Values this chapter turns on
- of perimeter enclosed: over this, it is a garage
- 60%
- of perimeter enclosed: over this, it is a garage
- per light, unfinished basements
- 30 m²
- per light, unfinished basements
- hot water delivered to fixtures
- 45°C to 60°C
- hot water delivered to fixtures
- or more: 3-way switches at head and foot
- 4 risers
- or more: 3-way switches at head and foot
This chapter collects the short Part 9 sections at the end of the Part:
- required plumbing facilities and service water heating (9.31.),
- one exhaust duct rule from 9.33.,
- electrical facilities and lighting outlets (9.34.),
- garages and carports (9.35.),
- seasonal recreational buildings, log construction and park model trailers (9.37. to 9.39.),
- small reinforced concrete slabs over cold rooms (9.40.),
- change of use (9.41.).
Each is short, so questions tend to test one clear number or exception. The plumbing system design itself is Part 7 and belongs to the Plumbing exams. The Ministry guide also leaves out the Section 9.31. sentences on non-dwelling occupancies and medical gas, and the wiring rule in 9.34.1.5.
Plumbing facilities and service water heating
Section 9.31. applies to plumbing facilities within dwelling units (OBC Div. B 9.31.1.1.OBC Div. B 9.31.1.1. Application(1) This Section applies to the plumbing facilities and plumbing systems within dwelling units. (2) In occupancies other than dwelling units, plumbing facilities, grab bars, floor drains, and floor and wall finishes around urinals shall conform to Subsection 3.7.4. (See also Section 3.8. regarding barrier-free…). Plumbing work itself must meet Part 7 (9.31.2.1.OBC Div. B 9.31.2.1. General(1) The construction, extension, alteration, renewal or repair of plumbing systems and sewage disposal systems shall conform to Part 7.). Where a water distribution system is available:
- the dwelling unit gets a water supply (9.31.3.1.OBC Div. B 9.31.3.1. Required Water Supply(1) Every dwelling unit shall be supplied with a water distribution system where a drinking water system is available.),
- hot and cold water go to every kitchen sink, lavatory, tub, shower, slop sink and laundry area, and cold water to every water closet (9.31.3.2.OBC Div. B 9.31.3.2. Required Connections(1) Where a water distribution system is available, piping for hot and cold water shall be connected to every kitchen sink, lavatory, bathtub, shower, slop sink and laundry area. (2) Piping for cold water shall be run to every water closet.),
- a kitchen sink, lavatory, bathtub or shower, and water closet are required (9.31.4.1.OBC Div. B 9.31.4.1. Required Fixtures(1) A kitchen sink, lavatory, bathtub or shower, and water closet shall be provided for every dwelling unit where a water distribution system is available.),
- hot water supply is required (9.31.4.2.OBC Div. B 9.31.4.2. Hot Water Supply(1) Where a water distribution system is available a hot water supply shall be provided in every dwelling unit. (2) A water distribution system supplying hot water to plumbing fixtures shall conform to the requirements in Subsection 7.2.10.).
Every dwelling unit also needs laundry facilities or space for them, or shared laundry that is conveniently accessible (9.31.4.1A.OBC Div. B 9.31.4.1A. Laundry Fixtures(1) Laundry facilities or a space for laundry facilities shall be provided in every dwelling unit or grouped elsewhere in the building in a location conveniently accessible to occupants of every dwelling unit.). A basement floor drain is required only where gravity drainage to a sewer, ditch or dry well is possible (9.31.4.3.OBC Div. B 9.31.4.3. Floor Drains(1) Where gravity drainage to a sewer, drainage ditch or dry well is possible, a floor drain shall be installed in a basement forming part of a dwelling unit.). Grab bars, where installed, resist 1.3 kN (9.31.2.3.OBC Div. B 9.31.2.3. Grab Bars(1) When provided, grab bars shall be capable of resisting a load of not less than 1.3 kN applied vertically or horizontally.).
Service water heating:
| Item | Requirement |
|---|---|
| Hot water delivered | 45°C to 60°C (9.31.6.1A.OBC Div. B 9.31.6.1A. Hot Water Temperature(1) Where a hot water supply is required by Article 9.31.4.3., equipment shall be installed to provide to every dwelling unit an adequate supply of service hot water with a temperature range from 45°C to 60°C. (2) An electric storage-type service water heater shall have a minimum set storage temperature of 60°C.) |
| Electric storage heater set point | At least 60°C |
| Seismic restraint | Secure against overturning where Sa(0.2) is more than 0.55 (9.31.6.2.OBC Div. B 9.31.6.2. Equipment and Installation(1) Every service water heater and its installation shall conform to Part 7. (2) Reserved (3) Where the building is in a location where the spectral response acceleration, S_a(0.2) , is greater than 0.55, service water heaters shall be secured to the structure to resist overturning. (See Note A-9.31.6.2.(3))) |
| Fuel-burning heater | Connected to a chimney flue meeting 9.21. (9.31.6.4.OBC Div. B 9.31.6.4. Fuel-Burning Heaters(1) Fuel-burning service water heaters shall be connected to a chimney flue conforming to Section 9.21.) |
| Steel tanks | Coated against corrosion, for example glass lined (9.31.6.3.OBC Div. B 9.31.6.3. Corrosion-Resistant Coating(1) Where storage tanks for service water heaters are of steel, they shall be coated with zinc, vitreous enamel (glass lined), hydraulic cement or other corrosion-resistant material.) |
"Service water heater" is defined in Div. A 1.4.1.2.OBC Div. A 1.4.1.2.(1) Service water heaterService water heater means a device for heating water for plumbing services. as a device for heating water for plumbing services.
Dryer exhaust ducts
Only Sentence (3) of 9.33.6.14A.OBC Div. B 9.33.6.14A. Exhaust Ducts and Outlets(1) Where an exhaust duct passes through or is adjacent to unheated space, the duct shall be insulated to prevent moisture or condensation in the duct. (2) Exhaust outlets shall be designed to prevent back draft under wind conditions. (3) Exhaust ducts directly connected to laundry drying equipment shall be… is on this exam. An exhaust duct connected directly to a clothes dryer must be independent of all other exhaust ducts. No tying into the bathroom fan duct.
Electrical facilities and lighting outlets
Where electrical service is available, Section 9.34. applies (9.34.1.2.OBC Div. B 9.34.1.2. Required Facilities(1) Where electrical services are available, electrical facilities shall be provided for every building in conformance with this Section.). Recessed fixtures may go in insulated ceilings only if designed for it (9.34.1.4.OBC Div. B 9.34.1.4. Recessed Lighting Fixtures(1) Recessed lighting fixtures shall not be located in insulated ceilings unless the fixtures are designed for such installations.). Lighting rules for houses:
- Entrances: every entrance gets an exterior light switched from inside (9.34.2.1.OBC Div. B 9.34.2.1. Lighting of Entrances(1) An exterior lighting outlet with fixture controlled by a wall switch located within the building shall be provided at every entrance to buildings of residential occupancy. (2) The exterior lighting outlet with fixture required by Sentence (1) may be controlled by a wall switch or panel accessible to authorized…).
- Rooms: kitchens, bedrooms, living rooms, utility and laundry rooms, dining rooms, bathrooms, water-closet rooms, vestibules and hallways get a wall-switched light. A switched receptacle may replace it in bedrooms and living rooms (9.34.2.2.OBC Div. B 9.34.2.2. Outlets in Dwelling Units(1) Except as provided in Sentence (2), a lighting outlet with fixture controlled by a wall switch shall be provided in kitchens, bedrooms, living rooms, utility rooms, laundry rooms, dining rooms, bathrooms, water-closet rooms, vestibules and hallways in dwelling units. (2) Where a receptacle controlled by a wall…).
- Stairs (9.34.2.3.OBC Div. B 9.34.2.3. Stairways(1) Every stairway shall be lighted. (2) Except as provided in Sentence (3), 3-way wall switches located at the head and foot of every stairway shall be provided to control at least one lighting outlet with fixture for stairways with 4 or more risers in dwelling units and houses with a secondary suite including their…): every stairway is lit. Stairs with 4 or more risers get 3-way switches at the head and foot. Exception: a basement with no finished space, no outside entrance and no built-in garage, serving one dwelling unit, may use one switch at the head.
- Unfinished basements (9.34.2.4.OBC Div. B 9.34.2.4. Basements(1) A lighting outlet with fixture shall be provided for each 30 m² or fraction thereof of floor area in unfinished basements. (2) The outlet required in Sentence (1) nearest the stairs shall be controlled by a wall switch located at the head of the stairs.): one light per 30 m² or part of 30 m². The one nearest the stairs is switched at the head of the stairs.
- Storage rooms, garages and carports (9.34.2.5.OBC Div. B 9.34.2.5. Storage Rooms(1) A lighting outlet with fixture shall be provided in storage rooms., 9.34.2.6.OBC Div. B 9.34.2.6. Garages and Carports(1) A lighting outlet with fixture shall be provided for an attached, built-in or detached garage or carport. (2) Except as provided in Sentence (3), outlets required in Sentence (1) shall be controlled by a wall switch near the doorway. (3) Where the outlet and fixture required in Sentence (1) are ceiling mounted…): a light is required. In garages it is wall-switched near the door, but a fixture with a built-in switch is fine where it is wall mounted or ceiling mounted away from the parked car.
Garages and carports
Section 9.35. covers garages and carports serving one dwelling unit (9.35.1.1.OBC Div. B 9.35.1.1. Application(1) This Section applies to garages and carports serving not more than one dwelling unit.). A "storage garage" is one with no provision for repairing or servicing vehicles (Div. A 1.4.1.2.OBC Div. A 1.4.1.2.(1) Storage garageStorage garage means a building or part thereof intended for the storage or parking of motor vehicles and containing no provision for the repair or servicing of such vehicles. (See Note A-1.4.1.2.(1))).
- Carport or garage? (9.35.2.1.OBC Div. B 9.35.2.1. Carport Considered to be Garage(1) Where a roofed enclosure used for the storage or parking of motor vehicles has more than 60 percent of the total perimeter enclosed by walls, doors or windows, the enclosure shall be considered a garage.) If more than 60% of the perimeter is enclosed by walls, doors or windows, it is a garage. Example: 6.0 m x 3.5 m with three sides walled is 13.0 / 19.0 m, about 68%, so it is a garage.
- Floor: an attached or built-in garage floor drains to the outdoors (9.35.2.2.OBC Div. B 9.35.2.2. Garage Floor(1) Where an attached or built-in garage is provided, the garage floor shall be sloped to drain liquids to the outdoors.).
- Foundations (9.35.3.1.OBC Div. B 9.35.3.1. Foundation Required(1) Except as permitted in this Subsection, foundations conforming to Sections 9.12. and 9.15. shall be provided for the support of carport and garage super-structures, including that portion beneath garage doors. (2) Detached garages of less than 55 m² floor area and not more than 1 storey in height that are not of…): normally full Part 9 foundations, including under the door. A detached garage under 55 m², one storey and not masonry may sit on wood mud sills or a slab at least 100 mm thick. The same small garage may skip foundation drainage where the ground slopes away (9.35.3.3.OBC Div. B 9.35.3.3. Drainage(1) Detached garages of less than 55 m² floor area and not more than 1 storey in height that are not of masonry or masonry veneer construction need not conform with the foundation drainage requirements stated in Section 9.14. where the finished ground level is at or near the elevation of the garage's floor and where…).
- Soil movement (9.35.3.2.OBC Div. B 9.35.3.2. Protection from Damage Due to Soil Movement(1) In clay-type soils subject to significant movement with a change in soil moisture content, the foundation depth of carports or garages connected to a dwelling unit directly or by a breezeway shall be approximately the same depth as the foundation of the main building. (2) Where slab-on-ground construction is used…): put a construction joint between the house slab and an attached garage slab. Foundations of attached unheated garages go below frost level.
- Columns and piers: carport piers extend 150 mm above ground and are at least 190 x 190 mm (9.35.3.4.OBC Div. B 9.35.3.4. Column Piers(1) Piers for the support of carport columns shall extend not less than 150 mm above ground level. (2) Piers referred to in Sentence (1) shall project not less than 25 mm beyond the base of the column but in no case be less than 190 mm by 190 mm in size.). 89 x 89 mm wood columns are allowed (9.35.4.2.OBC Div. B 9.35.4.2. Columns(1) Columns for garages and carports shall conform to Section 9.17., except that 89 mm by 89 mm wood columns may be used.). No interior finish is required (9.35.4.1.OBC Div. B 9.35.4.1. Interior Finish(1) Interior finish need not be applied to garage and carport walls.).
Cottages, log buildings and park model trailers
Seasonal recreational buildings (9.37.OBC Div. B 9.37.1.1. Application(1) This Section applies to buildings of residential occupancy used or intended to be used as seasonal recreational buildings. (2) The buildings described in Sentence (1) shall comply with all the requirements of this Part, except where they are specifically exempted in this Section.) follow Part 9 with exemptions. They need not meet 9.5. to 9.7. or 9.9. to 9.11. (9.37.2.1.OBC Div. B 9.37.2.1. Exclusions(1) Except as provided in Subsection 9.10.15. and Articles 9.37.2.4. and 9.37.3.1., buildings used or intended to be used as seasonal recreational buildings need not comply with Sections 9.5. to 9.7. and 9.9. to 9.11. (2) Flooring need not comply with Section 9.30., but tight-fitting floors shall be provided to…). Insulation, vapour and air barriers, interior finishes, plumbing, heating, ventilation and electrical are optional, but must meet Part 9 if installed. Continuous perimeter foundations are optional, and masonry column height is limited by unit type (9.37.2.2.OBC Div. B 9.37.2.2. Foundations(1) Continuous perimeter foundation walls are not required, but when they are provided, they shall comply with the requirements of this Part. (2) Where unit masonry columns are used, the height of such columns shall not exceed, (a) in the case of hollow masonry units, 4 times the least dimension of the units, (b) in…). A smoke alarm to 9.10.19. is always required (9.37.2.4.OBC Div. B 9.37.2.4. Smoke Alarms(1) Every dwelling unit within the scope of this Section shall be provided with a smoke alarm in accordance with Subsection 9.10.19.). If the building is rented or used for tourist accommodation, Sections 9.5. to 9.8. apply too (9.37.3.1.OBC Div. B 9.37.3.1. Buildings for Seasonal Tourist Accommodation or for Rent(1) Where buildings are used or intended to be used for seasonal tourist accommodation or for rent, they shall comply with Sections 9.5. to 9.8. in addition to the requirements of this Section.).
Log construction (9.38.):
- Logs touching masonry or concrete at or below grade are preservative treated (9.38.1.2.OBC Div. B 9.38.1.2. Requirement for Wood Preservative(1) The portion of any log coming in contact with masonry or concrete at or below grade shall be treated with a wood preservative to prevent decay.).
- Horizontal logs are fastened to the log below in at least three places, never more than 1,800 mm apart (9.38.2.3.OBC Div. B 9.38.2.3. Joining Logs(1) Each log in a horizontal position shall be scribed as close as possible to its bearer and fastened to the bearer in at least three places throughout its length, by dowels, continuous machined joints, vertical framing members or interlocking intersections or any combination of these, but in no case shall the…).
- Openings in horizontal log walls need a settlement gap above the rough buck of at least 13 mm per 300 mm of height (9.38.3.2.OBC Div. B 9.38.3.2. Clearance(1) At every opening in a wall made of logs in a horizontal position where shrinkage can occur there shall be a clearance between the rough buck header and the lintel log of not less than 13 mm in width for each 300 mm of height to allow for settlement.). A 1,500 mm high window needs 5 x 13 = 65 mm.
Park model trailers built to CAN/CSA-Z241 are deemed to comply when used as seasonal recreational buildings (9.39.2.1.OBC Div. B 9.39.2.1. General(1) Except as provided in Subsection 9.39.3., a manufactured building used or intended to be used as a seasonal recreational building of residential occupancy is deemed to comply with this Code if it is designed and constructed in conformance with CAN/CSA-Z241 Series, "Park model trailers."). Site-built parts must still meet the Code, and the units are anchored per the manufacturer.
Slabs over cold rooms and change of use
Section 9.40. covers a reinforced slab over a basement cold room, supported only by the foundation walls, with a clear span of no more than 2.5 m and no vehicle loads (9.40.1.1.OBC Div. B 9.40.1.1. Application(1) This Section applies to (a) reinforced concrete slabs that are suspended over cold rooms in basements, and are supported by foundation walls along the perimeter of the slab with no additional interior supports, and (b) slabs in which the clear span between supporting walls is not more than 2.5 m along the shortest…). Otherwise use Part 4. Key values (9.40.1.4.OBC Div. B 9.40.1.4. Slab Construction(1) Concrete shall be cast against formwork in accordance with CSA A23.1, "Concrete materials and methods of concrete construction." (2) The slab shall be not less than 125 mm thick. (3) The slab shall be reinforced with 10 M bars spaced not more than 200 mm o.c. in each direction, with 30 mm clear cover from the…):
- at least 125 mm thick,
- 10M bars at 200 mm both ways, with 30 mm bottom cover,
- 75 mm bearing on the walls,
- 10M bent dowels at 600 mm.
Section 9.41. applies when construction causes a listed change of use (9.41.1.1.OBC Div. B 9.41.1.1. Application(1) This Section applies where proposed construction in respect of an existing building will result in any of the following changes of use of all or part of the building: (a) a change of the major occupancy of all or part of a building that is designated with a "Y" in Table 1.3.1.4. of Division C, (b) a suite of a…). The building must then meet listed provisions for the new occupancy, including room sizes in 9.5., glass in 9.6., guards in 9.8.8.1., and Sections 9.31., 9.32. and 9.34. (9.41.2.1.OBC Div. B 9.41.2.1. Change of Use and Compensating Construction(1) Where proposed construction will result in a change of use described in Clauses 9.40.1.1.(1)(a) to (f), additional construction shall be required in order that the building or part of a building subject to the change of use conforms to the requirements of Subsections 9.5.1. and 9.5.3. to 9.5.10., Section 9.6.…). Its performance level after construction must not drop (9.41.2.2.OBC Div. B 9.41.2.2. Performance Level Evaluation and Compensating Construction(1) The performance level of a building after construction shall not be less than the performance level of the building prior to construction. (2) For the purposes of Sentence (1), reduction of performance level shall be determined in accordance with Articles 11.4.2.1., 11.4.2.3. and 11.4.2.5. (3) Where the proposed…).
Common traps
- Requiring a basement floor drain where gravity drainage is not possible.
- Rounding down the 30 m² basement lighting count.
- Calling a structure a carport because one side is open, without doing the 60% math.
- Forgetting the smoke alarm in a cottage that is otherwise exempt.
Chapter review
Chapter at a glance
One line per section: the idea to carry into the exam. Then the answers that most often catch candidates out.
- Plumbing facilities and service water heating
Section 9.31. applies to plumbing facilities within dwelling units.
- Dryer exhaust ducts
Only Sentence (3) of is on this exam.
- Electrical facilities and lighting outlets
Where electrical service is available, Section 9.34. applies.
- Garages and carports
Section 9.35. covers garages and carports serving one dwelling unit.
- Cottages, log buildings and park model trailers
Seasonal recreational buildings follow Part 9 with exemptions.
- Slabs over cold rooms and change of use
Section 9.40. covers a reinforced slab over a basement cold room, supported only by the foundation walls, with a clear span of no more than 2.5 m and no vehicle loads.
Usual exam traps
- Requiring a basement floor drain where gravity drainage is not possible.
- Rounding down the 30 m² basement lighting count.
- Calling a structure a carport because one side is open, without doing the 60% math.
- Forgetting the smoke alarm in a cottage that is otherwise exempt.
Practice this chapter
Questions on Plumbing facilities, electrical, garages and special buildings, in the exam format, every answer explained and cited to its article. Sign in to start; a free account gets the free questions.
Code cited in this chapter
Based on the official 2024 Building Code Compendium on ontario.ca.
© King's Printer for Ontario, 2024. Reproduced with permission.
OBC Div. B 9.31.1.1. Application
Open OBC Div. B 9.31.1.1. in the code viewer(1)This Section applies to the plumbing facilities and plumbing systems within dwelling units.
(2)In occupancies other than dwelling units, plumbing facilities, grab bars, floor drains, and floor and wall finishes around urinals shall conform to Subsection 3.7.4. (See also Section 3.8. regarding barrier-free plumbing facilities.)
(3)Medical gas piping systems shall conform to Subsection 3.7.5.
OBC Div. B 9.31.2.1. General
Open OBC Div. B 9.31.2.1. in the code viewer(1)The construction, extension, alteration, renewal or repair of plumbing systems and sewage disposal systems shall conform to Part 7.
OBC Div. B 9.31.3.1. Required Water Supply
Open OBC Div. B 9.31.3.1. in the code viewer(1)Every dwelling unit shall be supplied with a water distribution system where a drinking water system is available.
OBC Div. B 9.31.3.2. Required Connections
Open OBC Div. B 9.31.3.2. in the code viewer(1)Where a water distribution system is available, piping for hot and cold water shall be connected to every kitchen sink, lavatory, bathtub, shower, slop sink and laundry area.
(2)Piping for cold water shall be run to every water closet.
OBC Div. B 9.31.4.1. Required Fixtures
Open OBC Div. B 9.31.4.1. in the code viewer(1)A kitchen sink, lavatory, bathtub or shower, and water closet shall be provided for every dwelling unit where a water distribution system is available.
OBC Div. B 9.31.4.2. Hot Water Supply
Open OBC Div. B 9.31.4.2. in the code viewer(1)Where a water distribution system is available a hot water supply shall be provided in every dwelling unit.
(2)A water distribution system supplying hot water to plumbing fixtures shall conform to the requirements in Subsection 7.2.10.
OBC Div. B 9.31.4.1A. Laundry Fixtures
Open OBC Div. B 9.31.4.1A. in the code viewer(1)Laundry facilities or a space for laundry facilities shall be provided in every dwelling unit or grouped elsewhere in the building in a location conveniently accessible to occupants of every dwelling unit.
OBC Div. B 9.31.4.3. Floor Drains
Open OBC Div. B 9.31.4.3. in the code viewer(1)Where gravity drainage to a sewer, drainage ditch or dry well is possible, a floor drain shall be installed in a basement forming part of a dwelling unit.
Show all 47 articles
OBC Div. B 9.31.2.3. Grab Bars
Open OBC Div. B 9.31.2.3. in the code viewer(1)When provided, grab bars shall be capable of resisting a load of not less than 1.3 kN applied vertically or horizontally.
OBC Div. B 9.31.6.1A. Hot Water Temperature
Open OBC Div. B 9.31.6.1A. in the code viewer(1)Where a hot water supply is required by Article 9.31.4.3., equipment shall be installed to provide to every dwelling unit an adequate supply of service hot water with a temperature range from 45°C to 60°C.
(2)An electric storage-type service water heater shall have a minimum set storage temperature of 60°C.
OBC Div. B 9.31.6.2. Equipment and Installation
Open OBC Div. B 9.31.6.2. in the code viewer(1)Every service water heater and its installation shall conform to Part 7.
(2)Reserved
(3)Where the building is in a location where the spectral response acceleration, S_a(0.2) , is greater than 0.55, service water heaters shall be secured to the structure to resist overturning. (See Note A-9.31.6.2.(3))
OBC Div. B 9.31.6.4. Fuel-Burning Heaters
Open OBC Div. B 9.31.6.4. in the code viewer(1)Fuel-burning service water heaters shall be connected to a chimney flue conforming to Section 9.21.
OBC Div. B 9.31.6.3. Corrosion-Resistant Coating
Open OBC Div. B 9.31.6.3. in the code viewer(1)Where storage tanks for service water heaters are of steel, they shall be coated with zinc, vitreous enamel (glass lined), hydraulic cement or other corrosion-resistant material.
OBC Div. A 1.4.1.2.(1) Service water heater
Open OBC Div. A 1.4.1.2.(1) in the code viewerService water heater means a device for heating water for plumbing services.
OBC Div. B 9.33.6.14A. Exhaust Ducts and Outlets
Open OBC Div. B 9.33.6.14A. in the code viewer(1)Where an exhaust duct passes through or is adjacent to unheated space, the duct shall be insulated to prevent moisture or condensation in the duct.
(2)Exhaust outlets shall be designed to prevent back draft under wind conditions.
(3)Exhaust ducts directly connected to laundry drying equipment shall be independent of other exhaust ducts.
(4)Exhaust systems shall discharge directly to the outdoors.
OBC Div. B 9.34.1.2. Required Facilities
Open OBC Div. B 9.34.1.2. in the code viewer(1)Where electrical services are available, electrical facilities shall be provided for every building in conformance with this Section.
OBC Div. B 9.34.1.4. Recessed Lighting Fixtures
Open OBC Div. B 9.34.1.4. in the code viewer(1)Recessed lighting fixtures shall not be located in insulated ceilings unless the fixtures are designed for such installations.
OBC Div. B 9.34.2.1. Lighting of Entrances
Open OBC Div. B 9.34.2.1. in the code viewer(1)An exterior lighting outlet with fixture controlled by a wall switch located within the building shall be provided at every entrance to buildings of residential occupancy.
(2)The exterior lighting outlet with fixture required by Sentence (1) may be controlled by a wall switch or panel accessible to authorized personnel only, where it serves,
(a)a building entrance serving multiple suites of residential occupancy,
(b)multiple dwelling unit entrances,
(c)hotels, or
(d)motels.
OBC Div. B 9.34.2.2. Outlets in Dwelling Units
Open OBC Div. B 9.34.2.2. in the code viewer(1)Except as provided in Sentence (2), a lighting outlet with fixture controlled by a wall switch shall be provided in kitchens, bedrooms, living rooms, utility rooms, laundry rooms, dining rooms, bathrooms, water-closet rooms, vestibules and hallways in dwelling units.
(2)Where a receptacle controlled by a wall switch is provided in bedrooms or living rooms, such rooms need not conform to the requirements of Sentence (1).
OBC Div. B 9.34.2.3. Stairways
Open OBC Div. B 9.34.2.3. in the code viewer(1)Every stairway shall be lighted.
(2)Except as provided in Sentence (3), 3-way wall switches located at the head and foot of every stairway shall be provided to control at least one lighting outlet with fixture for stairways with 4 or more risers in dwelling units and houses with a secondary suite including their common spaces.
(3)The stairway lighting for basements that do not contain finished space or lead to an outside entrance or built-in garage and which serve not more than one dwelling unit is permitted to be controlled by a single switch located at the head of the stairs.
OBC Div. B 9.34.2.4. Basements
Open OBC Div. B 9.34.2.4. in the code viewer(1)A lighting outlet with fixture shall be provided for each 30 m² or fraction thereof of floor area in unfinished basements.
(2)The outlet required in Sentence (1) nearest the stairs shall be controlled by a wall switch located at the head of the stairs.
OBC Div. B 9.34.2.5. Storage Rooms
Open OBC Div. B 9.34.2.5. in the code viewer(1)A lighting outlet with fixture shall be provided in storage rooms.
OBC Div. B 9.34.2.6. Garages and Carports
Open OBC Div. B 9.34.2.6. in the code viewer(1)A lighting outlet with fixture shall be provided for an attached, built-in or detached garage or carport.
(2)Except as provided in Sentence (3), outlets required in Sentence (1) shall be controlled by a wall switch near the doorway.
(3)Where the outlet and fixture required in Sentence (1) are ceiling mounted above an area not normally occupied by a parked car, or are wall mounted, a fixture with a built-in switch is permitted to be used.
(4)Where a carport is lighted by a light at the entrance to a dwelling unit, additional carport lighting is not required.
OBC Div. B 9.35.1.1. Application
Open OBC Div. B 9.35.1.1. in the code viewer(1)This Section applies to garages and carports serving not more than one dwelling unit.
OBC Div. A 1.4.1.2.(1) Storage garage
Open OBC Div. A 1.4.1.2.(1) in the code viewerStorage garage means a building or part thereof intended for the storage or parking of motor vehicles and containing no provision for the repair or servicing of such vehicles. (See Note A-1.4.1.2.(1))
OBC Div. B 9.35.2.1. Carport Considered to be Garage
Open OBC Div. B 9.35.2.1. in the code viewer(1)Where a roofed enclosure used for the storage or parking of motor vehicles has more than 60 percent of the total perimeter enclosed by walls, doors or windows, the enclosure shall be considered a garage.
OBC Div. B 9.35.2.2. Garage Floor
Open OBC Div. B 9.35.2.2. in the code viewer(1)Where an attached or built-in garage is provided, the garage floor shall be sloped to drain liquids to the outdoors.
OBC Div. B 9.35.3.1. Foundation Required
Open OBC Div. B 9.35.3.1. in the code viewer(1)Except as permitted in this Subsection, foundations conforming to Sections 9.12. and 9.15. shall be provided for the support of carport and garage super-structures, including that portion beneath garage doors.
(2)Detached garages of less than 55 m² floor area and not more than 1 storey in height that are not of masonry or masonry veneer construction are permitted to be supported on
(a)wood mud sills, or
(b)a concrete floor slab having a minimum thickness of not less than 100 mm.
OBC Div. B 9.35.3.3. Drainage
Open OBC Div. B 9.35.3.3. in the code viewer(1)Detached garages of less than 55 m² floor area and not more than 1 storey in height that are not of masonry or masonry veneer construction need not conform with the foundation drainage requirements stated in Section 9.14. where the finished ground level is at or near the elevation of the garage's floor and where the ground slopes away from the building.
OBC Div. B 9.35.3.2. Protection from Damage Due to Soil Movement
Open OBC Div. B 9.35.3.2. in the code viewer(1)In clay-type soils subject to significant movement with a change in soil moisture content, the foundation depth of carports or garages connected to a dwelling unit directly or by a breezeway shall be approximately the same depth as the foundation of the main building.
(2)Where slab-on-ground construction is used, a construction joint shall be provided between the main building slab and a slab serving an attached garage, breezeway or carport.
(3)Except as provided in Section 9.12., foundations for attached unheated garages or carports shall be below frost level.
OBC Div. B 9.35.3.4. Column Piers
Open OBC Div. B 9.35.3.4. in the code viewer(1)Piers for the support of carport columns shall extend not less than 150 mm above ground level.
(2)Piers referred to in Sentence (1) shall project not less than 25 mm beyond the base of the column but in no case be less than 190 mm by 190 mm in size.
OBC Div. B 9.35.4.2. Columns
Open OBC Div. B 9.35.4.2. in the code viewer(1)Columns for garages and carports shall conform to Section 9.17., except that 89 mm by 89 mm wood columns may be used.
OBC Div. B 9.35.4.1. Interior Finish
Open OBC Div. B 9.35.4.1. in the code viewer(1)Interior finish need not be applied to garage and carport walls.
OBC Div. B 9.37.1.1. Application
Open OBC Div. B 9.37.1.1. in the code viewer(1)This Section applies to buildings of residential occupancy used or intended to be used as seasonal recreational buildings.
(2)The buildings described in Sentence (1) shall comply with all the requirements of this Part, except where they are specifically exempted in this Section.
OBC Div. B 9.37.2.1. Exclusions
Open OBC Div. B 9.37.2.1. in the code viewer(1)Except as provided in Subsection 9.10.15. and Articles 9.37.2.4. and 9.37.3.1., buildings used or intended to be used as seasonal recreational buildings need not comply with Sections 9.5. to 9.7. and 9.9. to 9.11.
(2)Flooring need not comply with Section 9.30., but tight-fitting floors shall be provided to support the live and dead loads.
(3)Except as provided in Sentence (4), thermal insulation, vapour barrier, air barrier construction, interior finishes, plumbing, heating, mechanical ventilation, air-conditioning and electrical facilities, need not be provided, but where any of these are provided, they shall comply with the requirements of this Part.
(4)Where heating and air-conditioning are provided, Article 9.33.3.1. need not be complied with.
OBC Div. B 9.37.2.2. Foundations
Open OBC Div. B 9.37.2.2. in the code viewer(1)Continuous perimeter foundation walls are not required, but when they are provided, they shall comply with the requirements of this Part.
(2)Where unit masonry columns are used, the height of such columns shall not exceed,
(a)in the case of hollow masonry units, 4 times the least dimension of the units,
(b)in the case of solid masonry units or hollow units with voids filled with concrete, 10 times the least dimension of the column, or
(c)where the column is reinforced with at least four 13 mm diam bars and filled with concrete, 18 times the least dimension of the column.
(3)Columns in excess of the height limitations of Clauses (2)(a) to (c) shall be designed in accordance with Part 4.
OBC Div. B 9.37.2.4. Smoke Alarms
Open OBC Div. B 9.37.2.4. in the code viewer(1)Every dwelling unit within the scope of this Section shall be provided with a smoke alarm in accordance with Subsection 9.10.19.
OBC Div. B 9.37.3.1. Buildings for Seasonal Tourist Accommodation or for Rent
Open OBC Div. B 9.37.3.1. in the code viewer(1)Where buildings are used or intended to be used for seasonal tourist accommodation or for rent, they shall comply with Sections 9.5. to 9.8. in addition to the requirements of this Section.
OBC Div. B 9.38.1.2. Requirement for Wood Preservative
Open OBC Div. B 9.38.1.2. in the code viewer(1)The portion of any log coming in contact with masonry or concrete at or below grade shall be treated with a wood preservative to prevent decay.
OBC Div. B 9.38.2.3. Joining Logs
Open OBC Div. B 9.38.2.3. in the code viewer(1)Each log in a horizontal position shall be scribed as close as possible to its bearer and fastened to the bearer in at least three places throughout its length, by dowels, continuous machined joints, vertical framing members or interlocking intersections or any combination of these, but in no case shall the distance between fastenings exceed 1,800 mm.
OBC Div. B 9.38.3.2. Clearance
Open OBC Div. B 9.38.3.2. in the code viewer(1)At every opening in a wall made of logs in a horizontal position where shrinkage can occur there shall be a clearance between the rough buck header and the lintel log of not less than 13 mm in width for each 300 mm of height to allow for settlement.
OBC Div. B 9.39.2.1. General
Open OBC Div. B 9.39.2.1. in the code viewer(1)Except as provided in Subsection 9.39.3., a manufactured building used or intended to be used as a seasonal recreational building of residential occupancy is deemed to comply with this Code if it is designed and constructed in conformance with CAN/CSA-Z241 Series, "Park model trailers."
OBC Div. B 9.40.1.1. Application
Open OBC Div. B 9.40.1.1. in the code viewer(1)This Section applies to
(a)reinforced concrete slabs that are suspended over cold rooms in basements, and are supported by foundation walls along the perimeter of the slab with no additional interior supports, and
(b)slabs in which the clear span between supporting walls is not more than 2.5 m along the shortest dimension of the slab.
(2)Slabs for conditions other than described in Sentence (1) shall be designed in accordance with Part 4.
(3)This Section does not apply to reinforced concrete slabs intended to support motor vehicles.
OBC Div. B 9.40.1.4. Slab Construction
Open OBC Div. B 9.40.1.4. in the code viewer(1)Concrete shall be cast against formwork in accordance with CSA A23.1, "Concrete materials and methods of concrete construction."
(2)The slab shall be not less than 125 mm thick.
(3)The slab shall be reinforced with 10 M bars spaced not more than 200 mm o.c. in each direction, with 30 mm clear cover from the bottom of the slab to the first layer of bars, and the second layer of bars laid directly on top of the lower layer in the opposite direction.
(4)The slab shall bear not less than 75 mm on the supporting foundation walls and be anchored to the walls with 600mm × 600mm 10 M bent dowels spaced at not more than 600 mm o.c.
(5)Exposed slabs shall be sloped to effectively shed water away from the exterior wall.
OBC Div. B 9.41.1.1. Application
Open OBC Div. B 9.41.1.1. in the code viewer(1)This Section applies where proposed construction in respect of an existing building will result in any of the following changes of use of all or part of the building:
(a)a change of the major occupancy of all or part of a building that is designated with a "Y" in Table 1.3.1.4. of Division C,
(b)a suite of a Group C major occupancy is converted into more than one suite of a Group C major occupancy,
(c)a farm building or part of a farm building is changed to another major occupancy other than a Group G major occupancy,
(d)a building or part of a building is changed to a post-disaster building,
(e)the use of a building or part of a building is changed and the previous major occupancy of the building or part of the building cannot be determined, or
(f)a farm building or part of a farm building is changed to a Group G, Division 1 major occupancy.
(2)For the purposes of this Section and Sentences 11.4.2.1.(1) and 11.4.2.5.(4), the changes of use set out in Clauses (1)(b) to (f) are also deemed to constitute a change in major occupancy.
(3)The requirements of this Section are in addition to the requirements of other Parts of the Code as they apply to the proposed construction.
OBC Div. B 9.41.2.1. Change of Use and Compensating Construction
Open OBC Div. B 9.41.2.1. in the code viewer(1)Where proposed construction will result in a change of use described in Clauses 9.40.1.1.(1)(a) to (f), additional construction shall be required in order that the building or part of a building subject to the change of use conforms to the requirements of Subsections 9.5.1. and 9.5.3. to 9.5.10., Section 9.6., Article 9.7.2.3. Sentences 9.7.5.1.(2) and 9.7.6.2.(1) and (3), Articles 9.8.8.1. and 9.9.10.1., Subsection 9.10.17. and Sections 9.31., 9.32. and 9.34. as they apply to the new major occupancy that the building or part of a building is to support.
(2)For the purposes of this Article, existing buildings shall be classified as to their construction and occupancy as provided for in Sentence 11.2.1.1.(1).
OBC Div. B 9.41.2.2. Performance Level Evaluation and Compensating Construction
Open OBC Div. B 9.41.2.2. in the code viewer(1)The performance level of a building after construction shall not be less than the performance level of the building prior to construction.
(2)For the purposes of Sentence (1), reduction of performance level shall be determined in accordance with Articles 11.4.2.1., 11.4.2.3. and 11.4.2.5.
(3)Where the proposed construction would reduce the performance level of an existing building, compensating construction shall be required in conformance with Articles 11.4.3.1., 11.4.3.2., 11.4.3.4. and 11.4.3.6.
(4)Section 11.5. applies in respect of the requirements of Sentences 11.4.3.4.(1), (3) and (4).