Values this chapter turns on
- min open area, bedroom egress window
- 0.35 m²
- min open area, bedroom egress window
- min dimension, bedroom egress window
- 380 mm
- min dimension, bedroom egress window
- max sill height above floor (not basements)
- 1,000 mm
- max sill height above floor (not basements)
- window well clearance in front of window
- 550 mm
- window well clearance in front of window
Section 9.9 sets the rules for getting people out of a building. For a house exam, the key skill is knowing which Articles switch off for a single dwelling unit or a house with a secondary suite, and which still apply. The bedroom window rule in 9.9.10. applies to every house and is tested often.
A means of egress is a continuous path of travel from any point in a building to a safe place outside, and it includes both exits and access to exits (Div. A 1.4.1.2.OBC Div. A 1.4.1.2.(1) Means of egressMeans of egress means a continuous path of travel provided for the escape of persons from any point in a building or contained open space to a separate building, an open public thoroughfare, or an exterior open space protected from fire exposure from the building and having access to an open public thoroughfare. means…). An exit leads from the floor area to a separate building, a public thoroughfare or a protected open space (Div. AOBC Div. A 1.4.1.2.(1) ExitExit means that part of a means of egress, including doorways, that leads from the floor areait serves to a separate building, an open public thoroughfare, or an exterior open space protected from fire exposure from the building and having access to an open public thoroughfare. (See Note A-1.4.1.2.(1))). Access to exit is the part within the floor area that leads to an exit (Div. AOBC Div. A 1.4.1.2.(1) Access to exitAccess to exit means that part of a means of egress within a floor area that provides access to an exit serving the floor area.).
Stairs, handrails and guards in a means of egress must meet Section 9.8 as well as 9.9 OBC Div. B 9.9.1.1.OBC Div. B 9.9.1.1. Application(1) Stairways, handrails and guards in a means of egress shall conform to the requirements in Section 9.8. as well as to the requirements in this Section.. Occupant load is two persons per sleeping room in a dwelling unit OBC Div. B 9.9.1.3.OBC Div. B 9.9.1.3. Occupant Load(1) The occupant load of a floor area or part of a floor area shall be based on (a) two persons per sleeping room or sleeping area in a dwelling unit or suite, and (b) for occupancies other than as described in Clause (a), the number of persons (i) for which the area is designed, or (ii) determined from Table 3.1.17.1..
Types of exits and dimensions
An exit can be an exterior doorway, passageway, ramp or stairway, a fire escape, a horizontal exit, or an interior passageway, ramp or stairway OBC Div. B 9.9.2.1.OBC Div. B 9.9.2.1. Types of Exits(1) Except as otherwise provided in this Section, an exit from any floor area shall be one of the following used singly or in combination: (a) an exterior doorway, (b) an exterior passageway, (c) an exterior ramp, (d) an exterior stairway, (e) a fire escape, (f) a horizontal exit, (g) an interior passageway, (h) an…. Fire escapes may be used only on existing buildings and may not be installed on any new building. Elevators, slide escapes and windows do not count as part of a required means of egress OBC Div. B 9.9.2.3.OBC Div. B 9.9.2.3. Elevators, Slide Escapes and Windows as Means of Egress(1) Elevators, slide escapes or windows shall not be considered as part of a required means of egress. (2) Except for floor areas of mercantile occupancy, casement windows not less than 1,060 mm high, 560 mm wide, with a sill height not more than 900 mm above the inside floor, are permitted to be considered part of a…. The bedroom window in 9.9.10. is a separate safety rule, not a required exit.
The width and height rules in Subsection 9.9.3. do not apply to exits serving only one dwelling unit, or to access to exits within dwelling units OBC Div. B 9.9.3.1.OBC Div. B 9.9.3.1. Application(1) This Subsection applies to every means of egress except (a) exits that serve not more than one dwelling unit or a house with a secondary suite including their common spaces, and (b) access to exits within dwelling units and within houses with a secondary suite including their common spaces.. Where they apply:
| Item | Minimum |
|---|---|
| Exit width (other than doors and corridors) | 900 mm 9.9.3.2.OBC Div. B 9.9.3.2. Exit Width(1) Except for doors and corridors, the width of every exit facility shall be not less than 900 mm. (See Article 9.9.6.3. for doors, Article 9.8.2.1. for stairs, and Article 9.8.5.2. for ramps.) |
| Public and exit corridor width | 1,100 mm 9.9.3.3.OBC Div. B 9.9.3.3. Width of Corridors(1) The width of every public corridor, corridor used by the public, and exit corridor shall be not less than 1,100 mm. (See also Subsection 9.9.5. for obstructions in corridors.) |
| Clear height in exits and access to exits | 2.1 m 9.9.3.4.OBC Div. B 9.9.3.4. Clear Height(1) Except for stairways, doorways and storage garages, the minimum clear height in exits and access to exits shall be 2.1 m. (See Article 9.8.2.2. for stairs, Article 9.8.5.3. for ramps, Article 9.8.6.4. for landings and Article 9.9.6.2. for doorways.) (2) The clear height in exits and access to exits in a storage… |
Fire protection of exits and obstructions
Subsection 9.9.4. does not apply to exits serving only one dwelling unit OBC Div. B 9.9.4.1.OBC Div. B 9.9.4.1. Application(1) Except as provided in Articles 9.9.4.4. and 9.9.4.6., this Subsection applies to the fire protection of all exits except exits serving not more than one dwelling unit.. It keeps two Articles in force, though, and one matters for houses with a secondary suite. Suppose an unenclosed exterior exit stair is the only way out of a suite and is exposed to openings in another dwelling unit or common space. Then openings within 3 m horizontally, and less than 10 m below or 5 m above the stair, must be wired glass in fixed steel frames or glass block OBC Div. B 9.9.4.4.OBC Div. B 9.9.4.4. Openings Near Unenclosed Exterior Exit Stairs and Ramps(1) Where an unenclosed exterior exit stair or ramp provides the only means of egress from a suite, and is exposed to fire from openings in the exterior walls of another fire compartment, or another dwelling unit, ancillary space or common space in a house with a secondary suite, the openings in the exterior walls of….
Where exits do need fire separations, the rating is at least that of the floor above, and never less than 45 min where there is no floor above OBC Div. B 9.9.4.2.OBC Div. B 9.9.4.2. Fire Separation for Exits(1) Except as provided in Sentence (5) and Article 9.9.8.5., every exit other than an exit doorway shall be separated from each adjacent floor area or from another exit by a fire separation having a fire-resistance rating not less than that required for the floor assembly above the floor area. (2) Where there is no….
Obstructions: fuel-fired appliances may not be installed in an exit or in a corridor that serves as access to exits OBC Div. B 9.9.5.7.OBC Div. B 9.9.5.7. Fuel-Fired Appliances(1) Fuel-fired appliances shall not be installed in an exit or corridor serving as an access to exits.. Service rooms with equipment that could explode, such as boilers over 100 kPa, may not sit under required exits OBC Div. B 9.9.5.8.OBC Div. B 9.9.5.8. Service Rooms(1) Service rooms containing equipment subject to possible explosion, such as boilers designed to operate at a pressure in excess of 100 kPa, and certain types of refrigerating and transformer equipment, shall not be located under required exits.. Storage rooms, washrooms and laundry rooms may not open directly into an exit, except in houses with a secondary suite OBC Div. B 9.9.5.9.OBC Div. B 9.9.5.9. Ancillary Rooms(1) Except in houses with a secondary suite, ancillary rooms such as storage rooms, washrooms, toilet rooms, laundry rooms and service rooms shall not open directly into an exit..
Doors in a means of egress
Many door rules exempt doors serving a single dwelling unit or a house with a secondary suite: swing obstruction (9.9.6.1.), clear height (9.9.6.2.), clear width (9.9.6.3.) and opening force (9.9.6.8.). For house doorway sizes, use 9.5.5. instead. The rules that still reach houses:
- Exterior doors of dwelling units must open from the inside without keys, special devices or special knowledge OBC Div. B 9.9.6.7.OBC Div. B 9.9.6.7. Door Latching, Locking and Opening Mechanisms(1) Principal entrance doors, exit doors and doors to suites, including exterior doors of dwelling units, and other doors in an access to exit shall (a) be openable from the inside or in travelling to an exit without requiring keys, special devices or specialized knowledge of the door-opening mechanism, or (b) be….
- Door release hardware sits 900 mm to 1,100 mm above the finished floor OBC Div. B 9.9.6.7.OBC Div. B 9.9.6.7. Door Latching, Locking and Opening Mechanisms(1) Principal entrance doors, exit doors and doors to suites, including exterior doors of dwelling units, and other doors in an access to exit shall (a) be openable from the inside or in travelling to an exit without requiring keys, special devices or specialized knowledge of the door-opening mechanism, or (b) be….
- Where ice or snow could block a door, an exit door, including one serving a single dwelling unit, may open onto one step whose riser is not more than 150 mm OBC Div. B 9.9.6.6.OBC Div. B 9.9.6.6. Nearness of Doors to Stairs(1) Except as provided in Sentence (2), the distance between a stair riser and the leading edge of a door during its swing, except for doors serving a single dwelling unit or a house with a secondary suite, shall be not less than 300 mm. (2) Where there is a danger of blockage from ice or snow, an exit door, including….
For other buildings, a door's leading edge must stay at least 300 mm from a stair riser during its swing. Single exit doors need a clear opening of at least 800 mm, and exit doors normally swing in the direction of travel.
Access to exits and exits from floor areas
Required access to exit from a suite may not pass through another dwelling unit, a service room or another occupancy OBC Div. B 9.9.7.5.OBC Div. B 9.9.7.5. Independent Access to Exit(1) Required access to exit from suites shall not be through any other dwelling unit, service room or other occupancy.. Outside dwelling units, a room or suite needs two egress doors when it exceeds 150 m² in residential occupancy (200 m² for Groups D, E, F2, F3), or when any point is more than 25 m from an egress door OBC Div. B 9.9.7.4.OBC Div. B 9.9.7.4. Number and Spacing of Egress Doors(1) Except for dwelling units, at least two egress doors shall be provided where (a) the area of a room or suite exceeds 200 m² in a Group D, E, F2 and F3 occupancy, or 150 m² in a Group C occupancy, or (b) the distance measured from any point within a room or suite to the nearest egress door exceeds 25 m. (2) Doors….
Floor areas normally need 2 exits OBC Div. B 9.9.8.2.OBC Div. B 9.9.8.2. Number of Required Exits(1) Except as provided in Sentences (2) and (3) and Subsection 9.9.9., at least 2 exits shall be provided from every floor area, spaced so that the travel distance to the nearest exit is not more than (a) 40 m in the case of business and personal services occupancies, (b) 45 m for all occupancies where the floor area…, with these travel distance limits:
| Floor area | Max. travel distance to nearest exit |
|---|---|
| Business and personal services | 40 m |
| Sprinklered, any occupancy | 45 m |
| All others | 30 m |
A single exit is allowed from each storey of a 1 or 2 storey building if the room or suite limits in 9.9.7.4. are met and the exit serves not more than 60 persons. Where 2 exits are required, each counts for at most half the required exit width OBC Div. B 9.9.8.3.OBC Div. B 9.9.8.3. Contribution of Each Exit(1) Where more than one exit is required from a floor area, each exit shall be considered as contributing not more than half the required exit width.. The 2 exits must be independent and remote from each other OBC Div. B 9.9.8.4.OBC Div. B 9.9.8.4. Location of Exits(1) Where more than one exit is required from a floor area, at least 2 exits shall be independent of each other and be placed remote from each other along the path of travel between them. (See Note A-9.9.8.4.(1)).
Egress from dwelling units and bedrooms
A multi-storey dwelling unit must have exits so that no one travels more than 1 storey up or down to reach an egress door or an exit doorway. That doorway can be at most 1.5 m above ground OBC Div. B 9.9.9.1.OBC Div. B 9.9.9.1. Travel Limit to Exits or Egress Doors(1) Except as provided in Sentences (2) and (3), every dwelling unit containing more than 1 storey shall have exits or egress doors located so that it shall not be necessary to travel up or down more than 1 storey to reach a level served by (a) an egress door to a public corridor, enclosed exit stair or exterior…. In a unit with no suite above or below, a floor may exceed this if it has an openable window or door at least 1 m high and 0.55 m wide. The sill must be not more than 1 m above the floor and 7 m above the ground.
Shared egress triggers a second means of egress OBC Div. B 9.9.9.3.OBC Div. B 9.9.9.3. Shared Egress Facilities(1) Except for dwelling units in a house with a secondary suite, a dwelling unit shall be provided with a second and separate means of egress where an egress door from the dwelling unit opens onto (a) an exit stairway serving more than one suite, (b) a public corridor (i) serving more than one suite, and (ii) served…, but dwelling units in a house with a secondary suite are mostly exempt. One case still applies: the upper unit needs a second means of egress when its door opens onto an exterior passageway that has a floor rating under 45 min, is served by a single stair, and is more than 1.5 m above ground.
Bedroom windows OBC Div. B 9.9.10.1.OBC Div. B 9.9.10.1. Egress Windows or Doors for Bedrooms(1) Except where a door on the same floor level as the bedroom provides direct access to the exterior, every floor level containing a bedroom in a suite shall be provided with at least one outside window that (a) is openable from the inside without the use of tools, (b) provides an individual, unobstructed open…. Unless a door on the same level opens directly outside, each floor level with a bedroom needs at least one outside window that:
| Requirement | Value |
|---|---|
| Opens from inside | without tools |
| Unobstructed open area | at least 0.35 m² |
| Smallest dimension | at least 380 mm |
| Sill height (not basements) | not more than 1,000 mm above floor |
| Window well clearance in front | at least 550 mm |
The window must stay open without extra support. For sliding windows, the dimensions apply to the openable part. A window well cover must open from inside without keys, tools or special knowledge.
Signs and lighting
Subsection 9.9.11. does not apply to exits serving only one dwelling unit or a house with a secondary suite OBC Div. B 9.9.11.1.OBC Div. B 9.9.11.1. Application(1) This Subsection applies to all exits except those serving not more than one dwelling unit or a house with a secondary suite.. Where it applies, exits must be clearly visible or their locations clearly shown OBC Div. B 9.9.11.2.OBC Div. B 9.9.11.2. Visibility of Exits(1) Exits shall be located so as to be clearly visible or their locations shall be clearly indicated. (2) Where an exit door leading directly to the outside is subject to being obstructed by a parked vehicle or storage because of its location, a visible sign prohibiting such obstructions shall be permanently mounted…. Floor numbers at exit stair doors are at least 60 mm high and mounted 1,500 mm above the floor OBC Div. B 9.9.11.5.OBC Div. B 9.9.11.5. Floor Numbering(1) Arabic numerals indicating the assigned floor number shall be (a) except in hotels, mounted permanently on the stair side of the wall at the latch side of doors to exit stair shafts, (b) in hotels, mounted permanently on each side of the exit doors to the exit stair shaft, (c) not less than 60 mm high, raised….
Lighting rules in 9.9.12. do not apply within dwelling units or a house with a secondary suite OBC Div. B 9.9.12.1.OBC Div. B 9.9.12.1. Application(1) This Subsection applies to the lighting of all means of egress except those within dwelling units or a house with a secondary suite.. Elsewhere:
| Lighting | Average | Minimum point |
|---|---|---|
| Normal, exits and public corridors | 50 lx 9.9.12.2.OBC Div. B 9.9.12.2. Required Lighting in Egress Facilities(1) Every exit, public corridor or corridor providing access to exit for the public shall be equipped to provide illumination to an average level of not less than 50 lx at floor or tread level and at all points such as angles and intersections at changes of level where there are stairs or ramps. (2) The minimum value… | 10 lx |
| Emergency | 10 lx 9.9.12.3.OBC Div. B 9.9.12.3. Emergency Lighting(1) Emergency lighting shall be provided in (a) exits. (b) principal routes providing access to exit in an open floor area, (c) corridors used by the public, (d) underground walkways, and (e) public corridors. (2) Emergency lighting required in Sentence (1) shall be provided from a source of energy separate from the… | 1 lx |
Emergency lighting must come from a separate energy source and switch on automatically for at least 30 min.
Common traps
- Applying corridor or door widths from 9.9. to a house. Most of 9.9.3. and 9.9.6. exempt single dwelling units.
- Checking only the 380 mm dimension of a bedroom window and missing the 0.35 m² area.
- Forgetting the 1,000 mm sill limit does not apply in basements, but the 550 mm window well clearance does.
- Thinking 9.9.4. never applies to houses. 9.9.4.4. reaches houses with a secondary suite.
Chapter review
Chapter at a glance
One line per section: the idea to carry into the exam. Then the answers that most often catch candidates out.
- Types of exits and dimensions
An exit can be an exterior doorway, passageway, ramp or stairway, a fire escape, a horizontal exit, or an interior passageway, ramp or stairway.
- Fire protection of exits and obstructions
Subsection 9.9.4. does not apply to exits serving only one dwelling unit.
- Doors in a means of egress
Many door rules exempt doors serving a single dwelling unit or a house with a secondary suite: swing obstruction (9.9.6.1.), clear height (9.9.6.2.), clear width (9.9.6.3.) and…
- Access to exits and exits from floor areas
Required access to exit from a suite may not pass through another dwelling unit, a service room or another occupancy.
- Egress from dwelling units and bedrooms
A multi-storey dwelling unit must have exits so that no one travels more than 1 storey up or down to reach an egress door or an exit doorway.
- Signs and lighting
Subsection 9.9.11. does not apply to exits serving only one dwelling unit or a house with a secondary suite.
Usual exam traps
- Applying corridor or door widths from 9.9. to a house. Most of 9.9.3. and 9.9.6. exempt single dwelling units.
- Checking only the 380 mm dimension of a bedroom window and missing the 0.35 m² area.
- Forgetting the 1,000 mm sill limit does not apply in basements, but the 550 mm window well clearance does.
- Thinking 9.9.4. never applies to houses. 9.9.4.4. reaches houses with a secondary suite.
Practice this chapter
Questions on Means of egress, in the exam format, every answer explained and cited to its article. Sign in to start; a free account gets the free questions.
Code cited in this chapter
Based on the official 2024 Building Code Compendium on ontario.ca.
© King's Printer for Ontario, 2024. Reproduced with permission.
OBC Div. A 1.4.1.2.(1) Means of egress
Open OBC Div. A 1.4.1.2.(1) in the code viewerMeans of egress means a continuous path of travel provided for the escape of persons from any point in a building or contained open space to a separate building, an open public thoroughfare, or an exterior open space protected from fire exposure from the building and having access to an open public thoroughfare. means of egress includes exits and access to exits.
OBC Div. A 1.4.1.2.(1) Exit
Open OBC Div. A 1.4.1.2.(1) in the code viewerExit means that part of a means of egress, including doorways, that leads from the floor areait serves to a separate building, an open public thoroughfare, or an exterior open space protected from fire exposure from the building and having access to an open public thoroughfare. (See Note A-1.4.1.2.(1))
OBC Div. A 1.4.1.2.(1) Access to exit
Open OBC Div. A 1.4.1.2.(1) in the code viewerAccess to exit means that part of a means of egress within a floor area that provides access to an exit serving the floor area.
OBC Div. B 9.9.1.1. Application
Open OBC Div. B 9.9.1.1. in the code viewer(1)Stairways, handrails and guards in a means of egress shall conform to the requirements in Section 9.8. as well as to the requirements in this Section.
OBC Div. B 9.9.1.3. Occupant Load
Open OBC Div. B 9.9.1.3. in the code viewer(1)The occupant load of a floor area or part of a floor area shall be based on
(a)two persons per sleeping room or sleeping area in a dwelling unit or suite, and
(b)for occupancies other than as described in Clause (a), the number of persons
(i)for which the area is designed, or
(ii)determined from Table 3.1.17.1.
OBC Div. B 9.9.2.1. Types of Exits
Open OBC Div. B 9.9.2.1. in the code viewer(1)Except as otherwise provided in this Section, an exit from any floor area shall be one of the following used singly or in combination:
(a)an exterior doorway,
(b)an exterior passageway,
(c)an exterior ramp,
(d)an exterior stairway,
(e)a fire escape,
(f)a horizontal exit,
(g)an interior passageway,
(h)an interior ramp, or
(i)an interior stairway.
(2)Fire escapes shall only be used as exits on existing buildings and shall be designed and installed in conformance with Subsection 3.4.7.
(2.1)Fire escapes shall not be installed on any new building.
(3)Where a horizontal exit is used, it shall conform to Sentence 3.4.1.6.(1) and Article 3.4.6.10.
OBC Div. B 9.9.2.3. Elevators, Slide Escapes and Windows as Means of Egress
Open OBC Div. B 9.9.2.3. in the code viewer(1)Elevators, slide escapes or windows shall not be considered as part of a required means of egress.
(2)Except for floor areas of mercantile occupancy, casement windows not less than 1,060 mm high, 560 mm wide, with a sill height not more than 900 mm above the inside floor, are permitted to be considered part of a required means of egress to provide access to fire escapes, when fire escapes are permitted.
OBC Div. B 9.9.3.1. Application
Open OBC Div. B 9.9.3.1. in the code viewer(1)This Subsection applies to every means of egress except
(a)exits that serve not more than one dwelling unit or a house with a secondary suite including their common spaces, and
(b)access to exits within dwelling units and within houses with a secondary suite including their common spaces.
Show all 33 articles
OBC Div. B 9.9.3.2. Exit Width
Open OBC Div. B 9.9.3.2. in the code viewer(1)Except for doors and corridors, the width of every exit facility shall be not less than 900 mm. (See Article 9.9.6.3. for doors, Article 9.8.2.1. for stairs, and Article 9.8.5.2. for ramps.)
OBC Div. B 9.9.3.3. Width of Corridors
Open OBC Div. B 9.9.3.3. in the code viewer(1)The width of every public corridor, corridor used by the public, and exit corridor shall be not less than 1,100 mm. (See also Subsection 9.9.5. for obstructions in corridors.)
OBC Div. B 9.9.3.4. Clear Height
Open OBC Div. B 9.9.3.4. in the code viewer(1)Except for stairways, doorways and storage garages, the minimum clear height in exits and access to exits shall be 2.1 m. (See Article 9.8.2.2. for stairs, Article 9.8.5.3. for ramps, Article 9.8.6.4. for landings and Article 9.9.6.2. for doorways.)
(2)The clear height in exits and access to exits in a storage garage shall be not less than 2 m.
OBC Div. B 9.9.4.1. Application
Open OBC Div. B 9.9.4.1. in the code viewer(1)Except as provided in Articles 9.9.4.4. and 9.9.4.6., this Subsection applies to the fire protection of all exits except exits serving not more than one dwelling unit.
OBC Div. B 9.9.4.4. Openings Near Unenclosed Exterior Exit Stairs and Ramps
Open OBC Div. B 9.9.4.4. in the code viewer(1)Where an unenclosed exterior exit stair or ramp provides the only means of egress from a suite, and is exposed to fire from openings in the exterior walls of another fire compartment, or another dwelling unit, ancillary space or common space in a house with a secondary suite, the openings in the exterior walls of the building shall be protected with wired glass in fixed steel frames or glass block conforming to Articles 9.10.13.5. and 9.10.13.7. when the openings in the exterior walls of the building are within 3 m horizontally and less than 10 m below or less than 5 m above the exit stair or ramp.
OBC Div. B 9.9.4.2. Fire Separation for Exits
Open OBC Div. B 9.9.4.2. in the code viewer(1)Except as provided in Sentence (5) and Article 9.9.8.5., every exit other than an exit doorway shall be separated from each adjacent floor area or from another exit by a fire separation having a fire-resistance rating not less than that required for the floor assembly above the floor area.
(2)Where there is no floor assembly above, the fire-resistance rating required in Sentence (1) shall not be less than that required by Subsection 9.10.8. for the floor assembly below, but in no case shall the fire-resistance rating be less than 45 min.
(3)A fire separation common to 2 exits shall be smoke-tight and not be pierced by doorways, duct work, piping or any other opening that may affect the continuity of the separation.
(4)A fire separation that separates an exit from the remainder of the building shall have no openings except those for electrical wiring, noncombustible conduit and noncombustible piping that serve only the exit, and for standpipes, sprinkler piping, exit doorways and wired glass and glass block permitted in Article 9.9.4.3.
(5)The requirements in Sentence (1) do not apply to an exterior exit passageway provided the passageway has at least 50% of its exterior sides open to the outdoors and is served by an exit stair at each end of the passageway.
OBC Div. B 9.9.5.7. Fuel-Fired Appliances
Open OBC Div. B 9.9.5.7. in the code viewer(1)Fuel-fired appliances shall not be installed in an exit or corridor serving as an access to exits.
OBC Div. B 9.9.5.8. Service Rooms
Open OBC Div. B 9.9.5.8. in the code viewer(1)Service rooms containing equipment subject to possible explosion, such as boilers designed to operate at a pressure in excess of 100 kPa, and certain types of refrigerating and transformer equipment, shall not be located under required exits.
OBC Div. B 9.9.5.9. Ancillary Rooms
Open OBC Div. B 9.9.5.9. in the code viewer(1)Except in houses with a secondary suite, ancillary rooms such as storage rooms, washrooms, toilet rooms, laundry rooms and service rooms shall not open directly into an exit.
OBC Div. B 9.9.6.7. Door Latching, Locking and Opening Mechanisms
Open OBC Div. B 9.9.6.7. in the code viewer(1)Principal entrance doors, exit doors and doors to suites, including exterior doors of dwelling units, and other doors in an access to exit shall
(a)be openable from the inside or in travelling to an exit without requiring keys, special devices or specialized knowledge of the door-opening mechanism, or
(b)be controlled by electromagnetic locking mechanisms in accordance with Sentence 3.4.6.16.(5).
(2)Except for doors serving a single dwelling unit or a house with a secondary suite, and doors to accessory buildings and to garages serving a single dwelling unit, door release hardware on doors in a means of egress shall be operable with one hand and the door shall be openable with not more than one releasing operation. (See also Sentence 3.8.3.6.(4) and Note A-3.3.1.13.(4))
(3)Door release hardware on doors in a means of egress shall be installed 900 mm to 1,100 mm above the finished floor.
(4)Except for hotels, a door opening onto a public corridor that provides access to exit from suites shall be designed not to lock automatically when such doors are equipped with an automatic self-closing device. (See Note A-3.3.4.5.(1))
OBC Div. B 9.9.6.6. Nearness of Doors to Stairs
Open OBC Div. B 9.9.6.6. in the code viewer(1)Except as provided in Sentence (2), the distance between a stair riser and the leading edge of a door during its swing, except for doors serving a single dwelling unit or a house with a secondary suite, shall be not less than 300 mm.
(2)Where there is a danger of blockage from ice or snow, an exit door, including doors serving a single dwelling unit, may open onto not more than one step, provided the riser of such a step does not exceed 150 mm.
OBC Div. B 9.9.7.5. Independent Access to Exit
Open OBC Div. B 9.9.7.5. in the code viewer(1)Required access to exit from suites shall not be through any other dwelling unit, service room or other occupancy.
OBC Div. B 9.9.7.4. Number and Spacing of Egress Doors
Open OBC Div. B 9.9.7.4. in the code viewer(1)Except for dwelling units, at least two egress doors shall be provided where
(a)the area of a room or suite exceeds 200 m² in a Group D, E, F2 and F3 occupancy, or 150 m² in a Group C occupancy, or
(b)the distance measured from any point within a room or suite to the nearest egress door exceeds 25 m.
(2)Doors required in Sentence (1) shall be spaced so that in the event one door is made inaccessible by a fire within such a room or suite, the other door will provide safe egress.
OBC Div. B 9.9.8.2. Number of Required Exits
Open OBC Div. B 9.9.8.2. in the code viewer(1)Except as provided in Sentences (2) and (3) and Subsection 9.9.9., at least 2 exits shall be provided from every floor area, spaced so that the travel distance to the nearest exit is not more than
(a)40 m in the case of business and personal services occupancies,
(b)45 m for all occupancies where the floor area is sprinklered, and
(c)30 m for all other occupancies.
(2)Except as provided in Subsection 9.9.9., a single exit is permitted from each storey in buildings of 1 and 2 storeys in building height provided the floor area and travel distance requirements conform to those required in Article 9.9.7.4. and the total occupant load served by an exit facility does not exceed 60 persons.
(3)In boarding, lodging or rooming houses,
(a)where sleeping accommodation is provided for not more than eight persons, a single exit is permitted from each floor area, or
(b)where sleeping accommodation is not provided in the basement, a single exit is permitted from the basement floor area.
OBC Div. B 9.9.8.3. Contribution of Each Exit
Open OBC Div. B 9.9.8.3. in the code viewer(1)Where more than one exit is required from a floor area, each exit shall be considered as contributing not more than half the required exit width.
OBC Div. B 9.9.8.4. Location of Exits
Open OBC Div. B 9.9.8.4. in the code viewer(1)Where more than one exit is required from a floor area, at least 2 exits shall be independent of each other and be placed remote from each other along the path of travel between them. (See Note A-9.9.8.4.(1))
OBC Div. B 9.9.9.1. Travel Limit to Exits or Egress Doors
Open OBC Div. B 9.9.9.1. in the code viewer(1)Except as provided in Sentences (2) and (3), every dwelling unit containing more than 1 storey shall have exits or egress doors located so that it shall not be necessary to travel up or down more than 1 storey to reach a level served by
(a)an egress door to a public corridor, enclosed exit stair or exterior passageway, or
(b)an exit doorway not more than 1.5 m above adjacent ground level.
(2)Where a dwelling unit is not located above or below another suite, the travel limit from a floor level in the dwelling unit to an exit or egress door may exceed 1 storey where that floor level is served by an openable window or door
(a)providing an unobstructed opening of not less than 1 m in height and 0.55 m in width, and
(b)located so that the sill is not more than
(i)1 m above the floor, and
(ii)7 m above adjacent ground level.
(3)The travel limit from a floor level in a dwelling unit to an exit or egress door may exceed 1 storey where that floor level has direct access to a balcony.
OBC Div. B 9.9.9.3. Shared Egress Facilities
Open OBC Div. B 9.9.9.3. in the code viewer(1)Except for dwelling units in a house with a secondary suite, a dwelling unit shall be provided with a second and separate means of egress where an egress door from the dwelling unit opens onto
(a)an exit stairway serving more than one suite,
(b)a public corridor
(i)serving more than one suite, and
(ii)served by a single exit,
(c)an exterior passageway
(i)serving more than one suite,
(ii)served by a single exit stairway or ramp, and
(iii)more than 1.5 m above adjacent ground level, or
(d)a balcony
(i)serving more than one suite,
(ii)served by a single exit stairway or ramp, and
(iii)more than 1.5 m above adjacent ground level.
(2)Where a dwelling unit is located above another dwelling unit or common space in a house with a secondary suite, the upper dwelling unit shall be provided with as second and separate means of egress where an egress door from that dwelling unit opens onto an exterior passageway that
(a)has a floor assembly with a fire-resistance rating less than 45 min,
(b)is served by a single exit stairway or ramp, and
(c)is located more than 1.5 m above adjacent ground level.
OBC Div. B 9.9.10.1. Egress Windows or Doors for Bedrooms
Open OBC Div. B 9.9.10.1. in the code viewer(1)Except where a door on the same floor level as the bedroom provides direct access to the exterior, every floor level containing a bedroom in a suite shall be provided with at least one outside window that
(a)is openable from the inside without the use of tools,
(b)provides an individual, unobstructed open portion having a minimum area of 0.35 m² with no dimension less than 380 mm, and
(c)maintains the required opening described in Clause (b) without the need for additional support. (See Note A-9.9.10.1.(1))
(2)Except for basement areas, the window required in Sentence (1) shall have a maximum sill height of 1,000 mm above the floor. (See Note A-9.9.10.1.(2))
(3)Where a window required in Sentence (1) opens into a window well, a clearance of not less than 550 mm shall be provided in front of the window. (See Note A-9.9.10.1.(3))
(4)Where the sash of a window referred to in Sentence (3) swings towards the window well, the operation of the sash shall not reduce the clearance in a manner that would restrict escape in an emergency.
(5)Where a protective enclosure is installed over the window well referred to in Sentence (3), the enclosure shall be openable from the inside without the use of keys, tools or special knowledge of the opening mechanism.
(6)When sliding windows are used, the minimum dimension described in Sentence (1) shall apply to the openable portion of the window.
(7)Where the sleeping area within a live/work unit is on a mezzanine with no obstructions more than 1,070 mm above the floor, the window required in Sentence (1) may be provided on the main level of the live/work unit provided the mezzanine is not more than 25% of the area of the live/work unit or 20 m², whichever is less, and an unobstructed direct path of travel is provided from the mezzanine to this window.
OBC Div. B 9.9.11.1. Application
Open OBC Div. B 9.9.11.1. in the code viewer(1)This Subsection applies to all exits except those serving not more than one dwelling unit or a house with a secondary suite.
OBC Div. B 9.9.11.2. Visibility of Exits
Open OBC Div. B 9.9.11.2. in the code viewer(1)Exits shall be located so as to be clearly visible or their locations shall be clearly indicated.
(2)Where an exit door leading directly to the outside is subject to being obstructed by a parked vehicle or storage because of its location, a visible sign prohibiting such obstructions shall be permanently mounted on the exterior side of the door.
OBC Div. B 9.9.11.5. Floor Numbering
Open OBC Div. B 9.9.11.5. in the code viewer(1)Arabic numerals indicating the assigned floor number shall be
(a)except in hotels, mounted permanently on the stair side of the wall at the latch side of doors to exit stair shafts,
(b)in hotels, mounted permanently on each side of the exit doors to the exit stair shaft,
(c)not less than 60 mm high, raised approximately 0.8 mm above the surface,
(d)located 1,500 mm from the finished floor and not more than 300 mm from the door, and
(e)contrasting in colour with the surface on which they are applied. (See Note A-9.9.11.5.(1) (e))
OBC Div. B 9.9.12.1. Application
Open OBC Div. B 9.9.12.1. in the code viewer(1)This Subsection applies to the lighting of all means of egress except those within dwelling units or a house with a secondary suite.
OBC Div. B 9.9.12.2. Required Lighting in Egress Facilities
Open OBC Div. B 9.9.12.2. in the code viewer(1)Every exit, public corridor or corridor providing access to exit for the public shall be equipped to provide illumination to an average level of not less than 50 lx at floor or tread level and at all points such as angles and intersections at changes of level where there are stairs or ramps.
(2)The minimum value of the illumination required by Sentence (1) shall be not less than 10 lx.
OBC Div. B 9.9.12.3. Emergency Lighting
Open OBC Div. B 9.9.12.3. in the code viewer(1)Emergency lighting shall be provided in
(a)exits.
(b)principal routes providing access to exit in an open floor area,
(c)corridors used by the public,
(d)underground walkways, and
(e)public corridors.
(2)Emergency lighting required in Sentence (1) shall be provided from a source of energy separate from the electrical supply for the building.
(3)Lighting required in Sentence (1) shall be designed to be automatically actuated for a period of at least 30 min when the electric lighting in the affected area is interrupted.
(4)Illumination from lighting required in Sentence (1) shall be provided to average levels of not less than 10 lx at floor or tread level.
(5)The minimum value of the illumination required by Sentence (4) shall be not less than 1 1x.
(6)Where incandescent lighting is provided, lighting equal to 1 W/m² of floor area shall be considered to meet the requirement in Sentence (4).
(7)Where self-contained emergency lighting units are used, they shall conform to CSA C22.2 No. 141, "Emergency lighting equipment."