Part 9 fire protection for services

Windows thermal performance, occupant load, exit signs and lighting, Part 3 and Part 6 jurisdiction items, penetrations, exhaust ducts, central vacuum, service rooms, fuel-fired appliances, incinerators, emergency power, closures, dampers, fire stop flaps, fire blocks, alarm and detection systems, smoke alarms, extinguishers, freeze protection and construction camp items.

chapters in this guide
11 of 13
chapters in this guide
to read
6 min
to read
code articles cited
38
code articles cited

Last updated

Values this chapter turns on

max building area for the appliance room exemption
400 m²
max building area for the appliance room exemption
small branch duct size that skips a fire damper
130 cm²
small branch duct size that skips a fire damper
incandescent emergency lighting deemed to give 10 lx
1 W/m²
incandescent emergency lighting deemed to give 10 lx
min tank for a worker camp hose station
4,500 L
min tank for a worker camp hose station

This chapter collects the Part 9 items a building services examiner cares about: how windows and doors are rated, exit signs and egress lighting, service penetrations of fire separations, service rooms and generators, fire dampers and fire stop flaps, and fire alarm, smoke alarm and extinguisher rules. Part 9 often hands the detail back to Part 3, so many answers are "which Article does Part 9 send you to".

Windows and doors: thermal and manufactured units

Metal window, door and skylight frames need a thermal break, except vehicular doors, storm units, and units required to have a fire-resistance rating OBC Div. B 9.7.3.3.OBC Div. B 9.7.3.3. Thermal Characteristics of Windows, Doors and Skylights(1) Metal frames and sash of windows, doors and skylights shall incorporate a thermal break. (2) Windows and doors described in Sentence (1) do not require a thermal break where they are installed as (a) vehicular access doors, (b) storm windows and doors, or (c) windows and doors that are required to have a…. Units in ordinary spaces meet a maximum U-value or minimum temperature index from the Part 9 window table; units serving high-moisture spaces (an indoor pool, for example) are designed under Subsection 5.3.

Manufactured windows, doors and skylights follow the North American Fenestration Standard (AAMA/WDMA/CSA 101/I.S.2/A440) and the Canadian Supplement CSA A440S1 OBC Div. B 9.7.4.2.OBC Div. B 9.7.4.2. General(1) Manufactured and pre-assembled windows, doors and skylights and their installation shall conform to (a) AAMA/WDMA/CSA 101/I.S.2/A440, "North American Fenestration Standard/Specification for windows, doors, and skylights" (Harmonized Standard), (b) CSA A440S1, "Canadian Supplement to AAMA/WDMA/CSA…. Performance grades are chosen for the location, and the minimum is Performance Class R OBC Div. B 9.7.4.3.OBC Div. B 9.7.4.3. Performance Requirements(1) Performance grades for windows, doors and skylights shall be selected according to CSA A440S1, "Canadian Supplement to AAMA/WDMA/CSA 101/I.S.2/A440-17, North American Fenestration Standard/Specification for windows, doors, and skylights" so as to be appropriate for the conditions and geographic location in which…. Site-built units outside that standard's scope follow Subsection 9.7.5 or Part 5, with glass to Section 9.6 OBC Div. B 9.7.5.1.OBC Div. B 9.7.5.1. Application and Compliance(1) Materials, design, construction and installation of windows, doors and skylights that separate conditioned space from unconditioned space or the exterior but that are not within the scope of AAMA/WDMA/CSA 101/I.S.2/A440, "North American Fenestration Standard/Specification for windows, doors, and skylights," shall….

Practice this topic

Exit signs and lighting

Occupant load counts two persons per sleeping room in a dwelling unit or suite; other areas use the design number or the Part 3 occupant load table OBC Div. B 9.9.1.3.OBC Div. B 9.9.1.3. Occupant Load(1) The occupant load of a floor area or part of a floor area shall be based on (a) two persons per sleeping room or sleeping area in a dwelling unit or suite, and (b) for occupancies other than as described in Clause (a), the number of persons (i) for which the area is designed, or (ii) determined from Table 3.1.17.1..

Exit signs are needed over or beside every exit door where the exit serves a 3-storey building, an occupant load over 150, or a floor area using a fire escape OBC Div. B 9.9.11.3.OBC Div. B 9.9.11.3. Exit Signs(1) Except as required in Sentence (7), every exit door shall have an exit sign placed over it or adjacent to it if the exit serves (a) a building that is 3 storeys in building height, (b) a building having an occupant load of more than 150, or (c) a room or floor area that has a fire escape as part of a required…. They use the green running-man pictogram (ISO 7010), stay continuously lit, and electrically lit signs are built to CSA C22.2 No. 141. Exits serving only one dwelling unit or a house with a secondary suite are outside this Subsection OBC Div. B 9.9.11.1.OBC Div. B 9.9.11.1. Application(1) This Subsection applies to all exits except those serving not more than one dwelling unit or a house with a secondary suite..

Lighting item Normal lighting Emergency lighting
Average level at floor or tread 50 lx 10 lx
Minimum at any point 10 lx 1 lx
Power source Building supply Separate from the building supply
Duration Not stated At least 30 min, automatic

Sources: OBC Div. B 9.9.12.2.OBC Div. B 9.9.12.2. Required Lighting in Egress Facilities(1) Every exit, public corridor or corridor providing access to exit for the public shall be equipped to provide illumination to an average level of not less than 50 lx at floor or tread level and at all points such as angles and intersections at changes of level where there are stairs or ramps. (2) The minimum value… and OBC Div. B 9.9.12.3.OBC Div. B 9.9.12.3. Emergency Lighting(1) Emergency lighting shall be provided in (a) exits. (b) principal routes providing access to exit in an open floor area, (c) corridors used by the public, (d) underground walkways, and (e) public corridors. (2) Emergency lighting required in Sentence (1) shall be provided from a source of energy separate from the…. Emergency lighting goes in exits, principal routes to exits in open floor areas, corridors used by the public, underground walkways and public corridors. Incandescent lighting of 1 W/m² is deemed to give the 10 lx average.

Practice this topic

Penetrations, exhaust ducts and central vacuum

Part 9 sends tents, transformer vaults, elevators, sprinkler design (Articles 3.2.5.12. to 3.2.5.15. and 3.2.5.17.), standpipes and fire pumps to Part 3 OBC Div. B 9.10.1.3.OBC Div. B 9.10.1.3. Items Under Part 3 Jurisdiction(1) Tents, air-supported structures, transformer vaults, walkways, elevators and escalators shall conform to Part 3. (2) Where rooms or spaces are intended for an assembly occupancy, such rooms or spaces shall conform to Part 3. (3) Basements containing more than 1 storey or exceeding 600 m² in area shall conform to…, and commercial cooking ventilation to Article 6.3.1.6. OBC Div. B 9.10.1.4.OBC Div. B 9.10.1.4. Items Under Part 6 Jurisdiction(1) In kitchens containing commercial cooking equipment used in processes producing grease-laden vapours, the equipment shall be designed and installed in conformance with Article 6.3.1.6. (See Note A-9.10.1.4.(1)).

A penetration of a fire separation is sealed by a firestop with an F rating (CAN/ULC-S115) at least equal to the separation's rating, or is tightly fitted or cast in place where the item is steel, ferrous, copper, concrete or masonry. A firewall penetration needs an FT rating OBC Div. B 9.10.9.6.OBC Div. B 9.10.9.6. General Requirements for Penetrations of Fire Separations(1) Except as required by Sentence (2) and Articles 9.10.9.7. and 9.10.9.8. and as permitted by Article 9.10.9.9., penetrations of a required fire separation or a membrane forming part of an assembly required to be a fire separation shall be (a) sealed by a firestop that, when subjected to the fire test method in….

Service item Part 9 permission
Combustible raceway in a slab At least 50 mm of concrete below it
Sprinkler piping through a fire separation Only if both fire compartments are sprinklered
Sprinkler head through a membrane No firestop if a metal escutcheon plate per NFPA 13 covers the gap
Fire damper No separate firestop if installed per NFPA 80 or designed with one

Source: OBC Div. B 9.10.9.9.OBC Div. B 9.10.9.9. Penetrations by Raceways, Sprinklers and Fire Dampers(1) Combustible totally enclosed raceways that are embedded in a concrete floor slab are permitted in an assembly required to have a fire-resistance rating, provided the concrete cover between the raceway and the bottom of the slab is not less than 50 mm. (2) Totally enclosed raceways are permitted to penetrate a fire…. Outlet box rules are in OBC Div. B 9.10.9.8.OBC Div. B 9.10.9.8. Penetrations by Outlet Boxes or Service Equipment in Concealed Spaces(1) Except as provided in Sentences (2) to (5), outlet boxes are permitted to penetrate the membrane of an assembly required to have a fire-resistance rating, provided they are sealed at the penetration by a firestop that, when subjected to the fire test method in CAN/ULC-S115, "Standard Method of Fire Tests of….

An exhaust duct in a vertical service space serving more than one fire compartment needs a fan at or near the outlet to keep it under negative pressure, and individual compartments may not have fans blowing straight into it OBC Div. B 9.10.9.20.OBC Div. B 9.10.9.20. Exhaust Ducts Serving More Than One Fire Compartment(1) Where a vertical service space contains an exhaust duct that serves more than one fire compartment, the duct shall have a fan located at or near the exhaust outlet to ensure that the duct is under negative pressure. (2) Individual fire compartments referred to in Sentence (1) shall not have fans that exhaust…. A central vacuum system serves only one suite OBC Div. B 9.10.9.21.OBC Div. B 9.10.9.21. Central Vacuum Systems(1) Except as permitted by Sentence 9.10.18.7.(1), a central vacuum system shall serve not more than one suite., unless the building has a fire alarm system and the vacuum shuts down when the alarm activates OBC Div. B 9.10.18.7.OBC Div. B 9.10.18.7. Central Vacuum Systems(1) Central vacuum cleaning systems serving more than one suite or storey in a building equipped with a fire alarm system shall be designed to shut down upon activation of the fire alarm system..

Practice this topic

Service rooms, fuel-fired appliances and emergency power

Room Minimum fire separation
Service room, unsprinklered floor area 1 h (not needed for a room with a small amount of non-hazardous equipment)
Room with fuel-fired appliances 1 h
Incinerator room 2 h
Refuse or recycling storage room 1 h, or 45 min if sprinklered or the floor needs only 45 min
Emergency generator room 1 h, or 2 h where the floor must exceed 1 h

Sources: OBC Div. B 9.10.10.3.OBC Div. B 9.10.10.3. Separation of Service Rooms(1) Except as provided in Sentence (2) and Articles 9.10.10.5. and 9.10.10.6., service rooms shall be separated from the remainder of the building by a fire separation having a fire-resistance rating of not less than 1 h when the floor area containing the service room is not sprinklered. (2) Where a room contains a…, OBC Div. B 9.10.10.4.OBC Div. B 9.10.10.4. Locations of Fuel-Fired Appliances(1) Except as provided in Sentences (2) and (3) and Article 9.10.10.5., fuel-fired appliances shall be located in a service room separated from the remainder of the building by a fire separation having not less than a 1 h fire-resistance rating. (2) Except as required in the appliance installation standards referenced…, OBC Div. B 9.10.10.5.OBC Div. B 9.10.10.5. Incinerators(1) Service rooms containing incinerators shall be separated from the remainder of the building by a fire separation having a fire-resistance rating of not less than 2 h. (2) The design, construction, installation and alteration of each indoor incinerator shall conform to NFPA 82, "Standard on Incinerators and Waste…, OBC Div. B 9.10.10.6.OBC Div. B 9.10.10.6. Storage Rooms(1) Rooms for the temporary storage of combustible refuse and materials for recycling in all occupancies or for public storage in residential occupancies shall be separated from the remainder of the building by a fire separation having not less than a 1 h fire-resistance rating, except that a fire separation with a… and OBC Div. B 9.10.10.7.OBC Div. B 9.10.10.7. Emergency Power Installation(1) Where a generator intended to supply emergency power for lighting, fire safety and life safety systems is located in a building, it shall be located in a room that, (a) is separated from the remainder of the building by a fire separation with a fire-resistance rating not less than (i) 1 h, if the floor assembly is….

Fuel-fired heating, cooling and water heating appliances escape the separation if they serve one room or suite, or a building of not more than 400 m² building area and 2 storeys, or a house with a secondary suite with a 15.9 mm Type X gypsum smoke-tight barrier. Fireplaces and cooking appliances are exempt. A generator room holds only the generator and its related equipment.

Practice this topic

Closures, fire dampers and fire stop flaps

Openings in fire separations get closures from the Part 9 closure table, installed per NFPA 80 OBC Div. B 9.10.13.1.OBC Div. B 9.10.13.1. Closures(1) Except as provided in Article 9.10.13.2., openings in required fire separations shall be protected with a closure conforming to Table 9.10.13.1. and shall be installed in conformance with NFPA 80, "Standard for Fire Doors and Other Opening Protectives," unless otherwise specified in this Part. (See also Article…. Hold-open devices follow 3.1.8.14. OBC Div. B 9.10.13.11.OBC Div. B 9.10.13.11. Hold-Open Devices(1) Where hold-open devices are used on doors in required fire separations, they shall be installed in accordance with Article 3.1.8.14..

A duct through a rated fire separation needs a fire damper (3.1.8.4. and 3.1.8.10.) OBC Div. B 9.10.13.13.OBC Div. B 9.10.13.13. Fire Dampers(1) Except as permitted in Sentences (2) to (5), 9.10.5.1.(3) and 9.10.9.9.(5), a duct that penetrates an assembly required to be a fire separation with a fire-resistance rating shall be equipped with a fire damper in conformance with Articles 3.1.8.4. and 3.1.8.10. (2) A fire damper is not required where a…, except:

  • small noncombustible branch ducts (melting point at least 760°C, under 130 cm²) feeding air units that discharge no higher than 1.2 m above the floor,
  • noncombustible branch ducts carried at least 500 mm up inside an upward-flow exhaust riser under negative pressure,
  • noncombustible ducts exhausting directly outdoors at the top of a vertical service space,
  • ducts serving commercial cooking equipment.

Fire stop flaps in rated ceiling membranes conform to CAN/ULC-S112.2 and activate at about 30°C above the normal maximum duct temperature OBC Div. B 9.10.13.14.OBC Div. B 9.10.13.14. Fire Stop Flaps(1) Fire stop flaps in ceiling membranes required in Sentence 9.10.5.1.(3) shall (a) conform to CAN/ULC-S112.2, "Standard Method of Fire Test of Ceiling Firestop Flap Assemblies," and (b) activate at a temperature approximately 30°C above the normal maximum temperature that occurs in the ducts, whether the air duct…. Fire blocks pierced by pipes or ducts must keep their effectiveness OBC Div. B 9.10.16.4.OBC Div. B 9.10.16.4. Penetration of Fire Blocks(1) Where fire blocks are pierced by pipes, ducts or other elements, the effectiveness of the fire blocks shall be maintained around such elements..

Practice this topic

Fire alarm systems, smoke alarms and extinguishers

A fire alarm system is required in a building of more than 3 storeys (counting storeys below the first storey), where total occupant load exceeds 300, or where the Part 9 occupant load table is exceeded (for example more than 10 sleeping occupants in residential) OBC Div. B 9.10.18.2.OBC Div. B 9.10.18.2. Fire Alarm System Required(1) Reserved. (2) Except as provided in Sentence (5), a fire alarm system shall be installed (a) in every building that contains more than 3 storeys, including storeys below the first storey, (b) where the total occupant load exceeds 300, or (c) when the occupant load for any major occupancy in Table 9.10.18.2. is…. It is not needed in residential buildings where each exit or public corridor serves no more than 4 suites, or each suite has its own exterior exit. Design follows Subsection 3.2.4., minus the Articles listed in OBC Div. B 9.10.18.3.OBC Div. B 9.10.18.3. Design and Installation Requirements(1) Except as provided in Sentence (2), and as required by this Subsection, where fire alarm, fire detection and smoke detection devices and systems are installed, these devices and systems and their installation shall conform to Subsection 3.2.4., 3.2.7.8. and 3.2.7.10. (See Note A-9.10.18.3.(1)) (2) The following….

Smoke alarms (CAN/ULC-S531) go in each dwelling unit and each sleeping room not in a dwelling unit OBC Div. B 9.10.19.1.OBC Div. B 9.10.19.1. Required Smoke Alarms(1) Except as permitted by Article 9.10.19.8., smoke alarms conforming to CAN/ULC-S531, "Standard for Smoke Alarms," shall be installed in (a) each dwelling unit, (b) each sleeping room not within a dwelling unit, and (c) ancillary spaces and common spaces not in dwelling units in a house with a secondary suite. (2)…: one per storey, one in each sleeping room, one in the hallway outside the bedrooms OBC Div. B 9.10.19.3.OBC Div. B 9.10.19.3. Location of Smoke Alarms(1) Except as permitted in Article 9.10.19.8., within dwelling units, sufficient smoke alarms shall be installed so that (a) there is at least one smoke alarm installed on each storey, including basements, and (b) on any storey of a dwelling unit containing sleeping rooms, a smoke alarm is installed (i) in each…. They are hardwired with a battery good for 7 days then 4 minutes of alarm OBC Div. B 9.10.19.4.OBC Div. B 9.10.19.4. Power Supply(1) Except as provided in Sentences (2) and (3), smoke alarms described in Sentence 9.10.19.1.(1) and 9.10.19.3.(1.1) shall (a) be installed with permanent connections to an electrical circuit, (See Note A-3.2.4.20.(9) (a)) (b) have no disconnect switch between the overcurrent device and the smoke alarm, and (c) in…, interconnected within the unit OBC Div. B 9.10.19.5.OBC Div. B 9.10.19.5. Interconnection of Smoke Alarms(1) Where more than one smoke alarm is required in a dwelling unit, the smoke alarms shall be wired so that the activation of one alarm will cause all alarms within the dwelling unit to sound. (2) Smoke alarms in a house with a secondary suite shall be wirelessly interconnected or interconnected by hard-wiring so that…, and may be silenced for no more than 10 min OBC Div. B 9.10.19.6.OBC Div. B 9.10.19.6. Silencing of Smoke Alarms(1) Except as permitted in Sentence (2), a manually operated device shall be incorporated within the circuitry of a smoke alarm installed in a dwelling unit so that the signal emitted by the smoke alarm can be silenced for a period of not more than 10 min, after which the smoke alarm will reset and sound again if the….

Portable extinguishers follow the Fire Code, except inside dwelling units OBC Div. B 9.10.20.4.OBC Div. B 9.10.20.4. Portable Extinguishers(1) Portable extinguishers shall be installed in all buildings, except within dwelling units, in conformance with the provisions of the Fire Code made under the Fire Protection and Prevention Act, 1997.. Fire protection equipment in unheated areas is protected from freezing OBC Div. B 9.10.20.5.OBC Div. B 9.10.20.5. Freeze Protection for Fire Protection Systems(1) Equipment forming part of a fire protection system that may be adversely affected by freezing temperatures and that is located in an unheated area shall be protected from freezing.. Worker camps sleeping more than 30 need a hose station near an exit, fed by a central supply or a 4,500 L tank delivering 5 L/s at 300 kPa OBC Div. B 9.10.21.9.OBC Div. B 9.10.21.9. Hose Stations(1) Every building in a camp for housing of workers providing sleeping accommodation for more than 30 persons shall be provided with a hose station that is protected from freezing and equipped with a hose of sufficient length so that every portion of the building is within the range of a hose stream. (2) Hose stations…. Seasonal recreational dwellings still need smoke alarms OBC Div. B 9.37.2.4.OBC Div. B 9.37.2.4. Smoke Alarms(1) Every dwelling unit within the scope of this Section shall be provided with a smoke alarm in accordance with Subsection 9.10.19..

Practice this topic

Common traps

  • Leaving out the basement when counting storeys for the fire alarm trigger. Storeys below the first storey count.
  • Running sprinkler pipe through a separation into an unsprinklered compartment. Both sides must be sprinklered.
  • Applying the 400 m² appliance exemption to a 3-storey building. It needs both 400 m² or less and 2 storeys or less.
  • Giving an emergency generator room only 1 h when the floor assembly must exceed 1 h.
  • Confusing fire stop flaps (ceiling membranes) with fire dampers (fire separations).

Chapter review

Chapter at a glance

One line per section: the idea to carry into the exam. Then the answers that most often catch candidates out.

Usual exam traps

  • Leaving out the basement when counting storeys for the fire alarm trigger. Storeys below the first storey count.
  • Running sprinkler pipe through a separation into an unsprinklered compartment. Both sides must be sprinklered.
  • Applying the 400 m² appliance exemption to a 3-storey building. It needs both 400 m² or less and 2 storeys or less.
  • Giving an emergency generator room only 1 h when the floor assembly must exceed 1 h.
  • Confusing fire stop flaps (ceiling membranes) with fire dampers (fire separations).

Practice this chapter

Questions on Part 9 fire protection for services, in the exam format, every answer explained and cited to its article. Sign in to start; a free account gets the free questions.

Code cited in this chapter

Based on the official 2024 Building Code Compendium on ontario.ca.

© King's Printer for Ontario, 2024. Reproduced with permission.

  • OBC Div. B 9.7.3.3. Thermal Characteristics of Windows, Doors and Skylights

    (1)Metal frames and sash of windows, doors and skylights shall incorporate a thermal break.

    (2)Windows and doors described in Sentence (1) do not require a thermal break where they are installed as

    (a)vehicular access doors,

    (b)storm windows and doors, or

    (c)windows and doors that are required to have a fire-resistance rating.

    (3)Windows, doors and skylights with or without storm doors or sash that are installed in buildings where the intended use of the interior space will not result in high moisture generation shall have a maximum thermal transmittance (U-value) or minimum temperature index (I) in accordance with Table 9.7.3.3.

    (4)Windows, doors and skylights, with or without storm doors or sash that are installed in portions of buildings where the intended use of the interior space will result in high moisture generation shall be designed in conformance with Subsection 5.3. (See Note A-9.25.5.2.)

    Open OBC Div. B 9.7.3.3. in the code viewer
  • OBC Div. B 9.7.4.2. General

    (1)Manufactured and pre-assembled windows, doors and skylights and their installation shall conform to

    (a)AAMA/WDMA/CSA 101/I.S.2/A440, "North American Fenestration Standard/Specification for windows, doors, and skylights" (Harmonized Standard),

    (b)CSA A440S1, "Canadian Supplement to AAMA/WDMA/CSA 101/I.S.2/A440-17, North American Fenestration Standard/Specification for windows, doors, and skylights,"

    (c)the remainder of this Subsection, and

    (d)the applicable requirements in Subsection 9.7.6. (See Note A-9.7.4.2.(1))

    Open OBC Div. B 9.7.4.2. in the code viewer
  • OBC Div. B 9.7.4.3. Performance Requirements

    (1)Performance grades for windows, doors and skylights shall be selected according to CSA A440S1, "Canadian Supplement to AAMA/WDMA/CSA 101/I.S.2/A440-17, North American Fenestration Standard/Specification for windows, doors, and skylights" so as to be appropriate for the conditions and geographic location in which the window, door or skylight will be installed.

    (2)Windows, doors and skylights shall conform to the performance grades selected under Sentence (1) when tested in accordance with AAMA/WDMA/CSA 101/I.S.2/A440, "North American Fenestration Standard/Specification for windows, doors, and skylights" (Harmonized Standard).

    (3)The minimum level of performance required for windows, doors and skylights shall be that of the Performance Class R.

    (4)Exterior wood doors shall conform to CAN/CSA-O132.2 Series, "Wood Flush Doors," and shall have legibly indicated on them

    (a)the name of the manufacturer,

    (b)the standard to which they were produced, and

    (c)that they are of an exterior type.

    Open OBC Div. B 9.7.4.3. in the code viewer
  • OBC Div. B 9.7.5.1. Application and Compliance

    (1)Materials, design, construction and installation of windows, doors and skylights that separate conditioned space from unconditioned space or the exterior but that are not within the scope of AAMA/WDMA/CSA 101/I.S.2/A440, "North American Fenestration Standard/Specification for windows, doors, and skylights," shall conform

    (a)to

    (i)the remainder of this Subsection or Subsection 9.7.4., and

    (ii)the applicable requirements in Subsection 9.7.6., or

    (b)to Part 5.

    (2)Glass for site-built windows, doors, sidelights for doors, and skylights shall comply with Section 9.6.

    Open OBC Div. B 9.7.5.1. in the code viewer
  • OBC Div. B 9.9.1.3. Occupant Load

    (1)The occupant load of a floor area or part of a floor area shall be based on

    (a)two persons per sleeping room or sleeping area in a dwelling unit or suite, and

    (b)for occupancies other than as described in Clause (a), the number of persons

    (i)for which the area is designed, or

    (ii)determined from Table 3.1.17.1.

    Open OBC Div. B 9.9.1.3. in the code viewer
  • OBC Div. B 9.9.11.3. Exit Signs

    (1)Except as required in Sentence (7), every exit door shall have an exit sign placed over it or adjacent to it if the exit serves

    (a)a building that is 3 storeys in building height,

    (b)a building having an occupant load of more than 150, or

    (c)a room or floor area that has a fire escape as part of a required means of egress.

    (2)Except as required in Sentence (6), every exit sign shall

    (a)be visible on approach to the exit,

    (b)consist of a green pictogram and a white or lightly tinted graphical symbol meeting the colour specifications referred to in ISO 3864-1, "Graphical symbols – Safety colours and safety signs – Part 1: Design principles for safety signs and safety markings," and

    (c)conform to ISO 7010, "Graphical symbols – Safety colours and safety signs – Registered safety signs," for the following symbols: (See Note A-3.4.5.1.(2) (c))

    (i)E001 emergency exit left,

    (ii)E002 emergency exit right,

    (iii)E005 90-degree directional arrow, and

    (iv)E006 45-degree directional arrow.

    (3)Internally illuminated exit signs shall be continuously illuminated, and

    (a)where illumination of the sign is powered by an electrical circuit, be constructed in conformance with CSA C22.2 No. 141, "Emergency lighting equipment," or

    (b)where illumination of the sign is not powered by an electrical circuit, be

    (i)constructed in conformance with CAN/ULC-S572, "Standard for Photoluminescent and Self-Luminous Exit Signs and Path Marking Systems," and

    (ii)labelled in accordance with the time duration for which they have been tested and listed.

    (4)Externally illuminated exit signs shall be continuously illuminated at all times by a light fixture supplied by an electrical circuit.

    (5)The circuitry serving lighting for externally and internally illuminated exit signs shall

    (a)serve no equipment other than emergency lighting in the area where the exit signs are installed, and

    (b)be connected to an emergency power supply as described in Sentences 9.9.12.3.(2), (3) and (7).

    (6)An exit sign conforming to Clauses (2)(b) and (c) with an arrow or other indicator pointing at the direction of egress shall be provided where no exit is visible from

    (a)a public corridor,

    (b)a corridor used by the public, or

    (c)a principal route serving an open floor area having an occupant load of more than 150.

    (7)Except for suite doors opening directly to the exterior, every exit serving a hotel shall have an exit sign placed over it or adjacent to it.

    Open OBC Div. B 9.9.11.3. in the code viewer
  • OBC Div. B 9.9.11.1. Application

    (1)This Subsection applies to all exits except those serving not more than one dwelling unit or a house with a secondary suite.

    Open OBC Div. B 9.9.11.1. in the code viewer
  • OBC Div. B 9.9.12.2. Required Lighting in Egress Facilities

    (1)Every exit, public corridor or corridor providing access to exit for the public shall be equipped to provide illumination to an average level of not less than 50 lx at floor or tread level and at all points such as angles and intersections at changes of level where there are stairs or ramps.

    (2)The minimum value of the illumination required by Sentence (1) shall be not less than 10 lx.

    Open OBC Div. B 9.9.12.2. in the code viewer
Show all 38 articles
  • OBC Div. B 9.9.12.3. Emergency Lighting

    (1)Emergency lighting shall be provided in

    (a)exits.

    (b)principal routes providing access to exit in an open floor area,

    (c)corridors used by the public,

    (d)underground walkways, and

    (e)public corridors.

    (2)Emergency lighting required in Sentence (1) shall be provided from a source of energy separate from the electrical supply for the building.

    (3)Lighting required in Sentence (1) shall be designed to be automatically actuated for a period of at least 30 min when the electric lighting in the affected area is interrupted.

    (4)Illumination from lighting required in Sentence (1) shall be provided to average levels of not less than 10 lx at floor or tread level.

    (5)The minimum value of the illumination required by Sentence (4) shall be not less than 1 1x.

    (6)Where incandescent lighting is provided, lighting equal to 1 W/m² of floor area shall be considered to meet the requirement in Sentence (4).

    (7)Where self-contained emergency lighting units are used, they shall conform to CSA C22.2 No. 141, "Emergency lighting equipment."

    Open OBC Div. B 9.9.12.3. in the code viewer
  • OBC Div. B 9.10.1.3. Items Under Part 3 Jurisdiction

    (1)Tents, air-supported structures, transformer vaults, walkways, elevators and escalators shall conform to Part 3.

    (2)Where rooms or spaces are intended for an assembly occupancy, such rooms or spaces shall conform to Part 3.

    (3)Basements containing more than 1 storey or exceeding 600 m² in area shall conform to Part 3.

    (4)Where rooms or spaces are intended for the storage, manufacture or use of hazardous or explosive material, such rooms or spaces shall conform to Part 3.

    (5)Reserved.

    (6)Openings through floors that are not protected by shafts or closures shall be protected in conformance with Subsection 3.2.8. (See also Sentence 9.9.4.7.(1))

    (7)Chutes and shafts shall conform to Subsection 3.6.3. except where they are entirely contained within a dwelling unit.

    (8)Sprinkler systems shall be designed, constructed and installed in conformance with Articles 3.2.5.12. to 3.2.5.15. and 3.2.5.17. (See Note A-9.10.1.3.(8) and (9))

    (9)Standpipe and hose systems shall be designed, constructed and installed in conformance with Articles 3.2.5.8. to 3.2.5.11. and 3.2.5.17. (See Note A-9.10.1.3.(8) and (9))

    (10)Fire pumps shall be installed in conformance with Articles 3.2.5.17. and 3.2.5.18.

    (11)Where fuel-fired appliances are installed on a roof, such appliances shall be installed in conformance with Article 3.6.1.5.

    Open OBC Div. B 9.10.1.3. in the code viewer
  • OBC Div. B 9.10.1.4. Items Under Part 6 Jurisdiction

    (1)In kitchens containing commercial cooking equipment used in processes producing grease-laden vapours, the equipment shall be designed and installed in conformance with Article 6.3.1.6. (See Note A-9.10.1.4.(1))

    Open OBC Div. B 9.10.1.4. in the code viewer
  • OBC Div. B 9.10.9.6. General Requirements for Penetrations of Fire Separations

    (1)Except as required by Sentence (2) and Articles 9.10.9.7. and 9.10.9.8. and as permitted by Article 9.10.9.9., penetrations of a required fire separation or a membrane forming part of an assembly required to be a fire separation shall be

    (a)sealed by a firestop that, when subjected to the fire test method in CAN/ULC-S115, "Standard Method of Fire Tests of Firestop Systems," has an F rating not less than the required fire-resistance rating for the fire separation,

    (b)tightly fitted or cast in place, provided the penetrating item is made of steel, ferrous, copper, concrete or masonry, or

    (c)sealed to maintain the integrity of the fire separation. (See Note A-9.10.9.6.(1))

    (2)Penetrations of a firewall shall be sealed at the penetration by a firestop that, when subjected to the fire test method in "CAN/ULC-S115, "Standard Method of Fire Tests of Firestop Systems," has an FT rating not less than the fire-resistance rating for the fire separation.

    Open OBC Div. B 9.10.9.6. in the code viewer
  • OBC Div. B 9.10.9.9. Penetrations by Raceways, Sprinklers and Fire Dampers

    (1)Combustible totally enclosed raceways that are embedded in a concrete floor slab are permitted in an assembly required to have a fire-resistance rating, provided the concrete cover between the raceway and the bottom of the slab is not less than 50 mm.

    (2)Totally enclosed raceways are permitted to penetrate a fire separation, provided they are sealed at the penetration by a firestop conforming to Clause 9.10.9.6.(1)(a).

    (3)Sprinkler piping is permitted to penetrate a fire separation, provided the fire compartments on each side of the fire separation are sprinklered.

    (4)Sprinklers are permitted to penetrate a fire separation or a membrane forming part of an assembly required to have a fire-resistance rating without having to meet the firestop requirements of Article 9.10.9.6. and Clause 9.10.9.8.(6)(a), provided the annular space created by the penetration of a fire sprinkler is covered by a metal escutcheon plate in accordance with NFPA 13, "Standard for the Installation of Sprinkler Systems."

    (5)Fire dampers are permitted to penetrate a fire separation or a membrane forming part of an assembly required to have a fire-resistance rating without having to meet the firestop requirements of Sentence 9.10.9.6.(1), provided the fire damper is

    (a)installed in conformance with NFPA 80, "Standard for Fire Doors and Other Opening Protectives,"

    (b)specifically designed with a firestop, or

    (c)provided in conformance with Sentence 9.10.5.1.(3). (See also Note A-3.1.9.2.(1).)

    Open OBC Div. B 9.10.9.9. in the code viewer
  • OBC Div. B 9.10.9.8. Penetrations by Outlet Boxes or Service Equipment in Concealed Spaces

    (1)Except as provided in Sentences (2) to (5), outlet boxes are permitted to penetrate the membrane of an assembly required to have a fire-resistance rating, provided they are sealed at the penetration by a firestop that, when subjected to the fire test method in CAN/ULC-S115, "Standard Method of Fire Tests of Firestop Systems," has an FT rating not less than the fire-resistance rating of the fire separation. (See Note A-9.10.9.8.(1))

    (2)Except as provided in Sentence 9.10.9.6.(2), noncombustible outlet boxes that penetrate a fire separation or a membrane forming part of an assembly required to have a fire-resistance rating need not conform to Sentence (1), provided

    (a)they do not exceed

    (i)0.016 m² in area, and

    (ii)an aggregate area of 0.065 m² in any 9.3 m² of surface area, and

    (b)the annular space between the membrane and the noncombustible outlet boxes does not exceed 3 mm.

    (3)Except as provided in Sentence 9.10.9.6.(2), combustible outlet boxes that penetrate a fire separation or a membrane forming part of an assembly required to have a fire-resistance rating need not conform to Sentence (1), provided

    (a)the outlet boxes are

    (i)separated from the remainder of the space within the assembly by an enclosure of not more than 0.3 m² in area made of fire block material conforming to Article 9.10.16.3., or (See Note A-9.10.9.8.(3) (a)(i))

    (ii)located in a space within the assembly that is filled with preformed fibre insulation processed from rock or slag conforming to CAN/ULC-S702.1, "Standard for Mineral Fibre Thermal Insulation for Buildings, Part 1: Material Specification," and having a mass per unit area of not less than 1.22 kg/m² of wall surface such that the exposed sides and back of the outlet box are encapsulated by the noncombustible insulation, and

    (b)the outlet boxes do not exceed an aggregate area of 0.016 m² in any individual enclosure as described in Subclause (a)(i) or any individual insulated space as described in Subclause (a)(ii).

    (4)Noncombustible outlet boxes conforming to Sentence (2) are permitted to be located on opposite sides of a vertical fire separation having a fire-resistance rating and need not conform to Sentence (1), provided they are

    (a)separated from each other by a horizontal distance of not less than 600 mm,

    (b)separated from each other and the remainder of the wall space by an enclosure conforming to Subclause (3)(a)(i), or

    (c)located in an insulated wall space in accordance with Subclause (3)(a)(ii).

    (5)Combustible outlet boxes conforming to Sentence (3) are permitted to be located on opposite sides of a vertical fire separation having a fire-resistance rating and need not conform to Sentence (1).

    (6)Service equipment is permitted to penetrate a horizontal fire separation conforming to Sentence 9.10.9.12.(2), provided the penetration is sealed by

    (a)a firestop that, when subjected to the fire test method in CAN/ULC-S115, "Standard Method of Fire Tests of Firestop Systems," has an FT rating not less than the required fire-resistance rating for the fire separation,

    (b)a firestop conforming to Clause 9.10.9.6.(1)(a), where the service equipment is located entirely within the cavity of a wall assembly above and below the horizontal fire separation having a required fire-resistance rating, or

    (c)a firestop conforming to Clause 9.10.9.6.(1)(a), where the penetration is

    (i)contained within the concealed space of a floor or ceiling assembly having a fire-resistance rating,

    (ii)located above a ceiling membrane providing a horizontal fire separation, or

    (iii)contained within a horizontal service space conforming to Sentence 9.10.9.12.(2) that is directly above or below a floor or ceiling.

    Open OBC Div. B 9.10.9.8. in the code viewer
  • OBC Div. B 9.10.9.20. Exhaust Ducts Serving More Than One Fire Compartment

    (1)Where a vertical service space contains an exhaust duct that serves more than one fire compartment, the duct shall have a fan located at or near the exhaust outlet to ensure that the duct is under negative pressure.

    (2)Individual fire compartments referred to in Sentence (1) shall not have fans that exhaust directly into the duct in the vertical service space.

    Open OBC Div. B 9.10.9.20. in the code viewer
  • OBC Div. B 9.10.9.21. Central Vacuum Systems

    (1)Except as permitted by Sentence 9.10.18.7.(1), a central vacuum system shall serve not more than one suite.

    Open OBC Div. B 9.10.9.21. in the code viewer
  • OBC Div. B 9.10.18.7. Central Vacuum Systems

    (1)Central vacuum cleaning systems serving more than one suite or storey in a building equipped with a fire alarm system shall be designed to shut down upon activation of the fire alarm system.

    Open OBC Div. B 9.10.18.7. in the code viewer
  • OBC Div. B 9.10.10.3. Separation of Service Rooms

    (1)Except as provided in Sentence (2) and Articles 9.10.10.5. and 9.10.10.6., service rooms shall be separated from the remainder of the building by a fire separation having a fire-resistance rating of not less than 1 h when the floor area containing the service room is not sprinklered.

    (2)Where a room contains a limited quantity of service equipment and the service equipment does not constitute a fire hazard, the requirements in Sentence (1) shall not apply.

    Open OBC Div. B 9.10.10.3. in the code viewer
  • OBC Div. B 9.10.10.4. Locations of Fuel-Fired Appliances

    (1)Except as provided in Sentences (2) and (3) and Article 9.10.10.5., fuel-fired appliances shall be located in a service room separated from the remainder of the building by a fire separation having not less than a 1 h fire-resistance rating.

    (2)Except as required in the appliance installation standards referenced in Sentences 6.2.1.5.(1) and 9.10.10.5.(1), fuel-fired space-heating appliances, space-cooling appliances and service water heaters need not be separated from the remainder of the building as required in Sentence (1),

    (a)where the appliances serve

    (i)not more than one room or suite, or

    (ii)a building with a building area of not more than 400 m² and a building height of not more than 2 storeys, or

    (b)where the appliances

    (i)serve a house with a secondary suite including their common spaces, and

    (ii)are located in a service room where both sides of any wall assemblies and the underside of any floor-ceiling framing separating this room from both dwelling units or their common spaces are protected by a continuous smoke-tight barrier consisting of not less than 15.9 mm thick Type X gypsum board.

    (3)Sentence (1) does not apply to fireplaces and cooking appliances.

    Open OBC Div. B 9.10.10.4. in the code viewer
  • OBC Div. B 9.10.10.5. Incinerators

    (1)Service rooms containing incinerators shall be separated from the remainder of the building by a fire separation having a fire-resistance rating of not less than 2 h.

    (2)The design, construction, installation and alteration of each indoor incinerator shall conform to NFPA 82, "Standard on Incinerators and Waste and Linen Handling Systems and Equipment."

    (3)Every incinerator shall be connected to a chimney flue conforming to the requirements in Section 9.21. and serving no other appliance.

    (4)An incinerator shall not be located in a room with other fuel-fired appliances.

    Open OBC Div. B 9.10.10.5. in the code viewer
  • OBC Div. B 9.10.10.6. Storage Rooms

    (1)Rooms for the temporary storage of combustible refuse and materials for recycling in all occupancies or for public storage in residential occupancies shall be separated from the remainder of the building by a fire separation having not less than a 1 h fire-resistance rating, except that a fire separation with a fire-resistance rating of not less than 45 min is permitted where

    (a)the fire-resistance rating of the floor assembly is not required to exceed 45 min, or

    (b)the room is sprinklered.

    Open OBC Div. B 9.10.10.6. in the code viewer
  • OBC Div. B 9.10.10.7. Emergency Power Installation

    (1)Where a generator intended to supply emergency power for lighting, fire safety and life safety systems is located in a building, it shall be located in a room that,

    (a)is separated from the remainder of the building by a fire separation with a fire-resistance rating not less than

    (i)1 h, if the floor assembly is not required to have a fire-resistance rating of more than 1 h, and

    (ii)2 h, if the floor assembly is required to have a fire-resistance rating of more than 1 h, and

    (b)contains only the generating set and equipment that is related to the emergency power supply system.

    Open OBC Div. B 9.10.10.7. in the code viewer
  • OBC Div. B 9.10.13.1. Closures

    (1)Except as provided in Article 9.10.13.2., openings in required fire separations shall be protected with a closure conforming to Table 9.10.13.1. and shall be installed in conformance with NFPA 80, "Standard for Fire Doors and Other Opening Protectives," unless otherwise specified in this Part. (See also Article 9.10.3.1.)

    Open OBC Div. B 9.10.13.1. in the code viewer
  • OBC Div. B 9.10.13.11. Hold-Open Devices

    (1)Where hold-open devices are used on doors in required fire separations, they shall be installed in accordance with Article 3.1.8.14.

    Open OBC Div. B 9.10.13.11. in the code viewer
  • OBC Div. B 9.10.13.13. Fire Dampers

    (1)Except as permitted in Sentences (2) to (5), 9.10.5.1.(3) and 9.10.9.9.(5), a duct that penetrates an assembly required to be a fire separation with a fire-resistance rating shall be equipped with a fire damper in conformance with Articles 3.1.8.4. and 3.1.8.10.

    (2)A fire damper is not required where a noncombustible branch duct pierces a required fire separation provided the duct

    (a)has a melting point not below 760°C,

    (b)has a cross-sectional area less than 130 cm², and

    (c)supplies only air-conditioning units or combined air-conditioning and heating units discharging air at not more than 1.2 m above the floor.

    (3)A fire damper is not required where a noncombustible branch duct pierces a required fire separation around an exhaust duct riser in which the air flow is upward provided

    (a)the melting point of the branch duct is not below 760°C,

    (b)the branch duct is carried up inside the riser at least 500 mm, and

    (c)the exhaust duct is under negative pressure as described in Article 9.10.9.20.

    (4)Noncombustible ducts that penetrate a fire separation separating a vertical service space from the remainder of the building need not be equipped with a fire damper at the fire separation provided

    (a)the ducts have a melting point above 760°C, and

    (b)each individual duct exhausts directly to the outside at the top of the vertical service space.

    (5)A duct serving commercial cooking equipment and piercing a required fire separation need not be equipped with a fire damper at the fire separation.

    Open OBC Div. B 9.10.13.13. in the code viewer
  • OBC Div. B 9.10.13.14. Fire Stop Flaps

    (1)Fire stop flaps in ceiling membranes required in Sentence 9.10.5.1.(3) shall

    (a)conform to CAN/ULC-S112.2, "Standard Method of Fire Test of Ceiling Firestop Flap Assemblies," and

    (b)activate at a temperature approximately 30°C above the normal maximum temperature that occurs in the ducts, whether the air duct system is operating or shut down.

    Open OBC Div. B 9.10.13.14. in the code viewer
  • OBC Div. B 9.10.16.4. Penetration of Fire Blocks

    (1)Where fire blocks are pierced by pipes, ducts or other elements, the effectiveness of the fire blocks shall be maintained around such elements.

    Open OBC Div. B 9.10.16.4. in the code viewer
  • OBC Div. B 9.10.18.2. Fire Alarm System Required

    (1)Reserved.

    (2)Except as provided in Sentence (5), a fire alarm system shall be installed

    (a)in every building that contains more than 3 storeys, including storeys below the first storey,

    (b)where the total occupant load exceeds 300, or

    (c)when the occupant load for any major occupancy in Table 9.10.18.2. is exceeded.

    (3)Reserved.

    (4)Reserved.

    (5)A fire alarm system is not required in a residential occupancy where an exit or public corridor serves not more than 4 suites or where each suite has direct access to an exterior exit facility leading to ground level.

    Open OBC Div. B 9.10.18.2. in the code viewer
  • OBC Div. B 9.10.18.3. Design and Installation Requirements

    (1)Except as provided in Sentence (2), and as required by this Subsection, where fire alarm, fire detection and smoke detection devices and systems are installed, these devices and systems and their installation shall conform to Subsection 3.2.4., 3.2.7.8. and 3.2.7.10. (See Note A-9.10.18.3.(1))

    (2)The following Articles in Subsection 3.2.4. regarding fire alarm systems do not apply to Part 9 buildings: Articles 3.2.4.1., 3.2.4.10., 3.2.4.11., 3.2.4.12., 3.2.4.20. and 3.2.4.22.

    Open OBC Div. B 9.10.18.3. in the code viewer
  • OBC Div. B 9.10.19.1. Required Smoke Alarms

    (1)Except as permitted by Article 9.10.19.8., smoke alarms conforming to CAN/ULC-S531, "Standard for Smoke Alarms," shall be installed in

    (a)each dwelling unit,

    (b)each sleeping room not within a dwelling unit, and

    (c)ancillary spaces and common spaces not in dwelling units in a house with a secondary suite.

    (2)Smoke alarms required in Sentence (1) shall have a visual signalling component conforming to the requirements in 18.5.3. (Light, Color and Pulse Characteristics) of NFPA 72, "National Fire Alarm and Signaling Code."

    (3)The visual signalling component required in Sentence (2) need not

    (a)be integrated with the smoke alarm provided it is interconnected to it,

    (b)be on battery backup, or

    (c)have synchronized flash rates, when installed in a house with a secondary suite or an individual dwelling unit.

    (4)The luminous intensity for visual signalling components required in Sentence (2) that are installed in sleeping rooms shall be a minimum of 175 cd.

    Open OBC Div. B 9.10.19.1. in the code viewer
  • OBC Div. B 9.10.19.3. Location of Smoke Alarms

    (1)Except as permitted in Article 9.10.19.8., within dwelling units, sufficient smoke alarms shall be installed so that

    (a)there is at least one smoke alarm installed on each storey, including basements, and

    (b)on any storey of a dwelling unit containing sleeping rooms, a smoke alarm is installed

    (i)in each sleeping room, and

    (ii)in a location between the sleeping rooms and the remainder of the storey, and if the sleeping rooms are served by a hallway, the smoke alarm shall be located in the hallway. (See Note A-9.10.19.3.(1))

    (1.1)Except as permitted in Article 9.10.19.8., within a house with a secondary suite that contains an interior shared means of egress or common area, a smoke alarm shall be installed in each shared means of egress and common area.

    (2)A smoke alarm required in Sentences (1) and (1.1) shall be installed in conformance with CAN/ULC-S553, "Standard for Installation of Smoke Alarms."

    (3)Smoke alarms required in Article 9.10.19.1. and Sentences (1) and (1.1) shall be installed on or near the ceiling.

    (4)A smoke alarm required in Sentences (1) and (1.1) shall have a visual signalling component conforming to the requirements in 18.5.3. (Light, Color and Pulse Characteristics) of NFPA 72, "National Fire Alarm and Signaling Code."

    (5)The visual signalling component required in Sentence (4) need not

    (a)be integrated with the smoke alarm provided it is interconnected to it,

    (b)be on battery backup, or

    (c)have synchronized flash rates, when installed in a house with a secondary suite or an individual dwelling unit.

    (6)The luminous intensity for visual signalling components required in Sentence (4) that are installed in sleeping rooms shall be a minimum of 175 cd.

    Open OBC Div. B 9.10.19.3. in the code viewer
  • OBC Div. B 9.10.19.4. Power Supply

    (1)Except as provided in Sentences (2) and (3), smoke alarms described in Sentence 9.10.19.1.(1) and 9.10.19.3.(1.1) shall

    (a)be installed with permanent connections to an electrical circuit, (See Note A-3.2.4.20.(9) (a))

    (b)have no disconnect switch between the overcurrent device and the smoke alarm, and

    (c)in case the regular power supply to the smoke alarm is interrupted, be provided with a battery as an alternative power source that can continue to provide power to the smoke alarm for a period of not less than 7 days in the normal condition, followed by 4 minutes of alarm.

    (2)Where the building is not supplied with electrical power, smoke alarms are permitted to be battery-operated.

    (3)Suites of residential occupancy are permitted to be equipped with smoke detectors in lieu of smoke alarms, provided the smoke detectors

    (a)are capable of independently sounding audible signals with a sound pressure level between 75 dBA and 110 dBA within the individual suites, (See also Note A-3.2.4.18.(4))

    (b)except as permitted in Sentence (4), are installed in conformance with CAN/ULC-S524, "Standard for Installation of Fire Alarm Systems," and

    (c)form part of the fire alarm system. (See Note A-9.10.19.5.(2))

    (4)Smoke detectors permitted to be installed in lieu of smoke alarms as stated in Sentence (3) are permitted to sound localized alarms within individual suites, and need not sound an alarm throughout the rest of the building.

    Open OBC Div. B 9.10.19.4. in the code viewer
  • OBC Div. B 9.10.19.5. Interconnection of Smoke Alarms

    (1)Where more than one smoke alarm is required in a dwelling unit, the smoke alarms shall be wired so that the activation of one alarm will cause all alarms within the dwelling unit to sound.

    (2)Smoke alarms in a house with a secondary suite shall be wirelessly interconnected or interconnected by hard-wiring so that the activation of any one smoke alarm causes all smoke alarms within the house with a secondary suite to sound. (See Note A-9.10.19.5.(2))

    Open OBC Div. B 9.10.19.5. in the code viewer
  • OBC Div. B 9.10.19.6. Silencing of Smoke Alarms

    (1)Except as permitted in Sentence (2), a manually operated device shall be incorporated within the circuitry of a smoke alarm installed in a dwelling unit so that the signal emitted by the smoke alarm can be silenced for a period of not more than 10 min, after which the smoke alarm will reset and sound again if the level of smoke in the vicinity is sufficient to reactuate it.

    (2)Suites of residential occupancy equipped with smoke detectors installed to CAN/ULC-S524, "Standard for Installation of Fire Alarm Systems," which are part of the fire alarm system in lieu of smoke alarms as permitted in Sentence 9.10.19.4.(3), need not incorporate the manually operated device required in Sentence (1).

    Open OBC Div. B 9.10.19.6. in the code viewer
  • OBC Div. B 9.10.20.4. Portable Extinguishers

    (1)Portable extinguishers shall be installed in all buildings, except within dwelling units, in conformance with the provisions of the Fire Code made under the Fire Protection and Prevention Act, 1997.

    Open OBC Div. B 9.10.20.4. in the code viewer
  • OBC Div. B 9.10.20.5. Freeze Protection for Fire Protection Systems

    (1)Equipment forming part of a fire protection system that may be adversely affected by freezing temperatures and that is located in an unheated area shall be protected from freezing.

    Open OBC Div. B 9.10.20.5. in the code viewer
  • OBC Div. B 9.10.21.9. Hose Stations

    (1)Every building in a camp for housing of workers providing sleeping accommodation for more than 30 persons shall be provided with a hose station that is protected from freezing and equipped with a hose of sufficient length so that every portion of the building is within the range of a hose stream.

    (2)Hose stations required in Sentence (1) shall be located near an exit.

    (3)Hoses referred to in Sentence (1) shall be not less than 19 mm inside diam and shall be connected to a central water supply or to a storage tank having a capacity of not less than 4,500 L with a pumping system capable of supplying a flow of not less than 5 L/s at a gauge pressure of 300 kPa.

    Open OBC Div. B 9.10.21.9. in the code viewer
  • OBC Div. B 9.37.2.4. Smoke Alarms

    (1)Every dwelling unit within the scope of this Section shall be provided with a smoke alarm in accordance with Subsection 9.10.19.

    Open OBC Div. B 9.37.2.4. in the code viewer