Values this chapter turns on
- minimum age of a building for Part 11 to apply
- 5 years
- minimum age of a building for Part 11 to apply
- occupant load increase above which performance drops
- 15%
- occupant load increase above which performance drops
- construction index scale, lowest to highest
- 1 to 8
- construction index scale, lowest to highest
- combustible extension above this must be sprinklered
- 4 storeys
- combustible extension above this must be sprinklered
Parts 10 and 11 of Division B deal with existing buildings. Part 10 applies when the use of a building changes and a section 10 permit is needed OBC Div. A 1.3.3.3A.OBC Div. A 1.3.3.3A. Application of Part 10(1) Part 10 of Division B applies to existing buildings requiring a permit under section 10 of the Act.. Part 11 applies to renovation of buildings that have been in existence for at least five years OBC Div. A 1.3.3.3B.OBC Div. A 1.3.3.3B. Application of Part 11(1) Except as provided in Sentence (2), Part 11 of Division B applies to the design and construction of existing buildings, or parts of existing buildings, that have been in existence for at least five years. (2) If a building has been in existence for at least five years but includes an addition that has been in…. Both rest on one idea: after the work, the building must perform at least as well as it did before. If it would not, you add compensating construction or use a compliance alternative.
Change of use: scope, classification and performance level
Scope. Part 10 applies to existing buildings needing a section 10 permit OBC Div. B 10.1.1.1.OBC Div. B 10.1.1.1. Scope(1) The scope of this Part shall be as described in Subsection 1.3.3. of Division A.. Several changes are deemed a change in major occupancy, matching the permit triggers in Division C 1.3.1.4.: one Group C suite becoming more than one, A-2 or A-4 space becoming a gaming premises, a farm building changing to a non-G occupancy or to G-1, a change to a post-disaster building or retirement home, and an unknown previous occupancy OBC Div. B 10.1.1.2.OBC Div. B 10.1.1.2. Change in Major Occupancy(1) The following changes of use are also deemed to be a change in major occupancy for the purposes of this Part: (a) a suite of a Group C major occupancy is converted into more than one suite of a Group C major occupancy, (b) a suite or part of a suite of a Group A, Division 2 or Group A, Division 4 major occupancy….
Classification. The existing building is classified by major occupancy under Part 2 or 3.1.2. OBC Div. B 10.2.1.1.OBC Div. B 10.2.1.1. Classification of Major Occupancy(1) Every existing building or part of it shall be classified according to its major occupancy in accordance with the requirements of Part 2 or Subsection 3.1.2., and by construction and occupancy using the indexes in 11.2.1.1. A Group G occupancy may be indexed as if it were F-2 OBC Div. B 10.2.1.2.OBC Div. B 10.2.1.2. Classification According to Construction and Occupancy(1) Except as provided in Sentence (2), for the purposes of this Part, existing buildings shall be classified as to their construction and occupancy as provided for in Sentence 11.2.1.1.(1). (2) For the purpose of Parts 10 and 11, the calculation of the construction index and hazard index for Group G major occupancy…. The building size and construction articles 3.2.2.20. to 3.2.2.93. do not apply OBC Div. B 10.2.1.3.OBC Div. B 10.2.1.3. Building Size and Construction(1) The requirements of Articles 2.2.2.3. to 2.2.2.8. and 3.2.2.20. to 3.2.2.93. do not apply to this Part..
Requirements. The changed part must meet a short list of requirements for the new occupancy, such as Subsection 3.2.6., Sections 3.7, 3.11 and 3.12, parts of Section 9.5, and Sections 9.31 (plumbing facilities) and 9.32 (ventilation) OBC Div. B 10.3.1.1.OBC Div. B 10.3.1.1. General(1) Except as provided in Section 10.4., a building or part of a building subject to a change of major occupancy shall conform to the requirements of Subsection 3.2.6., Sections 3.7., 3.11. and 3.12., Sentences 6.3.1.1.(2) and 6.3.2.7.(1), Subsections 9.5.1. and 9.5.3., 9.5.3A. to 9.5.3F. and 9.5.4., Sentences…. The performance level after the change must not be less than before OBC Div. B 10.3.2.1.OBC Div. B 10.3.2.1. General(1) The performance level of a building after the change of major occupancy shall not be less than the performance level prior to the change of major occupancy. (2) For the purposes of Sentence (1), reduction of performance level shall be determined in accordance with Article 10.3.2.2. (3) For the purpose of this….
When is performance reduced? Article 10.3.2.2. lists the triggers OBC Div. B 10.3.2.2.OBC Div. B 10.3.2.2. Reduction in Performance Level(1) Except as provided in Sentence (2), the performance level of a building or part of a building is reduced where the existing structural floor and roof framing systems and their supporting members are not adequate to support the proposed dead loads and live loads of the new major occupancy that the building is to…. The main ones:
- floor or roof framing cannot carry the new loads (unless the floor is load-restricted and signed),
- early warning and evacuation systems fall short for the new occupancy,
- the new occupancy has a higher hazard index, unless that hazard index is not above the building's construction index,
- a combustible building becomes residential where a new building would need noncombustible construction (not reduced if sprinklered and 6 storeys or less),
- fire separations between occupancies fall short,
- sewage flow exceeds system capacity,
- a change to a retirement home without sprinklers, required voice communication or self-closing suite doors.
Renovation: scope, application and classification of existing buildings
Part 11 covers buildings in existence at least five years. If an older building has a newer addition (under five years), Part 11 applies to the whole building OBC Div. A 1.3.3.3B.OBC Div. A 1.3.3.3B. Application of Part 11(1) Except as provided in Sentence (2), Part 11 of Division B applies to the design and construction of existing buildings, or parts of existing buildings, that have been in existence for at least five years. (2) If a building has been in existence for at least five years but includes an addition that has been in…. For extension, material alteration or repair, the work must meet Section 11.3 and the performance level must be checked and compensated under Section 11.4 OBC Div. B 11.1.2.1.OBC Div. B 11.1.2.1. Extension, Material Alteration or Repair(1) Where an existing building is subject to extension, material alteration or repair, (a) the proposed construction shall comply with Section 11.3., and (b) the performance level of the building shall be evaluated and compensating construction shall be undertaken in accordance with Section 11.4..
A "building system" is a complete major division of construction, such as framing, roofing, a fire alarm system, plumbing, a sewage system or HVAC OBC Div. B 11.1.1.2.OBC Div. B 11.1.1.2. Definitions(1) In this Part, Building system means a combination of elements or components that form a complete major division of construction in the design of a building or part of a building, including a structural or framing system, a waterproofing system, a drainage system, an exterior cladding system, a roofing system, a….
Two indexes. When construction changes the major occupancy, the building gets two numbers OBC Div. B 11.2.1.1.OBC Div. B 11.2.1.1. Construction Index and Hazard Index(1) Where proposed construction will result in the change of major occupancy of all or part of an existing building to another major occupancy, the building shall be classified as to its, (a) construction on the basis of its construction index as provided for in this Part, including Table 11.2.1.1.-A, and (See Note…:
| Index | Measures | Scale | From |
|---|---|---|---|
| Construction index (C.I.) | How well the existing structure performs in a fire: type of construction and fire-resistance ratings | 1 (lowest) to 8 (highest) | Table 11.2.1.1.-AOBC Div. B Table 11.2.1.1-A. Construction Index — Forming Part of Sentence 11.2.1.1.(1)Table 11.2.1.1.-A — Construction Index — Forming Part of Sentence 11.2.1.1.(1) Fire-Resistance Rating of Floors over Basement | Fire-Resistance Rating of Other Floors | Fire-Resistance Rating of Roof | Type of Construction | C.I.[2] 3 h | 3 h | 1.5 h | Noncombustible | 8[1] 2 h | 2 h | 1 h | Noncombustible | 7 1 h | 1… |
| Hazard index (H.I.) | How hazardous the new occupancy is, by building size | Number read by occupancy and building size | Tables 11.2.1.1.-B to -N |
See the definitions of construction indexOBC Div. A 1.4.1.2.(1) Construction indexConstruction index means a level on a scale of 1 to 8 determined in accordance with Table 11.2.1.1.-A of Division B designating the expected performance level of the building structure with respect to the type of construction and fire protection of an existing building, and "C.I." has a corresponding meaning. and performance levelOBC Div. A 1.4.1.2.(1) Performance levelPerformance level means the level of performance under which all or part of an existing building functions with respect to its building systems.. The rule of thumb: if the new H.I. is not greater than the existing C.I., the change does not reduce performance on that ground. Small or medium buildings facing more than one street may take a hazard index credit of 1 if they hold no B-1, C or F-1 occupancy and have firefighting access. Nothing in Part 11 excuses the prohibited occupancy combinations, including the one-suite limit in F-2 buildings OBC Div. B 11.2.1.3.OBC Div. B 11.2.1.3. Prohibition of Occupancy Combinations(1) Nothing in this Part relieves an applicant from complying with the requirements of Article 2.2.1.2., 3.1.3.2. or 9.10.9.14..
Proposed construction: extensions, renovation, plumbing and sewage
- A materially altered building system must leave performance at least equal to before OBC Div. B 11.3.1.1.OBC Div. B 11.3.1.1. Material Alteration or Repair of a Building System(1) Where an existing building system is materially altered or repaired, the performance level of the building after the material alteration or repair shall be at least equal to the performance level of the building prior to the material alteration or repair. (See Note A-11.3.1.1.(1)).
- New building systems and extensions of systems follow the other Parts, except as allowed by basic renovation and compliance alternatives OBC Div. B 11.3.1.2.OBC Div. B 11.3.1.2. New Building Systems and Extension of Existing Building Systems(1) Except as provided in Article 11.3.3.1. and Section 11.5., the design and construction of a new building system or the extension of an existing building system, shall comply with all other Parts. (See Note A-11.3.1.2.(1)).
- In an extended building, Part 11 governs the existing portion and the addition follows the other Parts OBC Div. B 11.3.2.1.OBC Div. B 11.3.2.1. Portion of Extended Buildings(1) Where an existing building is extended, (a) this Part applies to the existing portion of the building, and (b) the extended portion of the building shall comply with all other Parts..
- Basic renovation lets you reuse or extend the same or similar materials to keep character or heritage value, if early warning and evacuation, fire separations, structure and health are not harmed OBC Div. B 11.3.3.1.OBC Div. B 11.3.3.1. Basic Renovation(1) Except as provided in Sentence (2) and Article 11.3.3.2., construction may be carried out to maintain the existing performance level of all or part of an existing building, by the reuse, relocation or extension of the same or similar materials or components, to retain the existing character, structural uniqueness….
- Extensive renovation, where walls, ceilings, floors or roofs are substantially removed and replaced, needs structural and fire-resistance elements to meet the other Parts, and a storey with a Group C occupancy in a building over 3 storeys must be sprinklered (with an exception) OBC Div. B 11.3.3.2.OBC Div. B 11.3.3.2. Extensive Renovation(1) Where existing interior walls or ceilings or floor assemblies or roof assemblies are substantially removed in an existing building and new interior walls, ceilings, floor assemblies or roof assemblies are installed in the building, structural and fire-resistance elements shall be constructed in compliance with the….
- Part 7 applies to plumbing in the new or altered work and to plumbing adversely affected OBC Div. B 11.3.4.1.OBC Div. B 11.3.4.1. Extension, Material Alteration or Repair(1) Despite Subsections 11.3.1. to 11.3.3., when an existing building is extended or subject to material alteration or repair, Part 7 applies, (a) to the design and construction of plumbing in the extensions and those parts of the building subject to material alteration and repair, and (b) to plumbing which is…. An altered or replaced septic tank must meet Part 8 OBC Div. B 11.3.5.1.OBC Div. B 11.3.5.1. Existing Septic Tanks(1) Despite Subsections 11.3.1. to 11.3.3., where an existing septic tank is subject to material alteration, repair or replacement, the construction of the septic tank shall comply with Part 8., and the vertical separation to the water table applies to old and new parts of an extended sewage system OBC Div. B 11.3.5.2.OBC Div. B 11.3.5.2. Vertical Separations and Existing Sewage Systems(1) Despite Subsections 11.3.1. to 11.3.3., where an existing sewage system is extended or is subject to material alteration or repair, the requirements respecting the vertical separation to the water table set out in Part 8 apply to the extended, altered or repaired portions of the sewage system as well as to the….
Performance level evaluation and compensating construction
Performance after construction may not be less than before; if it would be, compensating construction is required OBC Div. B 11.4.1.1.OBC Div. B 11.4.1.1. Performance Level(1) The performance level of a building after construction shall not be less than the performance level of the building prior to construction. (2) For the purposes of Sentence (1), reduction of performance level shall be determined in accordance with Subsection 11.4.2. (3) Where the proposed construction would reduce….
| Trigger (11.4.2.) | Compensating construction (11.4.3.) |
|---|---|
| Occupancy, occupant load (over 15%) or live load change and the framing is inadequate | Strengthen, or restrict and sign the floor loading |
| Occupant load up more than 15% | Evaluate and upgrade early warning and evacuation per Table 11.4.3.3. |
| Occupant load up 15% or less, but more than 15% over the fire alarm threshold or the existing exit capacity | Same evaluation and upgrade |
| Change to a higher hazard index occupancy | Raise C.I. to at least the new H.I., with upgrading from Table 11.4.3.4.-A |
| Plumbing or sewage system adversely affected | Upgrade to Part 7 or Part 8 |
| Combustible building extended above 4 storeys | Sprinkler the building |
Sources: 11.4.2.1.OBC Div. B 11.4.2.1. Structural(1) The performance level of an existing building is reduced where after proposed construction in all or part of an existing building, (a) the major occupancy will change to a different major occupancy, (b) the occupant load will increase by more than 15%, or (c) the live load will increase due to change in use within…, 11.4.2.2.OBC Div. B 11.4.2.2. Increase in Occupant Load(1) Except as provided in Sentences 11.4.2.5.(2) and (3), the performance level of an existing building is reduced where proposed construction will increase the occupant load of an existing building by more than 15%. (2) The performance level of an existing building is reduced where proposed construction will increase…, 11.4.2.3.OBC Div. B 11.4.2.3. Change of Major Occupancy(1) Except as provided in Sentence 11.4.2.5.(4), the performance level of an existing building is reduced where proposed construction will result in, (a) the change of the major occupancy of all or part of an existing building to another major occupancy of a greater hazard index. (b) the conversion of a suite of a…, 11.4.2.5.OBC Div. B 11.4.2.5. Sewage Systems(1) The performance level of an existing building is reduced where the existing building is extended or subject to material alteration or repair and a sewage system serving the existing building is adversely affected by the extension, alteration or repair of the existing building. (2) Except as provided in Sentence…, 11.4.2.6.OBC Div. B 11.4.2.6. Extension of Buildings of Combustible Construction(1) The performance level of an existing building of combustible construction is reduced where the existing building is extended by adding a storey or storeys such that the extended building will be more than four storeys in building height., 11.4.3.1.OBC Div. B 11.4.3.1. General(1) Where the performance level of an existing building is reduced under Subsection 11.4.2., compensating construction shall be carried out in accordance with this Subsection. (2) Except as provided in Sentence (3), compensating construction required under this Subsection applies to the part of the building being…, 11.4.3.3.OBC Div. B 11.4.3.3. Increase in Occupant Load(1) Where the performance level of an existing building is reduced under Sentence 11.4.2.2.(1), (2) or (3), the building shall be evaluated, and the early warning and evacuation systems shall be upgraded, in conformance with the applicable requirements of Table 11.4.3.3. (2) Sentence (1) does not apply in a Group C…, 11.4.3.4.OBC Div. B 11.4.3.4. Change in Major Occupancy(1) Where the performance level of an existing building is reduced under Clause 11.4.2.3.(1)(a), (b), (c), (d), (e) or (g), additional upgrading shall be required in conformance with Table 11.4.3.4.-A and so that the construction index of the building is increased to at least equal the hazard index of the new major…, 11.4.3.7.OBC Div. B 11.4.3.7. Extension of Buildings of Combustible Construction(1) Where the performance level of an existing building is reduced under Article 11.4.2.6., the building shall be sprinklered..
Compensating construction applies to the part being altered. It includes fire separations from the floors above and below and adjacent areas, and exit work if the exit system is affected. Small Group C buildings are relieved of the Table 11.4.3.3. upgrade: 14 persons or fewer in a boarding, lodging or rooming house, or 16 or fewer where the suites are dwelling units, with interconnected smoke alarms near stairs in the stated ranges.
Compliance alternatives
A compliance alternative (C.A.) is a substitute, listed in Part 10 or 11, for a requirement elsewhere in Division B definitionOBC Div. A 1.4.1.2.(1) Compliance alternativeCompliance alternative means a substitute for a requirement in another Part of Division B that is listed in Part 10 or 11 of Division B, and "C.A." has a corresponding meaning.. The Tables 11.5.1.1.-A to -F list them by occupancy OBC Div. B 11.5.1.1.OBC Div. B 11.5.1.1. Compliance Alternatives(1) A compliance alternative shown in Table 11.5.1.1.-A, 11.5.1.1.-B, 11.5.1.1.-C, 11.5.1.1.-D/E or 11.5.1.1.-F may be substituted for a requirement contained in Part 3, 4, 6 or 8 where the chief building official is satisfied that compliance with the requirement is impracticable because, (a) of structural or…. Part 10 uses the same tables OBC Div. B 10.4.1.1.OBC Div. B 10.4.1.1. Substitution(1) Except as provided in Sentence (3), a compliance alternative to a requirement contained in Part 3, 4, 6 or 8 that is shown in Tables 11.5.1.1.-A, 11.5.1.1.-B, 11.5.1.1.-C, 11.5.1.1.-D/E or 11.5.1.1.-F may be substituted for the requirement where the chief building official is satisfied that compliance with the….
| Requirement in | Test before using a C.A. |
|---|---|
| Part 3, 4, 6 or 8 | CBO must be satisfied compliance is impracticable because of structural or construction difficulties, or harm to a heritage building |
| Part 9 or 12 | No impracticable test needed |
| Building in existence less than five years (Part 10) | C.A.s limited to the early warning and fire separation items referenced in 10.3.2.2.(3), (5) and Table 10.3.2.2.-B |
Common traps
- Part 11 is for buildings at least five years old; a younger addition pulls the whole building in.
- Higher H.I. alone is not a reduction if it does not exceed the existing C.I.
- The 15% trigger is "more than 15%". Exactly 15% does not trigger 11.4.2.2.(1).
- C.A.s for Part 9 need no impracticable finding; for Part 3 they do.
- The combustible extension trigger is "more than four storeys".
Chapter review
Chapter at a glance
One line per section: the idea to carry into the exam. Then the answers that most often catch candidates out.
- Renovation: scope, application and classification of existing buildings
Part 11 covers buildings in existence at least five years.
- Performance level evaluation and compensating construction
Performance after construction may not be less than before; if it would be, compensating construction is required.
- Compliance alternatives
A compliance alternative (C.A.) is a substitute, listed in Part 10 or 11, for a requirement elsewhere in Division B. The Tables 11.5.1.1.-A to -F list them by occupancy.
Usual exam traps
- Part 11 is for buildings at least five years old; a younger addition pulls the whole building in.
- Higher H.I. alone is not a reduction if it does not exceed the existing C.I.
- The 15% trigger is "more than 15%". Exactly 15% does not trigger 11.4.2.2.(1).
- C.A.s for Part 9 need no impracticable finding; for Part 3 they do.
- The combustible extension trigger is "more than four storeys".
Practice this chapter
Questions on Change of use and renovation (Parts 10 and 11), in the exam format, every answer explained and cited to its article. Sign in to start; a free account gets the free questions.
Code cited in this chapter
Based on the official 2024 Building Code Compendium on ontario.ca.
© King's Printer for Ontario, 2024. Reproduced with permission.
OBC Div. A 1.3.3.3A. Application of Part 10
Open OBC Div. A 1.3.3.3A. in the code viewer(1)Part 10 of Division B applies to existing buildings requiring a permit under section 10 of the Act.
OBC Div. A 1.3.3.3B. Application of Part 11
Open OBC Div. A 1.3.3.3B. in the code viewer(1)Except as provided in Sentence (2), Part 11 of Division B applies to the design and construction of existing buildings, or parts of existing buildings, that have been in existence for at least five years.
(2)If a building has been in existence for at least five years but includes an addition that has been in existence for less than five years, Part 11 of Division B applies to the entire building.
OBC Div. B 10.1.1.1. Scope
Open OBC Div. B 10.1.1.1. in the code viewer(1)The scope of this Part shall be as described in Subsection 1.3.3. of Division A.
OBC Div. B 10.1.1.2. Change in Major Occupancy
Open OBC Div. B 10.1.1.2. in the code viewer(1)The following changes of use are also deemed to be a change in major occupancy for the purposes of this Part:
(a)a suite of a Group C major occupancy is converted into more than one suite of a Group C major occupancy,
(b)a suite or part of a suite of a Group A, Division 2 or Group A, Division 4 major occupancy is converted to a gaming premises,
(c)a farm building or part of a farm building is changed to another major occupancy other than a Group G major occupancy,
(d)a building or part of a building is changed to a post-disaster building,
(e)a building or part of a building is changed to a retirement home,
(f)the use of a building or part of a building is changed and the previous major occupancy of the building or part of the building cannot be determined, or
(g)a farm building or part of a farm building is changed to a Group G, Division 1 major occupancy.
OBC Div. B 10.2.1.1. Classification of Major Occupancy
Open OBC Div. B 10.2.1.1. in the code viewer(1)Every existing building or part of it shall be classified according to its major occupancy in accordance with the requirements of Part 2 or Subsection 3.1.2.
OBC Div. B 10.2.1.2. Classification According to Construction and Occupancy
Open OBC Div. B 10.2.1.2. in the code viewer(1)Except as provided in Sentence (2), for the purposes of this Part, existing buildings shall be classified as to their construction and occupancy as provided for in Sentence 11.2.1.1.(1).
(2)For the purpose of Parts 10 and 11, the calculation of the construction index and hazard index for Group G major occupancy is permitted to be based on Group F, Division 2 major occupancy.
OBC Div. B 10.2.1.3. Building Size and Construction
Open OBC Div. B 10.2.1.3. in the code viewer(1)The requirements of Articles 2.2.2.3. to 2.2.2.8. and 3.2.2.20. to 3.2.2.93. do not apply to this Part.
OBC Div. B 10.3.1.1. General
Open OBC Div. B 10.3.1.1. in the code viewer(1)Except as provided in Section 10.4., a building or part of a building subject to a change of major occupancy shall conform to the requirements of Subsection 3.2.6., Sections 3.7., 3.11. and 3.12., Sentences 6.3.1.1.(2) and 6.3.2.7.(1), Subsections 9.5.1. and 9.5.3., 9.5.3A. to 9.5.3F. and 9.5.4., Sentences 9.6.1.4.(3), (4), Article 9.7.2.3., Sentences 9.8.8.1.(4) to (8) and 9.9.10.1.(1) to (7), Subsection 9.10.17., Sections 9.31. and 9.32., Sentence 9.33.6.13.(7.1), and Subsections 9.34.1. to 9.34.3. as they apply to the new major occupancy that the building or part of a building is to support.
(2)Where a major occupancy is changed to a Group B, Division 2 major occupancy, heating, ventilating, and air conditioning systems shall conform to the requirements of Sentence 6.2.1.1.(1).
(3)Where a major occupancy is changed to a Group B, Division 3 major occupancy, ventilation, air circulation, and filtration systems, shall conform to the requirements of Sentence 6.2.1.1.(1).
Show all 38 articles
OBC Div. B 10.3.2.1. General
Open OBC Div. B 10.3.2.1. in the code viewer(1)The performance level of a building after the change of major occupancy shall not be less than the performance level prior to the change of major occupancy.
(2)For the purposes of Sentence (1), reduction of performance level shall be determined in accordance with Article 10.3.2.2.
(3)For the purpose of this Subsection, where a permit to construct a farm building has been applied for before January 1, 2025, the performance level of the farm building is permitted to be evaluated based on the applicable requirements of Ontario Regulation 332/12 (Building Code) made under the Act, as it read on December 31, 2024.
OBC Div. B 10.3.2.2. Reduction in Performance Level
Open OBC Div. B 10.3.2.2. in the code viewer(1)Except as provided in Sentence (2), the performance level of a building or part of a building is reduced where the existing structural floor and roof framing systems and their supporting members are not adequate to support the proposed dead loads and live loads of the new major occupancy that the building is to support.
(2)The inadequacy of the existing structural floor or roof framing system and its supporting members to support the proposed dead loads and live loads does not reduce the performance level of the building if the portion of the floor affected by the proposed loads is restricted to the loading it will support and signs stating the restrictions are posted.
(3)Except as provided in Section 10.4., the performance level of a building or part of a building is reduced where the early warning and evacuation systems requirements of the building do not meet the early warning and evacuation systems requirements set out in Table 10.3.2.2.-A for the new major occupancy that the building is to support.
(4)Except as provided in Sentence (5), the performance level of an existing building is reduced where a change in use will result in a change of the major occupancy of all or part of an existing building to another major occupancy of a greater hazard index.
(5)Except as provided in Sentence (6), if the hazard index of the new major occupancy is greater than the hazard index of the existing major occupancy, the performance level is not reduced where the hazard index of the new major occupancy is not greater than the construction index of the existing building.
(6)Small or medium sized existing buildings as determined in Tables 11.2.1.1.-B to 11.2.1.1.-N facing multiple streets may be assigned a hazard index credit of 1, which may be subtracted from the hazard index of the new major occupancy provided,
(a)the building does not contain a Group B, Division 1, a Group C, or a Group F, Division 1 occupancy, and
(b)firefighting access complying with Articles 3.2.5.1. to 3.2.5.5. or Subsection 9.10.20. is provided.
(7)Except as provided in Sentence (8), the performance level of a building or part of a building is reduced in an existing building of combustible construction where,
(a)the occupancy is changed to a residential occupancy in all or part of the building, and
(b)if the building was new, it would have been required to be of noncombustible construction or to be constructed in accordance with Article 3.2.2.51. or 3.2.2.60.
(8)A change in the occupancy of a building or part of a building to a residential occupancy does not reduce the performance level of the building or part of the building where,
(a)the building is sprinklered, and
(b)the building does not exceed 6 storeys in building height.
(9)The performance level of a building or part of a building is reduced where the new major occupancy in an existing building of multiple occupancy is not separated from adjoining major occupancies by fire separations having fire-resistance ratings conforming to Article 3.1.3.1., Subsection 9.10.9. or Table 10.3.2.2.-B.
(10)The performance level of a building is reduced where the building after the change of major occupancy will not comply with Article 3.1.3.2. or 9.10.9.14.
(11)The performance level of a building or part of a building is reduced where, after a change of major occupancy,
(a)the total daily design sanitary sewage flow of the new major occupancy, calculated in accordance with Article 8.2.1.3., exceeds the capacity of any component of a sewage system serving the building, or
(b)the type or amount of sanitary sewage that will, under the new major occupancy, be discharged to a sewage system serving the building is prohibited by Article 8.1.3.1.
(12)The performance level of an existing building or part of an existing building is reduced where,
(a)the use of the building or part of the building is changed to a retirement home, and
(b)any of the following applies:
(i)the retirement home is not sprinklered throughout,
(ii)Clause 3.2.6.8.(1)(b) or
(c)as applicable, requires that a voice communication system conforming to Article 3.2.4.22. be provided in the building and such a system is not provided in the building, or
(iii) the retirement home contains one or more doors to suites or sleeping rooms not within suites, other than doors leading directly to the exterior, that are not equipped with self-closing devices.
OBC Div. B 11.1.2.1. Extension, Material Alteration or Repair
Open OBC Div. B 11.1.2.1. in the code viewer(1)Where an existing building is subject to extension, material alteration or repair,
(a)the proposed construction shall comply with Section 11.3., and
(b)the performance level of the building shall be evaluated and compensating construction shall be undertaken in accordance with Section 11.4.
OBC Div. B 11.1.1.2. Definitions
Open OBC Div. B 11.1.1.2. in the code viewer(1)In this Part,
Building system means a combination of elements or components that form a complete major division of construction in the design of a building or part of a building, including a structural or framing system, a waterproofing system, a drainage system, an exterior cladding system, a roofing system, a window system, a partition system, a corridor system, a stair system, a fire alarm and detection system, a sprinkler system or a heating, ventilation or air-conditioning system, a foundation system, a standpipe and hose system, a flooring system, a plumbing system, a sewage system or an electrical system.
OBC Div. B 11.2.1.1. Construction Index and Hazard Index
Open OBC Div. B 11.2.1.1. in the code viewer(1)Where proposed construction will result in the change of major occupancy of all or part of an existing building to another major occupancy, the building shall be classified as to its,
(a)construction on the basis of its construction index as provided for in this Part, including Table 11.2.1.1.-A, and (See Note A-11.2.1.1.(1)(a))
(b)occupancy on the basis of its hazard index as provided for in this Part, including Tables 11.2.1.1.-B to 11.2.1.1.-N. (See Note A-11.2.1.1.(1)(b))
(2)Small or medium sized existing buildings as determined in Tables 11.2.1.1.-B to 11.2.1.1.-N facing multiple streets may be assigned a hazard index credit of 1, which may be subtracted from the hazard index of the proposed major occupancy to reduce the additional upgrading required by Table 11.4.3.4.-A provided,
(a)the building does not contain a Group B, Division 1, a Group C, or a Group F, Division 1 occupancy, and
(b)firefighting access complying with Articles 3.2.5.1. to 3.2.5.5. or Subsection 9.10.20. is provided.
(3)The requirements of Articles 2.2.2.3. to 2.2.2.8. and 3.2.2.20. to 3.2.2.93. do not apply to this Part.
(4)For the purpose of this Part, the calculation of the construction index and hazard index for a Group G major occupancy is permitted to be based on a Group F, Division 2 major occupancy.
OBC Div. B Table 11.2.1.1-A. Construction Index — Forming Part of Sentence 11.2.1.1.(1)
Open OBC Div. B Table 11.2.1.1-A. in the code viewerTable 11.2.1.1.-A — Construction Index — Forming Part of Sentence 11.2.1.1.(1) Fire-Resistance Rating of Floors over Basement | Fire-Resistance Rating of Other Floors | Fire-Resistance Rating of Roof | Type of Construction | C.I.[2] 3 h | 3 h | 1.5 h | Noncombustible | 8[1] 2 h | 2 h | 1 h | Noncombustible | 7 1 h | 1 h | 45 min | Noncombustible | 6 45 min | 45 min | 0 h | Noncombustible | 5 45 min | 45 min | 45 min | Heavy Timber | 5 45 min | 45 min | 45 min | Combustible | 5 45 min | 0 h | 0 h | Noncombustible | 4 45 min | 45 min | 0 h | Combustible | 4 30 min | 0 h | 0 h | Noncombustible | 3 30 min | 30 min | 0 h | Combustible | 3 0 h | 30 min | 0 h | Combustible | 2 0 h | 0 h | 0 h | Combustible | 1[1] Notes to Table 11.2.1.1.-A: (1) C.I. of 1 is lowest fire protection performance level and C.I. of 8 is highest. (2) Take highest rating for C.I. from Table 11.2.1.1.-A for existing building.
OBC Div. A 1.4.1.2.(1) Construction index
Open OBC Div. A 1.4.1.2.(1) in the code viewerConstruction index means a level on a scale of 1 to 8 determined in accordance with Table 11.2.1.1.-A of Division B designating the expected performance level of the building structure with respect to the type of construction and fire protection of an existing building, and "C.I." has a corresponding meaning.
OBC Div. A 1.4.1.2.(1) Performance level
Open OBC Div. A 1.4.1.2.(1) in the code viewerPerformance level means the level of performance under which all or part of an existing building functions with respect to its building systems.
OBC Div. B 11.2.1.3. Prohibition of Occupancy Combinations
Open OBC Div. B 11.2.1.3. in the code viewer(1)Nothing in this Part relieves an applicant from complying with the requirements of Article 2.2.1.2., 3.1.3.2. or 9.10.9.14.
OBC Div. B 11.3.1.1. Material Alteration or Repair of a Building System
Open OBC Div. B 11.3.1.1. in the code viewer(1)Where an existing building system is materially altered or repaired, the performance level of the building after the material alteration or repair shall be at least equal to the performance level of the building prior to the material alteration or repair. (See Note A-11.3.1.1.(1))
OBC Div. B 11.3.1.2. New Building Systems and Extension of Existing Building Systems
Open OBC Div. B 11.3.1.2. in the code viewer(1)Except as provided in Article 11.3.3.1. and Section 11.5., the design and construction of a new building system or the extension of an existing building system, shall comply with all other Parts. (See Note A-11.3.1.2.(1))
OBC Div. B 11.3.2.1. Portion of Extended Buildings
Open OBC Div. B 11.3.2.1. in the code viewer(1)Where an existing building is extended,
(a)this Part applies to the existing portion of the building, and
(b)the extended portion of the building shall comply with all other Parts.
OBC Div. B 11.3.3.1. Basic Renovation
Open OBC Div. B 11.3.3.1. in the code viewer(1)Except as provided in Sentence (2) and Article 11.3.3.2., construction may be carried out to maintain the existing performance level of all or part of an existing building, by the reuse, relocation or extension of the same or similar materials or components, to retain the existing character, structural uniqueness, heritage value, or aesthetic appearance of all or part of the building, if the construction will not adversely affect the early warning and evacuation systems, fire separations or the structural adequacy or will not create an unhealthy environment in the building.
(2)Construction in respect of a Group B, Division 3 occupancy, a hotel or a retirement home may be carried out in accordance with Sentence (1) only if the construction will be in conformance with the Fire Code made under the Fire Protection and Prevention Act, 1997.
OBC Div. B 11.3.3.2. Extensive Renovation
Open OBC Div. B 11.3.3.2. in the code viewer(1)Where existing interior walls or ceilings or floor assemblies or roof assemblies are substantially removed in an existing building and new interior walls, ceilings, floor assemblies or roof assemblies are installed in the building, structural and fire-resistance elements shall be constructed in compliance with the requirements of the other Parts.
(2)Except as provided in Section 11.5., the proposed construction within an existing suite shall comply with the requirements of Section 3.8. where,
(a)new interior walls or floor assemblies are installed,
(b)the suite has an area greater than 300 m², and
(c)the suite is located in,
(i)a floor area where the existing difference in elevation between the adjacent ground level and the floor level is not more than 200 mm, or
(ii)a normally occupied floor area which is accessible by a passenger type elevator or other platform equipped passenger elevating device from an entrance storey where the existing difference in elevation between the adjacent ground level and the entrance storey level is not more than 200 mm.
(3)Except as provided in Section 11.5., the proposed construction within an existing suite, other than a suite described in Sentence (2) or a suite in a building described in Clause 3.8.1.1.(1)(a), (b), (c) or (d), shall comply with the requirements of Sentences 3.8.1.3.(6), 3.8.2.3.(6), 3.8.3.1.(6), 3.8.3.3.(19), 3.8.3.7.(1), 3.8.3.15.(5) and 3.8.3.16.(4) where new interior walls or floor assemblies are installed. (See Note A-11.3.3.2.(3))
(4)Except as provided in Sentence (5), where existing interior walls or ceilings or floor assemblies or roof assemblies are substantially removed on any storey in an existing building and new interior walls, ceilings, floor assemblies or roof assemblies are installed, the storey shall be sprinklered if,
(a)the storey will contain a Group C major occupancy, and
(b)the building is over 3 storeys in building height.
(5)Sentence (4) does not apply where the building,
(a)conforms to Subclause 3.2.2.50.(1)(a)(ii), and
(b)contains dwelling units having means of egress conforming to Sentence 3.3.4.4.(8).
(6)Where existing interior walls or ceilings or floor assemblies or roof assemblies are substantially removed and new interior walls, ceilings, floor assemblies or roof assemblies are installed in an existing building or part of an existing building that is a retirement home, the following requirements apply:
(a)the retirement home shall be sprinklered,
(b)a voice communication system conforming to Article 3.2.4.23. shall be provided in the building, if Clause 3.2.6.8.(1)(b) or
(c)as applicable, requires that such a voice communication system be provided in the building, and
(c) doors to suites and sleeping rooms not within suites in the retirement home, other than doors leading directly to the exterior, shall be equipped with self-closing devices.
OBC Div. B 11.3.4.1. Extension, Material Alteration or Repair
Open OBC Div. B 11.3.4.1. in the code viewer(1)Despite Subsections 11.3.1. to 11.3.3., when an existing building is extended or subject to material alteration or repair, Part 7 applies,
(a)to the design and construction of plumbing in the extensions and those parts of the building subject to material alteration and repair, and
(b)to plumbing which is adversely affected by the extension, alteration or repair.
OBC Div. B 11.3.5.1. Existing Septic Tanks
Open OBC Div. B 11.3.5.1. in the code viewer(1)Despite Subsections 11.3.1. to 11.3.3., where an existing septic tank is subject to material alteration, repair or replacement, the construction of the septic tank shall comply with Part 8.
OBC Div. B 11.3.5.2. Vertical Separations and Existing Sewage Systems
Open OBC Div. B 11.3.5.2. in the code viewer(1)Despite Subsections 11.3.1. to 11.3.3., where an existing sewage system is extended or is subject to material alteration or repair, the requirements respecting the vertical separation to the water table set out in Part 8 apply to the extended, altered or repaired portions of the sewage system as well as to the existing portions of the sewage system.
OBC Div. B 11.4.1.1. Performance Level
Open OBC Div. B 11.4.1.1. in the code viewer(1)The performance level of a building after construction shall not be less than the performance level of the building prior to construction.
(2)For the purposes of Sentence (1), reduction of performance level shall be determined in accordance with Subsection 11.4.2.
(3)Where the proposed construction would reduce the performance level of an existing building, compensating construction shall be required in conformance with Subsection 11.4.3.
(4)For the purpose of this Subsection, where a permit to construct a farm building has been applied for before January 1, 2025, the performance level of the farm building is permitted to be evaluated based on the applicable requirements of Ontario Regulation 332/12 (Building Code) made under the Act, as it read on December 31, 2024.
OBC Div. B 11.4.2.1. Structural
Open OBC Div. B 11.4.2.1. in the code viewer(1)The performance level of an existing building is reduced where after proposed construction in all or part of an existing building,
(a)the major occupancy will change to a different major occupancy,
(b)the occupant load will increase by more than 15%, or
(c)the live load will increase due to change in use within the same major occupancy,
and the existing structural floor and roof framing systems and their supporting members after the construction are not adequate to support the proposed dead loads and live loads.
OBC Div. B 11.4.2.2. Increase in Occupant Load
Open OBC Div. B 11.4.2.2. in the code viewer(1)Except as provided in Sentences 11.4.2.5.(2) and (3), the performance level of an existing building is reduced where proposed construction will increase the occupant load of an existing building by more than 15%.
(2)The performance level of an existing building is reduced where proposed construction will increase the occupant load by 15% or less and the new occupant load will be more than 15% above the occupant load for which a fire alarm system is required under Sentence 3.2.4.1.(2).
(3)The performance level of an existing building is reduced where proposed construction will increase the occupant load by 15% or less and the new occupant load will be more than 15% above the existing exit capacity as required under Article 3.4.3.2.
OBC Div. B 11.4.2.3. Change of Major Occupancy
Open OBC Div. B 11.4.2.3. in the code viewer(1)Except as provided in Sentence 11.4.2.5.(4), the performance level of an existing building is reduced where proposed construction will result in,
(a)the change of the major occupancy of all or part of an existing building to another major occupancy of a greater hazard index.
(b)the conversion of a suite of a Group C major occupancy into more than one suite of Group C major occupancy,
(c)the conversion of a suite or part of a suite of a Group A, Division 2 or a Group A, Division 4 major occupancy into a gaming premises,
(d)the change of a farm building or part of a farm building to another major occupancy other than a Group G major occupancy,
(e)the change of a building or part of a building to a post-disaster building,
(f)the change of a building or part of a building to a retirement home,
(g)the change in use of a building or part of a building where the previous major occupancy of the building or part of the building cannot be determined, or
(h)the change of a farm building or part of a farm building to a Group G, Division 1 major occupancy.
(2)For the purpose of this Article and Sentences 11.4.2.1.(1) and 11.4.2.5.(4), the change of use set out in Clauses (1)(b) to (h) is also deemed to constitute a change in major occupancy.
(3)The performance level of an existing building is reduced where the early warning and evacuation systems requirements of other Parts for the proposed major occupancy exceed those of the existing building.
(4)The performance level of an existing building is reduced where the proposed major occupancy in the building is not separated from the adjoining major occupancies by fire separations having fire-resistance ratings conforming to Tables 2.2.1.4., 3.1.3.1. and 11.4.3.4.-B.
(5)The performance level of an existing building is reduced where the occupancy of all or part of an existing building of combustible construction is changed to a new major occupancy that would require the building, if it were a new building, to be of noncombustible construction or to be constructed in accordance with Article 3.2.2.51. or 3.2.2.60.
(6)Despite Clause (1)(a), the performance level of an existing building is reduced where proposed construction will result in the change of the major occupancy of all or part of an existing building to a Group C major occupancy in a building over 3 storeys in building height, except in a building conforming to Subclause 3.2.2.50.(1)(a)(ii) and having an egress facility conforming to Sentence 3.3.4.4.(8).
OBC Div. B 11.4.2.5. Sewage Systems
Open OBC Div. B 11.4.2.5. in the code viewer(1)The performance level of an existing building is reduced where the existing building is extended or subject to material alteration or repair and a sewage system serving the existing building is adversely affected by the extension, alteration or repair of the existing building.
(2)Except as provided in Sentence (3), the performance level of an existing building is reduced where proposed construction will increase the occupant load of an existing building, and the new occupant load will result in the total daily design sanitary sewage flow of the building, calculated in accordance with Article 8.2.1.3., exceeding the capacity of any component of a sewage system serving the building.
(3)The performance level of an existing dwelling unit is reduced where proposed construction that,
(a)increases the number of bedrooms in the dwelling unit,
(b)exceeds 15% of the finished area of the dwelling unit, or
(c)adds new plumbing fixtures to the dwelling unit,
will result in the total daily design sanitary sewage flow of the dwelling unit, calculated in accordance with Article 8.2.1.3., exceeding the capacity of any component of a sewage system serving the dwelling unit.
(4)The performance level of an existing building is reduced where proposed construction will result in the change of a major occupancy of all or part of the existing building to another major occupancy and,
(a)the total daily design sanitary sewage flow of the proposed major occupancy, calculated in accordance with Article 8.2.1.3., exceeds the capacity of any component of a sewage system serving the building, or
(b)the type or amount of sanitary sewage which will, under the proposed major occupancy, be discharged to a sewage system serving the building, is prohibited by Article 8.1.3.1.
OBC Div. B 11.4.2.6. Extension of Buildings of Combustible Construction
Open OBC Div. B 11.4.2.6. in the code viewer(1)The performance level of an existing building of combustible construction is reduced where the existing building is extended by adding a storey or storeys such that the extended building will be more than four storeys in building height.
OBC Div. B 11.4.3.1. General
Open OBC Div. B 11.4.3.1. in the code viewer(1)Where the performance level of an existing building is reduced under Subsection 11.4.2., compensating construction shall be carried out in accordance with this Subsection.
(2)Except as provided in Sentence (3), compensating construction required under this Subsection applies to the part of the building being altered and shall include,
(a)fire separations, with the required fire-resistance ratings, separating the part being altered from the floor areas immediately above and below and from the immediate adjacent areas, and
(b)access to exits and exits from the building, where the alteration adversely affects the exit system of the building.
(3)Compensating construction required under this Subsection applies to the existing building systems that are adversely affected by the proposed construction.
OBC Div. B 11.4.3.3. Increase in Occupant Load
Open OBC Div. B 11.4.3.3. in the code viewer(1)Where the performance level of an existing building is reduced under Sentence 11.4.2.2.(1), (2) or (3), the building shall be evaluated, and the early warning and evacuation systems shall be upgraded, in conformance with the applicable requirements of Table 11.4.3.3.
(2)Sentence (1) does not apply in a Group C occupancy where the new total occupant load is,
(a)14 persons or fewer in a boarding, lodging or rooming house, except that where the occupant load is between 10 and 15 persons, an interconnected system of smoke alarms in corridors near stairways is required, or
(b)16 persons or fewer in a building containing residential suites which are dwelling units, except that where the occupant load is between 10 and 17 persons, an interconnected system of smoke alarms in corridors near stairways is required.
(3)Where the performance level of an existing building is reduced under Sentence 11.4.2.2.(1), additional construction shall be required in order that the building or part of the building subject to the increase in occupant load conforms to the requirements of Sentences 2.4.2.1.(1) and 6.3.1.1.(2), Subsection 3.7.4. and Article 9.31.1.1.
OBC Div. B 11.4.3.4. Change in Major Occupancy
Open OBC Div. B 11.4.3.4. in the code viewer(1)Where the performance level of an existing building is reduced under Clause 11.4.2.3.(1)(a), (b), (c), (d), (e) or (g), additional upgrading shall be required in conformance with Table 11.4.3.4.-A and so that the construction index of the building is increased to at least equal the hazard index of the new major occupancy that the building is to support.
(2)A building or part of the building subject to a change of major occupancy shall conform to the requirements of Articles 2.4.2.3. to 2.4.2.5., Subsection 3.2.6., Sections 3.7., 3.11., 3.12., Sentences 6.3.1.1.(2), and 6.3.2.7.(1) and 9.33.6.13.(7.1), Subsections 9.5.1. and 9.5.3., 9.5.3A. to 9.5.3F. and 9.5.4., Section 9.7., Subsection 9.10.17., Sections 9.31. and 9.32., and Subsections 9.34.1. to 9.34.3. as they apply to the new major occupancy that the building or part of the building is to support.
(3)Where the performance level of an existing building is reduced under Sentence 11.4.2.3.(3), the building shall be evaluated, and the early warning and evacuation systems shall be upgraded, in conformance with the applicable requirements of Table 11.4.3.3.
(4)Where the performance level of an existing building is reduced under Sentence 11.4.2.3.(4), upgrading of the fire separations shall be required in conformance with the applicable requirements of Article 3.1.3.1. and Table 11.4.3.4.-B.
(5)Where the performance level is reduced under Sentence 11.4.2.3.(5), the requirement for the building to be of noncombustible construction or to be constructed in accordance with Article 3.2.2.51. or 3.2.2.60. is satisfied if the building is sprinklered.
(6)Where the performance level is reduced under Sentence 11.4.2.3.(6), the storey subject to the change shall be sprinklered.
(7)Where the performance level of an existing building is reduced under Clause 11.4.2.3.(1)(f), the following requirements apply:
(a)the retirement home shall be sprinklered,
(b)a voice communication system conforming to Article 3.2.4.22. shall be provided in the building, and
(c)doors to suites and sleeping rooms not within suites in the retirement home, other than doors leading directly to the exterior, shall be equipped with self-closing devices.
(8)Where a major occupancy is changed to a Group B, Division 2 major occupancy, heating, ventilating, air conditioning systems shall conform to the requirements of Sentence 6.2.1.1.(1).
(9)Where a major occupancy is changed to a Group B, Division 3 major occupancy, ventilation, air circulation, and filtration systems shall conform to the requirements of Sentence 6.2.1.1.(1).
OBC Div. B 11.4.3.7. Extension of Buildings of Combustible Construction
Open OBC Div. B 11.4.3.7. in the code viewer(1)Where the performance level of an existing building is reduced under Article 11.4.2.6., the building shall be sprinklered.
OBC Div. A 1.4.1.2.(1) Compliance alternative
Open OBC Div. A 1.4.1.2.(1) in the code viewerCompliance alternative means a substitute for a requirement in another Part of Division B that is listed in Part 10 or 11 of Division B, and "C.A." has a corresponding meaning.
OBC Div. B 11.5.1.1. Compliance Alternatives
Open OBC Div. B 11.5.1.1. in the code viewer(1)A compliance alternative shown in Table 11.5.1.1.-A, 11.5.1.1.-B, 11.5.1.1.-C, 11.5.1.1.-D/E or 11.5.1.1.-F may be substituted for a requirement contained in Part 3, 4, 6 or 8 where the chief building official is satisfied that compliance with the requirement is impracticable because,
(a)of structural or construction difficulties, or
(b)it is detrimental to the preservation of a heritage building.
(2)A compliance alternative shown in Table 11.5.1.1.-A, 11.5.1.1.-B, 11.5.1.1.-C, 11.5.1.1.-D/E or 11.5.1.1.-F may be substituted for a requirement contained in Part 9 or 12 without satisfying the chief building official that compliance with the requirement is impracticable.
OBC Div. B 10.4.1.1. Substitution
Open OBC Div. B 10.4.1.1. in the code viewer(1)Except as provided in Sentence (3), a compliance alternative to a requirement contained in Part 3, 4, 6 or 8 that is shown in Tables 11.5.1.1.-A, 11.5.1.1.-B, 11.5.1.1.-C, 11.5.1.1.-D/E or 11.5.1.1.-F may be substituted for the requirement where the chief building official is satisfied that compliance with the requirement is impracticable because,
(a)of structural or construction difficulties, or
(b)it is detrimental to the preservation of a heritage building.
(2)Except as provided in Sentence (3), a compliance alternative to a requirement contained in Part 9 or 12 shown in Tables 11.5.1.1.-C, 11.5.1.1.-D/E or 11.5.1.1.-F may be substituted for the requirement without satisfying the chief building official that the requirement is impracticable.
(3)Where the building has been in existence for less than five years, compliance alternatives may only be used in respect of requirements of this Division that are referenced in Sentences 10.3.2.2.(3), (5) and Table 10.3.2.2.-B.