Part 9 general, structure, rooms, glass and windows

Part 9 application, materials, structural requirements, room and space design, barrier-free requirements in Part 9, glass, and windows, doors and skylights.

chapters in this guide
9 of 15
chapters in this guide
to read
6 min
to read
code articles cited
36
code articles cited

Last updated

Values this chapter turns on

concrete for garage floors and exterior flatwork
32 MPa
concrete for garage floors and exterior flatwork
maximum building area for Part 9
600 m²
maximum building area for Part 9
minimum specified snow load for Part 9
1 kPa
minimum specified snow load for Part 9
max lumber moisture content at installation
19%
max lumber moisture content at installation

This chapter covers the front end of Part 9: which buildings Part 9 applies to, the basic material and structural rules (Sections 9.3 and 9.4), room sizes and doorways (Section 9.5), glass (Section 9.6) and windows, doors and skylights (Section 9.7). On the Small Buildings exam these sections are tested with offices, stores, small apartment buildings and light industrial buildings in mind, not just houses. Expect questions that ask "does this rule apply to this building at all?" as often as "what is the number?".

Application of Part 9

Part 9 does not set its own scope. OBC Div. B 9.1.1.1.OBC Div. B 9.1.1.1. Application(1) The application of this Part shall be as described in Subsection 1.3.3. of Division A. sends you to Division A, Subsection 1.3.3. The key article is OBC Div. A 1.3.3.3.OBC Div. A 1.3.3.3. Application of Part 9(1) Subject to Article 1.3.3.3B., Part 9 of Division B applies to all buildings described in Article 1.1.1.1. of 3 storeys or less in building height, having a building area not exceeding 600 m², and used for major occupancies classified as (a) reserved (b) Group C, residential occupancies other than buildings used…: Part 9 applies to buildings of 3 storeys or less in building height, with a building area not exceeding 600 m², used for Group C (other than retirement homes), Group D, Group E, or Group F Division 2 and 3 major occupancies. Assembly, care, treatment, detention and high-hazard industrial buildings go to Part 3 regardless of size (OBC Div. A 1.3.3.2.OBC Div. A 1.3.3.2. Application of Parts 3, 4, 5 and 6(1) Subject to Articles 1.3.3.1A., 1.3.3.3B., Parts 3, 4, 5, and 6 of Division B apply to all buildings described in Article 1.1.1.1. and (a) classified as post-disaster buildings, (b) used for major occupancies classified as (i) Group A, assembly occupancies, (ii) Group B, care, care and treatment or detention…).

Test Part 9 limit
Building height 3 storeys or less
Building area 600 m² or less
Occupancies C (not retirement homes), D, E, F2, F3

Section 9.1 also points certain building types straight back to Part 3: signs (3.15), self-service storage (3.10), tents and air-supported structures (3.14), public pools and spas (3.11, 3.12), shelf and rack storage (3.16), and food premises (3.7.6). See OBC Div. B 9.1.1.2.OBC Div. B 9.1.1.2. Signs(1) Signs shall conform to the requirements in Section 3.15. to OBC Div. B 9.1.1.11.OBC Div. B 9.1.1.11. Shelf and Rack Storage Systems(1) Shelf and rack storage systems shall conform to the requirements of Section 3.16.. Two Ontario specific items: radon limits apply in Elliot Lake, Faraday Township and Hyman Township (OBC Div. B 9.1.1.7.OBC Div. B 9.1.1.7. Radon(1) In addition to all other requirements, a building in the following designated areas shall be designed and constructed so that the annual average concentration of radon 222 does not exceed 200 Bq/m³ of air and the annual average concentration of the short lived daughters of radon 222 does not exceed 0.02 working…), and buildings on flood plains must resist hydrostatic pressure and keep exits usable during floods (OBC Div. B 9.1.1.8.OBC Div. B 9.1.1.8. Building in Flood Plains(1) Buildings constructed on flood plains shall, (a) be designed and constructed in accordance with good engineering practice to withstand anticipated vertical and horizontal hydrostatic pressures acting on the structure, and (b) incorporate floodproofing measures that will preserve the integrity of exits and means of…).

Practice this topic

Materials and structural requirements

Section 9.3 sets the basic material rules.

Item Key value Source
Concrete, garage floors, carports, exterior flatwork 32 MPa at 28 days 9.3.1.6.OBC Div. B 9.3.1.6. Compressive Strength (See also Article 9.12.4.1., Sentence 9.15.4.2.(1) and Article 9.18.6.1.)(1) Except as provided elsewhere in this Part, the compressive strength of unreinforced concrete after 28 days shall be not less than, (a) 32 MPa for garage floors, carport floors and all exterior flatwork, (b) 20 MPa for interior floors other than those for garages and carports, and (c) 15 MPa for all other…
Concrete, other interior floors 20 MPa 9.3.1.6.OBC Div. B 9.3.1.6. Compressive Strength (See also Article 9.12.4.1., Sentence 9.15.4.2.(1) and Article 9.18.6.1.)(1) Except as provided elsewhere in this Part, the compressive strength of unreinforced concrete after 28 days shall be not less than, (a) 32 MPa for garage floors, carport floors and all exterior flatwork, (b) 20 MPa for interior floors other than those for garages and carports, and (c) 15 MPa for all other…
Concrete, all other uses 15 MPa 9.3.1.6.OBC Div. B 9.3.1.6. Compressive Strength (See also Article 9.12.4.1., Sentence 9.15.4.2.(1) and Article 9.18.6.1.)(1) Except as provided elsewhere in this Part, the compressive strength of unreinforced concrete after 28 days shall be not less than, (a) 32 MPa for garage floors, carport floors and all exterior flatwork, (b) 20 MPa for interior floors other than those for garages and carports, and (c) 15 MPa for all other…
Cold weather trigger air below 5°C 9.3.1.9.OBC Div. B 9.3.1.9. Cold Weather Requirements(1) When the air temperature is below 5°C, concrete shall be (a) kept at a temperature of not less than 10°C or more than 25°C while being mixed and placed, and (b) maintained at a temperature of not less than 10°C for 72 h after placing. (2) No frozen material or ice shall be used in concrete described in Sentence…
Lumber moisture at installation 19% max 9.3.2.5.OBC Div. B 9.3.2.5. Moisture Content(1) Moisture content of lumber shall be not more than 19% at the time of installation.
Wood to ground, decay treatment under 150 mm clearance 9.3.2.9.OBC Div. B 9.3.2.9. Termite and Decay Protection(1) In localities where termites are known to occur, (a) clearance between structural wood elements and the finished ground level directly below them shall be not less than 450 mm and, except as provided in Sentence (2), all sides of the supporting elements shall be visible to permit inspection, or (b) structural wood…

In cold weather, concrete is kept between 10°C and 25°C while mixed and placed and at 10°C or more for 72 h. Undersized lumber (up to 5% small) may be used if spans are cut by 5% (OBC Div. B 9.3.2.8.OBC Div. B 9.3.2.8. Undersized Lumber(1) Joist, rafter, lintel and beam members up to 5% less than the actual Canadian standard sizes are permitted to be used provided the allowable spans for the grade and species of lumber under consideration are reduced 5% from those shown in the Span Tables for full size members. (See Note A-9.3.2.8.(1))).

Section 9.4 tells you when Part 9 structural tables are good enough. Structure may follow the Part 9 rules, good engineering practice such as the CWC guide, or Part 4 (OBC Div. B 9.4.1.1.OBC Div. B 9.4.1.1. General(1) Subject to the application limitations defined elsewhere in this Part, structural members and their connections shall (a) conform to requirements provided elsewhere in this Part, (b) be designed according to good engineering practice such as provided in the CWC 2014, "Engineering Guide for Wood Frame…). The light-frame limits in OBC Div. B 9.4.2.1.OBC Div. B 9.4.2.1. Application(1) This Subsection applies to light-frame construction whose wall, floor and roof planes are generally comprised of frames of small repetitive structural members, and where (a) the roof and wall planes are clad, sheathed or braced on at least one side, (b) the small repetitive structural members are spaced not more… matter for small commercial buildings: members at 600 mm o.c. or less, clear span of any member not over 12.2 m, and total roof area not over 4,550 m².

Snow load is S = Cb x Ss + Sr, where Cb is 0.45 for roofs not wider than 4.3 m and 0.55 for all others, and S is never less than 1 kPa (OBC Div. B 9.4.2.2.OBC Div. B 9.4.2.2. Specified Snow Loads(1) Except as provided in Sentences (2) and (4), specified snow loads shall be not less than those calculated using the following formula: S = C_bS_s + S_r where S = specified snow load, C_b = basic snow load roof factor, which is 0.45 where the entire width of a roof does not exceed 4.3 m and 0.55 for all other…). Decks and balconies serving a single dwelling unit use the greater of roof snow load or 1.9 kPa (OBC Div. B 9.4.2.3.OBC Div. B 9.4.2.3. Platforms Subject to Snow and Occupancy Loads(1) Balconies, decks and other accessible exterior platforms intended for an occupancy and subject to snow loads shall be designed to carry the specified roof snow load or 1.9 kPa, whichever is greater, where the platform, or each segregated area of the platform, serves a single dwelling unit. (See Note A-9.4.2.3.(1))). Deflection limits are in Table 9.4.3.1.OBC Div. B Table 9.4.3.1. Maximum Deflections — Forming Part of Sentence 9.4.3.1.(1)Table 9.4.3.1 — Maximum Deflections — Forming Part of Sentence 9.4.3.1.(1) Structural Members | Type of Ceiling Supported | Max. Allowable Deflection as an Expressed Ratio of the Clear Span Roof rafters, roof joists and roof beams | No ceiling | 1/180 Roof rafters, roof joists and roof beams | Other than plaster or…: floors are L/360 in all cases; roof members with no ceiling are L/180. Footings use Table 9.4.4.1.OBC Div. B Table 9.4.4.1. Allowable Bearing Pressure for Soil or Rock — Forming Part of Sentence 9.4.4.1.(1)Table 9.4.4.1 — Allowable Bearing Pressure for Soil or Rock — Forming Part of Sentence 9.4.4.1.(1) Type and Condition of Soil or Rock | Maximum Allowable Bearing Pressure, kPa Dense or compact sand or gravel[1] | 150 Loose sand or gravel[1] | 50 Dense or compact silt[1] | 100 Stiff clay[1] | 150 Firm clay[1] | 75 Soft… bearing pressures, halved for gravel, sand or silt when the water table is within one footing width of the bearing surface (OBC Div. B 9.4.4.3.OBC Div. B 9.4.4.3. High Water Table(1) Where a foundation bears on gravel, sand or silt, and the water table is within a distance below the bearing surface equal to the width of the foundation, the allowable bearing pressure shall be 50% of that determined in Article 9.4.4.1.).

Practice this topic

Design of areas, spaces and doorways

Most of Section 9.5 is about dwelling units used as a principal residence (OBC Div. B 9.5.1.0A.OBC Div. B 9.5.1.0A. Application(1) Except as otherwise specified in this Part, this Section applies only to dwelling units that are intended for use on a continuing or year-round basis as the principal residence of the occupant.). For small buildings, the important parts are the ones that reach past the house:

  • Barrier-free design. Every Part 9 building must meet Section 3.8, except detached and semi-detached houses, houses with a secondary suite, duplexes, triplexes, row houses, and boarding or rooming houses with fewer than eight boarders (OBC Div. B 9.5.2.1.OBC Div. B 9.5.2.1. General(1) Except as provided in Sentence (2) and Article 3.8.1.1., every building shall be designed in conformance with Section 3.8. (2) The requirements of Section 3.8. need not be provided for detached houses, semi-detached houses, houses with a secondary suite, duplexes, triplexes, row houses and boarding or rooming…). So a Part 9 office, store or apartment building needs barrier-free design. If a barrier-free path reaches a storey above the first storey, Article 3.3.1.7. applies (OBC Div. B 9.5.2.2.OBC Div. B 9.5.2.2. Protection on Floor Areas With a Barrier-Free Path of Travel(1) Where a barrier-free path of travel required in Article 9.5.2.1. is provided to any storey above the first storey, the requirements in Article 3.3.1.7. shall apply.).
  • Mezzanines. Ceiling height above and below a mezzanine is at least 2.1 m in all occupancies (OBC Div. B 9.5.3.2.OBC Div. B 9.5.3.2. Mezzanines(1) The ceiling height above and below a mezzanine floor assembly in all occupancies shall be not less than 2.1 m.).
  • Storage garages. Clear height is at least 2 m (OBC Div. B 9.5.3.3.OBC Div. B 9.5.3.3. Storage Garages(1) The clear height in a storage garage shall be not less than 2 m.).
  • Sleeping rooms outside dwelling units. 7 m² per person for single occupancy and 4.6 m² per person for multiple occupancy (OBC Div. B 9.5.3D.4.OBC Div. B 9.5.3D.4. Areas of Other Sleeping Rooms(1) Sleeping rooms other than in dwelling units shall have an area not less than 7 m² per person for single occupancy and 4.6 m² per person for multiple occupancy.).
  • Public water-closet rooms. Doors at least 810 mm wide and 2,030 mm high (OBC Div. B 9.5.5.2.OBC Div. B 9.5.5.2. Doors to Public Water-Closet Rooms(1) Doors to public water closet rooms shall be not less than 810 mm wide and 2,030 mm high.).

Inside dwelling units, the familiar numbers apply: living area 13.5 m², master bedroom 9.8 m² without built-in cabinets, other bedrooms 7 m², hallways 860 mm (710 mm in limited cases under OBC Div. B 9.5.4.1.OBC Div. B 9.5.4.1. Hallway Width(1) The unobstructed width of a hallway within a dwelling unit shall be not less than 860 mm, except that the hallway width is permitted to be 710 mm where (a) there are only bedrooms and bathrooms at the end of the hallway furthest from the living area, and (b) a second exit is provided (i) in the hallway near the…), and ceiling heights from Table 9.5.3.1.OBC Div. B Table 9.5.3.1. Room Ceiling Heights — Forming Part of Sentences 9.5.3.1.(1) and (4)Table 9.5.3.1 — Room Ceiling Heights — Forming Part of Sentences 9.5.3.1.(1) and (4) Room or Space | Minimum Heights[1] Living room or space, dining room or space, kitchen or kitchen space | 2,300 mm over at least 75% of the required floor area with a clear height of 2,100 mm at any point over the required area…. Where a barrier-free path leads into a residential suite, bathroom and bedroom doors on that level need 760 mm clear (served by a space 1,060 mm wide or more) or 810 mm clear (narrower space) (OBC Div. B 9.5.5.3.OBC Div. B 9.5.5.3. Doors to Bathrooms(1) Where a barrier-free path of travel conforming to Section 3.8. is provided into a suite of residential occupancy and where a bathroom within the suite is at the level of the suite entrance door, the doorway to such bathroom and to each bedroom at the same level as such bathroom shall have, when the door is in the…).

Practice this topic

Glass, windows, doors and skylights

Section 9.6 covers glass. Pane size for windows comes from Tables 9.6.1.3.-A to -F based on wind pressure, and for doors from Table 9.6.1.3.-G (OBC Div. B 9.6.1.3.OBC Div. B 9.6.1.3. Structural Sufficiency of Glass(1) Except as provided in Sentence (2), glass shall be designed in conformance with Article 4.3.6.1. (2) Where the building has an essentially uniform distribution of paths for air leakage, including operable openings, but no large openings that would permit wind gusts to rapidly enter the building and the building is…). In public areas, the safety glazing rules in OBC Div. B 9.6.1.4.OBC Div. B 9.6.1.4. Types of Glass and Protection of Glass(1) Glass sidelights greater than 500 mm wide that could be mistaken for doors, glass in storm doors and glass in sliding doors within or at every entrance to a dwelling unit and in public areas shall be (a) safety glazing of the tempered or laminated type conforming to CAN/CGSB-12.1, "Safety Glazing," or (b) wired… matter:

  • Sidelights wider than 500 mm that could be mistaken for doors, storm door glass and sliding door glass must be tempered or laminated safety glass or wired glass.
  • Other entrance door glass needs safety or wired glass where the pane is over 0.5 m² and reaches lower than 900 mm from the bottom of the door.
  • Glass doors open to the public need hardware, bars or fixtures that make the door obvious.
  • Shower and bathtub enclosures need Class A safety glazing.

Section 9.7 covers windows, doors and skylights. Each dwelling unit entrance needs a door, and the main entrance needs a viewer, glazing or a sidelight (OBC Div. B 9.7.2.1.OBC Div. B 9.7.2.1. Entrance Doors(1) A door shall be provided at each entrance to a dwelling unit. (2) Main entrance doors to dwelling units shall be provided with (a) a door viewer or transparent glazing in the door, or (b) a sidelight.). Minimum glass areas for residential rooms are in Table 9.7.2.3.OBC Div. B Table 9.7.2.3. Glass Areas for Rooms of Residential Occupancy — Forming Part of Sentence 9.7.2.3.(1)Table 9.7.2.3 — Glass Areas for Rooms of Residential Occupancy — Forming Part of Sentence 9.7.2.3.(1) Location | Minimum Unobstructed Glass Area — With No Electric Lighting | Minimum Unobstructed Glass Area — With Electric Lighting Laundry, basement recreation room, unfinished basement | 4% of area served | Windows…: 10% of the area for living and dining rooms and 5% for bedrooms. Metal frames need a thermal break, except vehicle doors, storm units and fire-rated units (OBC Div. B 9.7.3.3.OBC Div. B 9.7.3.3. Thermal Characteristics of Windows, Doors and Skylights(1) Metal frames and sash of windows, doors and skylights shall incorporate a thermal break. (2) Windows and doors described in Sentence (1) do not require a thermal break where they are installed as (a) vehicular access doors, (b) storm windows and doors, or (c) windows and doors that are required to have a…). The forced-entry rules for dwelling unit entrance doors in OBC Div. B 9.7.5.2.OBC Div. B 9.7.5.2. Resistance to Forced Entry for Doors(1) Except for exterior doors to garages and to other ancillary spaces, this Article applies to (a) swinging entrance doors to dwelling units, (b) swinging doors between dwelling units and attached garages or other ancillary spaces, and (c) swinging doors that provide access directly or indirectly from a storage… (45 mm solid core wood, deadbolt with at least 5 pins and a 25 mm bolt throw) apply to apartments as well as houses.

Practice this topic

Common traps

  • Using building height alone. A 2 storey store of 700 m² building area is Part 3.
  • Forgetting that Part 9 sends signs, pools, tents, self-storage and racks back to Part 3.
  • Assuming barrier-free design is optional in Part 9. Only the listed housing types are exempt.
  • Mixing up 32 MPa (garage floors and exterior flatwork) with 20 MPa (other interior floors).
  • Applying the 0.45 snow factor to a wide roof. It is only for roofs 4.3 m wide or less.

Chapter review

Chapter at a glance

One line per section: the idea to carry into the exam. Then the answers that most often catch candidates out.

Usual exam traps

  • Using building height alone. A 2 storey store of 700 m² building area is Part 3.
  • Forgetting that Part 9 sends signs, pools, tents, self-storage and racks back to Part 3.
  • Assuming barrier-free design is optional in Part 9. Only the listed housing types are exempt.
  • Mixing up 32 MPa (garage floors and exterior flatwork) with 20 MPa (other interior floors).
  • Applying the 0.45 snow factor to a wide roof. It is only for roofs 4.3 m wide or less.

Practice this chapter

Questions on Part 9 general, structure, rooms, glass and windows, in the exam format, every answer explained and cited to its article. Sign in to start; a free account gets the free questions.

Code cited in this chapter

Based on the official 2024 Building Code Compendium on ontario.ca.

© King's Printer for Ontario, 2024. Reproduced with permission.

  • OBC Div. B 9.1.1.1. Application

    (1)The application of this Part shall be as described in Subsection 1.3.3. of Division A.

    Open OBC Div. B 9.1.1.1. in the code viewer
  • OBC Div. A 1.3.3.3. Application of Part 9

    (1)Subject to Article 1.3.3.3B., Part 9 of Division B applies to all buildings described in Article 1.1.1.1. of 3 storeys or less in building height, having a building area not exceeding 600 m², and used for major occupancies classified as

    (a)reserved

    (b)Group C, residential occupancies other than buildings used for retirement homes, (See Note A-9.1.1.1.(1) of Division B)

    (c)Group D, business and personal services occupancies,

    (d)Group E, mercantile occupancies, or

    (e)Group F, Divisions 2 and 3, medium- and low-hazard industrial occupancies.

    Open OBC Div. A 1.3.3.3. in the code viewer
  • OBC Div. A 1.3.3.2. Application of Parts 3, 4, 5 and 6

    (1)Subject to Articles 1.3.3.1A., 1.3.3.3B., Parts 3, 4, 5, and 6 of Division B apply to all buildings described in Article 1.1.1.1. and

    (a)classified as post-disaster buildings,

    (b)used for major occupancies classified as

    (i)Group A, assembly occupancies,

    (ii)Group B, care, care and treatment or detention occupancies, or

    (iii)Group F, Division 1, high-hazard industrial occupancies, or

    (c)exceeding 600 m² in building area or exceeding 3 storeys in building height used for major occupancies classified as

    (i)Group C, residential occupancies,

    (ii)Group D, business and personal services occupancies,

    (iii)Group E, mercantile occupancies, or

    (iv)Group F, Divisions 2 and 3, medium- and low-hazard industrial occupancies.

    (2)Subject to Articles 1.3.3.1A. and 1.3.3.3B., Part 4 of Division B applies to

    (a)a retaining wall exceeding 1,000 mm in exposed height adjacent to

    (i)public property,

    (ii)access to a building, or

    (iii)private property to which the public is admitted,

    (b)a pedestrian bridge appurtenant to a building,

    (c)a crane runway,

    (d)an exterior storage tank and its supporting structure that is not regulated by the Technical Standards and Safety Act, 2000,

    (e)signs regulated by Section 3.15. of Division B that are not structurally supported by a building,

    (f)a structure that supports a wind turbine generator having a rated output of more than 3 kW,

    (g)an outdoor pool that has a water depth greater than 3.5 m at any point, and

    (h)a permanent solid nutrient storage facility with supporting walls exceeding 1,000 mm in exposed height.

    (3)Section 3.11. of Division B applies to public pools.

    (4)Section 3.12. of Division B applies to public spas.

    (5)Section 3.15. of Division B applies to signs.

    (6)Section 3.17. of Division B applies to demountable stages and demountable support structures.

    Open OBC Div. A 1.3.3.2. in the code viewer
  • OBC Div. B 9.1.1.2. Signs

    (1)Signs shall conform to the requirements in Section 3.15.

    Open OBC Div. B 9.1.1.2. in the code viewer
  • OBC Div. B 9.1.1.11. Shelf and Rack Storage Systems

    (1)Shelf and rack storage systems shall conform to the requirements of Section 3.16.

    Open OBC Div. B 9.1.1.11. in the code viewer
  • OBC Div. B 9.1.1.7. Radon

    (1)In addition to all other requirements, a building in the following designated areas shall be designed and constructed so that the annual average concentration of radon 222 does not exceed 200 Bq/m³ of air and the annual average concentration of the short lived daughters of radon 222 does not exceed 0.02 working levels inside the building for,

    (a)the City of Elliot Lake in the Territorial District of Algoma,

    (b)the Township of Faraday in the County of Hastings, and

    (c)the geographic Township of Hyman in the Territorial District of Sudbury.

    Open OBC Div. B 9.1.1.7. in the code viewer
  • OBC Div. B 9.1.1.8. Building in Flood Plains

    (1)Buildings constructed on flood plains shall,

    (a)be designed and constructed in accordance with good engineering practice to withstand anticipated vertical and horizontal hydrostatic pressures acting on the structure, and

    (b)incorporate floodproofing measures that will preserve the integrity of exits and means of egress during times of flooding.

    Open OBC Div. B 9.1.1.8. in the code viewer
  • OBC Div. B 3.1.2.7. Restaurants

    (1)A restaurant is permitted to be classified as a Group E major occupancy within the application of Part 3 provided the restaurant is designed to accommodate not more than 30 persons consuming food or drink.

    Open OBC Div. B 3.1.2.7. in the code viewer
Show all 36 articles
  • OBC Div. B 9.3.1.6. Compressive Strength (See also Article 9.12.4.1., Sentence 9.15.4.2.(1) and Article 9.18.6.1.)

    (1)Except as provided elsewhere in this Part, the compressive strength of unreinforced concrete after 28 days shall be not less than,

    (a)32 MPa for garage floors, carport floors and all exterior flatwork,

    (b)20 MPa for interior floors other than those for garages and carports, and

    (c)15 MPa for all other applications.

    (2)Site-batched concrete used for garage floors, carport floors and exterior flatwork shall have air entrainment of 5 to 8%.

    Open OBC Div. B 9.3.1.6. in the code viewer
  • OBC Div. B 9.3.1.9. Cold Weather Requirements

    (1)When the air temperature is below 5°C, concrete shall be

    (a)kept at a temperature of not less than 10°C or more than 25°C while being mixed and placed, and

    (b)maintained at a temperature of not less than 10°C for 72 h after placing.

    (2)No frozen material or ice shall be used in concrete described in Sentence (1).

    Open OBC Div. B 9.3.1.9. in the code viewer
  • OBC Div. B 9.3.2.5. Moisture Content

    (1)Moisture content of lumber shall be not more than 19% at the time of installation.

    Open OBC Div. B 9.3.2.5. in the code viewer
  • OBC Div. B 9.3.2.9. Termite and Decay Protection

    (1)In localities where termites are known to occur,

    (a)clearance between structural wood elements and the finished ground level directly below them shall be not less than 450 mm and, except as provided in Sentence (2), all sides of the supporting elements shall be visible to permit inspection, or

    (b)structural wood elements, supported by elements in contact with the ground or exposed over bare soil, shall be pressure-treated with a chemical that is toxic to termites. (See Note A-9.3.2.9.(1))

    (2)In localities where termites are known to occur and foundations are insulated or otherwise finished in a manner that could conceal a termite infestation,

    (a)a metal or plastic barrier shall be installed through the insulation and any other separation or finish materials above finished ground level to control the passage of termites behind or through the insulation, separation or finish materials, and

    (b)all sides of the finished supporting assembly shall be visible to permit inspection.

    (3)Structural wood elements shall be pressure-treated with a preservative to resist decay where the vertical clearance between structural wood elements and the finished ground level is less than 150 mm. (See Note A-9.3.2.9.(3))

    (3.1)In localities where termites are known to occur and where windows or other openings at or below grade contain wood elements, the bottom of window wells or adjacent ground shall be at least 150 mm below the nearest wood unless the wood is pressure-treated with a chemical toxic to termites.

    (4)Structural wood elements used in retaining walls and cribbing shall be pressure-treated with a preservative to resist decay, where

    (a)the retaining wall or cribbing supports ground that is critical to the stability of building foundations, or

    (b)the retaining wall or cribbing is greater than 1.2 m in height. (See Note A-9.3.2.9.(4))

    (5)Where wood is required by this Article to be treated to resist termites or decay, such treatment shall be in accordance with Table 2, "Use Categories for Specific Products, Uses, and Exposures," of CAN/CSA-O80.1, "Specification of treated wood," as follows:

    (a)Use Category 1 (UC1), where the wood member is used in

    (i)interior construction,

    (ii)above-ground applications, and

    (iii)applications where the wood member remains dry,

    (b)Use Category 2 (UC2), where the wood member is used in

    (i)interior construction,

    (ii)above-ground applications, and

    (iii)applications where the wood member may be subjected to occasional sources of moisture,

    (c)Use Category 3.2 (UC3.2), where the wood member is used in

    (i)exterior construction,

    (ii)above-ground applications, and

    (iii)applications where the wood member is uncoated or is used in a configuration conducive to moisture accumulation,

    (d)Use Category 4.1 (UC4.1), where

    (i)the wood member is used in contact with the ground,

    (ii)the wood member is used in contact with fresh water, or

    (iii)the vertical clearance between the wood element and the finished ground level is less than 150 mm and the wood elements are not separated from permeable supporting materials by a moisture barrier, or

    (e)Use Category 4.2 (UC4.2), where the wood member is used in critical structural components, including permanent wood foundations.

    (6)Where wood is protected in accordance with UC1 or UC2 using an inorganic boron preservative, the wood shall be

    (a)protected from direct exposure to water during and after the completion of construction, and

    (b)separated from permeable supporting materials by a moisture barrier that is resistant to all expected mechanisms of deterioration in the service environment if the vertical clearance to the ground is less than 150 mm.

    (7)Wood that is required by this Article to be treated to resist termites or decay shall be identified by a mark to indicate the type of preservative used and conformance to the relevant required Use Category.

    Open OBC Div. B 9.3.2.9. in the code viewer
  • OBC Div. B 9.3.2.8. Undersized Lumber

    (1)Joist, rafter, lintel and beam members up to 5% less than the actual Canadian standard sizes are permitted to be used provided the allowable spans for the grade and species of lumber under consideration are reduced 5% from those shown in the Span Tables for full size members. (See Note A-9.3.2.8.(1))

    Open OBC Div. B 9.3.2.8. in the code viewer
  • OBC Div. B 9.4.1.1. General

    (1)Subject to the application limitations defined elsewhere in this Part, structural members and their connections shall

    (a)conform to requirements provided elsewhere in this Part,

    (b)be designed according to good engineering practice such as provided in the CWC 2014, "Engineering Guide for Wood Frame Construction," or

    (c)be designed according to Part 4 using the loads and deflection and vibration limits specified in,

    (i)this Part, or

    (ii)Part 4.

    (2)Where floor framing is designed in accordance with Clause (1)(b) or (c) and where supporting wall framing and fastenings, or footings, are designed according to Clause (1)(a), the maximum specified live load on the floor according to Table 4.1.5.3. shall not exceed 2.4 kPa.

    (3)Location-specific information for structural design, including snow and wind loads and seismic spectral response accelerations, shall be determined according to MMAH Supplementary Standard SB-1, "Climatic and Seismic Data." (See Note A-9.4.1.1.(3))

    Open OBC Div. B 9.4.1.1. in the code viewer
  • OBC Div. B 9.4.2.1. Application

    (1)This Subsection applies to light-frame construction whose wall, floor and roof planes are generally comprised of frames of small repetitive structural members, and where

    (a)the roof and wall planes are clad, sheathed or braced on at least one side,

    (b)the small repetitive structural members are spaced not more than 600 mm o.c.,

    (c)the clear span of any structural member does not exceed 12.2 m,

    (d)the maximum deflection of the structural roof members conforms to Article 9.4.3.1.,

    (e)the maximum total roof area, notwithstanding any separation of adjoining buildings by firewalls, is 4,550 m², and

    (f)for flat roofs, there are no significant obstructions on the roof, such as parapet walls, spaced closer than the distance calculated by

    D_0 = 10(H_0 - 0.8S_s/γ)

    where

    D_o = minimum distance between obstructions, m,

    H_0 = height of the obstruction above the roof, m,

    S_s = ground snow load, kPa, and

    γ = specific weight of snow taken as 4.0kN/m^3or 0.43S_s + 2.2kN/m^3,whichever is lesser.

    Open OBC Div. B 9.4.2.1. in the code viewer
  • OBC Div. B 9.4.2.2. Specified Snow Loads

    (1)Except as provided in Sentences (2) and (4), specified snow loads shall be not less than those calculated using the following formula:

    S = C_bS_s + S_r

    where

    S = specified snow load,

    C_b = basic snow load roof factor, which is 0.45 where the entire width of a roof does not exceed 4.3 m and 0.55 for all other roofs,

    S_s = 1 -in-50 year ground snow load in kPa, determined according to MMAH Supplementary Standard SB-1, "Climatic and Seismic Data," and

    S_r = associated 1-in-50 year rain load in kPa, determined according to MMAH Supplementary Standard SB-1, "Climatic and Seismic Data."

    (2)In no case shall the specified snow load be less than 1 kPa.

    (3)Bow string, arch or semi-circular roof trusses having an unsupported span greater than 6 m shall be designed in conformance with the snow load requirements in Subsection 4.1.6.

    (4)Where the height of a roof step at the intersection of an upper level roof and a lower level roof is greater than 2 m, and the upper level roof has a slope less than 1 in 6 and an area greater than 600 m², the specified snow load on the lower level roof shall be

    (a)for distances from the roof step that are less than or equal to the drift length, x_d , calculated in accordance with Sentence (5), not less than 1.5 times the specified snow load, S, calculated using the formula in Sentence (1) with C_b equal to 0.55, and

    (b)for distances from the roof step that are greater than the drift length, x_d , calculated in accordance with Sentence (5), as specified in Sentence (1).

    (5)For the purposes of Sentence (4), the drift length, x_d , in m, shall be calculated as follows:

    x_rmd = 5(h - (0.55S_rms)/(γ))

    where

    h = height of the roof step, in m, and

    γ = specific weight of snow as specified in Clause 9.4.2.1.(1)(f).

    Open OBC Div. B 9.4.2.2. in the code viewer
  • OBC Div. B 9.4.2.3. Platforms Subject to Snow and Occupancy Loads

    (1)Balconies, decks and other accessible exterior platforms intended for an occupancy and subject to snow loads shall be designed to carry the specified roof snow load or 1.9 kPa, whichever is greater, where the platform, or each segregated area of the platform, serves a single dwelling unit. (See Note A-9.4.2.3.(1))

    Open OBC Div. B 9.4.2.3. in the code viewer
  • OBC Div. B Table 9.4.3.1. Maximum Deflections — Forming Part of Sentence 9.4.3.1.(1)

    Table 9.4.3.1 — Maximum Deflections — Forming Part of Sentence 9.4.3.1.(1) Structural Members | Type of Ceiling Supported | Max. Allowable Deflection as an Expressed Ratio of the Clear Span Roof rafters, roof joists and roof beams | No ceiling | 1/180 Roof rafters, roof joists and roof beams | Other than plaster or gypsum board | 1/240 Roof rafters, roof joists and roof beams | Plaster or gypsum board | 1/360 Ceiling joists | Other than plaster or gypsum board | 1/240 Ceiling joists | Plaster or gypsum board | 1/360 Floor beams, floor joists and floor decking | All cases | 1/360 Beams, joists and decking for balconies, decks and other accessible exterior platforms | Serving a single dwelling unit | 1/240 Beams, joists and decking for balconies, decks and other accessible exterior platforms | Other | 1/360

    Open OBC Div. B Table 9.4.3.1. in the code viewer
  • OBC Div. B Table 9.4.4.1. Allowable Bearing Pressure for Soil or Rock — Forming Part of Sentence 9.4.4.1.(1)

    Table 9.4.4.1 — Allowable Bearing Pressure for Soil or Rock — Forming Part of Sentence 9.4.4.1.(1) Type and Condition of Soil or Rock | Maximum Allowable Bearing Pressure, kPa Dense or compact sand or gravel[1] | 150 Loose sand or gravel[1] | 50 Dense or compact silt[1] | 100 Stiff clay[1] | 150 Firm clay[1] | 75 Soft clay[1] | 40 Till | 200 Clay shale | 300 Sound rock | 500 Notes to Table 9.4.4.1.: (1) See Note A-Table 9.4.1.1.

    Open OBC Div. B Table 9.4.4.1. in the code viewer
  • OBC Div. B 9.4.4.3. High Water Table

    (1)Where a foundation bears on gravel, sand or silt, and the water table is within a distance below the bearing surface equal to the width of the foundation, the allowable bearing pressure shall be 50% of that determined in Article 9.4.4.1.

    Open OBC Div. B 9.4.4.3. in the code viewer
  • OBC Div. B 9.5.1.0A. Application

    (1)Except as otherwise specified in this Part, this Section applies only to dwelling units that are intended for use on a continuing or year-round basis as the principal residence of the occupant.

    Open OBC Div. B 9.5.1.0A. in the code viewer
  • OBC Div. B 9.5.2.1. General

    (1)Except as provided in Sentence (2) and Article 3.8.1.1., every building shall be designed in conformance with Section 3.8.

    (2)The requirements of Section 3.8. need not be provided for detached houses, semi-detached houses, houses with a secondary suite, duplexes, triplexes, row houses and boarding or rooming houses with fewer than eight boarders or roomers.

    Open OBC Div. B 9.5.2.1. in the code viewer
  • OBC Div. B 9.5.2.2. Protection on Floor Areas With a Barrier-Free Path of Travel

    (1)Where a barrier-free path of travel required in Article 9.5.2.1. is provided to any storey above the first storey, the requirements in Article 3.3.1.7. shall apply.

    Open OBC Div. B 9.5.2.2. in the code viewer
  • OBC Div. B 9.5.3.2. Mezzanines

    (1)The ceiling height above and below a mezzanine floor assembly in all occupancies shall be not less than 2.1 m.

    Open OBC Div. B 9.5.3.2. in the code viewer
  • OBC Div. B 9.5.3.3. Storage Garages

    (1)The clear height in a storage garage shall be not less than 2 m.

    Open OBC Div. B 9.5.3.3. in the code viewer
  • OBC Div. B 9.5.3D.4. Areas of Other Sleeping Rooms

    (1)Sleeping rooms other than in dwelling units shall have an area not less than 7 m² per person for single occupancy and 4.6 m² per person for multiple occupancy.

    Open OBC Div. B 9.5.3D.4. in the code viewer
  • OBC Div. B 9.5.5.2. Doors to Public Water-Closet Rooms

    (1)Doors to public water closet rooms shall be not less than 810 mm wide and 2,030 mm high.

    Open OBC Div. B 9.5.5.2. in the code viewer
  • OBC Div. B 9.5.4.1. Hallway Width

    (1)The unobstructed width of a hallway within a dwelling unit shall be not less than 860 mm, except that the hallway width is permitted to be 710 mm where

    (a)there are only bedrooms and bathrooms at the end of the hallway furthest from the living area, and

    (b)a second exit is provided

    (i)in the hallway near the end furthest from the living area, or

    (ii)in each bedroom served by the hallway.

    Open OBC Div. B 9.5.4.1. in the code viewer
  • OBC Div. B Table 9.5.3.1. Room Ceiling Heights — Forming Part of Sentences 9.5.3.1.(1) and (4)

    Table 9.5.3.1 — Room Ceiling Heights — Forming Part of Sentences 9.5.3.1.(1) and (4) Room or Space | Minimum Heights[1] Living room or space, dining room or space, kitchen or kitchen space | 2,300 mm over at least 75% of the required floor area with a clear height of 2,100 mm at any point over the required area Bedroom or bedroom space | 2,300 mm over at least 50% of the required area or 2,100 mm over all of the required floor area. Any part of the floor having a clear height of less than 1,400 mm shall not be considered in computing the required floor area Basement space | 2,100 mm over at least 75% of the basement area except that under beams and ducts the clearance is permitted to be reduced to 1,950 mm Bathroom, water closet room or laundry area above grade | 2,100 mm in any area where a person would normally be in a standing position Passage, hall or main entrance vestibule and finished rooms not specifically mentioned above | 2,100 mm Notes to Table 9.5.3.1.: (1) Area of the space shall be measured at floor level.

    Open OBC Div. B Table 9.5.3.1. in the code viewer
  • OBC Div. B 9.5.5.3. Doors to Bathrooms

    (1)Where a barrier-free path of travel conforming to Section 3.8. is provided into a suite of residential occupancy and where a bathroom within the suite is at the level of the suite entrance door, the doorway to such bathroom and to each bedroom at the same level as such bathroom shall have, when the door is in the open position, a clear width of not less than,

    (a)760 mm where the door is served by a corridor or space not less than 1,060 mm wide, and

    (b)810 mm where the door is served by a corridor or space less than 1,060 mm wide.

    Open OBC Div. B 9.5.5.3. in the code viewer
  • OBC Div. B 9.6.1.3. Structural Sufficiency of Glass

    (1)Except as provided in Sentence (2), glass shall be designed in conformance with Article 4.3.6.1.

    (2)Where the building has an essentially uniform distribution of paths for air leakage, including operable openings, but no large openings that would permit wind gusts to rapidly enter the building and the building is not in an exceptionally exposed location such as a hilltop, the maximum area of individual panes of glass for windows shall conform to

    (a)Tables 9.6.1.3.-A to 9.6.1.3.-C, where the building has a height from grade to the uppermost roof of 12 m or less, and is located in a built-up area, no less than 120 m away from the boundary between this area and open terrain, or

    (b)Tables 9.6.1.3.-D to 9.6.1.3.-F.

    (See Note A-9.6.1.3.(2))

    (3)The maximum area of individual panes of glass for doors shall conform to Table 9.6.1.3.-G.

    Open OBC Div. B 9.6.1.3. in the code viewer
  • OBC Div. B 9.6.1.4. Types of Glass and Protection of Glass

    (1)Glass sidelights greater than 500 mm wide that could be mistaken for doors, glass in storm doors and glass in sliding doors within or at every entrance to a dwelling unit and in public areas shall be

    (a)safety glazing of the tempered or laminated type conforming to CAN/CGSB-12.1, "Safety Glazing," or

    (b)wired glass conforming to CAN/CGSB-12.11-M, "Wired Safety Glass."

    (2)Except as provided in Sentence (4), glass in entrance doors to dwelling units and in public areas, other than the entrance doors described in Sentence (1), shall be safety glazing or wired glass of the type described in Sentence (1) where the glass area exceeds 0.5m^2 and extends to less than 900 mm from the bottom of the door.

    (3)Except as provided in Sentence (4), transparent panels that could be mistaken as a means of egress shall be protected by barriers or railings.

    (4)Sliding glass partitions that separate a public corridor from an adjacent occupancy and that are open during normal working hours need not conform to Sentences (2), (3) and (5), except that such partitions shall be suitably marked to indicate their existence and position.

    (5)Except as provided in Sentence (4), every glass or transparent door accessible to the public shall be equipped with hardware, bars or other permanent fixtures designed so that the existence and position of such doors is readily apparent.

    (6)Glazing used for a shower or bathtub enclosure shall conform to Class A of CAN/CGSB-12.1, "Safety Glazing."

    Open OBC Div. B 9.6.1.4. in the code viewer
  • OBC Div. B 9.7.2.1. Entrance Doors

    (1)A door shall be provided at each entrance to a dwelling unit.

    (2)Main entrance doors to dwelling units shall be provided with

    (a)a door viewer or transparent glazing in the door, or

    (b)a sidelight.

    Open OBC Div. B 9.7.2.1. in the code viewer
  • OBC Div. B Table 9.7.2.3. Glass Areas for Rooms of Residential Occupancy — Forming Part of Sentence 9.7.2.3.(1)

    Table 9.7.2.3 — Glass Areas for Rooms of Residential Occupancy — Forming Part of Sentence 9.7.2.3.(1) Location | Minimum Unobstructed Glass Area — With No Electric Lighting | Minimum Unobstructed Glass Area — With Electric Lighting Laundry, basement recreation room, unfinished basement | 4% of area served | Windows not required Water-closet room | 0.37 m² | Windows not required Kitchen space | 10% of area served | Windows not required Kitchen alcove | 10% of area served | Windows not required Living rooms and dining rooms | 10% of area served | 10% of area served Bedrooms and other finished rooms not mentioned above | 5% of area served[1] | 5% of area served[1] Notes to Table 9.7.2.3.: (1) See Subsection 9.9.10.

    Open OBC Div. B Table 9.7.2.3. in the code viewer
  • OBC Div. B 9.7.3.3. Thermal Characteristics of Windows, Doors and Skylights

    (1)Metal frames and sash of windows, doors and skylights shall incorporate a thermal break.

    (2)Windows and doors described in Sentence (1) do not require a thermal break where they are installed as

    (a)vehicular access doors,

    (b)storm windows and doors, or

    (c)windows and doors that are required to have a fire-resistance rating.

    (3)Windows, doors and skylights with or without storm doors or sash that are installed in buildings where the intended use of the interior space will not result in high moisture generation shall have a maximum thermal transmittance (U-value) or minimum temperature index (I) in accordance with Table 9.7.3.3.

    (4)Windows, doors and skylights, with or without storm doors or sash that are installed in portions of buildings where the intended use of the interior space will result in high moisture generation shall be designed in conformance with Subsection 5.3. (See Note A-9.25.5.2.)

    Open OBC Div. B 9.7.3.3. in the code viewer
  • OBC Div. B 9.7.5.2. Resistance to Forced Entry for Doors

    (1)Except for exterior doors to garages and to other ancillary spaces, this Article applies to

    (a)swinging entrance doors to dwelling units,

    (b)swinging doors between dwelling units and attached garages or other ancillary spaces, and

    (c)swinging doors that provide access directly or indirectly from a storage garage to a dwelling unit. (See Note A-9.7.5.2.(1))

    (2)Doors, frames and hardware that conform to a security level of at least Grade 10 as described in the Annex to ASTM F476, "Standard Test Methods for Security of Swinging Door Assemblies," are not required to conform to Sentences (3) to (7). (See Note A-9.7.5.2.(2))

    (3)Except as permitted in Sentence (2), wood doors as described in Sentence (1) shall

    (a)be solid core or stile-and-rail type,

    (b)be not less than 45 mm thick, and

    (c)if of the stile-and-rail type, have a panel thickness of not less than 19 mm, with a total panel area not more than half of the door area.

    (4)Except as permitted in Sentence (2), doors described in Sentence (1) shall be provided with

    (a)a deadbolt lock with a cylinder having no fewer than 5 pins, and

    (b)a bolt throw not less than 25 mm long, protected with a solid or hardened free-turning ring or beveled cylinder housing. (See Article 9.9.6.7.)

    (5)Except as permitted in Sentence (2), an inactive leaf in double doors used in locations specified in Sentence (1) shall be provided with heavy-duty bolts top and bottom having an engagement of not less than 15 mm.

    (6)Except as permitted in Sentence (2), hinges for doors described in Sentence (1) shall be fastened

    (a)to wood doors with wood screws not less than 25 mm long and to wood frames with wood screws such that at least 2 screws per hinge penetrate not less than 30 mm into solid wood, or

    (b)to metal doors and metal frames with machine screws not smaller than No. 10 and not less than 10 mm long. (See Note A-9.7.5.2.(6))

    (7)Strikeplates for deadbolts described in Sentence (4) shall be fastened

    (a)to wood frames with wood screws that penetrate not less than 30 mm into solid wood, or

    (b)to metal frames with machine screws not smaller than No. 8 and not less than 10 mm long. (See Note A-9.7.5.2.(6))

    (8)Except for storm doors or screen doors, doors described in Sentence (1) that swing outward shall be provided with hinges or pins so that the doors cannot be removed when they are in the closed position. (See Note A-9.7.5.2.(8))

    (9)Solid blocking shall be provided on both sides at the lock height between the jambs for doors described in Sentence (1) and the structural framing so that the jambs will resist spreading by force.

    Open OBC Div. B 9.7.5.2. in the code viewer