hinge into solid wood at least 30 mm
Blocking solid, both sides at lock height

A door that meets ASTM F476 Grade 10 is exempt from the detailed list. Windows within 2 m of adjacent ground must meet the forced entry clause of the NAFS standard (OBC Div. B 9.7.5.3.OBC Div. B 9.7.5.3. Resistance to Forced Entry for Windows(1) In dwelling units, windows, any part of which is located within 2 m of adjacent ground level, shall conform to the requirements for resistance to forced entry as described in Clause 5.3.6 of AAMA/WDMA/CSA 101/I.S.2/A440, "North American Fenestration Standard/Specification for windows, doors, and skylights." (See…). Installation follows CSA A440.4, and windows and doors are sealed to the air barrier (OBC Div. B 9.7.6.1.OBC Div. B 9.7.6.1. Installation of Windows, Doors and Skylights(1) The installation of windows, doors and skylights shall conform to CSA A440.4, "Window, door, and skylight installation," except that (a) shims used to support windows, doors and skylights are permitted to be made of treated plywood, and (b) protection from precipitation for walls incorporating windows or doors and…).

Practice this topic

Common traps

  • Using the 9.8 m² master bedroom figure for every bedroom.
  • Forgetting that the kitchen glass requirement disappears with electric lighting but the living room one does not.
  • Reading 810 mm for a bathroom door. Bathrooms are 610 mm.
  • Measuring ceiling heights to the joists instead of the finished ceiling.

Chapter review

Chapter at a glance

One line per section: the idea to carry into the exam. Then the answers that most often catch candidates out.

  • Ceiling heights and room areas

    Section 9.5 applies to dwelling units used year-round as a principal residence.

  • Hallways and doorway sizes

    Hallways inside a dwelling unit are at least 860 mm wide.

  • Glass

    Section 9.6 covers glass in interior doors and windows, closets, site-built exterior windows, doors and skylights, shower and tub enclosures, and glazed panels.

  • Windows, doors and skylights

    Section 9.7 covers windows, doors and skylights between conditioned space and unconditioned space or the outdoors, plus main entrance doors.

Usual exam traps

  • Using the 9.8 m² master bedroom figure for every bedroom.
  • Forgetting that the kitchen glass requirement disappears with electric lighting but the living room one does not.
  • Reading 810 mm for a bathroom door. Bathrooms are 610 mm.
  • Measuring ceiling heights to the joists instead of the finished ceiling.

Practice this chapter

Questions on Rooms and spaces, glass, windows and doors, in the exam format, every answer explained and cited to its article. Sign in to start; a free account gets the free questions.

Code cited in this chapter

Based on the official 2024 Building Code Compendium on ontario.ca.

© King's Printer for Ontario, 2024. Reproduced with permission.

  • OBC Div. B 9.5.1.0A. Application

    (1)Except as otherwise specified in this Part, this Section applies only to dwelling units that are intended for use on a continuing or year-round basis as the principal residence of the occupant.

    Open OBC Div. B 9.5.1.0A. in the code viewer
  • OBC Div. B 9.5.1.1. Method of Measurement

    (1)Except as otherwise specified in this Part, the areas, dimensions and heights of rooms or spaces shall be measured between finished wall surfaces and between finished floor and ceiling surfaces.

    Open OBC Div. B 9.5.1.1. in the code viewer
  • OBC Div. B 9.5.1.1A. Floor Areas

    (1)Minimum floor areas specified in this Section do not include closets or built-in bedroom cabinets unless otherwise indicated.

    Open OBC Div. B 9.5.1.1A. in the code viewer
  • OBC Div. B 9.5.1.2. Combination Rooms

    (1)Two or more areas may be considered as a combination room if the opening between the areas occupies the larger of 3 m² or 40% or more of the wall measured on the side of the dependent area.

    (2)Where the dependent area is a bedroom, direct passage shall be provided between the two areas.

    (3)The opening required in Sentence (1) shall not contain doors or windows.

    Open OBC Div. B 9.5.1.2. in the code viewer
  • OBC Div. B 9.5.3.1. Ceiling Heights of Rooms or Spaces

    (1)Except as provided in Sentences (2) and (3), the ceiling heights and clear heights in rooms or spaces in residential occupancies and live/work units shall conform to Table 9.5.3.1.

    (2)Ceiling heights in secondary suites shall be not less than 1.95 m.

    (3)Clear heights under beams and ducting in secondary suites shall be not less than 1.85 m.

    (4)Areas in rooms or spaces over which ceiling height and clear height are not less than the minimum specified in Table 9.5.3.1. or Sentence (2) or (3) shall be contiguous with the entry or entries to those rooms or spaces.

    Open OBC Div. B 9.5.3.1. in the code viewer
  • OBC Div. B 9.5.3.3. Storage Garages

    (1)The clear height in a storage garage shall be not less than 2 m.

    Open OBC Div. B 9.5.3.3. in the code viewer
  • OBC Div. B 9.5.1.3. Lesser Areas and Dimensions

    (1)Areas of rooms and spaces are permitted to be less than required in this Section provided it can be shown that the rooms and spaces are adequate for their intended use, such as by the provision of built-in furniture to compensate for reduced sizes.

    Open OBC Div. B 9.5.1.3. in the code viewer
  • OBC Div. B 9.5.3F.2. Doors to Rooms Containing Water Closets

    (1)A door shall be provided to each room containing a water closet within a dwelling unit.

    Open OBC Div. B 9.5.3F.2. in the code viewer
Show all 25 articles
  • OBC Div. B 9.5.4.1. Hallway Width

    (1)The unobstructed width of a hallway within a dwelling unit shall be not less than 860 mm, except that the hallway width is permitted to be 710 mm where

    (a)there are only bedrooms and bathrooms at the end of the hallway furthest from the living area, and

    (b)a second exit is provided

    (i)in the hallway near the end furthest from the living area, or

    (ii)in each bedroom served by the hallway.

    Open OBC Div. B 9.5.4.1. in the code viewer
  • OBC Div. B 9.5.5.1. Doorway Opening Sizes

    (1)Except as provided in Sentence (2) and Articles 9.5.5.3., 9.9.6.2. and 9.9.6.3., doorway openings within dwelling units and within houses with a secondary suite including their common spaces shall be designed to accommodate at least the door sizes given in Table 9.5.5.1. for swing-type and folding doors.

    (2)Doorway openings within secondary suites shall be designed to accommodate swing-type and folding doors not less than 1,890 mm high where the ceiling height complies with Sentence 9.5.3.1.(2).

    Open OBC Div. B 9.5.5.1. in the code viewer
  • OBC Div. B 9.6.1.1. Application

    (1)This Section applies to

    (a)glass in

    (i)interior doors and interior windows and their sidelights,

    (ii)clothes closets.

    (iii)site-built exterior windows, doors and skylights,

    (iv)shower or bathtub enclosures,

    (v)glazed panels and partitions, and

    (b)the protection of glass.

    Open OBC Div. B 9.6.1.1. in the code viewer
  • OBC Div. B 9.6.1.2. Material Standards for Glass

    (1)Glass shall conform to

    (a)CAN/CGSB-12.1, "Safety Glazing,"

    (b)CAN/CGSB-12.2-M, "Flat, Clear Sheet Glass,"

    (c)CAN/CGSB-12.3-M, "Flat, Clear Float Glass,"

    (d)CAN/CGSB-12.4-M, "Heat Absorbing Glass,"

    (e)CAN/CGSB-12.8, "Insulating glass units,"

    (f)CAN/CGSB-12.9, "Spandrel glass,"

    (g)CAN/CGSB-12.10-M, "Glass, Light and Heat Reflecting,"

    (h)CAN/CGSB-12.11-M, "Wired Safety Glass," or

    (i)ASTM E2190, "Standard Specification for Insulating Glass Unit Performance and Evaluation."

    (2)Mirrored glass doors are only permitted to be used at the entrance to clothes closets and shall conform to the requirements of CAN/CGSB-82.6-M, "Doors, Mirrored Glass, Sliding or Folding, Wardrobe." (See Note A-9.6.1.2.(2))

    (3)Mirrored glass doors reinforced with a film backing shall meet the impact resistance requirements specified in CAN/CGSB-12.5-M, "Mirrors, Silvered."

    Open OBC Div. B 9.6.1.2. in the code viewer
  • OBC Div. B 9.6.1.3. Structural Sufficiency of Glass

    (1)Except as provided in Sentence (2), glass shall be designed in conformance with Article 4.3.6.1.

    (2)Where the building has an essentially uniform distribution of paths for air leakage, including operable openings, but no large openings that would permit wind gusts to rapidly enter the building and the building is not in an exceptionally exposed location such as a hilltop, the maximum area of individual panes of glass for windows shall conform to

    (a)Tables 9.6.1.3.-A to 9.6.1.3.-C, where the building has a height from grade to the uppermost roof of 12 m or less, and is located in a built-up area, no less than 120 m away from the boundary between this area and open terrain, or

    (b)Tables 9.6.1.3.-D to 9.6.1.3.-F.

    (See Note A-9.6.1.3.(2))

    (3)The maximum area of individual panes of glass for doors shall conform to Table 9.6.1.3.-G.

    Open OBC Div. B 9.6.1.3. in the code viewer
  • OBC Div. B Table 9.6.1.3-G. Maximum Glass Area, m²[1]

    Table 9.6.1.3.-G. — Maximum Glass Area, m²[1] Forming Part of Sentence 9.6.1.3.(3) Glass Thickness, mm | Type of Glass: Annealed | Type of Glass: Annealed, Multiple-Glazed, Factory-Sealed Units | Type of Glass: Laminated | Type of Glass: Wired | Type of Glass: Heat-Strengthened | Type of Glass: Fully Tempered | Type of Glass: Fully Tempered, Multiple-Glazed, Factory-Sealed 3 | 0.50 | 0.70 | N/A | N/A | 1.00 | 1.00 | 2.00 4 | 1.00 | 1.50 | N/A | N/A | 1.50 | 4.00 | 4.00 5 | 1.50 | 1.50 | N/A | N/A | 1.50 | No limit | No limit 6 | 1.50 | 1.50 | 1.20 | 1.00 | 1.50 | No limit | No limit Notes to Table 9.6.1.3.-G: (1) See Note A-Table 9.6.1.3.-G. (2) Not generally available.

    Open OBC Div. B Table 9.6.1.3-G. in the code viewer
  • OBC Div. B 9.6.1.4. Types of Glass and Protection of Glass

    (1)Glass sidelights greater than 500 mm wide that could be mistaken for doors, glass in storm doors and glass in sliding doors within or at every entrance to a dwelling unit and in public areas shall be

    (a)safety glazing of the tempered or laminated type conforming to CAN/CGSB-12.1, "Safety Glazing," or

    (b)wired glass conforming to CAN/CGSB-12.11-M, "Wired Safety Glass."

    (2)Except as provided in Sentence (4), glass in entrance doors to dwelling units and in public areas, other than the entrance doors described in Sentence (1), shall be safety glazing or wired glass of the type described in Sentence (1) where the glass area exceeds 0.5m^2 and extends to less than 900 mm from the bottom of the door.

    (3)Except as provided in Sentence (4), transparent panels that could be mistaken as a means of egress shall be protected by barriers or railings.

    (4)Sliding glass partitions that separate a public corridor from an adjacent occupancy and that are open during normal working hours need not conform to Sentences (2), (3) and (5), except that such partitions shall be suitably marked to indicate their existence and position.

    (5)Except as provided in Sentence (4), every glass or transparent door accessible to the public shall be equipped with hardware, bars or other permanent fixtures designed so that the existence and position of such doors is readily apparent.

    (6)Glazing used for a shower or bathtub enclosure shall conform to Class A of CAN/CGSB-12.1, "Safety Glazing."

    Open OBC Div. B 9.6.1.4. in the code viewer
  • OBC Div. B 9.7.1.1. Application

    (1)This Section applies to

    (a)windows, doors and skylights separating conditioned space from unconditioned space or the exterior, and

    (b)main entrance doors.

    (2)For the purpose of this Section, the term "skylight" refers to unit skylights, roof windows and tubular daylighting devices.

    (3)For the purpose of this Section, the term "doors" includes glazing in doors and sidelights for doors.

    Open OBC Div. B 9.7.1.1. in the code viewer
  • OBC Div. B 9.7.2.1. Entrance Doors

    (1)A door shall be provided at each entrance to a dwelling unit.

    (2)Main entrance doors to dwelling units shall be provided with

    (a)a door viewer or transparent glazing in the door, or

    (b)a sidelight.

    Open OBC Div. B 9.7.2.1. in the code viewer
  • OBC Div. B 9.7.2.3. Minimum Window Areas

    (1)Except as required in Article 9.9.10.1. and Sentence (3), the minimum window glass areas for rooms in buildings of residential occupancy or rooms that are used for sleeping shall conform to Table 9.7.2.3.

    (2)The unobstructed glass area of a door or skylight is considered equivalent to that of a window.

    (3)Work areas in live/work units shall conform to Clause 3.7.2.1.(2)(a).

    (4)Where rooms with different requirements for window glass area are combined as described in Sentence 9.5.1.2.(1), the more restrictive requirement shall govern.

    Open OBC Div. B 9.7.2.3. in the code viewer
  • OBC Div. B 9.7.3.1. General Performance Criteria

    (1)Except as provided in Sentences (2) to (4), windows, doors and skylights and their components separating conditioned space from unconditioned space or the exterior shall be designed, constructed and installed so that, when in the closed position, they

    (a)resist the ingress of precipitation into interior space, (See Note A-9.7.4.2.(1))

    (b)resist wind loads,

    (c)control air leakage,

    (d)resist the ingress of insects and vermin,

    (e)where required, resist forced entry, and

    (f)are easily operable when not intended to be fixed.

    (2)Skylights and their components shall be designed, constructed and installed so that, when in the closed position, they resist snow loads.

    (3)Main entrance doors and their components shall be designed, constructed and installed so that, when in the closed position, they

    (a)control air leakage,

    (b)resist the ingress of insects and vermin,

    (c)resist forced entry, and

    (d)are easily operable.

    (4)Storm doors, sliding doors and their components shall be designed, constructed and installed so that, when in the closed position, they

    (a)resist wind loads,

    (b)control air leakage to a minimum allowable 5 m³h/m and a maximum allowable 8.35 m³h/m,

    (c)resist the ingress of insects and vermin, and

    (d)are easily operable.

    (5)Compliance with the performance requirements described in Sentences (1) to (4) shall be demonstrated by

    (a)complying with the requirements in

    (i)Subsection 9.7.4. or 9.7.5., and

    (ii)Subsection 9.7.6., or

    (b)design and construction conforming to Part 5.

    Open OBC Div. B 9.7.3.1. in the code viewer
  • OBC Div. B 9.7.3.3. Thermal Characteristics of Windows, Doors and Skylights

    (1)Metal frames and sash of windows, doors and skylights shall incorporate a thermal break.

    (2)Windows and doors described in Sentence (1) do not require a thermal break where they are installed as

    (a)vehicular access doors,

    (b)storm windows and doors, or

    (c)windows and doors that are required to have a fire-resistance rating.

    (3)Windows, doors and skylights with or without storm doors or sash that are installed in buildings where the intended use of the interior space will not result in high moisture generation shall have a maximum thermal transmittance (U-value) or minimum temperature index (I) in accordance with Table 9.7.3.3.

    (4)Windows, doors and skylights, with or without storm doors or sash that are installed in portions of buildings where the intended use of the interior space will result in high moisture generation shall be designed in conformance with Subsection 5.3. (See Note A-9.25.5.2.)

    Open OBC Div. B 9.7.3.3. in the code viewer
  • OBC Div. B Table 9.7.3.3. Maximum U-value or Minimum Temperature Index (I) for Windows, Doors and Skylights[1][2][3]

    Table 9.7.3.3. — Maximum U-value or Minimum Temperature Index (I) for Windows, Doors and Skylights[1][2][3] Forming Part of Sentence 9.7.3.3.(3) Component | max. U-value, W/m²K (2.5% January Design Temperature: Between −15°C and −30°C) | min. I (2.5% January Design Temperature: Between −15°C and −30°C) | max. U-value, W/m²K (2.5% January Design Temperature: Colder than −30°C) | min. I (2.5% January Design Temperature: Colder than −30°C) Windows and Doors | 2.0 | 68 | 1.7 | 77 Skylights | 3.0 | [2] | 2.7 | [2] Notes to Table 9.7.3.3.: (1) U-values for specific products can be determined according to measures referenced in AAMA/WDMA/CSA 101/I.S.2/A440, "NAFS - North American Fenestration Standard/Specification for windows, doors, and skylights." Temperature index (I) is determined according to the physical test procedure given in CSA A440.2/A440.3, "Fenestration energy performance/User guide to CSA A440.2-19, Fenestration energy performance." (2) There is no appropriate test procedure available for testing the condensation resistance of sloped glazing. (3) Where the U-value in this Table differs from the U-value provided in MMA Supplementary Standard SB-10, "Energy Efficiency Requirements" or MMA Supplementary Standard SB-12, "Energy Efficiency for Housing", the most restrictive U-value shall apply.

    Open OBC Div. B Table 9.7.3.3. in the code viewer
  • OBC Div. B 9.7.4.3. Performance Requirements

    (1)Performance grades for windows, doors and skylights shall be selected according to CSA A440S1, "Canadian Supplement to AAMA/WDMA/CSA 101/I.S.2/A440-17, North American Fenestration Standard/Specification for windows, doors, and skylights" so as to be appropriate for the conditions and geographic location in which the window, door or skylight will be installed.

    (2)Windows, doors and skylights shall conform to the performance grades selected under Sentence (1) when tested in accordance with AAMA/WDMA/CSA 101/I.S.2/A440, "North American Fenestration Standard/Specification for windows, doors, and skylights" (Harmonized Standard).

    (3)The minimum level of performance required for windows, doors and skylights shall be that of the Performance Class R.

    (4)Exterior wood doors shall conform to CAN/CSA-O132.2 Series, "Wood Flush Doors," and shall have legibly indicated on them

    (a)the name of the manufacturer,

    (b)the standard to which they were produced, and

    (c)that they are of an exterior type.

    Open OBC Div. B 9.7.4.3. in the code viewer
  • OBC Div. B 9.7.5.2. Resistance to Forced Entry for Doors

    (1)Except for exterior doors to garages and to other ancillary spaces, this Article applies to

    (a)swinging entrance doors to dwelling units,

    (b)swinging doors between dwelling units and attached garages or other ancillary spaces, and

    (c)swinging doors that provide access directly or indirectly from a storage garage to a dwelling unit. (See Note A-9.7.5.2.(1))

    (2)Doors, frames and hardware that conform to a security level of at least Grade 10 as described in the Annex to ASTM F476, "Standard Test Methods for Security of Swinging Door Assemblies," are not required to conform to Sentences (3) to (7). (See Note A-9.7.5.2.(2))

    (3)Except as permitted in Sentence (2), wood doors as described in Sentence (1) shall

    (a)be solid core or stile-and-rail type,

    (b)be not less than 45 mm thick, and

    (c)if of the stile-and-rail type, have a panel thickness of not less than 19 mm, with a total panel area not more than half of the door area.

    (4)Except as permitted in Sentence (2), doors described in Sentence (1) shall be provided with

    (a)a deadbolt lock with a cylinder having no fewer than 5 pins, and

    (b)a bolt throw not less than 25 mm long, protected with a solid or hardened free-turning ring or beveled cylinder housing. (See Article 9.9.6.7.)

    (5)Except as permitted in Sentence (2), an inactive leaf in double doors used in locations specified in Sentence (1) shall be provided with heavy-duty bolts top and bottom having an engagement of not less than 15 mm.

    (6)Except as permitted in Sentence (2), hinges for doors described in Sentence (1) shall be fastened

    (a)to wood doors with wood screws not less than 25 mm long and to wood frames with wood screws such that at least 2 screws per hinge penetrate not less than 30 mm into solid wood, or

    (b)to metal doors and metal frames with machine screws not smaller than No. 10 and not less than 10 mm long. (See Note A-9.7.5.2.(6))

    (7)Strikeplates for deadbolts described in Sentence (4) shall be fastened

    (a)to wood frames with wood screws that penetrate not less than 30 mm into solid wood, or

    (b)to metal frames with machine screws not smaller than No. 8 and not less than 10 mm long. (See Note A-9.7.5.2.(6))

    (8)Except for storm doors or screen doors, doors described in Sentence (1) that swing outward shall be provided with hinges or pins so that the doors cannot be removed when they are in the closed position. (See Note A-9.7.5.2.(8))

    (9)Solid blocking shall be provided on both sides at the lock height between the jambs for doors described in Sentence (1) and the structural framing so that the jambs will resist spreading by force.

    Open OBC Div. B 9.7.5.2. in the code viewer
  • OBC Div. B 9.7.5.3. Resistance to Forced Entry for Windows

    (1)In dwelling units, windows, any part of which is located within 2 m of adjacent ground level, shall conform to the requirements for resistance to forced entry as described in Clause 5.3.6 of AAMA/WDMA/CSA 101/I.S.2/A440, "North American Fenestration Standard/Specification for windows, doors, and skylights." (See Note A-9.7.5.3.(1))

    Open OBC Div. B 9.7.5.3. in the code viewer
  • OBC Div. B 9.7.6.1. Installation of Windows, Doors and Skylights

    (1)The installation of windows, doors and skylights shall conform to CSA A440.4, "Window, door, and skylight installation," except that

    (a)shims used to support windows, doors and skylights are permitted to be made of treated plywood, and

    (b)protection from precipitation for walls incorporating windows or doors and for roofs incorporating skylights, and the interfaces of these walls with windows or doors and of roofs with skylights, shall also conform to Section 9.27.

    (2)The installation of manufactured and pre-assembled windows, doors and skylights and the field assembly of manufactured window and door combination units shall conform to the manufacturer's instructions.

    (3)Windows, doors and skylights shall be sealed to air barriers.

    Open OBC Div. B 9.7.6.1. in the code viewer