Parts 3 to 7 provisions referenced by Part 9

The specific Part 3, 4, 5, 6 and 7 provisions listed in the guide: noncombustible materials, firewalls, ratings, building height exceptions, spatial separation, selected fire alarm, standpipe and sprinkler rules, fire escapes, service spaces, plumbing facilities, structural loads on guards, foundations, environmental separation and potable water relief valves.

chapters in this guide
2 of 15
chapters in this guide
to read
7 min
to read
code articles cited
42
code articles cited

Last updated

Values this chapter turns on

closure rating in a 1 h fire separation
45 min
closure rating in a 1 h fire separation
min firewall rating, residential buildings
2 h
min firewall rating, residential buildings
max firewall openings, per storey by length
25%
max firewall openings, per storey by length
outward horizontal load on house guards
0.75 kN/m
outward horizontal load on house guards

Part 9 is not self-contained. It sends you into Parts 3 to 7 for specific items, and the House syllabus names those items one by one. This chapter covers the ones most likely to show up: firewalls, closures, building height exceptions, streets, spatial separation tables, sprinkler standards for houses, fire escapes, loads on guards, and a handful of Part 5, 6 and 7 rules. You do not need to master Part 3. You need to know what each listed article says and how to find it fast.

Part 3: materials, fire separations, firewalls and ratings

Heavy timber. Where heavy timber construction is used, minimum member sizes come from Table 3.1.4.7. (OBC Div. B 3.1.4.7.OBC Div. B 3.1.4.7. Heavy Timber Construction(1) Wood elements in heavy timber construction shall be arranged in heavy solid masses and with essentially smooth flat surfaces to avoid thin sections and sharp projections. (2) Except as permitted by Sentences (3) to (6) and (12), the minimum dimensions of wood elements in heavy timber construction shall conform to…). Floors must be plank at least 64 mm thick if splined or tongued and grooved, or 38 mm by 89 mm planks set on edge. Roof plank is at least 38 mm thick, and panel roof decks at least 28 mm.

Noncombustible construction. Where noncombustible construction is required, noncombustible materials must be used, with listed exceptions (OBC Div. B 3.1.5.1.OBC Div. B 3.1.5.1. Noncombustible Materials)(1) Except as permitted by Sentences (2) to (4) and Articles 3.1.5.2. to 3.1.5.29., 3.1.13.4. and 3.2.2.16., a building or part of a building required to be of noncombustible construction, shall be constructed with noncombustible materials. (See also Subsection 3.1.13. for the requirements regarding the flame-spread…). Combustible components in exterior walls are allowed in limited cases, for example when the building is not more than 3 storeys or is sprinklered and the wall passes the referenced test or has masonry or concrete cladding at least 25 mm thick (OBC Div. B 3.1.5.6.OBC Div. B 3.1.5.6. Combustible Components in Exterior Walls(1) Combustible components, other than those permitted by Article 3.1.5.5. and Sentence 3.1.5.7.(2), are permitted to be used in an exterior wall assembly of a building required to be of noncombustible construction, provided (a) the building is (i) not more than 3 storeys in building height, or (ii) sprinklered…).

Closures. A closure's fire-protection rating is tied to the fire-resistance rating of the fire separation it sits in, through Table 3.1.8.4. (OBC Div. B 3.1.8.4.OBC Div. B 3.1.8.4. Determination of Ratings and Classifications(1) Except as permitted by Sentences (2) and 3.1.8.16.(1), the fire-protection rating of a closure shall be determined in accordance with (a) CAN/ULC-S104, "Standard Method for Fire Tests of Door Assemblies," (b) CAN/ULC-S106, "Standard Method for Fire Tests of Window and Glass Block Assemblies," or (c) CAN/ULC-S112…). Values worth remembering:

Fire separation Closure rating
30 min 20 min
45 min or 1 h 45 min
2 h 1.5 h

Fire dampers go in the plane of the fire separation, close by a fusible link or other heat- or smoke-actuated device, and need a tightly fitted access door for inspection and resetting (OBC Div. B 3.1.8.10.OBC Div. B 3.1.8.10. Installation of Fire Dampers(1) A fire damper shall be installed in the plane of the fire separation so as to stay in place should the duct become dislodged during a fire. (See Note A-3.1.8.10.(1)) (2) A fire damper shall be arranged so as to close automatically upon the operation of a fusible link conforming to ULC-S505, "Standard for Fusible…).

Firewalls. A firewall between residential buildings needs a fire-resistance rating of at least 2 h; 4 h applies where Group E or F-1 or F-2 floor areas are involved (OBC Div. B 3.1.10.2.OBC Div. B 3.1.10.2. Rating of Firewalls(1) A firewall that separates a building or buildings with floor areas containing a Group E or a Group F, Division 1 or 2 major occupancy shall be constructed as a fire separation of noncombustible construction having a fire-resistance rating not less than 4 h, except that where the upper portion of a firewall…). The rating is normally provided by masonry or concrete, but a firewall of not more than 2 h may use another assembly if it meets the conditions in Sentence (4), including design to Article 4.1.5.17. A firewall runs continuously from the ground through all storeys (OBC Div. B 3.1.10.3.OBC Div. B 3.1.10.3. Continuity of Firewalls(1) A firewall shall extend from the ground continuously through, or adjacent to, all storeys of a building or buildings so separated, except that a firewall located above a basement storage garage conforming to Article 3.2.1.2. is permitted to commence at the floor assembly immediately above the storage garage. (See…) and forms a parapet at least 150 mm high for a 2 h wall or 900 mm high for a 4 h wall (OBC Div. B 3.1.10.4.OBC Div. B 3.1.10.4. Parapets(1) Except as permitted by Sentences (2) and 3.1.10.3.(2), a firewall shall extend above the roof surface to form a parapet not less than (a) 150 mm high for a firewall required to have a fire-resistance rating not less than 2 h, and (b) 900 mm high for a firewall required to have a fire-resistance rating not less…). No parapet is needed where roofs on each side differ in elevation by more than 3 m. Openings in a firewall may total not more than 25% of its length in any storey (OBC Div. B 3.1.10.5.OBC Div. B 3.1.10.5. Maximum Openings(1) Openings in a firewall shall conform to the size limits described in Article 3.1.8.6. (2) The aggregate width of openings in a firewall within a storey shall be not more than 25% of the entire length of the firewall.). Combustible projections beyond the end of a firewall must stay 2.4 m from combustible projections and openings of the adjacent building (OBC Div. B 3.1.10.7.OBC Div. B 3.1.10.7. Combustible Projections(1) Combustible material shall not extend across the end of a firewall but is permitted to extend across a roof above a firewall that is terminated in conformance with Sentence 3.1.10.3.(2). (2) If buildings are separated by a firewall, combustible projections on the exterior of one building, including balconies…).

Flame-spread ratings are found from at least three tests to CAN/ULC-S102, or assigned from SB-2 (OBC Div. B 3.1.12.1.OBC Div. B 3.1.12.1. Determination of Ratings(1) Except as required by Sentence (2) and as permitted by Sentence (3), the flame-spread rating and smoke developed classification of a material, assembly, or structural member shall be determined on the basis of not less than three tests conducted in conformance with CAN/ULC-S102, "Standard Method of Test for…).

Practice this topic

Part 3: building height, streets, balconies and sprinklers

Rooftop enclosures for elevator machinery, a stairway or a service room used only for the building are not counted as a storey (OBC Div. B 3.2.1.1.(1)OBC Div. B 3.2.1.1. Exceptions in Determining Building Height(1) A rooftop enclosure provided for elevator machinery, a stairway or a service room used for no purpose other than for service to the building, shall not be considered as a storey in calculating the building height. (2) Space under tiers of seats in a building of the arena type shall not be considered as adding to…). Space above a mezzanine is not a storey if the mezzanines total not more than 40% of the open area of the room and stay open above 1,070 mm.

A building "faces" 2 streets when at least 50% of its perimeter is within 15 m of a street, and 3 streets at 75% (OBC Div. B 3.2.2.10.OBC Div. B 3.2.2.10. Streets(1) Every building shall face a street located in conformance with the requirements of Articles 3.2.5.4 and 3.2.5.5 for access routes. (2) For the purposes of Subsections 3.2.2. and 3.2.5. an access route conforming to Subsection 3.2.5. is permitted to be considered as a street. (3) A building conforming to Article…). Exterior balconies follow the construction type required for the building (OBC Div. B 3.2.2.11.OBC Div. B 3.2.2.11. Exterior Balconies(1) Except as provided in Sentence (2), an exterior balcony shall be constructed in accordance with the type of construction required by Articles 3.2.2.20. to 3.2.2.93., as applicable to the occupancy classification of the building. (2) The floor assembly of an exterior balcony in a building or part thereof conforming…). If any storey must be sprinklered, all lower storeys must be too (OBC Div. B 3.2.2.18.(2)OBC Div. B 3.2.2.18. Automatic Sprinkler System Required(1) Except as permitted by Sentence (2), an automatic sprinkler system conforming to the requirements of Articles 3.2.4.7., 3.2.4.8., 3.2.4.9. and 3.2.5.12. shall be installed throughout a building regulated by one or more of Articles 3.2.2.20., 3.2.2.21., 3.2.2.22., 3.2.2.23., 3.2.2.24., 3.2.2.26., 3.2.2.27.…).

For Group C up to 3 storeys, Article 3.2.2.54. allows combustible construction with 45 min floor fire separations. In a building with no dwelling unit above another, the rating for floors entirely inside a dwelling unit is waived (OBC Div. B 3.2.2.54.(4)OBC Div. B 3.2.2.54. Group C, up to 3 Storeys(1) A building classified as Group C, other than a retirement home, is permitted to conform to Sentence (2) provided (a) it is not more than 3 storeys in building height, and (b) it has a building area not more than the value in Table 3.2.2.54. (2) The building referred to in Sentence (1) is permitted to be of…).

Practice this topic

Part 3: spatial separation and exposure protection

The area of unprotected openings allowed in an exposing building face depends on the limiting distance and the size of the face, from Tables 3.2.3.1.-B to -E (OBC Div. B 3.2.3.1.OBC Div. B 3.2.3.1. Limiting Distance and Area of Unprotected Openings(1) Except as permitted by Articles 3.2.3.10. to 3.2.3.12., the area of unprotected openings in an exposing building face for the applicable limiting distance shall be not more than the value determined in accordance with (a) Table 3.2.3.1.-B or Table 3.2.3.1.-C for an exposing building face conforming to Article…). For unsprinklered buildings with a limiting distance of 2 m or less, each individual opening is also capped by Table 3.2.3.1.-A: 0.35 m² at 1.2 m, 0.78 m² at 1.5 m and 1.88 m² at 2.0 m (Table 3.2.3.1.-AOBC Div. B Table 3.2.3.1-A. Maximum Concentrated Area of Unprotected OpeningsTable 3.2.3.1.-A Maximum Concentrated Area of Unprotected Openings Forming Part of Sentence 3.2.3.1.(5) Limiting Distance, m | Maximum Area of Individual Unprotected Openings, m² 1.2 | 0.35 1.5 | 0.78 2.0 | 1.88). If firefighters cannot reach an unsprinklered storey within 10 min of the alarm, the required limiting distance is doubled.

Construction of the face follows Table 3.2.3.7. (OBC Div. B 3.2.3.7.OBC Div. B 3.2.3.7. Construction of Exposing Building Face(1) Except as provided by Sentences (3) and (4) and Articles 3.2.3.10. and 3.2.3.11., the fire-resistance rating, construction and cladding for exposing building faces of buildings or fire compartments of Group A, B, C, D or Group F, Division 3 occupancy classification shall comply with Table 3.2.3.7. (2) Except as…). For Group C:

Unprotected openings permitted Fire-resistance rating Cladding
0 to 10% 1 h Noncombustible (construction also noncombustible)
over 10 to 25% 1 h Noncombustible
over 25 to 50% 45 min Noncombustible
over 50% to under 100% 45 min Combustible or noncombustible

In an unsprinklered building, openings glazed with glass block or qualifying wired glass may be doubled in area (OBC Div. B 3.2.3.12.OBC Div. B 3.2.3.12. Area Increase for Unprotected Openings(1) Except as required by Sentence 3.2.3.7.(5), the maximum area of unprotected openings in any exposing building face of a building that is not sprinklered is permitted to be doubled if the openings are glazed with (a) glass block conforming to the requirements of Article 3.1.8.16., or (b) wired glass assemblies…).

Practice this topic

Part 3: fire alarm, standpipe and sprinkler items

For houses the key sprinkler rule is the choice of standard. NFPA 13 is the default, NFPA 13R is permitted for low-rise residential buildings named in the article, and NFPA 13D is permitted in a residential building with not more than two dwelling units (OBC Div. B 3.2.5.12.(3)OBC Div. B 3.2.5.12. Automatic Sprinkler Systems(1) Except as provided by Sentences (2) to (4) and (9), an automatic sprinkler system shall be designed, constructed, installed and tested in conformance with NFPA 13, "Standard for the Installation of Sprinkler Systems." (See Note A-3.2.5.12.(1)) (2) Instead of the requirements of Sentence (1), NFPA 13R, "Standard…). A building with fewer than 9 sprinklers may take its sprinkler water from the domestic system if it can meet the flow. Standpipes follow NFPA 14, and a dry standpipe not connected to water does not count (OBC Div. B 3.2.5.9.OBC Div. B 3.2.5.9. Standpipe System Design(1) Except as provided in Sentences (2) to (5), Articles 3.2.5.10. and 3.2.5.11., and Sentence 3.2.4.9.(2), the design, construction, installation and testing of a standpipe system shall conform to NFPA 14, "Standard for the Installation of Standpipe and Hose Systems." (2) A dry standpipe that is not connected to a…).

Practice this topic

Part 3: exits, fire escapes, service spaces and plumbing facilities

Fire escapes are not allowed on new buildings; they may serve existing buildings only where other exits are impracticable (OBC Div. B 3.4.7.1.OBC Div. B 3.4.7.1. Scope(1) Except as permitted by Sentence (2), fire escapes shall not be erected on a building. (2) If it is impracticable to provide one or more of the exit facilities listed in Article 3.4.1.4., fire escapes conforming to Articles 3.4.7.2. to 3.4.7.7. are permitted to serve floor areas in an existing building provided the…). Fire escape stairs have risers not more than 210 mm, treads at least 220 mm, and an incline not more than 45° (OBC Div. B 3.4.7.5.OBC Div. B 3.4.7.5. Stairs(1) Stairs shall be inclined at an angle of not more than 45° with the horizontal, and their steps shall have risers not more than 210 mm high and treads not less than 220 mm wide exclusive of nosing. (2) Stairway headroom shall be not less than 1,950 mm plus the height of one riser measured vertically above the…). Access from a dwelling unit may be by a casement window at least 1,100 mm high by 550 mm wide with a sill not more than 900 mm above the floor (OBC Div. B 3.4.7.3.OBC Div. B 3.4.7.3. Access to Fire Escapes(1) Access to fire escapes shall be from corridors through doors at floor level, except that access from a dwelling unit is permitted to be through a casement window having an unobstructed opening not less than 1,100 mm high by 550 mm wide with a sill height of not more than 900 mm above the inside floor. (2) The…). Guards are at least 920 mm high (OBC Div. B 3.4.7.6.OBC Div. B 3.4.7.6. Guards and Railings(1) The open sides of every platform, balcony and stairway forming part of a fire escape shall be protected by guards not less than 920 mm high measured vertically above the nosing of any tread or platform. (2) The top rail of a guard is permitted to serve as a handrail if it is free from obstructions that could break…).

Vertical service spaces are separated from each storey by a fire separation based on Table 3.6.3.1. (OBC Div. B 3.6.3.1.OBC Div. B 3.6.3.1. Fire Separations for Vertical Service Spaces(1) Except as provided in Articles 3.6.3.3. and 3.6.3.5. and Section 3.5., a vertical service space shall be separated from all other portions of each adjacent storey by a fire separation having a fire-resistance rating conforming to Table 3.6.3.1. for the fire-resistance rating required by Subsection 3.2.2. for (a)…). A dwelling unit with piped water needs a kitchen sink, lavatory, water closet (or drainless composting toilet) and a bathtub or shower stall (OBC Div. B 3.7.4.5.OBC Div. B 3.7.4.5. Plumbing Facilities for Dwelling Units(1) A dwelling unit where a piped water supply is available shall be provided with a (a) kitchen sink, (b) lavatory, (c) water closet or drainless composting water closet, and (d) bathtub or shower stall.).

Practice this topic

Part 4: loads on guards, firewalls, foundations and materials

Required guards in houses are designed for an outward horizontal load of 0.75 kN/m or 1.0 kN at any point, whichever governs; the inward load is half of that, and the vertical load at the top is 1.5 kN/m. Individual elements such as pickets take 0.5 kN over a 100 mm by 100 mm area. Handrails take 0.9 kN at any point (OBC Div. B 4.1.5.14.OBC Div. B 4.1.5.14. Loads on Guards and Handrails)(1) The minimum horizontal specified live load applied outward at the minimum required height of every required guard shall be (a) 3.0 kN/m for open viewing stands without fixed seats and for means of egress in grandstands, stadia, bleachers and arenas, (b) 1.0 kN applied at any point, so as to produce the most…). Firewalls resist the greater of the normal lateral loads or a factored 0.5 kPa lateral load under fire conditions (OBC Div. B 4.1.5.17.OBC Div. B 4.1.5.17. Firewalls(1) Firewalls shall be designed to resist the maximum effect due to, (a) the appropriate lateral design loads prescribed elsewhere in this Section, or (b) a factored lateral load of 0.5 kPa under fire conditions, as described in Sentence (2). (2) Under fire conditions, where the fire-resistance rating of the structure…).

Engineered foundations under Section 4.2. start with a subsurface investigation by or under a professional engineer (OBC Div. B 4.2.2.1.OBC Div. B 4.2.2.1. Subsurface Investigation(1) A subsurface investigation, including groundwater conditions, shall be carried out by or under the direction of a professional engineer having knowledge and experience in planning and executing such investigations to a degree appropriate for the building and its use, the ground and the surrounding site conditions…). Section 4.3. names the design standards: CSA O86 for wood, CSA S304 for masonry and CSA S16 for structural steel (OBC Div. B 4.3.1.1.OBC Div. B 4.3.1.1. Design Basis for Wood(1) Buildings and their structural members made of wood shall conform to CSA O86, "Engineering design in wood.", 4.3.2.1.OBC Div. B 4.3.2.1. Design Basis for Plain and Reinforced Masonry(1) Buildings and their structural members made of plain and reinforced masonry shall conform to CSA S304, "Design of masonry structures.", 4.3.4.1.OBC Div. B 4.3.4.1. Design Basis for Structural Steel(1) Buildings and their structural members made of structural steel shall conform to CSA S16, "Design of steel structures." (See Note A-4.3.4.1.(1))).

Practice this topic

Part 5: environmental separation

Part 5 is the performance version of the envelope rules in 9.25 to 9.28. It covers condensation control and the transfer of heat, air, moisture and sound (OBC Div. B 5.1.1.1.OBC Div. B 5.1.1.1. Scope(1) This Part is concerned with (a) the control of condensation (i) in building components and assemblies, and (ii) on building materials, components and assemblies, and (b) the transfer of heat, air, moisture and sound through (i) building materials, components and assemblies, and (ii) interfaces between building…). A vapour barrier provides the principal resistance to vapour diffusion, unless it can be shown that uncontrolled diffusion will not harm health or safety, the intended use or building services (OBC Div. B 5.5.1.1.OBC Div. B 5.5.1.1. Required Resistance to Vapour Diffusion(1) Where a building component or assembly is subjected to differentials in temperature and water vapour pressure, the properties and position of the materials and components in those components or assemblies shall be such that they control vapour diffusion or permit venting to the exterior so as to minimize…). Joints exposed to precipitation are either sealed or drained (OBC Div. B 5.6.2.1.OBC Div. B 5.6.2.1. Sealing and Drainage(1) Except as provided in Sentence (2), materials, components, assemblies, joints in materials, junctions between components and junctions between assemblies exposed to precipitation shall be (a) sealed to prevent ingress of precipitation, or (b) drained to direct precipitation to the exterior. (2) Sealing or drainage…).

Practice this topic

Parts 6 and 7

  • Solid-fuel central heating appliances are installed to CSA B365; earth energy systems for a house to CAN/CSA-C448.2 (OBC Div. B 6.2.1.5.OBC Div. B 6.2.1.5. Installation Standards(1) The installation of solid fuel-burning appliances for central heating systems shall comply with CSA B365, "Installation code for solid-fuel-burning appliances and equipment" and the manufacturer's installation instructions. (2) The solid fuel-fired appliances in Sentence (1) shall conform to CSA B366.1…).
  • Supply, return and exhaust openings less than 2 m above the floor need grilles that stop a 15 mm sphere; outdoor intakes are at least 0.3 m above roofs or grade, with screens of mesh not larger than 15 mm (OBC Div. B 6.3.2.9.OBC Div. B 6.3.2.9. Supply, Return, Intake and Exhaust Air Openings(1) Supply, return and exhaust air openings located less than 2 m above the floor in rooms or spaces in buildings shall be protected by grilles having openings of a size that will not allow the passage of a 15 mm diam sphere. (2) Outdoor air intakes shall be located so that (a) the quality of the air entering the…).
  • Storm drainage connects to a public storm sewer, a public combined sewer or a designated storm water disposal location (OBC Div. B 7.1.2.2.OBC Div. B 7.1.2.2. Storm Drainage Systems(1) Except as provided in Section 7.7., storm drainage systems and private sewers conveying storm sewage shall be connected to a public storm sewer, a public combined sewer or a designated storm water disposal location.).
  • A storage-type water heater needs a temperature-relief valve sensing within the top 150 mm of the tank, set to keep water from exceeding 99°C. Relief discharge pipes are full size, rigid, slope down, and end with an air break of not more than 300 mm. No shut-off valve between tank and relief valve (OBC Div. B 7.6.1.7.OBC Div. B 7.6.1.7. Relief Valves(1) Every pressure vessel that is part of a plumbing system or connected to a plumbing system shall be equipped with a pressure-relief valve designed to open when the water pressure in the tank reaches the rated working pressure of the tank, and so located that the pressure in the tank shall not exceed 1,100 kPa or…).
  • Water efficiency fittings for public lavatories and showers are in OBC Div. B 7.6.4.1.OBC Div. B 7.6.4.1. Water Supply Fittings(1) Each lavatory in a washroom with fixtures for public use shall be equipped with a device capable of automatically shutting off the flow of water when the lavatory is not in use. (See Note A-7.6.4.1.(1) and (3)) (2) An automatic compensating valve serving an individual shower head shall have a manufacturer's…

Practice this topic

Common traps

  • Mixing up the closure rating with the fire separation rating: a 1 h separation needs only a 45 min door.
  • Assuming the 25% opening limit in a firewall is per building; it is per storey, by length.
  • Reading the guard load as 1.5 kN/m horizontal. That figure is the vertical load.

Chapter review

Chapter at a glance

One line per section: the idea to carry into the exam. Then the answers that most often catch candidates out.

Usual exam traps

  • Mixing up the closure rating with the fire separation rating: a 1 h separation needs only a 45 min door.
  • Assuming the 25% opening limit in a firewall is per building; it is per storey, by length.
  • Reading the guard load as 1.5 kN/m horizontal. That figure is the vertical load.

Practice this chapter

Questions on Parts 3 to 7 provisions referenced by Part 9, in the exam format, every answer explained and cited to its article. Sign in to start; a free account gets the free questions.

Code cited in this chapter

Based on the official 2024 Building Code Compendium on ontario.ca.

© King's Printer for Ontario, 2024. Reproduced with permission.

  • OBC Div. B 3.1.4.7. Heavy Timber Construction

    (1)Wood elements in heavy timber construction shall be arranged in heavy solid masses and with essentially smooth flat surfaces to avoid thin sections and sharp projections.

    (2)Except as permitted by Sentences (3) to (6) and (12), the minimum dimensions of wood elements in heavy timber construction shall conform to Table 3.1.4.7.

    (3)Where splice plates are used at splices of roof arches supported on the tops of walls or abutments, roof trusses, roof beams and roof girders in heavy timber construction, they shall be not less than 64 mm thick.

    (4)Floors in heavy timber construction shall be of glued-laminated or solid sawn plank not less than

    (a)64 mm thick, splined or tongued and grooved, or

    (b)38 mm wide and 89 mm deep set on edge and well-spiked together.

    (5)Floors in heavy timber construction shall be laid

    (a)so that no continuous line of end joints will occur except at points of support, and covered with

    (i)tongued and grooved flooring not less than 19 mm thick laid crosswise or diagonally, or

    (ii)tongued and grooved phenolic-bonded plywood, strandboard or waferboard not less than 12.5 mm thick, and

    (b)not closer than 15 mm to the walls to provide for expansion, with the gap covered at the top or bottom.

    (6)Roofs in heavy timber construction shall be of tongued and grooved phenolic-bonded plywood, strandboard or waferboard not less than 28 mm thick, or glued-laminated or solid sawn plank that is

    (a)not less than 38 mm thick, splined or tongued and grooved, or

    (b)not less than 38 mm wide and 64 mm deep set on edge and laid so that no continuous line of end joints will occur except at the points of support.

    (7)Wood columns in heavy timber construction shall be continuous or superimposed throughout all storeys.

    (8)Superimposed wood columns in heavy timber construction shall be connected by

    (a)reinforced concrete or metal caps with brackets,

    (b)steel or iron caps with pintles and base plates, or

    (c)timber splice plates fastened to the columns by metal connectors housed within the contact faces.

    (9)Where beams and girders in heavy timber construction enter masonry, wall plates, boxes of the self-releasing type or hangers shall be used.

    (10)Wood girders and beams in heavy timber construction shall be closely fitted to columns, and adjoining ends shall be connected by ties or caps to transfer horizontal loads across the joints.

    (11)In heavy timber construction, intermediate wood beams used to support a floor shall be supported on top of the girders or on metal hangers into which the ends of the beams are closely fitted.

    (12)Roof arches supported on the tops of walls or abutments, roof trusses, roof beams and roof girders in heavy timber construction are permitted to be not less than 64 mm wide provided

    (a)where two or more spaced members are used, the intervening spaces are

    (i)blocked solidly throughout, or

    (ii)tightly closed by a continuous wood cover plate not less than 38 mm thick secured to the underside of the members, or

    (b)the underneath of the roof deck or sheathing is sprinklered.

    Open OBC Div. B 3.1.4.7. in the code viewer
  • OBC Div. B 3.1.5.1. Noncombustible Materials)

    (1)Except as permitted by Sentences (2) to (4) and Articles 3.1.5.2. to 3.1.5.29., 3.1.13.4. and 3.2.2.16., a building or part of a building required to be of noncombustible construction, shall be constructed with noncombustible materials. (See also Subsection 3.1.13. for the requirements regarding the flame-spread rating of interior finishes.)

    (2)Notwithstanding the definition of noncombustible materials stated in Article 1.4.1.2. of Division A, a material is permitted to be used in noncombustible construction provided that, when tested in accordance with ULC S135, "Standard Test Method for the Determination of Combustibility Parameters of Building Materials Using an Oxygen Consumption Calorimeter (Cone Calorimeter)", at a heat flux of 50 kW/m²,

    (a)its average total heat release is not more than 3 MJ/m²,

    (b)its average total smoke extinction area is not more than 1.0 m², and

    (c)the test duration is extended beyond the time stipulated in the referenced standard until it is clear that there is no further release of heat or smoke.

    (3)If a material referred to in Sentence (2) consists of a number of discrete layers and testing reveals that the surface layer or layers protect the underlying layers such that complete combustion of the underlying layers does not occur, the test shall be repeated by removing the outer layers sequentially until all layers have been exposed during testing, or until complete combustion has occurred.

    (4)The acceptance criteria for a material tested in accordance with Sentence (3) shall be based on the cumulative emissions from all layers, which must not exceed the criteria stated in Clauses (2)(a) and (b).

    Open OBC Div. B 3.1.5.1. in the code viewer
  • OBC Div. B 3.1.5.6. Combustible Components in Exterior Walls

    (1)Combustible components, other than those permitted by Article 3.1.5.5. and Sentence 3.1.5.7.(2), are permitted to be used in an exterior wall assembly of a building required to be of noncombustible construction, provided

    (a)the building is

    (i)not more than 3 storeys in building height, or

    (ii)sprinklered throughout, and

    (b)the wall assembly

    (i)except as provided in Sentence (2), satisfies the criteria of Clause 3.1.5.5.(1)(b), or

    (ii)is protected by masonry or concrete cladding not less than 25 mm thick. (See Note A-3.1.5.5.(1)(b))

    (2)Exterior wall assemblies constructed in accordance with Section 6 of MMAH Supplementary Standard SB-2, "Fire Performance Ratings" are deemed to comply with Subclause (1)(b)(i).

    Open OBC Div. B 3.1.5.6. in the code viewer
  • OBC Div. B 3.1.8.4. Determination of Ratings and Classifications

    (1)Except as permitted by Sentences (2) and 3.1.8.16.(1), the fire-protection rating of a closure shall be determined in accordance with

    (a)CAN/ULC-S104, "Standard Method for Fire Tests of Door Assemblies,"

    (b)CAN/ULC-S106, "Standard Method for Fire Tests of Window and Glass Block Assemblies," or

    (c)CAN/ULC-S112, "Standard Method for Fire Test of Fire Damper Assemblies." (See Articles 3.1.8.17. to 3.1.8.19. for additional requirements for closures.)

    (2)Except as permitted by Sentence 3.1.8.12.(1), the fire-protection rating of a closure shall conform to Table 3.1.8.4. for the required fire-resistance rating of the fire separation.

    (3)The leakage rate of smoke dampers and combination smoke/ fire dampers shall

    (a)be determined in accordance with the applicable provisions in CAN/ULC-S112.1, "Standard for Leakage Rated Dampers for Use in Smoke Control Systems," and

    (b)conform to Class I, II or III of that standard.

    (4)The leakage rate of a door assembly shall be determined in accordance with ANSI/UL-1784, "Standard for Air Leakage Tests of Door Assemblies and Other Opening Protectives."

    Open OBC Div. B 3.1.8.4. in the code viewer
  • OBC Div. B 3.1.8.10. Installation of Fire Dampers

    (1)A fire damper shall be installed in the plane of the fire separation so as to stay in place should the duct become dislodged during a fire. (See Note A-3.1.8.10.(1))

    (2)A fire damper shall be arranged so as to close automatically upon the operation of a fusible link conforming to ULC-S505, "Standard for Fusible Links for Fire Protection Services," or other heat-actuated or smoke-actuated device.

    (3)A heat-actuated device referred to in Sentence (2) shall

    (a)be located where it is readily affected by an abnormal rise of temperature in the duct, and

    (b)have a temperature rating approximately 30°C above the maximum temperature that would exist in the system either with the system in operation or shut down.

    (4)A fire damper tested in the vertical or horizontal position shall be installed in the position in which it was tested.

    (5)A tightly fitted access door shall be installed for each fire damper to provide access for the inspection of the damper and the resetting of the release device. (See Note A-3.1.8.10.(5))

    Open OBC Div. B 3.1.8.10. in the code viewer
  • OBC Div. B 3.1.10.2. Rating of Firewalls

    (1)A firewall that separates a building or buildings with floor areas containing a Group E or a Group F, Division 1 or 2 major occupancy shall be constructed as a fire separation of noncombustible construction having a fire-resistance rating not less than 4 h, except that where the upper portion of a firewall separates floor areas containing other than Group E or Group F, Division 1 or 2 major occupancies, the fire-resistance rating of the upper portion of the firewall is permitted to be not less than 2 h.

    (2)A firewall that separates a building or buildings with floor areas containing major occupancies other than Group E or Group F, Division 1 or 2 shall be constructed as a fire separation of noncombustible construction having a fire-resistance rating not less than 2 h.

    (3)Except as permitted by Sentence (4), the required fire-resistance rating of a firewall, except for closures, shall be provided by masonry or concrete.

    (4)A firewall permitted to have a fire-resistance rating not more than 2 h need not be constructed of masonry or concrete provided

    (a)the assembly providing the fire-resistance rating is protected against damage that would compromise the integrity of the assembly,

    (b)the design conforms to Article 4.1.5.17.,

    (c)the level of performance of the firewall is not less than of masonry or concrete in the areas of

    (i)performance during fire conditions,

    (ii)mechanical damage during the normal use of the building, and

    (iii)resistance to damage from moisture,

    (d)the firewall separates buildings or buildings with floor areas that do not contain

    (i)a Group B, Division 1 major occupancy, or

    (ii)a Group B, Division 2 major occupancy, and

    (e)the firewall does not separate a building regulated by the provisions of Subsection 3.2.6. or a building within the scope of Article 3.2.2.51. or 3.2.2.60. from another building unless the buildings on both sides of the firewall are sprinklered. (See Note A-3.1.10.2.(4))

    Open OBC Div. B 3.1.10.2. in the code viewer
  • OBC Div. B 3.1.10.3. Continuity of Firewalls

    (1)A firewall shall extend from the ground continuously through, or adjacent to, all storeys of a building or buildings so separated, except that a firewall located above a basement storage garage conforming to Article 3.2.1.2. is permitted to commence at the floor assembly immediately above the storage garage. (See also Sentence 3.1.10.1.(3))

    (2)A firewall is permitted to terminate on the underside of a reinforced concrete roof slab provided

    (a)the roof slab on both sides of the firewall has a fire-resistance rating not less than

    (i)1 h if the firewall is required to have a fire-resistance rating not less than 2 h, or

    (ii)2 h if the firewall is required to have a fire-resistance rating not less than 4 h, and

    (b)there are no concealed spaces within the roof slab in that portion immediately above the firewall.

    Open OBC Div. B 3.1.10.3. in the code viewer
  • OBC Div. B 3.1.10.4. Parapets

    (1)Except as permitted by Sentences (2) and 3.1.10.3.(2), a firewall shall extend above the roof surface to form a parapet not less than

    (a)150 mm high for a firewall required to have a fire-resistance rating not less than 2 h, and

    (b)900 mm high for a firewall required to have a fire-resistance rating not less than 4 h.

    (2)A firewall that separates 2 buildings with roofs at different elevations need not extend above the upper roof surface to form a parapet, provided the difference in elevation between the roofs is more than 3 m.

    Open OBC Div. B 3.1.10.4. in the code viewer
Show all 42 articles
  • OBC Div. B 3.1.10.5. Maximum Openings

    (1)Openings in a firewall shall conform to the size limits described in Article 3.1.8.6.

    (2)The aggregate width of openings in a firewall within a storey shall be not more than 25% of the entire length of the firewall.

    Open OBC Div. B 3.1.10.5. in the code viewer
  • OBC Div. B 3.1.10.7. Combustible Projections

    (1)Combustible material shall not extend across the end of a firewall but is permitted to extend across a roof above a firewall that is terminated in conformance with Sentence 3.1.10.3.(2).

    (2)If buildings are separated by a firewall, combustible projections on the exterior of one building, including balconies, platforms, canopies, eave projections and stairs, that extend outward beyond the end of the firewall, shall not be permitted within 2.4 m of combustible projections and window or door openings of the adjacent building. (See also Article 3.2.3.6.)

    Open OBC Div. B 3.1.10.7. in the code viewer
  • OBC Div. B 3.1.12.1. Determination of Ratings

    (1)Except as required by Sentence (2) and as permitted by Sentence (3), the flame-spread rating and smoke developed classification of a material, assembly, or structural member shall be determined on the basis of not less than three tests conducted in conformance with CAN/ULC-S102, "Standard Method of Test for Surface Burning Characteristics of Building Materials and Assemblies."

    (2)The flame-spread rating and smoke developed classification of a material or assembly shall be determined on the basis of not less than three tests conducted in conformance with CAN/ULC-S102.2, "Standard Method of Test for Surface Burning Characteristics of Flooring, Floor Coverings, and Miscellaneous Materials and Assemblies," if the material or assembly

    (a)is designed for use in a relatively horizontal position with only its top surface exposed to air,

    (b)cannot be tested in conformance with Sentence (1) without the use of supporting material that is not representative of the intended installation, or

    (c)is thermoplastic.

    (3)A material, assembly, or structural member is permitted to be assigned a flame-spread rating and smoke developed classification on the basis of MMAH Supplementary Standard SB-2, "Fire Performance Ratings."

    Open OBC Div. B 3.1.12.1. in the code viewer
  • OBC Div. B 3.2.1.1. Exceptions in Determining Building Height

    (1)A rooftop enclosure provided for elevator machinery, a stairway or a service room used for no purpose other than for service to the building, shall not be considered as a storey in calculating the building height.

    (2)Space under tiers of seats in a building of the arena type shall not be considered as adding to the building height provided the space is used only for dressing rooms, concession stands and similar purposes incidental to the major occupancy of the building.

    (3)Except as required by Sentence (5), the space above a mezzanine need not be considered as a storey in calculating building height provided

    (a)the aggregate area of mezzanines that are not superimposed does not exceed 40% of the open area of the room in which they are located, and (See Note A-3.2.1.1.(3)(a))

    (b)except as permitted in Sentences (7) and 3.3.2.13.(3) the space above the mezzanine is used as an open area without partitions or subdividing walls higher than 1,070 mm above the mezzanine floor.

    (4)Except as required by Sentence (5), the space above a mezzanine need not be considered as a storey in calculating the building height provided

    (a)the aggregate area of mezzanines that are not superimposed and do not meet the conditions of Sentence (3) does not exceed 10% of the floor area in which they are located, and

    (b)the area of a mezzanine in a suite does not exceed 10% of the area of that suite.

    (5)Except as permitted by Sentence (6), each level of mezzanine that is partly or wholly superimposed above the first level of mezzanine shall be considered as a storey in calculating the building height.

    (6)Platforms intended solely for periodic inspection and elevated maintenance catwalks need not be considered as floor assemblies or mezzanines for the purpose of calculating building height, provided

    (a)they are not used for storage, and

    (b)they are constructed with noncombustible materials unless the building is permitted to be of combustible construction.

    (7)The space above a mezzanine conforming to Sentence (3) is permitted to include an enclosed space whose area does not exceed 10% of the open area of the room in which the mezzanine is located, provided the enclosed space does not obstruct visual communication between the open space above the mezzanine and the room in which it is located. (See Note A-3.2.1.1.(3)(a)

    (8)A service space in which facilities are included to permit a person to enter and to undertake maintenance and other operations pertaining to building services from within the service space need not be considered a storey if it conforms to Articles 3.2.5.14. and 3.3.1.25., and Sentences 3.2.4.18.(11), 3.2.7.3.(2), 3.3.1.3.(7), 3.4.2.4.(3) and 3.4.4.4.(9). (See Note A-3.2.1.1.(8))

    Open OBC Div. B 3.2.1.1. in the code viewer
  • OBC Div. B 3.2.2.10. Streets

    (1)Every building shall face a street located in conformance with the requirements of Articles 3.2.5.4 and 3.2.5.5 for access routes.

    (2)For the purposes of Subsections 3.2.2. and 3.2.5. an access route conforming to Subsection 3.2.5. is permitted to be considered as a street.

    (3)A building conforming to Article 3.2.2.51. or 3.2.2.60. is considered to face one street, where

    (a)not less than 25% of the building perimeter is located within 15 m of a street or streets, or

    (b)not less than 10% of the building perimeter is located within 15 m of a street or streets, provided the exterior cladding conforms to Sentence 3.1.4.8.(2).

    (4)A building is considered to face 2 streets provided not less than 50% of the building perimeter is located within 15 m of the street or streets.

    (5)A building is considered to face 3 streets provided not less than 75% of the building perimeter is located within 15 m of the street or streets.

    (6)Enclosed spaces, tunnels, bridges and similar structures, even though used for vehicular or pedestrian traffic, are not considered as streets for the purpose of this Part.

    Open OBC Div. B 3.2.2.10. in the code viewer
  • OBC Div. B 3.2.2.11. Exterior Balconies

    (1)Except as provided in Sentence (2), an exterior balcony shall be constructed in accordance with the type of construction required by Articles 3.2.2.20. to 3.2.2.93., as applicable to the occupancy classification of the building.

    (2)The floor assembly of an exterior balcony in a building or part thereof conforming to Article 3.2.2.48., 3.2.2.57. or 3.2.2.93. shall

    (a)be of noncombustible construction, or

    (b)be constructed in accordance with Article 3.1.6.3., but need not comply with Sentence 3.1.6.4.(1).

    Open OBC Div. B 3.2.2.11. in the code viewer
  • OBC Div. B 3.2.2.18. Automatic Sprinkler System Required

    (1)Except as permitted by Sentence (2), an automatic sprinkler system conforming to the requirements of Articles 3.2.4.7., 3.2.4.8., 3.2.4.9. and 3.2.5.12. shall be installed throughout a building regulated by one or more of Articles 3.2.2.20., 3.2.2.21., 3.2.2.22., 3.2.2.23., 3.2.2.24., 3.2.2.26., 3.2.2.27., 3.2.2.29., 3.2.2.31., 3.2.2.33., 3.2.2.36., 3.2.2.37., 3.2.2.38., 3.2.2.39., 3.2.2.40., 3.2.2.41., 3.2.2.42., 3.2.2.43., 3.2.2.44., 3.2.2.45., 3.2.2.46., 3.2.2.47., 3.2.2.48., 3.2.2.49., 3.2.2.51., 3.2.2.52., 3.2.2.55., 3.2.2.55A., 3.2.2.55B., 3.2.2.55C., 3.2.2.55D., 3.2.2.55.E., 3.2.2.56., 3.2.2.57., 3.2.2.59., 3.2.2.60., 3.2.2.61., 3.2.2.63., 3.2.2.65., 3.2.2.66., 3.2.2.67., 3.2.2.69., 3.2.2.71., 3.2.2.72., 3.2.2.73., 3.2.2.74., 3.2.2.76., 3.2.2.77., 3.2.2.79., 3.2.2.81., 3.2.2.82., 3.2.2.84., 3.2.2.86., 3.2.2.88., 3.2.2.90. and 3.2.2.93.

    (2)If a storey in a building or a floor area is required to have an automatic sprinkler system installed throughout in accordance with one or more of Articles 3.2.2.20. to 3.2.2.93. or Section 3.3., the automatic sprinkler system shall also be installed throughout all lower storeys in the building notwithstanding permission in Articles 3.2.2.20. to 3.2.2.93. to construct one or more of those storeys without installing automatic sprinkler protection. (See Note A-3.2.2.18.(2))

    Open OBC Div. B 3.2.2.18. in the code viewer
  • OBC Div. B 3.2.2.54. Group C, up to 3 Storeys

    (1)A building classified as Group C, other than a retirement home, is permitted to conform to Sentence (2) provided

    (a)it is not more than 3 storeys in building height, and

    (b)it has a building area not more than the value in Table 3.2.2.54.

    (2)The building referred to in Sentence (1) is permitted to be of combustible construction or noncombustible construction used singly or in combination, and

    (a)except as permitted by Sentences (3) and (4), floor assemblies shall be fire separations with a fire-resistance rating not less than 45 min,

    (b)mezzanines shall have, if of combustible construction, a fire-resistance rating not less than 45 min, and

    (c)loadbearing walls, columns and arches shall have a fire-resistance rating not less than that required for the supported assembly.

    (3)In a building that contains dwelling units that have more than one storey, subject to the requirements of Sentence 3.3.4.2.(3), the floor assemblies, including floors over basements, that are entirely contained within these dwelling units, shall have a fire-resistance rating not less than 45 min but need not be constructed as fire separations.

    (4)In a building in which there is no dwelling unit above another dwelling unit, the fire-resistance rating for floor assemblies entirely within the dwelling unit is waived.

    Open OBC Div. B 3.2.2.54. in the code viewer
  • OBC Div. B 3.2.3.1. Limiting Distance and Area of Unprotected Openings

    (1)Except as permitted by Articles 3.2.3.10. to 3.2.3.12., the area of unprotected openings in an exposing building face for the applicable limiting distance shall be not more than the value determined in accordance with

    (a)Table 3.2.3.1.-B or Table 3.2.3.1.-C for an exposing building face conforming to Article 3.2.3.2. of a building or fire compartment which is not sprinklered, or

    (b)Table 3.2.3.1.-D or Table 3.2.3.1.-E for an exposing building face conforming to Article 3.2.3.2. of a sprinklered fire compartment that is part of a building which is sprinklered in conformance with Section 3.2. (See Note A-3) (See also Article 3.1.18.3.)

    (2)The area of the unprotected openings in an exposing building face shall be the aggregate area of unprotected openings expressed as a percentage of the area of the exposing building face in Table 3.2.3.1.-B, 3.2.3.1.-C, 3.2.3.1.-D or 3.2.3.1.-E. (See Sentence 3.2.3.2.(1))

    (3)For the purpose of determining the type of construction and cladding and the fire-resistance rating of an exterior wall,

    (a)the exposing building face shall be taken as the projection of the exterior wall onto a vertical plane located so that no portion of the exterior wall of the building or of a fire compartment, if the fire compartment complies with the requirements of Article 3.2.3.2., is between the vertical plane and the line to which the limiting distance is measured, and

    (b)the area of unprotected openings shall be determined from Table 3.2.3.1.-B, 3.2.3.1.-C, 3.2.3.1.-D or 3.2.3.1.-E.

    (4)For the purpose of determining the actual percentage of unprotected openings permitted in an exterior wall, the location of the exposing building face is permitted to be taken at a vertical plane located so that there are no unprotected openings between the vertical plane and the line to which the limiting distance is measured. (See Note A-3.2.3.1.(4))

    (5)Except for buildings that are sprinklered, where the limiting distance is 2 m or less, individual unprotected openings in an exposing building face shall be no greater than

    (a)the area stated in Table 3.2.3.1.-A, or

    (b)where the limiting distance equal to or greater than 1.2 m, the area calculated by

    Area =

    Area = 0.24[((2 × LD) − 1.2)^2]

    where

    Area = area of the unprotected opening, and

    LD = limiting distance.

    (6)The spacing between individual unprotected openings described in Sentence (5) that serve a single room or space described in Sentence (7) shall not be less than

    (a)2 m horizontally of another unprotected opening that is on the same exposing building face and serves the single room or space, or

    (b)2 m vertically of another unprotected opening that serves the single room or space, or another room or space on the same storey.

    (7)For the purpose of Sentence (6), "single room or space" means a room or space that

    (a)is not divided by a wall,

    (b)is divided by

    (i)a wall that extends less than 1.5 m from the interior face of the exterior wall, or

    (ii)a partial height wall, or

    (c)consists of two or more stacked spaces that are on the same storey.

    (8)If a building has any storey that is not sprinklered and firefighting facilities cannot reach it within 10 min of the alarm being received, the required limiting distance shall be doubled.

    (9)If the surface temperature on the unexposed surface of a wall assembly exceeds the temperature limit of a standard fire test as permitted by Article 3.1.7.2., an allowance shall be made for the radiation from the hot unexposed wall surface by adding an equivalent area of unprotected opening to the area of actual openings as follows:

    A_C = A + (A_E × F_EO)

    where

    A_C = corrected area of unprotected openings including actual and equivalent openings,

    A = actual area of unprotected openings,

    A_F = area of exterior surface of the exposing building face, exclusive of openings, on which the temperature limit of the standard test is exceeded, and

    F_EO = an equivalent opening factor derived from the following expression:

    F_EO = ((T_u + 273)^4)/((T_e + 273)^4)

    T_u = average temperature in degrees Celsius of the unexposed wall surface at the time the required fire-resistance rating is reached under test conditions,

    T_e = 892°C for a fire-resistance rating not less than 45 min, 927°C for a fire-resistance rating not less than 1 h, and 1,010°C for a fire-resistance rating not less than 2 h.

    (10)Unless a closure used to protect an opening in an exposing building face has a protective performance equivalent to that required for the wall assembly in which it is located, an equivalent area of unprotected opening, determined in accordance with the procedures of Sentence (9) shall be added to the greater of

    (a)the actual area of unprotected openings, or

    (b)the corrected area of unprotected openings.

    (11)The required limiting distance for an exposing building face is permitted to be measured to a point beyond the property line that is not the centre line of a street, lane or public thoroughfare if

    (a)the owners of the properties on which the limiting distance is measured and the municipality enter into an agreement in which such owners agree that,

    (i)each owner covenants that, for the benefit of land owned by the other covenantors, the owner will not construct a building on his or her property unless the limiting distance for exposing building faces in respect of the proposed construction is measured in accordance with the agreement,

    (ii)the covenants contained in the agreement are intended to run with the lands, and the agreement shall be binding on the parties and their respective heirs, executors, administrators, successors and assigns,

    (iii)the agreement shall not be amended or deleted from title without the consent of the municipality, and

    (iv)they will comply with such other conditions as the municipality considers necessary, including indemnification of the municipality by the other parties, and

    (b)the agreement referred to in Clause (a) is registered against the title of the properties to which it applies.

    (12)Where an agreement referred to in Sentence (11) is registered against the title of a property, the limiting distance for exposing building faces shall be measured to the point referred to in the agreement.

    Open OBC Div. B 3.2.3.1. in the code viewer
  • OBC Div. B Table 3.2.3.1-A. Maximum Concentrated Area of Unprotected Openings

    Table 3.2.3.1.-A Maximum Concentrated Area of Unprotected Openings Forming Part of Sentence 3.2.3.1.(5) Limiting Distance, m | Maximum Area of Individual Unprotected Openings, m² 1.2 | 0.35 1.5 | 0.78 2.0 | 1.88

    Open OBC Div. B Table 3.2.3.1-A. in the code viewer
  • OBC Div. B 3.2.3.7. Construction of Exposing Building Face

    (1)Except as provided by Sentences (3) and (4) and Articles 3.2.3.10. and 3.2.3.11., the fire-resistance rating, construction and cladding for exposing building faces of buildings or fire compartments of Group A, B, C, D or Group F, Division 3 occupancy classification shall comply with Table 3.2.3.7.

    (2)Except as provided in Sentences (3) and (4) and Article 3.2.3.10., the fire-resistance rating, construction and cladding for exposing building faces of buildings or fire compartments of Group E or Group F, Division 1 or 2 occupancy classification shall comply with Table 3.2.3.7.

    (3)Except as provided in Articles 3.1.4.8. and 3.1.6.9., the requirement in Table 3.2.3.7. for noncombustible cladding for buildings or fire compartments where the maximum permitted area of unprotected openings is more than 10% of the exposing building face is permitted to be waived for exterior wall assemblies that comply with Article 3.1.5.5. or 3.1.5.6.

    (4)Except as provided by Articles 3.1.4.8. and 3.1.6.9., the requirement in Table 3.2.3.7. for noncombustible cladding for buildings or fire compartments where the maximum permitted area of unprotected openings is more than 25% but not more than 50% of the exposing building face is permitted to be waived where

    (a)the limiting distance is greater than 5 m,

    (b)the building or fire compartment and all combustible attic or roof spaces are sprinklered throughout,

    (c)the cladding

    (i)conforms to Subsection 9.27.6., 9.27.7., 9.27.8., 9.27.9. or 9.27.10.,

    (ii)is installed without furring members, or on furring not more than 25 mm thick, over gypsum sheathing at least 12.7 mm thick or over masonry, and

    (iii)after conditioning in conformance with ASTM D2898, "Standard Practice for Accelerated Weathering of Fire-Retardant-Treated Wood for Fire Testing," has a flame-spread rating not greater than 25 on the exterior face when tested in accordance with Sentence 3.1.12.1.(1),

    (d)the cladding

    (i)conforms to Subsection 9.27.12.,

    (ii)is installed with or without furring members over gypsum sheathing at least 12.7 mm thick or over masonry,

    (iii)has a flame-spread rating not greater than 25 when tested in accordance with Sentence 3.1.12.1.(2), and

    (iv)does not exceed 2 mm in thickness exclusive of fasteners, joints and local reinforcements, or (See Note A-3.2.3.7.(4)(d)(iv))

    (e)the exterior wall assembly complies with Article 3.1.5.5. or 3.1.5.6.

    (5)The construction requirements for the exposing building face stated in Sentences (1) and (2) shall be satisfied before increasing the unprotected opening area as permitted by Sentence 3.2.3.12.(1).

    Open OBC Div. B 3.2.3.7. in the code viewer
  • OBC Div. B 3.2.3.12. Area Increase for Unprotected Openings

    (1)Except as required by Sentence 3.2.3.7.(5), the maximum area of unprotected openings in any exposing building face of a building that is not sprinklered is permitted to be doubled if the openings are glazed with

    (a)glass block conforming to the requirements of Article 3.1.8.16., or

    (b)wired glass assemblies conforming to MMAH Supplementary Standard SB-2, "Fire Performance Ratings." (See Note A-3.2.3.12.(1)) (See A-2.3.15. of SB-2)

    Open OBC Div. B 3.2.3.12. in the code viewer
  • OBC Div. B 3.2.5.12. Automatic Sprinkler Systems

    (1)Except as provided by Sentences (2) to (4) and (9), an automatic sprinkler system shall be designed, constructed, installed and tested in conformance with NFPA 13, "Standard for the Installation of Sprinkler Systems." (See Note A-3.2.5.12.(1))

    (2)Instead of the requirements of Sentence (1), NFPA 13R, "Standard for the Installation of Sprinkler Systems in Low-Rise Residential Occupancies," is permitted to be used for the design, construction, installation and testing of an automatic sprinkler system installed

    (a)in a building of residential occupancy throughout that is not more than 4 storeys in building height and conforms to Article 3.2.2.47., 3.2.2.49., 3.2.2.51., 3.2.2.52. or 3.2.2.55.,

    (b)in a building of Group B, Division 3 occupancy that contains sleeping accommodation for not more than 10 persons and not more than six occupants require assistance in evacuation in case of an emergency,

    (c)in a building that contains a retirement home constructed in accordance with Article 3.2.2.55D., or

    (d)in a building that contains a retirement home constructed in accordance with Article 3.2.2.55E., where the fire separation required by Sentence 3.3.4.11.(2) on the storey immediately below the roof assembly is continuous to the underside of the roof deck. (See Note A-3.2.5.12.(2))

    (3)Instead of the requirements of Sentence (1), NFPA 13D, "Standard for the Installation of Sprinkler Systems in Oneand Two-Family Dwellings and Manufactured Homes," is permitted to be used for the design, construction and installation of an automatic sprinkler system installed

    (a)in a building of residential occupancy throughout that contains not more than two dwelling units,

    (b)reserved,

    (c)in a building of residential occupancy throughout that contains more than two dwelling units, provided

    (i)except for a secondary suite, no dwelling unit is located above another dwelling unit,

    (ii)all suites are separated by a vertical fire separation having a fire-resistance rating of not less than 1 h that provides continuous protection from the top of the footing to the underside of the roof deck, with any space between the top of the wall and the roof deck tightly filled with mineral wool or noncombustible material,

    (iii)each dwelling unit has its own sprinkler water supply provided in accordance with NFPA 13D, "Standard for the Installation of Sprinkler Systems in One- and Two-Family Dwellings and Manufactured Homes,"

    (iv)a passive purge sprinkler system design is used as described in NFPA 13D, "Standard for the Installation of Sprinkler Systems in One- and Two-Family Dwellings and Manufactured Homes," and

    (v)where the sprinkler system is taken into consideration for the reduction of limiting distance, all rooms, including closets, bathrooms and attached garages, that adjoin an exposing building face are sprinklered, notwithstanding any exemption stated in NFPA 13D, "Standard for the Installation of Sprinkler Systems in One- and Two-Family Dwellings and Manufactured Homes." (See Note A-3.2.5.12.(2))

    (4)If a building contains fewer than 9 sprinklers, the water supply for these sprinklers is permitted to be supplied from the domestic water system for the building provided the required flow for the sprinklers can be met by the domestic system.

    (5)If a water supply serves both an automatic sprinkler system and a system serving other equipment, control valves shall be provided so that either system can be shut off independently.

    (6)Notwithstanding the requirements of the standards referenced in Sentences (1) and (2) for the installation of automatic sprinkler systems, sprinklers shall not be omitted in any room or closet in the storey immediately below a roof assembly. (See Note A-3.2.5.12.(6))

    (7)Notwithstanding the requirements of the standards referenced in Sentences (1) and (2) regarding the installation of automatic sprinkler systems, in buildings conforming to Article 3.2.2.48., 3.2.2.51., 3.2.2.57., 3.2.2.60. or 3.2.2.93., sprinklers shall be provided for all balconies and decks, other than,

    (a)balconies or decks that are not more than 610 mm in depth measured perpendicular to the exterior wall of the building, or

    (b)decks on the uppermost roof of the building. (See Note A-3.2.5.12.(7))

    (8)Sprinklers in elevator machine rooms shall have a temperature rating not less than that required for an intermediate temperature classification and shall be protected against physical damage. (See Note A-3.2.5.12.(8))

    (9)Except as provided in Subsection 3.2.8., closely spaced sprinklers and associated draft stops need not be installed around floor openings in conformance with NFPA 13, "Standard for the Installation of Sprinkler Systems."

    (10)The sprinkler system described in Sentence (3) shall be provided with a minimum 20 min water supply when installed in a retirement home.

    Open OBC Div. B 3.2.5.12. in the code viewer
  • OBC Div. B 3.2.5.9. Standpipe System Design

    (1)Except as provided in Sentences (2) to (5), Articles 3.2.5.10. and 3.2.5.11., and Sentence 3.2.4.9.(2), the design, construction, installation and testing of a standpipe system shall conform to NFPA 14, "Standard for the Installation of Standpipe and Hose Systems."

    (2)A dry standpipe that is not connected to a water supply shall not be considered as fulfilling the requirements of this Article.

    (3)If more than one standpipe is provided, the total water supply need not be more than 30 L/s.

    (4)The residual water pressure at the design flow rate at the topmost hose connection of a standpipe system that is required to be installed in a building is permitted to be less than 690 kPa provided

    (a)the building is sprinklered throughout,

    (b)the water supply at the base of the sprinkler riser is capable of meeting, without a fire pump, the design flow rate and pressure demand of the sprinkler system, including the inside and outside hose allowance, and

    (c)fire protection equipment is available to deliver, by means of the fire department connection, the full demand flow rate at a residual water pressure of 690 kPa at the topmost hose connection of the standpipe system. (See Note A-3.2.5.9.(4)(c))

    (5)A fire department connection shall be provided for every standpipe system.

    Open OBC Div. B 3.2.5.9. in the code viewer
  • OBC Div. B 3.4.7.1. Scope

    (1)Except as permitted by Sentence (2), fire escapes shall not be erected on a building.

    (2)If it is impracticable to provide one or more of the exit facilities listed in Article 3.4.1.4., fire escapes conforming to Articles 3.4.7.2. to 3.4.7.7. are permitted to serve floor areas in an existing building provided the floor areas served are

    (a)not in an elementary or secondary school or a retirement home,

    (b)not more than 2 storeys above ground level in care, care and treatment or detention occupancies, and

    (c)not more than 5 storeys above ground level in other occupancies.

    Open OBC Div. B 3.4.7.1. in the code viewer
  • OBC Div. B 3.4.7.5. Stairs

    (1)Stairs shall be inclined at an angle of not more than 45° with the horizontal, and their steps shall have risers not more than 210 mm high and treads not less than 220 mm wide exclusive of nosing.

    (2)Stairway headroom shall be not less than 1,950 mm plus the height of one riser measured vertically above the nosing of any tread or platform.

    (3)The width of a fire escape shall conform to Articles 3.4.3.1. to 3.4.3.3., except that the width is permitted to be reduced to 550 mm provided the fire escape serves

    (a)not more than 3 storeys, and

    (b)not more than 15 persons.

    (4)If a flight of stairs leading to the ground at the foot of a fire escape is not fixed in position, it shall

    (a)be held in the raised position without a latch or locking device,

    (b)be fitted with a counterbalancing device,

    (c)be easily and quickly brought into position for use, and

    (d)reach the ground in the lowered position.

    Open OBC Div. B 3.4.7.5. in the code viewer
  • OBC Div. B 3.4.7.3. Access to Fire Escapes

    (1)Access to fire escapes shall be from corridors through doors at floor level, except that access from a dwelling unit is permitted to be through a casement window having an unobstructed opening not less than 1,100 mm high by 550 mm wide with a sill height of not more than 900 mm above the inside floor.

    (2)The clear area of a fire escape balcony onto which a door opens, shall be not less than 1 m².

    Open OBC Div. B 3.4.7.3. in the code viewer
  • OBC Div. B 3.4.7.6. Guards and Railings

    (1)The open sides of every platform, balcony and stairway forming part of a fire escape shall be protected by guards not less than 920 mm high measured vertically above the nosing of any tread or platform.

    (2)The top rail of a guard is permitted to serve as a handrail if it is free from obstructions that could break a handhold.

    (3)A wall handrail shall be installed if the fire escape is more than 550 mm wide.

    (4)Openings through any guard that is required by Sentence (1) shall be of a size that will prevent the passage of a sphere having a diameter more than 100 mm unless it can be shown that the location and size of openings that exceed this limit do not represent a hazard.

    (5)Unless it can be shown that the location and size of an opening do not present a hazard, a guard for a fire escape shall be designed so that no member, attachment or opening located between 140 mm and 900 mm above a platform or the nosing of any tread will facilitate climbing.

    Open OBC Div. B 3.4.7.6. in the code viewer
  • OBC Div. B 3.6.3.1. Fire Separations for Vertical Service Spaces

    (1)Except as provided in Articles 3.6.3.3. and 3.6.3.5. and Section 3.5., a vertical service space shall be separated from all other portions of each adjacent storey by a fire separation having a fire-resistance rating conforming to Table 3.6.3.1. for the fire-resistance rating required by Subsection 3.2.2. for

    (a)the floor assembly above the storey, or

    (b)the floor assembly below the storey, if there is no floor assembly above. (See Note A-3.6.3.1.(1))

    (2)A vertical service space that does not extend through the roof of a building shall be enclosed at the top with construction having a fire-resistance rating not less than that required for the vertical service space walls.

    (3)A vertical service space that does not extend to the bottom of a building shall be enclosed at the lowest level with construction having a fire-resistance rating not less than that required for the vertical service space walls.

    (4)A vent from a vertical service space not extending to the roof shall be enclosed within the building with construction having a fire-resistance rating not less than that required for the vertical service space walls.

    (5)Only openings that are necessary for the use of the vertical service space shall be permitted through a vertical service space enclosure.

    Open OBC Div. B 3.6.3.1. in the code viewer
  • OBC Div. B 3.7.4.5. Plumbing Facilities for Dwelling Units

    (1)A dwelling unit where a piped water supply is available shall be provided with a

    (a)kitchen sink,

    (b)lavatory,

    (c)water closet or drainless composting water closet, and

    (d)bathtub or shower stall.

    Open OBC Div. B 3.7.4.5. in the code viewer
  • OBC Div. B 4.1.5.14. Loads on Guards and Handrails)

    (1)The minimum horizontal specified live load applied outward at the minimum required height of every required guard shall be

    (a)3.0 kN/m for open viewing stands without fixed seats and for means of egress in grandstands, stadia, bleachers and arenas,

    (b)1.0 kN applied at any point, so as to produce the most critical effect, for access ways to equipment platforms, contiguous stairs and similar areas where the gathering of many people is improbable, and

    (c)0.75 kN/m or 1.0 kN applied at any point so as to produce the most critical effect, whichever governs for locations other than those described in Clauses (a) and (b).

    (2)The minimum horizontal specified live load applied inward at the minimum required height of every required guard shall be half that specified in Sentence (1).

    (3)Individual elements within the guard, including solid panels and pickets, shall be designed for a horizontal specified live load of 0.5 kN applied outward over an area of 100 mm by 100 mm located at any point on the element or elements so as to produce the most critical effect.

    (4)The size of the opening between any two adjacent vertical elements within a guard shall not exceed the limits required by Part 3 when each of these elements is subjected to a horizontal specified live load of 0.1 kN applied in opposite directions in the in-plane direction of the guard so as to produce the most critical effect.

    (5)The specified live loads required in Sentence (3) need not be considered to act simultaneously with the loads provided for in Sentences (1), (2), (6) and (7).

    (6)The minimum specified live load applied vertically at the top of every required guard shall be 1.5 kN/m and need not be considered to act simultaneously with the horizontal specified live load provided for in Sentences (1), (3) and (7).

    (7)Handrails and their supports shall be designed and constructed to withstand the following minimum specified live loads, which need not be considered to act simultaneously:

    (a)0.9 kN applied at any point and in any direction for all handrails, and

    (b)0.7 kN/m applied in any direction for handrails not located within dwelling units.

    Open OBC Div. B 4.1.5.14. in the code viewer
  • OBC Div. B 4.1.5.17. Firewalls

    (1)Firewalls shall be designed to resist the maximum effect due to,

    (a)the appropriate lateral design loads prescribed elsewhere in this Section, or

    (b)a factored lateral load of 0.5 kPa under fire conditions, as described in Sentence (2).

    (2)Under fire conditions, where the fire-resistance rating of the structure is less than that of the firewall,

    (a)lateral support shall be assumed to be provided by the structure on one side only, or

    (b)another structural support system capable of resisting the loads imposed by a fire on either side of the firewall shall be provided.

    Open OBC Div. B 4.1.5.17. in the code viewer
  • OBC Div. B 4.2.2.1. Subsurface Investigation

    (1)A subsurface investigation, including groundwater conditions, shall be carried out by or under the direction of a professional engineer having knowledge and experience in planning and executing such investigations to a degree appropriate for the building and its use, the ground and the surrounding site conditions. (See Note A-4.2.2.1.(1))

    Open OBC Div. B 4.2.2.1. in the code viewer
  • OBC Div. B 4.3.1.1. Design Basis for Wood

    (1)Buildings and their structural members made of wood shall conform to CSA O86, "Engineering design in wood."

    Open OBC Div. B 4.3.1.1. in the code viewer
  • OBC Div. B 4.3.2.1. Design Basis for Plain and Reinforced Masonry

    (1)Buildings and their structural members made of plain and reinforced masonry shall conform to CSA S304, "Design of masonry structures."

    Open OBC Div. B 4.3.2.1. in the code viewer
  • OBC Div. B 4.3.4.1. Design Basis for Structural Steel

    (1)Buildings and their structural members made of structural steel shall conform to CSA S16, "Design of steel structures." (See Note A-4.3.4.1.(1))

    Open OBC Div. B 4.3.4.1. in the code viewer
  • OBC Div. B 5.1.1.1. Scope

    (1)This Part is concerned with

    (a)the control of condensation

    (i)in building components and assemblies, and

    (ii)on building materials, components and assemblies, and

    (b)the transfer of heat, air, moisture and sound through

    (i)building materials, components and assemblies, and

    (ii)interfaces between building materials, components and assemblies. (See Note A-5.1.1.1.(1))

    Open OBC Div. B 5.1.1.1. in the code viewer
  • OBC Div. B 5.5.1.1. Required Resistance to Vapour Diffusion

    (1)Where a building component or assembly is subjected to differentials in temperature and water vapour pressure, the properties and position of the materials and components in those components or assemblies shall be such that they control vapour diffusion or permit venting to the exterior so as to minimize accumulation of condensation in the building component or assembly.

    (2)Except as provided in Sentence (3), a vapour barrier shall be installed to provide the principal resistance to water vapour diffusion.

    (3)A vapour barrier is not required where it can be shown that uncontrolled vapour diffusion will not adversely affect any of

    (a)the health or safety of building users,

    (b)the intended use of the building, or

    (c)the operation of building services.

    Open OBC Div. B 5.5.1.1. in the code viewer
  • OBC Div. B 5.6.2.1. Sealing and Drainage

    (1)Except as provided in Sentence (2), materials, components, assemblies, joints in materials, junctions between components and junctions between assemblies exposed to precipitation shall be

    (a)sealed to prevent ingress of precipitation, or

    (b)drained to direct precipitation to the exterior.

    (2)Sealing or drainage are not required where it can be shown that the omission of sealing and drainage will not adversely affect any of,

    (a)the health or safety of building users,

    (b)the intended use of the building, or

    (c)the operation of building services.

    Open OBC Div. B 5.6.2.1. in the code viewer
  • OBC Div. B 6.2.1.5. Installation Standards

    (1)The installation of solid fuel-burning appliances for central heating systems shall comply with CSA B365, "Installation code for solid-fuel-burning appliances and equipment" and the manufacturer's installation instructions.

    (2)The solid fuel-fired appliances in Sentence (1) shall conform to CSA B366.1, "Solid-fuel-fired central heating appliances."

    (3)The design and installation of earth energy systems shall conform to CAN/CSA-C448.2, "Design and installation of earth energy systems for residential and other small buildings," where such systems use groundwater, submerged heat exchangers or ground heat exchangers to serve,

    (a)a house with or without a secondary unit, or,

    (b)a building, other than a house with or without a secondary unit, where the conditioned space is not more than 1,400 m².

    (4)Except for a house with or without a secondary unit, the design and installation of earth energy systems shall conform to CAN/CSA-C448.1, "Design and installation of earth energy systems for commercial and institutional buildings," where such systems use groundwater, submerged heat exchangers or ground heat exchangers to condition a floor space area more than 1,400 m².

    (5)The design and installation of solid fuel-burning stoves, ranges and space heaters, including the requirements for combustion air, shall conform to the requirements of CSA B365, "Installation code for solid-fuel-burning appliances and equipment" and the manufacturer's installation instructions.

    (6)The design and installation of hydronic heating systems shall conform to

    (a)CSA B214, "Installation code for hydronic heating systems," or

    (b)good engineering practice appropriate to the circumstances such as described in Article 6.2.1.1.

    (7)Solid fuel-burning stoves, furnaces and hydronic heating systems designed to burn solid fuels, other than coal, shall conform to the particulate emission limits of,

    (a)CSA B415.1, "Performance Testing of Solid-Fuel-Burning Heating Appliances," or

    (b)the "Standards of Performance for New Residential Wood Heaters," set out in Subpart AAA of Part 60 of Title 40 of the Code of Federal Regulations, published by the United States Environmental Protection Agency, as it read on March 16, 2015.

    Open OBC Div. B 6.2.1.5. in the code viewer
  • OBC Div. B 6.3.2.9. Supply, Return, Intake and Exhaust Air Openings

    (1)Supply, return and exhaust air openings located less than 2 m above the floor in rooms or spaces in buildings shall be protected by grilles having openings of a size that will not allow the passage of a 15 mm diam sphere.

    (2)Outdoor air intakes shall be located so that

    (a)the quality of the air entering the building complies with Sentence 6.2.1.2.(1), and

    (b)they are separated a minimum distance from sources of contaminants in accordance with Table 6.3.2.9.

    (3)Outdoor air intakes shall be installed not less than 0.3 m above roofs, landscape grades or other surfaces, taking into account anticipated snow accumulation levels.

    (4)Exterior openings for outdoor air intakes and exhaust outlets shall be shielded from the entry of snow and rain and shall be fitted with corrosion-resistant screens of mesh having openings not larger than 15 mm, except where experience has shown that climatic conditions require larger openings to prevent the screen openings from icing over.

    (5)Screens required in Sentence (4) shall be accessible for maintenance.

    (6)Combustible grilles, diffusers and other devices covering supply, return, intake and exhaust openings shall comply with Article 3.6.5.7.

    Open OBC Div. B 6.3.2.9. in the code viewer
  • OBC Div. B 7.1.2.2. Storm Drainage Systems

    (1)Except as provided in Section 7.7., storm drainage systems and private sewers conveying storm sewage shall be connected to a public storm sewer, a public combined sewer or a designated storm water disposal location.

    Open OBC Div. B 7.1.2.2. in the code viewer
  • OBC Div. B 7.6.1.7. Relief Valves

    (1)Every pressure vessel that is part of a plumbing system or connected to a plumbing system shall be equipped with a pressure-relief valve designed to open when the water pressure in the tank reaches the rated working pressure of the tank, and so located that the pressure in the tank shall not exceed 1,100 kPa or one-half the maximum test pressure sustained by the tank, whichever is the lesser.

    (2)The hot water tank of a storage-type service water heater shall be equipped with a temperature-relief valve with a temperature-sensing element

    (a)located within the top 150 mm of the tank, and

    (b)designed to open and discharge sufficient water from the tank to keep the temperature of the water in the tank from exceeding 99°C under all operating conditions.

    (3)A pressure-relief valve and temperature-relief valve may be combined where Sentences (1) and (2) are complied with.

    (4)Indirect service water heaters shall be equipped with

    (a)a pressure-relief valve, and

    (b)a temperature-relief valve on every storage tank that forms part of the system.

    (5)Pipes that convey water from a temperature-relief, pressure-relief, or a combined temperature- and pressure-relief valve shall

    (a)be of a nominal pipe size at least equal to the NPS of the outlet of the valve,

    (b)be rigid, slope downward from the valve, and terminate with an indirect connection above a floor drain, sump, or other safe location, with an air break of not more than 300 mm,

    (c)have no thread at its outlet, and

    (d)be capable of operating at a temperature of not less than 99°C. (See Note A-7.6.1.7.(5))

    (6)The temperature-relief valve required in Clause (4)(b) shall

    (a)have a temperature-sensing element located within the top 150 mm of the tank, and

    (b)be designed to open and discharge sufficient water to keep the temperature of the water in the tank from exceeding 99°C under all operating conditions.

    (7)No shut-off valve shall be installed on the pipe between any tank and the relief valves or on the discharge lines from such relief valves.

    Open OBC Div. B 7.6.1.7. in the code viewer
  • OBC Div. B 7.6.4.1. Water Supply Fittings

    (1)Each lavatory in a washroom with fixtures for public use shall be equipped with a device capable of automatically shutting off the flow of water when the lavatory is not in use. (See Note A-7.6.4.1.(1) and (3))

    (2)An automatic compensating valve serving an individual shower head shall have a manufacturer's minimum-rated water flow rate equal to or less than the shower head it serves. (See Note A-7.6.4.1.(2))

    (3)Where multiple shower heads installed in a public showering facility are served by one temperature control, each shower head shall be equipped with a device capable of automatically shutting off the flow of water when the shower head is not in use. (See Note A-7.6.4.1.(1) and (3))

    Open OBC Div. B 7.6.4.1. in the code viewer