Values this chapter turns on
- energy savings over baseline, buildings in general
- 13%
- energy savings over baseline, buildings in general
- energy savings over baseline, Part 9 housing
- 15%
- energy savings over baseline, Part 9 housing
- min motion sensor timer in a public corridor
- 15 min
- min motion sensor timer in a public corridor
- insulated length of hot water tank outlet pipe
- 2.5 m
- insulated length of hot water tank outlet pipe
The last Building Services section mixes three things: the Part 12 energy and water rules (with the two Supplementary Standards SB-10 and SB-12), the Part 11 compliance alternatives used when renovating, and a short list of Division C administration items. Expect "which path applies" and "who must review" questions. The energy questions rarely ask for a full envelope design; they ask which Standard or which percentage the code points you to.
Energy efficiency design for Part 3 buildings (SB-10)
Article 12.2.1.2. gives every building two routes OBC Div. B 12.2.1.2.OBC Div. B 12.2.1.2. Energy Efficiency Design(1) Reserved. (2) Except as provided in Sentence (3) and Sentence (4), the energy efficiency of all buildings shall (a) be designed to exceed by not less than 13% the energy efficiency levels required by Sentence 12.2.1.1.(2) of O. Reg. 332/12 (Building Code) as it read on December 31, 2024, or (b) conform to Division…:
| Building | Route 1 (performance) | Route 2 (prescribed standard) |
|---|---|---|
| All buildings except Part 9 housing | Beat the 2024 baseline (O. Reg. 332/12 as it read on December 31, 2024) by at least 13% | SB-10, Division 1 and Division 3 or 5 |
| Part 9 residential, occupied all winter | Beat the same baseline by at least 15% | SB-12, Chapters 1 and 3 |
Farm buildings, buildings using no electrical power or fossil fuel, and seasonal recreational buildings under Sections 9.37 or 9.39 are exempt.
Two more SB-10 requirements apply to all buildings except Part 9 housing, farm buildings, fuel-free buildings and seasonal recreational buildings: the CO₂e emission limits OBC Div. B 12.2.2.1.OBC Div. B 12.2.2.1. Carbon Dioxide Equivalents(1) Except as provided in Sentence (2), all buildings shall be designed to conform to the CO₂e emission requirements set out in MMA Supplementary Standard SB-10, “Energy Efficiency Requirements.” (2) This Article does not apply to (a) a building or part of a building of residential occupancy that is within the scope… and the peak electric demand limits OBC Div. B 12.2.3.1.OBC Div. B 12.2.3.1. Peak Electric Demand(1) Except as provided in Sentence (2), all buildings shall be designed to conform to the peak electric demand requirements set out in MMA Supplementary Standard SB-10, “Energy Efficiency Requirements.” (2) This Article does not apply to (a) a building or part of a building of residential occupancy that is within the….
Inside SB-10, Division 3 is the default path, and it offers three equal options: ASHRAE 90.1-2013 with SB-10 Chapter 2, the 2015 NECB with Chapter 3, or Section 7 of ASHRAE 189.1-2014 SB-10 Div. 3, 1.1.2.1.OBC SB-10 1.1.2.1. Energy Efficiency Design(1) Except as provided in Sentence (2) and Article 1.2.1.1., the energy efficiency of all buildings shall be designed to achieve the energy efficiency levels attained by conforming to (a) 2013 ANSI/ASHRAE/IES 90.1 and Chapter 2, (b) 2015 NECB and Chapter 3, or (c) Section 7 "Energy Efficiency" of 2014…. Division 5 is a simpler path for small buildings, allowed only where the building is within Part 9, has no residential occupancy, does not use electric space heating, and is occupied through the winter SB-10 Div. 1, 1.1.1.3.OBC SB-10 1.1.1.3. Energy Efficiency Design(1) Except as permitted in Sentence (2), the energy efficiency design and construction of buildings required to comply with Sentence 12.2.1.2.(2) of Division B of the Building Code shall comply with Division 3 of this Supplementary Standard. (2) The energy efficiency of a building or part of a building may conform to….
Lighting controls are in Part 12 itself OBC Div. B 12.2.4.1.OBC Div. B 12.2.4.1. Motion Sensors(1) Lighting installed to provide the minimum illumination levels required by this Code may be controlled by motion sensors except where the lighting (a) is installed in an exit, (b) is installed in a corridor serving patients or residents in a Group B, Division 2 or Division 3 occupancy, or (c) is required to conform…. Motion sensors may control code-minimum lighting except in exits, in corridors serving patients or residents in Group B, Division 2 or 3, and where 3.2.7.1.(10) applies. In a public corridor or public access to exit they need fail-safe switching and timers of at least 15 minutes. Emergency lighting can never be on a motion sensor.
Energy efficiency for houses (SB-12) and water efficiency
Section 12.3 applies to Part 9 residential buildings occupied through the winter OBC Div. B 12.3.1.1.OBC Div. B 12.3.1.1. Application(1) This Section applies to the energy efficiency of a building or part of a building of residential occupancy that is within the scope of Part 9 and is intended for occupancy on a continuing basis during the winter months.. The house items that show up on a services exam:
| Item | Requirement (paraphrased) | Article |
|---|---|---|
| Thermostat | Programmable, at least 4 periods a day and 2 day-types a week, manual override, settable to 13°C or lower (heating) and 29°C or higher (cooling) | 12.3.1.3. |
| Thermostat exceptions | Solid-fuel or ground source heat pump heat; manual control allowed for systems of 2 kW or less or a single room | 12.3.1.3. |
| Hot water outlet pipe | First 2.5 m insulated to RSI 0.62 (non-recirculating) | 12.3.1.4. |
| Heat traps | On inlet and outlet of a vertically connected tank, unless integral or recirculating | 12.3.1.4. |
| Furnace motor | Brushless direct current motor | 12.3.1.5. |
| Kitchen and laundry energy | Electrical outlet, natural gas line or propane line | 12.3.1.6. |
Sources: OBC Div. B 12.3.1.3.OBC Div. B 12.3.1.3. Temperature Control in Houses and Dwelling Units(1) Except as provided in Sentence (3) and except where space heating energy is provided by a solid fuel-burning appliance or a ground source heat pump, (a) heating system in an individual dwelling unit shall be controlled by at least one programmable thermostatic control device located in the dwelling unit, and (b)…, OBC Div. B 12.3.1.4.OBC Div. B 12.3.1.4. Hot Water Piping Insulation(1) Hot water pipes that are vertically connected to a hot water storage tank shall have heat traps on both inlet and outlet piping as close as practical to the tank, except where the tank (a) has an integral heat trap, or (b) serves a recirculating system. (2) The first 2.5 m of hot water outlet piping of a hot water…, OBC Div. B 12.3.1.5.OBC Div. B 12.3.1.5. Residential Furnaces(1) A furnace serving an individual dwelling unit in a house shall be equipped with a brushless direct current motor. (See Note A-12.3.1.5.(1)), OBC Div. B 12.3.1.6.OBC Div. B 12.3.1.6. Energy Supply for Kitchen and Laundry Facilities(1) In order to supply energy to cooking appliances and clothes dryers, every kitchen and laundry space shall be provided with (a) an electrical outlet, (b) a natural gas line, or (c) a propane line..
SB-12 offers three compliance options: a prescriptive package from Subsection 3.1.1., performance compliance under 3.1.2., or other acceptable methods under 3.1.3. SB-12 1.1.1.3.OBC SB-12 1.1.1.3. Compliance Options(1) The energy efficiency of a building or part of a building of residential occupancy that is within the scope of Part 9 of Division B of the Building Code and is intended for occupancy on a continuing basis during the winter months shall comply with (a) Subsection 3.1.1. (Prescriptive Compliance Packages) of Chapter…. The prescriptive packages split Ontario into Zone 1 (less than 5000 heating degree-days) and Zone 2 (5000 or more) SB-12 3.1.1.1.OBC SB-12 3.1.1.1. Energy Efficiency(1) Except as provided in Articles 3.1.1.4. to 3.1.1.11., the building shall conform to (a) Article 3.1.1.2. if the building is located in Zone 1 with less than 5000 heating degree days, or (b) Article 3.1.1.3. if the building is located in Zone 2 with 5000 or more heating degree days. (2) Except as required in…. Under the performance path, the proposed house's simulated annual energy use must not exceed the reference house built to a package, and envelope performance may drop no more than 25% SB-12 3.1.2.1.OBC SB-12 3.1.2.1. Required Performance Level(1) The performance level shall be measured based on the simulated annual energy use of the building. (2) For the purpose of this Subsection, reference building means a building that is identical to the proposed building, except that it is designed to meet the requirements and performance level of an applicable….
Water efficiency. Part 12 sends every building to Subsection 7.6.4. OBC Div. B 12.4.1.1.OBC Div. B 12.4.1.1. Plumbing Systems(1) All buildings shall conform to the water efficiency requirements of Subsection 7.6.4.. For services, the notable items are automatic shut-off on public lavatories, and shut-off on each head where several public shower heads share one temperature control OBC Div. B 7.6.4.1.OBC Div. B 7.6.4.1. Water Supply Fittings(1) Each lavatory in a washroom with fixtures for public use shall be equipped with a device capable of automatically shutting off the flow of water when the lavatory is not in use. (See Note A-7.6.4.1.(1) and (3)) (2) An automatic compensating valve serving an individual shower head shall have a manufacturer's….
Renovation compliance alternatives (Section 11.5)
The Section 11.5 tables (one per occupancy group: A, B, C, D/E and F) list substitutes for current requirements in existing buildings OBC Div. B 11.5.1.1.OBC Div. B 11.5.1.1. Compliance Alternatives(1) A compliance alternative shown in Table 11.5.1.1.-A, 11.5.1.1.-B, 11.5.1.1.-C, 11.5.1.1.-D/E or 11.5.1.1.-F may be substituted for a requirement contained in Part 3, 4, 6 or 8 where the chief building official is satisfied that compliance with the requirement is impracticable because, (a) of structural or…. The key rule is who must agree:
- For a Part 3, 4, 6 or 8 requirement, the chief building official must be satisfied that compliance is impracticable, because of structural or construction difficulties or harm to a heritage building.
- For a Part 9 or 12 requirement, the alternative may be used without that finding.
Service-related examples in the residential table: fire dampers or fire stop flaps need not be added to existing ducts at existing fire separations (except in hotels); an existing fire alarm system may remain, and Article 3.2.4.5. does not apply where the fire safety plan covers the intent of 3.2.4.; existing non-NFPA 13 sprinkler systems may be extended if operational, adequate and evaluated by a qualified designer; carbon monoxide alarms may be battery operated or plug-in OBC Div. B Table 11.5.1.1.-COBC Div. B Table 11.5.1.1-C. Compliance Alternatives for Residential Occupancies — Forming Part of Article 11.5.1.1.Table 11.5.1.1.-C Compliance Alternatives for Residential Occupancies — Forming Part of Article 11.5.1.1. C.A. Number | Division B Requirements | Compliance Alternative C1 | 3.1.4.7. | Existing heavy timber construction acceptable where construction is within 90% of member sizes listed in Part 3. C2 | 3.1.5.2. to….
General review, permits and occupancy
General review. Table 1.2.2.1. of Division C decides when an architect, a professional engineer, or both must do the general review during construction OBC Div. C 1.2.2.1.OBC Div. C 1.2.2.1. General Review by Architect or Professional Engineer(1) The construction, including, for greater certainty, enlargement or alteration, of every building or part of it described in Table 1.2.2.1. shall be reviewed by an architect or a professional engineer or a combination of both as set out in Column 3 of the Table. (2) A person who intends to construct or have…. Every assembly, care, care and treatment, detention and retirement home building needs both. Business, mercantile and mixed residential buildings need both once they exceed 600 m² gross area or 3 storeys. The owner retains them, and their written reports go to the chief building official or registered code agency. Specific items always need an engineer, including a sprinkler-protected glazed wall assembly under 3.1.8.20. and a shelf and rack storage system under Section 3.16. OBC Div. C Table 1.2.2.1.OBC Div. C Table 1.2.2.1. General Review — Forming Part of Sentence 1.2.2.1.(1)Table 1.2.2.1. General Review — Forming Part of Sentence 1.2.2.1.(1) Forming Part of Sentence 1.2.2.1.(1) Building Classification by Major Occupancy[5] | Building Description | General Review by: Assembly occupancy only | Every building | Architect and professional engineer[1] Assembly occupancy and any other major….
Permits. Permit exemptions include demolishing a farm building on a farm, a Class 1 sewage system, a tent group of 60 m² or less (not attached and more than 3 m from other structures) and a shed of 15 m² or less with no plumbing OBC Div. C 1.3.1.1.OBC Div. C 1.3.1.1. Requirement for Permits(1) A person is exempt from the requirement to obtain a permit under section 8 of the Act, (a) for the demolition of a farm building located on a farm, (b) subject to Sentence (2), for the construction or demolition of a building in territory without municipal organization, or (c) for the construction of a Class 1….
Occupancy before completion. For a building not fully complete, the chief building official issues an occupancy permit only once a list of items is done, including standpipe, sprinkler and fire alarm systems operational for the storeys to be occupied (with pumper connections), corridor, stair and exit lighting operational, and service rooms' fire separations and closures completed OBC Div. C 1.3.3.1.OBC Div. C 1.3.3.1. Occupancy Permit — General(1) Except as permitted in Sentence 1.3.3.2.(1), a person may occupy or permit to be occupied any building or part of it that has not been fully completed at the date of occupation where the chief building official or a person designated by the chief building official has issued a permit authorizing occupation of the….
Alternative solutions and rulings
A designer proposing an alternative solution must document the applicable objectives, functional statements and acceptable solutions, and show by past performance, tests or other evaluation that it achieves the required level of performance OBC Div. C 2.1.1.1.OBC Div. C 2.1.1.1. Documentation(1) The person proposing the use of an alternative solution shall provide documentation to the chief building official or registered code agency that, (a) identifies applicable objectives, functional statements and acceptable solutions, and (b) establishes on the basis of past performance, tests described in Article…. The documentation includes assumptions, limits, test procedures and any commissioning, operation and maintenance needs. Where no published test exists, tests must simulate or exceed service conditions or compare against a known acceptable product OBC Div. C 2.1.1.2.OBC Div. C 2.1.1.2. Tests(1) Where no published test method to establish the suitability of an alternative solution proposed under Article 2.1.1.1. exists, then the tests used for the purposes of that Article shall be designed to simulate or exceed anticipated service conditions or shall be designed to compare the performance of the material….
A Minister's ruling approving an alternative material, system or design may only be consistent with a Building Code Commission decision, an approval in the whole of another province or territory, or an approved revision of the 2020 National Building or Plumbing Code OBC Div. C 2.4.2.1.OBC Div. C 2.4.2.1. Criteria(1) Sentence (2) sets out criteria to be followed by the Minister when making a ruling under clause 29(1)(c) of the Act to approve the use of an alternative material, system or building design. (2) The Minister’s approval of the use of an alternative material, system or building design referred to in Sentence (1) may…. Minister's interpretations are posted on the Building Code website OBC Div. C 2.4.3.1.OBC Div. C 2.4.3.1. Interpretations By Minister(1) Every interpretation issued by the Minister under section 28.1 of the Act shall be made available to the public, (a) by posting the interpretation on the Building Code website, and (b) by providing a written copy of the interpretation on receipt of a request for it..
Common traps
- Mixing up 13% (all buildings) and 15% (Part 9 housing) in 12.2.1.2.
- Assuming SB-10 Division 5 is open to any small building. It excludes residential and electric-heated buildings and anything outside Part 9.
- Using a motion sensor on emergency lighting. Never permitted.
- Thinking compliance alternatives for Part 3 or Part 6 apply automatically. The chief building official must be satisfied compliance is impracticable.
- Forgetting the occupancy permit needs fire protection systems working only "up to and including" the occupied storeys, not the whole building.
Chapter review
Chapter at a glance
One line per section: the idea to carry into the exam. Then the answers that most often catch candidates out.
- Energy efficiency design for Part 3 buildings (SB-10)
Farm buildings, buildings using no electrical power or fossil fuel, and seasonal recreational buildings under Sections 9.37 or 9.39 are exempt.
- Energy efficiency for houses (SB-12) and water efficiency
Section 12.3 applies to Part 9 residential buildings occupied through the winter.
- Renovation compliance alternatives (Section 11.5)
The Section 11.5 tables (one per occupancy group: A, B, C, D/E and F) list substitutes for current requirements in existing buildings.
- General review, permits and occupancy
A 9-storey apartment building is ready on floors 1 to 4 only.
- Alternative solutions and rulings
A designer proposing an alternative solution must document the applicable objectives, functional statements and acceptable solutions, and show by past performance, tests or other…
Usual exam traps
- Mixing up 13% (all buildings) and 15% (Part 9 housing) in 12.2.1.2.
- Assuming SB-10 Division 5 is open to any small building. It excludes residential and electric-heated buildings and anything outside Part 9.
- Using a motion sensor on emergency lighting. Never permitted.
- Thinking compliance alternatives for Part 3 or Part 6 apply automatically. The chief building official must be satisfied compliance is impracticable.
- Forgetting the occupancy permit needs fire protection systems working only "up to and including" the occupied storeys, not the whole building.
Practice this chapter
Questions on Energy efficiency, renovation and Division C administration, in the exam format, every answer explained and cited to its article. Sign in to start; a free account gets the free questions.
Code cited in this chapter
Based on the official 2024 Building Code Compendium on ontario.ca.
© King's Printer for Ontario, 2024. Reproduced with permission.
OBC Div. B 12.2.1.2. Energy Efficiency Design
Open OBC Div. B 12.2.1.2. in the code viewer(1)Reserved.
(2)Except as provided in Sentence (3) and Sentence (4), the energy efficiency of all buildings shall
(a)be designed to exceed by not less than 13% the energy efficiency levels required by Sentence 12.2.1.1.(2) of O. Reg. 332/12 (Building Code) as it read on December 31, 2024, or
(b)conform to Division 1 and Division 3 or 5 of MMA Supplementary Standard SB-10, “Energy Efficiency Requirements.”
(3)Except as provided in Sentence (4), the energy efficiency of a building or part of a building of residential occupancy that is within the scope of Part 9 and is intended for occupancy on a continuing basis during the winter months shall
(a)be designed to exceed by not less than 15% the energy efficiency levels required by Sentence 12.2.1.1.(3) of O. Reg. 332/12 (Building Code) as it read on December 31, 2024, or
(b)conform to Chapters 1 and 3 of MMA Supplementary Standard SB-12, “Energy Efficiency for Housing.”
(4)This Article does not apply to
(a)a farm building,
(b)a building that does not use electrical power or fossil fuel, or
(c)a seasonal recreational building described in Section 9.37. or 9.39.
OBC Div. B 12.2.2.1. Carbon Dioxide Equivalents
Open OBC Div. B 12.2.2.1. in the code viewer(1)Except as provided in Sentence (2), all buildings shall be designed to conform to the CO₂e emission requirements set out in MMA Supplementary Standard SB-10, “Energy Efficiency Requirements.”
(2)This Article does not apply to
(a)a building or part of a building of residential occupancy that is within the scope of Part 9 and is intended for occupancy on a continuing basis during the winter months,
(b)a farm building,
(c)a building that does not use electrical power or fossil fuel, or
(d)a seasonal recreational building described in Section 9.37. or 9.39.
OBC Div. B 12.2.3.1. Peak Electric Demand
Open OBC Div. B 12.2.3.1. in the code viewer(1)Except as provided in Sentence (2), all buildings shall be designed to conform to the peak electric demand requirements set out in MMA Supplementary Standard SB-10, “Energy Efficiency Requirements.”
(2)This Article does not apply to
(a)a building or part of a building of residential occupancy that is within the scope of Part 9 and is intended for occupancy on a continuing basis during the winter months,
(b)a farm building,
(c)a building that does not use electrical power or fossil fuel, or
(d)a seasonal recreational building described in Section 9.37. or 9.39.
OBC SB-10 1.1.2.1. Energy Efficiency Design
Open OBC SB-10 1.1.2.1. in the code viewer(1)Except as provided in Sentence (2) and Article 1.2.1.1., the energy efficiency of all buildings shall be designed to achieve the energy efficiency levels attained by conforming to
(a)2013 ANSI/ASHRAE/IES 90.1 and Chapter 2,
(b)2015 NECB and Chapter 3, or
(c)Section 7 "Energy Efficiency" of 2014 ANSI/ASHRAE/USGBC/IES 189.1, excluding Sections 7.2.b, 7.4.7.3, 7.4.8 and 7.5.
(2)Energy efficiency requirements do not apply to buildings or parts of buildings described in Article 1.2.1.1.
OBC SB-10 1.1.1.3. Energy Efficiency Design
Open OBC SB-10 1.1.1.3. in the code viewer(1)Except as permitted in Sentence (2), the energy efficiency design and construction of buildings required to comply with Sentence 12.2.1.2.(2) of Division B of the Building Code shall comply with Division 3 of this Supplementary Standard.
(2)The energy efficiency of a building or part of a building may conform to the design requirements of Division 5 of this Supplementary Standard, if the building or part of the building,
(a)is within the scope of Part 9 of Division B of the Building Code
(b)does not contain a residential occupancy
(c)does not use electric space heating, and
(d)is intended for occupancy on a continuing basis during the winter months.
OBC Div. B 12.2.4.1. Motion Sensors
Open OBC Div. B 12.2.4.1. in the code viewer(1)Lighting installed to provide the minimum illumination levels required by this Code may be controlled by motion sensors except where the lighting
(a)is installed in an exit,
(b)is installed in a corridor serving patients or residents in a Group B, Division 2 or Division 3 occupancy, or
(c)is required to conform to Sentence 3.2.7.1.(10).
(2)Where motion sensors are used to control minimum lighting in a public corridor or corridor providing access to exit for the public, the motion sensors shall be installed with switch controllers equipped for fail-safe operation and illumination timers set for a minimum 15-minute duration.
(3)A motion sensor shall not be used to control emergency lighting.
OBC Div. B 12.3.1.1. Application
Open OBC Div. B 12.3.1.1. in the code viewer(1)This Section applies to the energy efficiency of a building or part of a building of residential occupancy that is within the scope of Part 9 and is intended for occupancy on a continuing basis during the winter months.
OBC Div. B 12.3.1.3. Temperature Control in Houses and Dwelling Units
Open OBC Div. B 12.3.1.3. in the code viewer(1)Except as provided in Sentence (3) and except where space heating energy is provided by a solid fuel-burning appliance or a ground source heat pump,
(a)heating system in an individual dwelling unit shall be controlled by at least one programmable thermostatic control device located in the dwelling unit, and
(b)where a house contains a secondary suite, each dwelling unit shall be controlled by at least one programmable thermostatic control device located in the dwelling unit.
(2)The programmable thermostatic control device required in Sentence (1) shall
(a)allow the setting of different air temperatures for at least
(i)four time periods per day, and
(ii)two different day-types per week,
(b)include a manual override, and
(c)allow the setting of the air temperature to
(i)13°C or lower in heating mode, and
(ii)29°C or higher in cooling mode, where air-conditioning is provided.
(3)A manual thermostatic control device is permitted if it
(a)controls a heating or cooling system where the heating or cooling capacity is not more than 2 kW, or
(b)serves an individual room or space.
Show all 26 articles
OBC Div. B 12.3.1.4. Hot Water Piping Insulation
Open OBC Div. B 12.3.1.4. in the code viewer(1)Hot water pipes that are vertically connected to a hot water storage tank shall have heat traps on both inlet and outlet piping as close as practical to the tank, except where the tank
(a)has an integral heat trap, or
(b)serves a recirculating system.
(2)The first 2.5 m of hot water outlet piping of a hot water storage tank serving a non-recirculating system shall be insulated to provide a thermal resistance of not less than RSI 0.62.
(3)The inlet pipe of a hot water storage tank between the heat trap and the tank serving a non-recirculating system shall be insulated to provide a thermal resistance of not less than RSI 0.62.
OBC Div. B 12.3.1.5. Residential Furnaces
Open OBC Div. B 12.3.1.5. in the code viewer(1)A furnace serving an individual dwelling unit in a house shall be equipped with a brushless direct current motor. (See Note A-12.3.1.5.(1))
OBC Div. B 12.3.1.6. Energy Supply for Kitchen and Laundry Facilities
Open OBC Div. B 12.3.1.6. in the code viewer(1)In order to supply energy to cooking appliances and clothes dryers, every kitchen and laundry space shall be provided with
(a)an electrical outlet,
(b)a natural gas line, or
(c)a propane line.
OBC SB-12 1.1.1.3. Compliance Options
Open OBC SB-12 1.1.1.3. in the code viewer(1)The energy efficiency of a building or part of a building of residential occupancy that is within the scope of Part 9 of Division B of the Building Code and is intended for occupancy on a continuing basis during the winter months shall comply with
(a)Subsection 3.1.1. (Prescriptive Compliance Packages) of Chapter 3,
(b)Subsection 3.1.2. (Performance Compliance) of Chapter 3, or
(c)Subsection 3.1.3. (Other Acceptable Compliance Methods) of Chapter 3.
(2)Factory-built modular homes manufactured before January 1, 2017 in accordance with the Building Code as it read on December 31, 2016 shall be deemed to be in compliance with Sentence (1).
OBC SB-12 3.1.1.1. Energy Efficiency
Open OBC SB-12 3.1.1.1. in the code viewer(1)Except as provided in Articles 3.1.1.4. to 3.1.1.11., the building shall conform to
(a)Article 3.1.1.2. if the building is located in Zone 1 with less than 5000 heating degree days, or
(b)Article 3.1.1.3. if the building is located in Zone 2 with 5000 or more heating degree days.
(2)Except as required in Sentence (5), all walls, ceilings, floors, windows and doors that separate heated space from unheated space, the exterior air or the exterior soil shall have thermal resistance ratings conforming to this Subsection.
(3)Where specified in compliance packages in Tables 3.1.1.2.A to 3.1.1.2.C and Tables 3.1.1.3.A to 3.1.1.3.C, space heating equipment, domestic water heating equipment and heat or energy recovery ventilators shall be provided and have the efficiency rating conforming to this Subsection. (See Appendix A.)
(4)Except as required in Sentence (5), insulation shall be provided between heated and unheated spaces and between heated spaces and the exterior in accordance with this Chapter.
(5)A building envelope assembly that separates a conditioned space from an adjoining storage garage shall be treated as an assembly separating heated space from exterior, even if the storage garage is intended to be heated.
(6)Reflective surfaces of insulating materials shall not be considered in calculating the thermal resistance of building assemblies.
(7)Except as provided in Sentences (8) and 3.1.1.11.(3), where the ratio of the gross area of windows, sidelights, skylights, glazing in doors and sliding glass doors to the gross area of peripheral walls measured from grade to the top of the upper most ceiling is not more than 17%, the building shall comply with a compliance package selected from Tables 3.1.1.2.A to 3.1.1.2.C and Tables 3.1.1.3.A to 3.1.1.3.C, and Table 3.1.1.11. (See Appendix A.)
(8)Except as permitted in Sentences 3.1.1.11.(3), where the ratio of the gross area of windows, sidelights, skylights, glazing in doors and sliding glass doors to the gross area of peripheral walls measured from grade to the top of the upper most ceiling is more than 17% but not more than 22%, the building shall comply with a compliance package selected from Tables 3.1.1.2.A to 3.1.1.2.C, Tables 3.1.1.3.A to 3.1.1.3.C and Table 3.1.1.11. and the overall coefficient of heat transfer of the fenestration shall be upgraded to
(a)1.6 where 1.8 is required by the selected compliance package or permitted by Article 3.1.1.4.,
(b)1.4 where 1.6 is required by the selected compliance package or permitted by Article 3.1.1.4.,
(c)1.2 where 1.4 is required by the selected compliance package or permitted by Article 3.1.1.4., and
(d)1.0 where 1.2 is required by the selected compliance package or permitted by Article 3.1.1.4.
(See Appendix A.)
(9)Where the ratio of gross area of windows, sidelights, skylights, glazing in doors and sliding glass doors to the gross area of peripheral walls measured from grade to the top of the upper most ceiling is more than 22%, the building shall comply with Subsection 3.1.2. (See Appendix A.)
(10)Where a dwelling unit has a walkout basement, the thermal performance level of the exterior basement wall shall be not less than that required for the above grade wall for
(a)the basement wall containing the door opening, and
(b)any basement wall that has an exposed wall area above the ground level exceeding 50% of that basement wall area.
(11)For a conditioned space, the exterior building envelope or envelope that separates conditioned space from unconditioned space shall conform to the applicable values specified in Articles 3.1.1.2. and 3.1.1.3.
(12)Where an enclosed unheated space is separated from a heated space by glazing, the unheated enclosure may be considered to provide a thermal resistance of RSI 0.16.
(13)Where a compliance package in Tables 3.1.1.2.A to 3.1.1.2.C, Tables 3.1.1.3.A to 3.1.1.3.C, or Table 3.1.1.11. specifies a nominal RSI value, effective RSI value and U-Value for a component specified in Column 1 of the Table and the component conforms to one of the thermal values, the component need not conform to the other thermal values specified for the component.
(14)Insulation in the rim joist or header area where the floor assembly and wall assembly intersect shall have a thermal value not less than the thermal value of the insulation in the walls above grade.
(15)Where a compliance package in Tables 3.1.1.2.A to 3.1.1.2.C, Tables 3.1.1.3.A to 3.1.1.3.C, or Table 3.1.1.11. specifies an overall coefficient of heat transfer and an energy rating value for a fenestration component specified in Column 1 of the Table and the component conforms to one of the thermal values, the component need not conform to the other thermal value specified for the component.
(16)Ventilation systems serving dwelling units shall have a heat or energy recovery ventilator. (See Appendix A)
(17)Except as provided in Sentence (18), a building is permitted to be designed in conformance with any of the compliance packages available for the climate zone that the building is located in, if the primary space heating of the building is supplied by
(a)a wood burning appliance,
(b)an earth energy system, or
(c)an air or water source heat pump that does not use electric resistance as a back-up heat source.
(18)For the purpose of Sentence (17), the requirements in the compliance packages for space heating equipment do not apply.
(19)Heat or energy recovery ventilators specified in compliance packages in Tables 3.1.1.2.A to 3.1.1.2.C and Tables 3.1.1.3.A to 3.1.1.3.C, shall meet
(a)the requirements of Article 9.32.3.12. of Division B of the Building Code, and
(b)the minimum SRE required in this Chapter based on a test temperature of 0°C at an air flow rate equal to the principle exhaust flow but need not exceed 30 L/s.
(20)Building envelope components that enclose a common space and are exposed to exterior or unconditioned space shall conform to this Subsection.
(21)Heating, ventilating, air-conditioning and lighting systems serving common spaces need not comply with this Subsection but shall comply with the other parts of the Building Code.
(22)Drain water heat recovery units shall be installed in accordance with Article 3.1.1.12.
OBC SB-12 3.1.2.1. Required Performance Level
Open OBC SB-12 3.1.2.1. in the code viewer(1)The performance level shall be measured based on the simulated annual energy use of the building.
(2)For the purpose of this Subsection, reference building means a building that is identical to the proposed building, except that it is designed to meet the requirements and performance level of an applicable compliance package in Subsection 3.1.1. on the basis of
(a)zone location,
(b)energy source, and
(c)equipment efficiency.
(3)The simulated annual energy use of the proposed building shall not be greater than the simulated annual energy use of the reference building.
(4)The simulated annual energy use of the proposed building and the reference building shall be calculated in accordance with Table 3.1.2.1.
(5)For the purpose of calculations required in Sentence (4),
(a)the simulation software used shall be a recognized annual energy use simulation software,
(b)the climatic data used shall be the local climatic data,
(c)the equivalent domestic water loads, appliance loads and other plug-in loads shall be assumed for both the proposed building and the reference building, and
(d)the same software and climatic conditions shall be used for both the proposed building and the reference buildings.
(6)Where the overall thermal performance of the proposed building envelope is less than the envelope performance of the compliance package that is compared against it, the reduction in the performance level of the building envelope shall not be more than 25%.
(7)The annual energy use simulation of the reference building shall be in accordance with Subsection 3.1.1. of this Supplementary Standard, Part 12 and other applicable parts of the Building Code.
OBC Div. B 12.4.1.1. Plumbing Systems
Open OBC Div. B 12.4.1.1. in the code viewer(1)All buildings shall conform to the water efficiency requirements of Subsection 7.6.4.
OBC Div. B 7.6.4.1. Water Supply Fittings
Open OBC Div. B 7.6.4.1. in the code viewer(1)Each lavatory in a washroom with fixtures for public use shall be equipped with a device capable of automatically shutting off the flow of water when the lavatory is not in use. (See Note A-7.6.4.1.(1) and (3))
(2)An automatic compensating valve serving an individual shower head shall have a manufacturer's minimum-rated water flow rate equal to or less than the shower head it serves. (See Note A-7.6.4.1.(2))
(3)Where multiple shower heads installed in a public showering facility are served by one temperature control, each shower head shall be equipped with a device capable of automatically shutting off the flow of water when the shower head is not in use. (See Note A-7.6.4.1.(1) and (3))
OBC Div. B 11.5.1.1. Compliance Alternatives
Open OBC Div. B 11.5.1.1. in the code viewer(1)A compliance alternative shown in Table 11.5.1.1.-A, 11.5.1.1.-B, 11.5.1.1.-C, 11.5.1.1.-D/E or 11.5.1.1.-F may be substituted for a requirement contained in Part 3, 4, 6 or 8 where the chief building official is satisfied that compliance with the requirement is impracticable because,
(a)of structural or construction difficulties, or
(b)it is detrimental to the preservation of a heritage building.
(2)A compliance alternative shown in Table 11.5.1.1.-A, 11.5.1.1.-B, 11.5.1.1.-C, 11.5.1.1.-D/E or 11.5.1.1.-F may be substituted for a requirement contained in Part 9 or 12 without satisfying the chief building official that compliance with the requirement is impracticable.
OBC Div. B Table 11.5.1.1-C. Compliance Alternatives for Residential Occupancies — Forming Part of Article 11.5.1.1.
Open OBC Div. B Table 11.5.1.1-C. in the code viewerTable 11.5.1.1.-C Compliance Alternatives for Residential Occupancies — Forming Part of Article 11.5.1.1. C.A. Number | Division B Requirements | Compliance Alternative C1 | 3.1.4.7. | Existing heavy timber construction acceptable where construction is within 90% of member sizes listed in Part 3. C2 | 3.1.5.2. to 3.1.5.4.; 3.1.5.8. | Existing acceptable. C3 | 3.1.5.9. to 3.1.5.12. | Except for exposed foamed plastics, existing acceptable. To match existing, materials may be added from on or off site. C4 | 3.1.5.18. to 3.1.5.20.; 3.1.5.21. | Existing acceptable. C5 | 3.1.7.1. | Fire-resistance ratings may also be used where they are based on: (a) HUD Rehabilitation Guidelines, "Guideline on Fire Ratings of Archaic Materials and Assemblies". (b) DBR Technical Paper No. 194, "Fire Endurance of Protected Steel Columns and Beams". (c) DBR Technical Paper No. 207, "Fire Endurance of Unit Masonry Walls". (d) DBR Technical Paper No. 222, "Fire Endurance of Light-Framed and Miscellaneous Assemblies". C6 | 3.1.7.5.(3) | Existing assemblies required to be of noncombustible construction may be supported by combustible construction having at least the same fire-resistance rating as that supported. C7 | 3.1.8.1.(2); 3.1.8.6.(1) and (2) | Existing functional closures are acceptable and may be relocated within the same existing Fire separation. C8 | 3.1.8.5.(2) | (a) Existing functional and sound doors in existing buildings that are either hollow metal or kalamein and containing wired glass at least 6 mm thick and conforming to Sentence 3.1.8.16.(2) are permitted in lieu of doors not required to exceed 45 min. (b) All existing functional and sound hollow metal or kalamein doors which carry existing 1.5 h labels are acceptable in lieu of current 1.5 h labels and may contain wired glass panels not exceeding 0.0645 m², at least 6 mm thick and conforming to Sentence 3.1.8.16.(2). (c) Every fire door, window assembly or glass block used as a closure in a required Fire separation shall be installed in conformance with good engineering practice. C9 | 3.1.8.7. to 3.1.8.10. | Except for hotels, Fire dampers or fire stop flaps are not required to be installed in existing ducts at penetrations of existing Fire separations. C10 | 3.1.8.12.(1) | For existing unlabeled doors in existing buildings, at least 45 mm solid core wood or metal clad are acceptable. Except for residential occupancies, existing closure rating of 20 min will not be required where the entire floor area is sprinklered. C11 | 3.1.8.14.(1) and (2) | In retirement homes, between a suite and a public corridor, existing 'pause' type self-closing devices may be used as hold-open devices where functionally operable. C12 | 3.1.8.15. | Existing functionally operable latching devices, excluding draw bolts, are acceptable. C13 | 3.1.8.16. | Existing transoms or sidelights located in Fire separations not required to be greater than 1 h may be retained if wired glass, at least 6 mm thick, is securely fixed to a wood frame of at least 50 mm thickness with steel stops. Operable transoms shall be fixed closed. C14 | 3.1.8.17. to 3.1.8.19. | Existing acceptable. C15 | 3.1.11. | Where the concealed space is being materially altered, provide smoke or heat detection in that space in lieu of fire blocks and tie into fire alarm system. C16 | 3.2.3. | Existing windows. (a) Existing windows in walls may be relocated to another part of the wall, provided the existing opening is blocked up to provide the same fire rating for the wall, and the projection of the new opening, at a right angle to the property line onto another building, lies not closer than 300 mm from a window in such other building, where the "opposite" window is less than 2,400 mm from the opposite new opening. (b) Except relocation of units, shall be restricted to the same fire compartment and shall conform to the requirements of Article 3.2.3.14. or 9.10.12.3. where applicable. (c) Where a building does not satisfy the requirements of Subsection 3.2.3. for the amount of openings facing a yard or space that does not have sufficient limiting distance, such existing openings are allowed to be relocated provided: (i) Such openings are not increased in size and they are protected with wired glass in steel frames conforming to Sentence 3.1.8.16.(2). (ii) The building is sprinklered. C17 | 3.2.3.6.(3) | Existing roof soffit projections acceptable. C18 | 3.2.4. | (a) Existing fire alarm system may remain except that Article 3.2.4.5. does not apply where the fire safety plan (as described in the Fire Code made under the Fire Protection and Prevention Act, 1997) for the building addresses the intent of Subsection 3.2.4. (i.e. "stage" system, electrical supervision, detection as required, Fire Department connection, and emergency power supply). (b) Extension of an existing system must ensure continuity and compatibility, and integrity of the system. C19 | 3.2.4.8.(2)(e) | Does not apply to existing installations in buildings. C20 | 3.2.4.9.(5)(c) | Does not apply to existing installations in buildings. C21 | 3.2.4.20. | Except for retirement homes, such smoke alarms may be battery operated. C22 | 3.2.5.1.; 3.2.5.2. | Existing acceptable. C23 | 3.2.5.3.(1) | Existing access acceptable. C24 | 3.2.5.3.(2) | Existing acceptable. C25 | 3.2.5.4. to 3.2.5.6. | (a) For buildings 6 storeys and less, existing access to existing occupancy is acceptable. (b) Where existing building is changed to a "C" occupancy, an access route shall be provided, or the existing access is acceptable provided the building is sprinklered. C26 | 3.2.5.7. | Existing water supply and hydrants are acceptable in buildings up to 6 storeys in building height. C27 | 3.2.5.8. to 3.2.5.11. | Does not apply to buildings 4 storeys and less. For existing buildings over 4 storeys in building height, existing standpipe and hose systems water supply is acceptable provided it can deliver a minimum flow rate of 265 L/min for 30 min at 345 kPa (gauge) at the two highest and most remote hose valves, with not less than 132 L/min from each of the two simultaneously. C28 | 3.2.5.12. | Existing sprinkler systems in existing buildings that do not conform to NFPA 13 may be altered, added to, or extended from the existing system without complying with NFPA 13, provided the system is operational and adequate with respect to coverage, water supply and controls, and provided the system is evaluated by a qualified designer. C29 | 3.3.1.4.(1); 3.3.4.2.(1) | 30 min is acceptable to separate corridors or exits in buildings not exceeding 6 storeys in building height, except that 45 min is required for exits in buildings exceeding 3 storeys in building height. For buildings exceeding 6 storeys in building height, 30 min is acceptable where smoke detectors are installed in corridors, except 1 h is required in exits. 30 min is acceptable to separate public corridors, exits or suites in hotels, provided fire detectors are installed in every room in a suite and in every room not located in a suite, other than corridors, washrooms, closets in suites, saunas, refrigerated areas and swimming pools. C30 | 3.3.1.5.(1)(c); Tables 3.3.1.5.-A and 3.3.1.5.-B | In Column 2, maximum area of room or suite to be unlimited. C31 | 3.3.1.9. | Existing width of public corridors of not less than 914 mm is acceptable. C32 | 3.3.1.11.; 3.3.1.12. | Existing door swings may remain in heritage buildings, existing or being restored, with no change in major occupancy and with occupant load no greater than 100. C33 | 3.3.1.13. | Existing doors acceptable, provided not less than 600 mm wide. C34 | 3.3.1.14. | Existing curved or spiral stairs acceptable. C35 | 3.3.1.17. | Existing non-conforming capacities of access to exits are acceptable, provided that the excessive capacity is no greater than 15% and: (a) Corridor Fire separations are rated to Code plus early warning system provided. (b) There are sprinklers, plus smoke alarms in suites. C36 | 3.3.1.18. | Does not apply to heritage buildings. C37 | 3.3.1.20. | Existing stained, etched, bevelled, leaded or figured glass acceptable. C38 | 3.3.4.2.(3)(b)(i) 3.3.4.2.(3)(b)(ii), (iii) | 30 min Fire separation acceptable. 45 min Fire separation acceptable. C39 | 3.3.4.4.(4) and (5) | For buildings 6 storeys and less, doorway from dwelling unit will be permitted to open directly into exit stairway or interior corridor served by a single exit if a fire alarm system complying with Subsection 3.2.4. is installed and the dwelling unit has a second and separate means of egress. C40 | 3.3.5.4.(1) and 3.3.5.7.(4) | Need not comply where a gasketed door and self closer are provided in the existing Fire separation. C41 | 3.4.1.4. | Except for hotels and retirement homes, the following types of exits may also be used for buildings not over 6 storeys in building height: (a) Connected balconies, which connect across firewalls, or connect to another exit, or with access to ground level. (b) Areas of refuge where fire service rescue is possible and that comply with Measure L of Sentences (4) to (10), (18) and Clauses (20)(a), (b) and (d) in MMAH Supplementary Standard SB-4, "Measures for Fire Safety in High Buildings". C42 | 3.4.1.8. | Existing stained, etched, bevelled, leaded or figured glass acceptable. C43 | 3.4.2.5.(1) | Existing travel distance acceptable where floor area is sprinklered and provided fire separations comply with Part 3. C44 | 3.4.3.2.(7) | Existing width of exits acceptable provided the occupant load is not more than 15% above the exit capacity. C45 | 3.4.3.3. | Except for heritage buildings, existing acceptable, provided not less than 800 mm. C46 | 3.4.3.4. | Existing headroom clearance of not less than 1,980 mm is acceptable. C47 | 3.4.4.1.(1) | Except for exits, no rating required where floor areas are sprinklered. C48 | 3.4.4.1. | Fire separations of exits permitted in buildings: (a) 30 min, up to 3 storeys in building height. (b) 45 min, in hotels up to 3 storeys in building height. (c) 45 min, up to 6 storeys in building height. (d) 1 h, over 6 storeys in building height. C49 | 3.4.4.4.(8) | Existing washrooms opening directly into an exit stairwell shall be separated from the exit stairwell by a 45 min closure. C50 | 3.4.5.1.(2) and (9) | Existing illuminated legible exit signs are acceptable. C51 | 3.4.6.1. | Existing acceptable. C52 | 3.4.6.2. | Existing acceptable, if visually apparent. C53 | 3.4.6.3.(1) | Existing acceptable with rise no greater than 3.7 m. C54 | 3.4.6.4.(1) to (3) | Existing acceptable. C55 | 3.4.6.4.(4) and (5) | Existing acceptable. C56 | 3.4.6.5.(3) to (13) | Existing acceptable. C57 | 3.4.6.6.(2) to (4) | Existing acceptable. C58 | 3.4.6.7.(1) | Existing acceptable. C59 | 3.4.6.8. | Existing acceptable. C60 | 3.4.6.9. | (a) Except for retirement homes, existing acceptable. (b) For retirement homes, existing acceptable provided there is no change in major occupancy or increase in occupant load greater than 15%. C61 | 3.4.6.10.(2) to (6) | Existing acceptable. C62 | 3.4.6.11.(1) to (3) | Existing acceptable. C63 | 3.4.6.12. | Existing acceptable in heritage buildings provided the occupant load is not more than 60. C64 | 3.4.6.16.(1) to (4) | Existing functionally operable panic hardware acceptable. C65 | 3.4.7.2. | Except for retirement homes, combustible fire escapes which are protected from fire in accordance with Sentence 3.2.3.13.(2) are permitted or may be reconstructed or recreated (as in the case of a heritage building). C66 | 3.5.1. | Existing acceptable except where building is classified under Subsection 3.2.6. C67 | 3.6.2.1.(7) | 45 min Fire separation acceptable. C68 | 3.6.2.2. | Existing acceptable where explosion-resistant construction or venting is provided. C69 | 3.6.2.6. | Existing acceptable. C70 | 3.6.2.7.(1) | 2 h Fire separation acceptable. C71 | 3.6.3.1.(1) to (5) | 45 min Fire separation acceptable up to 6 storeys. C72 | 3.6.3.3.(2) | Where 2 h Fire separation is required, 1 h is acceptable. Except for linen discharge rooms where 1 h Fire separation is required, 45 min is acceptable. C73 | 3.6.3.3.(4) and (5) | Existing sizes acceptable. C74 | 3.6.3.3.(9) | Where 2 h Fire separation is required, 1 h is acceptable. C75 | 3.6.4.2. | Except for retirement homes, ceiling Fire separation need not have a fire-resistance rating where sprinklering, subject to C.A. C27, of fire compartments on both sides of vertical Fire separation is provided and where such Fire separation is not required to exceed 1 h. C76 | 3.6.4.3.(1) | Existing to meet flame-spread rating of 25 or to be sprinklered. C77 | 3.6.4.4. to 3.6.4.6. | Existing access acceptable. C78 | 3.7.1.1.(2) | Minimum room height shall be not less than 1,950 mm over the required floor area and any location that would normally be used as a means of egress. C79 | 3.7.2.1. | (a) Where windows are not used as means of egress and where they do not conflict with ventilation requirements, the minimum glass areas as shown in Table 9.7.2.3. may be reduced by 50%. (b) An existing room converted to an interior room, created by an addition, shall not require a window, provided there is an opening in a dividing wall occupying not less than 30% of the separating plane to an adjoining room, where the adjoining room has a minimum of 5% window area of the combined floor areas, and provided the required ventilation for the combined room is maintained. C80 | 3.7.4. | Where the occupant load is increased by more than 15% above the capacity of the existing facilities, facilities to be added to accommodate the increase. C81 | 3.8.1.2. | Existing accessible entrance acceptable. (see C.A. C88) Existing curb ramp conforming to Sentence 3.8.3.2.(3) is acceptable. Existing principal entrance acceptable, provided at least one barrier-free entrance is available. C82 | 3.8.1.3.(1) | Existing unobstructed width of 920 mm minimum is acceptable. C83 | 3.8.1.3.(4) | Existing unobstructed space not less than 1,500 mm in width and 1,500 mm in length located not more than 30 m apart is acceptable. C84 | 3.8.3.2.(3)(b) | Existing curb ramp acceptable, provided width not less than 1,200 mm. C85 | 3.8.3.3.(1) | Existing doorway acceptable, provided not less than 800 mm wide. C86 | 3.8.3.3.(11)(a) | Existing distance acceptable, provided not less than 1,200 mm plus the width of any door that swings into the space in the path of travel. C87 | 3.8.3.4.(1)(a) | Existing ramp acceptable, provided not less than 870 mm between handrails. C88 | 3.8.3.8.(5) | Existing grab bar is acceptable. C89 | 3.8.3.12. | Existing universal washroom acceptable. C90 | 3.8.3.13.(2) (g) | Existing grab bar is acceptable. C91 | 3.8.3.16. | Existing drinking fountain conforming to Clauses 3.8.3.16.(2)(a) and (b) acceptable. C92 | 3.11.3.1.(9) | Existing clear width acceptable, provided not less than 900 mm. C93 | 3.11.3.1.(14) | Existing painted line acceptable. C94 | 4.1.8. | The requirements under this Subsection do not apply. C95 | 6.3.1.1.(2) | Required outdoor air rates may be provided by mechanical, natural or combination of natural and mechanical means. C96 | 6.3.2.3.; 6.3.2.6.; 6.3.2.6A.; 6.3.2.10. | Existing acceptable. C97 | 6.3.2.7.(1) | In a building containing not more than four dwelling units or residential suites, the existing heating or air-conditioning system may be altered to serve more than one dwelling unit or suite, provided smoke alarms are installed in each dwelling unit or suite and provided a smoke detector is installed in the supply or return air duct system serving the entire building which would turn off the fuel supply and electrical power to the heating system upon activation of such detector. C98 | 6.3.2.9. | Existing openings, grilles and diffusers acceptable. C99 | 6.3.3. | Existing acceptable, provided products of combustion are safely vented. C100 | 6.5.1.1. | Existing acceptable. C101 | 6.9.4.4.(1) | Carbon monoxide alarms may be battery operated or plugged into an electrical outlet. C102 | 8.2.1.4. | Existing clearances acceptable where a sewage system is replaced with another sewage system within the same class and the capacity of the replacement sewage system does not exceed the capacity of the existing sewage system. C103 | 8.2.1.4. | Existing clearances are acceptable where a replacement sewage system requires lesser clearances than those required in Part 8 for the existing sewage system. C104 | 9.3.2.1. | Sound used lumber may be acceptable for reuse without a grade stamp provided that: (a) Visual examination shows no excessive weakening by holes, notches, nail splits or other damage. (b) Where the grade or species is unknown, the minimum grade shall apply for span table use. (c) Lumber has not been subjected to termite infestation. C105 | 9.5.3.1. | Except for secondary suites, in a dwelling unit: (a) Minimum room height shall not be less than 1,950 mm over the required floor area and in any location that would normally be used as a means of egress. (b) Minimum room height shall not be less than 2,030 mm over at least 50% of the required floor area, provided that any part of the floor having a clear height of less than 1,400 mm shall not be considered in computing the required floor area. C106 | 9.5.11.1. | Doors may be lesser heights to suit ceiling heights. C107 | 9.5.11.2. | Existing acceptable, provided not less than 600 mm. C108 | 9.6.1.2.(2) and (3); 9.6.1.4.(1) and (2) | Existing doors and sidelights being reused or relocated need not conform if identified or protected. C109 | 9.6.1.4.(3) | Existing acceptable, if marked to indicate their existence and position. C110 | 9.7.2.3. | (a) Where windows are not used as a means of egress and where they do not conflict with ventilation requirements, the minimum glass areas as shown in Table 9.7.2.3. may be reduced by 50%. (b) An existing room converted to an interior room, created by an addition, shall not require a window, provided there is an opening in a dividing wall occupying not less than 30% of the separating plane to an adjoining room, where the adjoining room has a minimum of 5% window area of the combined floor areas, and provided the required ventilation for the combined room is maintained. C111 | 9.7.4. | Existing acceptable. C112 | 9.8.1. to 9.8.4. | Replacement or extension of existing stair systems shall be exempt from the provisions of these Subsections, except that they shall have: (a) A minimum width between wall faces of 700 mm. (b) A minimum clear height over tread nosing or landing of 1,800 mm. C113 | 9.8.4.3. and 9.8.4.7. | Existing curved or spiral stairs are acceptable. C114 | 9.8.4.5. | Where a stair complies with Subsection 9.8.4., an extension to a stair may contain two sets of winders provided that they are separated by at least three treads or a landing. C115 | 9.8.5.1.(2) | Existing ramps acceptable, where practical. C116 | 9.8.7. | Existing handrails acceptable, unless considered unsafe by chief building official. C117 | 9.8.8. | Existing guards acceptable, unless considered unsafe by chief building official. C118 | 9.8.9.6.(4) | Existing acceptable. C119 | 9.9.2.1.(1) to (2.1) | Except for hotels, the following types of exits may also be used: (a) Connected balconies, which connect across firewalls, or connect to another exit, or with access to grade. (b) Areas of refuge approved by the chief building official, where fire service rescue is possible. (c) Combustible or noncombustible exterior stairways or fire escapes which are protected in accordance with Sentence 3.2.3.13.(2). These may be reconstructed or recreated (as in the case of a heritage building). C120 | 9.9.2.1.(4) | Except for hotels, existing acceptable. C121 | 9.9.3.2. | (a) In a building containing not more than four dwelling units, the width of every exit facility may be as the existing, but not less than 800 mm. (b) In a building containing more than four dwelling units, the width of every exit facility may be as the existing, but not less than 900 mm. C122 | 9.9.3.3. | (a) In a building containing not more than four dwelling units, the minimum width of a public corridor may be 800 mm. (b) In a building containing more than four dwelling units, the minimum width of a public corridor may be 900 mm. C123 | 9.9.3.4. | Existing clear height of not less than 1,950 mm is acceptable. C124 | 9.9.4.2. | Except as permitted in C.A. C136, in a building containing not more than four dwelling units or suites, one exit need not be separated from the remainder of the building at the first storey where there are one or more other exits complying with C.A. C122. C125 | 9.9.4.2.(1) and (2) | 30 min Fire separation acceptable. C126 | 9.9.5.4. | Existing acceptable. C127 | 9.9.5.8. | Existing acceptable provided minimum 45 min Fire separation and where explosion-resistant construction or venting is provided. C128 | 9.9.5.9. | Existing acceptable, provided that the enclosure has a 45 min fire-resistance rating. C129 | 9.9.6.1. | Except for hotels, existing acceptable. C130 | 9.9.6.2. | Existing clear opening height of not less than 1,950 mm is acceptable. C131 | 9.9.6.3. | Existing door widths are acceptable, provided exit widths conform to C.A. C117. C132 | 9.9.6.5. | Existing door swings acceptable. Existing acceptable in public heritage buildings, where approved by chief building official. C133 | 9.9.6.6.(1) | Where exit doors open onto a landing, they shall not extend beyond the face of the first riser. C134 | 9.9.6.8. | Existing functionally operable passage or panic hardware acceptable. C135 | 9.9.7.4.(1)(a) | Maximum area of existing room or suite does not apply. C136 | 9.9.7.5. | Except as provided in C.A. C139, in a single dwelling unit or a house with a secondary suite, the Code requirement applies. C137 | 9.9.8.2.(1) | Existing travel distance acceptable where floor area is sprinklered and provided fire separations comply with Part 9. C138 | 9.9.8.5. | In a building containing not more than four dwelling units or suites, existing glazed solid wood doors to lobby may remain in lieu of new 20 minute doors, provided the Fire separations for the floor above or below are provided as per C.A. C154, and a second means of egress from the dwelling units complies with the Code requirements. C139 | 9.9.9 | In a single dwelling unit or a house with a secondary suite, exit requirements are acceptable if at least one of the following conditions exists: (a) A door, including a sliding door, that opens directly to the exterior from a dwelling unit, serves only that dwelling unit and has reasonable access to ground level, and the dwelling units are equipped with smoke alarms installed in conformance with Subsection 9.10.19. (b) An exit that is accessible to more than one dwelling unit and provides the only means of egress from each dwelling unit, provided that the means of egress is separated from the remainder of the building and common areas by a Fire separation having a 30 min fire-resistance rating and provided further that the required access to exit from any dwelling unit cannot be through another dwelling unit, service room or other occupancy, and both dwelling units and common areas are provided with smoke alarms that are installed in conformance with Subsection 9.10.19. and are interconnected. (c) Access to an exit from one dwelling unit which leads through another dwelling unit where: (i) An additional means of escape is provided through a window that conforms to the following: (A) The sill height is not more than 1,000 mm above or below adjacent ground level. (B) The window can be opened from the inside without the use of tools. (C) The window has an individual unobstructed open portion having a minimum area of 0.38 m² with no dimension less than 460 mm. (D) The sill height does not exceed 900 mm above the floor or fixed steps. (E) Where the window opens into a window well, a clearance of not less than 1,000 mm shall be provided in front of the window. (F) Smoke alarms are installed in every dwelling unit and in common areas in conformance with Subsection 9.10.19. and are interconnected. (ii) An additional means of escape is provided through a window that conforms to the following: (A) The window is a casement window not less than 1,060 mm high, 560 mm wide, with a sill height not more than 900 mm above the inside floor. (B) The sill height of the window is not more than 5 m above adjacent ground level. (C) Smoke alarms are installed in every dwelling unit and in common areas in conformance with Subsection 9.10.19. and are interconnected. (iii) The building is sprinklered and the dwelling units are equipped with smoke alarms installed in conformance with Subsection 9.10.19. C140 | 9.9.10.1. | In a single dwelling unit or a house with a secondary suite, existing acceptable, where there is direct access to the exterior. C141 | 9.9.11. | In a single dwelling unit or a house with a secondary suite, the requirements under this Subsection do not apply. C142 | 9.9.11.3. | Existing illuminated legible signs are acceptable for exit signs, if approved by chief building official. C143 | 9.9.12. | In a single dwelling unit or a house with a secondary suite, the requirements under this Subsection apply only where the condition described in (b) of C.A. C139 exists. C144 | 9.10.1.1. | Assemblies required to be of noncombustible construction may be supported by combustible construction having at least the same fire-resistance rating as that supported. C145 | 9.10.1.3.(8) to (10) | Existing installations acceptable subject to C.A. C26, C27 and C28. C146 | 9.10.3. | Fire-resistance ratings may also be used where they are based on: (1) HUD Rehabilitation Guidelines, "Guideline on Fire Ratings of Archaic Materials and Assemblies". (2) DBR Technical Paper No. 194, "Fire Endurance of Protected Steel Columns and Beams". (3) DBR Technical Paper No. 207, "Fire Endurance of Unit Masonry Walls". (4) DBR Technical Paper No. 222, "Fire Endurance of Light-Framed and Miscellaneous Assemblies". C147 | 9.10.5.1. | (a) Existing openings in existing wall or ceiling membranes to remain. (b) Existing openings may be moved to another location in the same wall or ceiling, provided the aggregate area of openings does not increase and are not cumulative, and the existing opening is blocked up to provide the same rating as the existing wall or ceiling assembly. C148 | 9.10.6.2. | Existing heavy timber construction acceptable where construction is within 90% of member sizes listed in Part 3. C149 | 9.10.7. | Existing acceptable for heritage buildings, subject to approval of chief building official. C150 | 9.10.8.1.; 9.10.8.3.; 9.10.8.8. | (a) Except as provided in (b) and (c), 30 min rating is acceptable. (b) In a house with a secondary suite, 15 min horizontal Fire separation is acceptable where: (i) Smoke alarms are installed in every dwelling unit and in common areas in conformance with Subsection 9.10.19. (ii) Smoke alarms are interconnected. (c) In a house with a secondary suite, the fire-resistance rating of the Fire separation is waived where the building is sprinklered throughout. C151 | 9.10.8.4. | Assemblies required to be of noncombustible construction may be supported by combustible construction having at least the same fire-resistance rating as that supported. C152 | 9.10.9.7.; 9.10.9.11. | Existing acceptable in existing Fire separations. C153 | 9.10.9.12.(1) | Ceiling Fire separation need not have a fire-resistance rating where sprinklering, subject to C.A. C27, of fire compartments on both sides of vertical Fire separation is provided and where such Fire separation is not required to exceed 1 h. C154 | 9.10.9.13.(1) | Except for hotels, 30 min Fire separation acceptable. C155 | 9.10.9.13.(2) | In lieu of the 2 h Fire separation, sprinklers may be used in the mercantile occupancy or medium-hazard industrial occupancy, with a 1 h Fire separation. C156 | 9.10.9.16.(1) and (3); 9.10.9.17.(1) | (a) Except as provided in (b) and (c), 30 min Fire separation is acceptable. (b) In a house with a secondary suite, 15 min horizontal Fire separation is acceptable where: (i) Smoke alarms are installed in every dwelling unit and in common areas in conformance with Subsection 9.10.19. (ii) Smoke alarms are interconnected. (c) In a house with a secondary suite, the fire-resistance rating of the Fire separation is waived where the building is sprinklered throughout. C157 | 9.10.10.3. | (a) Except as provided in (b) and (c) and in Articles 9.10.10.5. and 9.10.10.6., 30 min Fire separation is acceptable. (b) In a house with a secondary suite, the fire-resistance rating of the vertical Fire separation is waived where: (i) Smoke alarms are installed in every dwelling unit and in common areas in conformance with Subsection 9.10.19. (ii) Smoke alarms are interconnected. (c) In a house with a secondary suite, the fire-resistance rating of the vertical Fire separation is waived where service rooms are sprinklered. C158 | 9.10.11.2.(1) | In an individual dwelling unit or a house with a secondary suite, a party wall with 1 h fire-resistance rating is acceptable. C159 | 9.10.13.1 | Existing functional closures are acceptable subject to C.A. C8 and C160. C160 | 9.10.13.2.(1) | In an individual dwelling unit or a house with a secondary suite, existing unlabelled doors at least 45 mm solid core wood or metal clad are acceptable. For existing closures, ratings of 20 min will not be required where the entire floor area is sprinklered. C161 | 9.10.13.2.(1) | In a building containing not more than four dwelling units or suites, existing glazed solid wood doors to corridors may remain in lieu of new 20 min doors, provided they are not located in a dead-end corridor. C162 | 9.10.13.3. | Existing acceptable provided that wood door frames are secured with hinge screws going through frame into the stud. C163 | 9.10.13.5. | Existing wired glass acceptable. Existing transoms or sidelights located in required Fire separations may be retained if wired glass, at least 6 mm thick, is securely fixed to a wood frame of at least 50 mm thickness with steel stops. Operable transoms shall be fixed closed. C164 | 9.10.13.6. | Existing steel door frames acceptable. C165 | 9.10.13.7. | Existing glass block acceptable. C166 | 9.10.13.8. | Existing sizes acceptable. C167 | 9.10.13.9. | Existing operable latches acceptable. C168 | 9.10.13.10.(1) | Existing functionally operable self-closing devices acceptable. C169 | 9.10.13.11. | Existing operable self-releasing electromagnetic hold-open device acceptable, and except for hotels, fusible link hold-open devices acceptable. C170 | 9.10.13.12. | Existing swings acceptable. C171 | 9.10.13.13.(1) | Except as permitted in C.A. C172, in a building containing not more than four dwelling units, the existing heating or air-conditioning system may be altered to serve more than one dwelling unit, provided smoke alarms are installed in each dwelling unit and provided a smoke detector is installed in the supply or return air duct system serving the entire building which would turn off the fuel supply and electrical power to the heating system upon activation of such detector. C172 | 9.10.13.13.(1) | In detached houses, semi-detached houses, townhouses and row houses containing not more than two dwelling units, or houses with a secondary suite, existing acceptable. C173 | 9.10.13.14.; 9.10.5.1. | Except as permitted in C.A. C174, in a building containing not more than four dwelling units, the existing heating or air-conditioning system may be altered to serve more than one dwelling unit, provided smoke alarms are installed in each dwelling unit and provided a smoke detector is installed in the supply or return air duct system serving the entire building which would turn off the fuel supply and electrical power to the heating system upon activation of such detector. C174 | 9.10.13.14.; 9.10.5.1. | In an individual dwelling unit or a house with a secondary suite, existing acceptable. C175 | 9.10.14.2.(2) and (3); 9.10.14.4.(2); 9.10.15.2.(3) and (4); 9.10.15.4.(9) | Where an addition to an existing residential building has its exposing building face further distant from the line than the existing exposing building face and the limiting distance is at least 1,200 mm, the total area of allowable unprotected openings may be determined under Sentence 9.10.14.2.(2) or 9.10.15.2.(3) for the combined new and existing exposing building faces and: (a) Where the existing exposing building face has no unprotected openings, or the existing unprotected openings are to be filled in, the total allowable area of unprotected openings may be installed in the new exposing building face. (b) Where the existing unprotected openings are to remain: (i) Their area shall be deducted from the total allowable area of unprotected openings, and the balance may be installed in the new exposing building face. (ii) Sentences 9.10.14.2.(3) and 9.10.14.4.(2) or Sentences 9.10.15.2.(4) and 9.10.15.4.(9) apply only to the new exposing building face. C176 | 9.10.14.4.; 9.10.15.4. | Existing windows. (a) Existing windows in walls may be relocated to another part of the wall, provided the existing opening is blocked up to provide the same fire rating for the wall, and the projection of the new opening, at a right angle to the property line onto another building, lies no closer than 300 mm from a window in such other building, where the "opposite" window is less than 2,400 mm from the opposite new opening. (b) Except relocation of units, to be restricted to the same fire compartment and shall conform to the requirements of Article 3.2.3.14. or 9.10.12.3. where applicable. (c) Where a building does not satisfy the requirements of Subsection 3.2.3. for the amount of openings facing a yard or space that does not have sufficient limiting distance, such existing openings are allowed to be relocated provided: (i) Such openings are not increased in size and they are protected with wired glass in steel frames conforming to Sentence 3.1.8.16.(2). (ii) The building is sprinklered. C177 | 9.10.16.2.(1) | Where balloon framing is exposed during renovation, fire blocks shall be provided. C178 | 9.10.18. | (a) Subject to approval by the chief building official, existing fire alarm system may remain where the fire safety plan (as described in the Fire Code made under the Fire Protection and Prevention Act, 1997) for the building addresses the intent of Subsection 3.2.4. (i.e. "stage" system, electrical supervision, detection as required, Fire Department connection, and emergency power supply). (b) Extension of an existing system must ensure continuity and compatibility, and integrity of the system. C179 | 9.10.19.4. | Smoke alarms may be battery operated. C180 | 9.10.20. | Existing access acceptable. C181 | 9.11.1.1. | Where a house contains a secondary suite, each dwelling unit shall be separated from every other space in the house in which noise may be transmitted by: (a) Construction: (i) Whose joist spaces are filled with sound-absorbing material of not less than 150 mm nominal thickness. (ii) Whose stud spaces are filled with sound-absorbing material. (iii) Having a resilient channel on one side of the separation spaced 400 or 600 mm o.c. (iv) Having not less than 12.7 mm thick gypsum board on ceilings and on both sides of walls. (b) Construction providing an STC rating of not less than 43. (c) A separating assembly and adjoining constructions, which together provide an ASTC rating of not less than 40. C182 | 9.14.2.1.(1.1) | Existing acceptable. C183 | 9.18.2. | Existing access acceptable. C184 | 9.18.3. | Existing vents and ventilation acceptable. C185 | 9.19. | Existing acceptable. C186 | 9.20.2.2. | Used masonry may be reused for patching and filling openings to match adjacent work. Used interior brick may not be used for exterior applications. C187 | 9.20.3. | Archaic mortars may be used to match existing jointing. C188 | 9.20.4.1. | Sound jointing techniques may be employed to match existing archaic joints. C189 | 9.20.12.1. | Corbelling may be constructed to match existing or original details, provided that it is structurally adequate for the proposed use. C190 | 9.21. | Existing acceptable, provided the products of combustion are safely vented and provided no fire hazard is created. C191 | 9.22.1. to 9.22.7. | Sound period materials, designs and techniques may be employed in recreated fireplaces, provided no fire hazard is created. Existing need not comply with Article 9.22.1.4. C192 | 9.23. | Existing acceptable. C193 | 9.24. | Existing acceptable. C194 | 9.25. | A vapour barrier may consist of paint or other coating with specified perm rating such as two coats of leafing aluminum pigmented paint. C195 | 9.26. | Existing acceptable, except when removing and replacing shingles, comply with the eave protection requirements of Subsection 9.26.5. C196 | 9.27. | Existing acceptable. C197 | 9.28. | All replacement or recreation of existing stucco may be compatible with the existing materials and application. C198 | 9.29.4. | Existing acceptable. All replacement or recreation of existing plaster may be compatible with the existing materials and application. C199 | 9.32. | In an individual dwelling unit or a house with a secondary suite, rooms or spaces shall be ventilated by natural means in accordance with Subsection 9.32.2. or by providing adequate mechanical ventilation. C200 | 9.32.3.9C. | Carbon monoxide alarms may be battery operated or plugged into an electrical outlet. C201 | 9.33.1.1. | In a building containing not more than four dwelling units, the existing heating or air-conditioning system may be altered to serve more than one dwelling unit, provided smoke alarms are installed in each dwelling unit and provided a smoke detector is installed in the supply or return air duct system serving the entire building which would turn off the fuel supply and electrical power to the heating system upon activation of such detector. C202 | 9.33.5.3. | Sound, used or antique appliances are acceptable, provided that: (a) Visual examination shows no excessive weakening by corrosion or other damage. (b) No structural parts are missing. (c) No cracks are present in the components intended to support the appliance or enclose the fire. (d) Loading and ash removal door latches and hinges hold the door closed. C203 | 9.33.6.5.(1); 9.33.6.6.(1) to (3), (5), (11) and (12) | Existing acceptable. C204 | 9.33.6.6.(8) | Where the duct system is being altered, lesser amounts and extent of insulation will be permitted. C205 | 9.33.6.13.(7.1) | In a building containing not more than four dwelling units or residential suites, the existing heating or air-conditioning system may be altered to serve more than one dwelling unit or suite, provided smoke alarms are installed in each dwelling unit or suite and provided a smoke detector is installed in the supply or return air duct system serving the entire building which would turn off the fuel supply and electrical power to the heating system upon activation of such detector. C206 | 9.38. | Sound used materials shall be acceptable for reuse, subject to the following limitations: (a) Visual examination shows no excessive weakening by holes, notches, nail splits or other damage. (b) Logs have not been subjected to termite infestation. C207 | 12.2.1.2.(3) | (a) Where the framing systems are being altered to match the existing framing, lesser amounts and extent of insulation and vapour barrier is acceptable. (b) Existing acceptable for Article 2.1.1.9. of MMA Supplementary Standard SB-12, "Energy Efficiency for Housing". (c) Existing previously occupied log houses that are dismantled and reconstructed are exempt from Article 3.1.1.6. of MMA Supplementary Standard SB-12, "Energy Efficiency for Housing".
OBC Div. C 1.2.2.1. General Review by Architect or Professional Engineer
Open OBC Div. C 1.2.2.1. in the code viewer(1)The construction, including, for greater certainty, enlargement or alteration, of every building or part of it described in Table 1.2.2.1. shall be reviewed by an architect or a professional engineer or a combination of both as set out in Column 3 of the Table.
(2)A person who intends to construct or have constructed a building or part of it required by Sentences (1) and (4) to (9) to be reviewed by an architect or a professional engineer or a combination of both, shall ensure that an architect, professional engineer or both are retained to undertake the general review of the construction of the building in accordance with the performance standards of the Ontario Association of Architects or the Association of Professional Engineers of Ontario, as applicable, to determine whether the construction is in general conformity with the plans, sketches, drawings, graphic representations, specifications and other documents that form the basis for the issuance of a permit under section 8 of the Act or any changes to it authorized by the chief building official.
(3)The architect, professional engineer or both who have been retained to undertake the general review of the construction of a building, shall forward copies of written reports arising out of the general review to the chief building official or registered code agency, as the case may be.
(4)The construction of a foundation of a building shall be reviewed by a professional engineer where,
(a)the foundation is to be constructed below the level of the footings of an adjacent building and within the angle of repose of the soil, as drawn from the bottom of the footings, or
(b)underpinning of a foundation is to be undertaken.
(5)The construction of a sprinkler protected glazed wall assembly described in Article 3.1.8.20. of Division B shall be reviewed by a professional engineer.
(6)The construction of a shelf and rack storage system described in Section 3.16. of Division B shall be reviewed by a professional engineer.
(7)The construction of a supporting framing structure and anchorage system for a tent occupying an area greater than 225 m² shall be reviewed by a professional engineer.
(8)The construction of a sign structure shall be reviewed by an architect or a professional engineer or a combination of both, where the sign is,
(a)a ground sign that exceeds 7.5 m in height above the adjacent finished ground,
(b)a projecting sign that weighs more than 115 kg, or
(c)a roof sign that has any face that is more than 10 m².
(9)The construction of a projecting sign attached in any manner to a parapet wall shall be reviewed by an architect, professional engineer or a combination of both.
(10)The construction of a demountable stage or demountable support structure regulated by Section 3.17. of Division B shall be reviewed by a professional engineer.
OBC Div. C Table 1.2.2.1. General Review — Forming Part of Sentence 1.2.2.1.(1)
Open OBC Div. C Table 1.2.2.1. in the code viewerTable 1.2.2.1. General Review — Forming Part of Sentence 1.2.2.1.(1) Forming Part of Sentence 1.2.2.1.(1) Building Classification by Major Occupancy[5] | Building Description | General Review by: Assembly occupancy only | Every building | Architect and professional engineer[1] Assembly occupancy and any other major occupancy except industrial | Every building | Architect and professional engineer[1] Care, care and treatment or detention occupancy only | Every building | Architect and professional engineer[1] Care, care and treatment or detention occupancy and any other major occupancy except industrial | Every building | Architect and professional engineer[1] Residential occupancy only, other than retirement homes | Every building that exceeds 3 storeys in building height | Architect and professional engineer[1] Residential occupancy only, other than retirement homes | Every building that exceeds 600 m² in gross area and that contains a residential occupancy other than a dwelling unit or dwelling units | Architect[2] Residential occupancy only, other than retirement homes | Every building that exceeds 600 m² in gross area and contains a dwelling unit above another dwelling unit | Architect[2] Residential occupancy only, other than retirement homes | Every building that exceeds 600 m² in building area, contains 3 or more dwelling units and has no dwelling unit above another dwelling unit | Architect[2] Residential occupancy, other than retirement homes, and any other major occupancy except assembly, care, care and treatment, detention or industrial occupancy | Every building that exceeds 600 m² in gross area or 3 storeys in building height | Architect and professional engineer[1] Retirement home only | Every building | Architect and professional engineer[1] Retirement home and any major occupancy except industrial | Every building | Architect and professional engineer[1] Business and personal services occupancy only | Every building that exceeds 600 m² in gross area or 3 storeys in building height | Architect and professional engineer[1] Business and personal services occupancy and any other major occupancy except assembly, care, care and treatment, detention or industrial occupancy | Every building that exceeds 600 m² in gross area or 3 storeys in building height | Architect and professional engineer[1] Mercantile occupancy only | Every building that exceeds 600 m² in gross area or 3 storeys in building height | Architect and professional engineer[1] Mercantile occupancy and any other major occupancy except assembly, care, care and treatment, detention or industrial occupancy | Every building that exceeds 600 m² in gross area or 3 storeys in building height | Architect and professional engineer[1] Industrial occupancy only and where there are no subsidiary occupancies | Every building that exceeds 600 m² in gross area or 3 storeys in building height | Architect or professional engineer[3] Industrial occupancy and one or more other major occupancies where the portion of the area occupied by one of the other major or subsidiary occupancies exceeds 600 m² | The non-industrial portion of every building | Architect and professional engineer[1] Industrial occupancy and one or more other major occupancies where the portion of the area occupied by one of the other major or subsidiary occupancies exceeds 600 m² | The industrial portion of every building | Architect or professional engineer[3] Industrial occupancy and one or more other major occupancies where no portion of the area occupied by one of the other major or subsidiary occupancies exceeds 600 m² | Every building that exceeds 600 m² in gross area or 3 storeys in building height | Architect or professional engineer[3] Agricultural occupancy only and where there are no subsidiary occupancies | Every building that exceeds 600 m² in gross area or 3 storeys in building height | Architect or professional engineer[3] Agricultural occupancy and one or more other major occupancies where the portion of the area occupied by one of the other major or subsidiary occupancies exceeds 600 m² | The non-agricultural portion of every building | Architect and professional engineer[1] Agricultural occupancy and one or more other major occupancies where the portion of the area occupied by one of the other major or subsidiary occupancies exceeds 600 m² | The agricultural portion of every building | Architect or professional engineer[3] Agricultural occupancy and one or more other major occupancies where no portion of the area occupied by one of the other major or subsidiary occupancies exceeds 600 m² | Every building that exceeds 600 m² in gross area or 3 storeys in building height | Architect or professional engineer[3] Column 1 | Column 2 | Column 3 Notes to Table 1.2.2.1.: (1) An architect shall provide general review services within the practice of architecture and a professional engineer shall provide general review services within the practice of professional engineering. (2) An architect may engage a professional engineer to provide general review services within the practice of professional engineering. (3) Only a professional engineer may provide general review services within the practice of professional engineering. (4) Requirements for general review by an architect or a professional engineer or a combination of both for the construction, including, for greater certainty, enlargement or alteration, of a building are set out in the Architects Act and the Professional Engineers Act. (5) For purposes of Table 1.2.2.1., a retirement home is deemed to be a separate major occupancy.
OBC Div. C 1.3.1.1. Requirement for Permits
Open OBC Div. C 1.3.1.1. in the code viewer(1)A person is exempt from the requirement to obtain a permit under section 8 of the Act,
(a)for the demolition of a farm building located on a farm,
(b)subject to Sentence (2), for the construction or demolition of a building in territory without municipal organization, or
(c)for the construction of a Class 1 sewage system.
(2)The exemption in Clause (1)(b) from the requirement to obtain a permit does not apply to the construction of a sewage system in territory without municipal organization.
(3)The application for a permit respecting the demolition of a building to which Sentence 1.2.2.3.(1) applies shall include descriptions of the structural design characteristics of the building and the method of demolition of the building.
(4)No person shall commence demolition of a building or any part of a building before the building has been vacated by the occupants except where the safety of the occupants is not affected.
(5)A tent or group of tents is exempt from the requirement to obtain a permit under section 8 of the Act and is exempt from compliance with the Code provided that the tent or group of tents are,
(a)not more than 60 m² in aggregate ground area,
(b)not attached to a building, and
(c)constructed more than 3 m from other structures.
(6)A shed is exempt from the requirement to obtain a permit under section 8 of the Act and is exempt from compliance with this Code, provided that the shed,
(a)is not more than 15 m² in gross area,
(b)is not more than one storey in building height,
(c)is not attached to a building or any other structure,
(d)is used only for storage purposes ancillary to a principal building on the lot, and
(e)does not have plumbing.
(7)A demountable stage or demountable support structure not regulated by Section 3.17. of Division B is exempt from the requirement to obtain a permit under section 8 of the Act and is exempt from compliance with this Code.
OBC Div. C 1.3.3.1. Occupancy Permit — General
Open OBC Div. C 1.3.3.1. in the code viewer(1)Except as permitted in Sentence 1.3.3.2.(1), a person may occupy or permit to be occupied any building or part of it that has not been fully completed at the date of occupation where the chief building official or a person designated by the chief building official has issued a permit authorizing occupation of the building or part of it prior to its completion in accordance with Sentence (3).
(2)Sentence (1) does not apply in respect of the occupancy of a building to which Article 1.3.3.4., 1.3.3.5. or 1.3.3.7. applies or a building or part of it to which Article 1.3.3.8. applies.
(3)The chief building official or a person designated by the chief building official shall issue a permit authorizing occupation of a building, where,
(a)the structure of the building or part of it is completed to the roof,
(b)the enclosing walls of the building or part of them are completed to the roof,
(c)the walls enclosing the space to be occupied are completed, including balcony guards,
(d)all required fire separations and closures are completed on all storeys to be occupied,
(e)all required exits are completed, including all fire separations, doors, door hardware, self-closing devices, guards and handrails, from the uppermost floor to be occupied down to grade level and below if an exit connects with lower storeys,
(f)all shafts including closures are completed to the floor-ceiling assembly above the storey to be occupied and have a temporary fire separation at such assembly,
(g)measures have been taken to prevent access to parts of the building and site that are incomplete or still under construction,
(h)floors, halls, lobbies and required means of egress are free of loose materials and other hazards,
(i)if service rooms should be in operation, required fire separations and closures are completed,
(j)all building drains, building sewers, water systems, drainage systems and venting systems are complete and tested as operational for the storeys to be occupied,
(k)required lighting, heating and electrical supply are provided for the suites, rooms and common areas to be occupied,
(l)required lighting in corridors, stairways and exits is completed and operational up to and including all storeys to be occupied,
(m)required standpipe, sprinkler and fire alarm systems are complete and operational up to and including all storeys to be occupied, together with required pumper connections for such standpipes and sprinklers,
(n)required fire extinguishers have been installed on all storeys to be occupied,
(o)main garbage rooms, chutes and ancillary services are completed to all storeys to be occupied,
(p)required firefighting access routes have been provided and are accessible, and
(q)the sewage system has been completed and is operational.
(4)Where a registered code agency has been appointed to perform the functions described in clause 4.1(4)(b) or (c) of the Act in respect of the construction of the building, the chief building official or a person designated by the chief building official shall issue the permit referred to in Sentence (3) after receipt of a certificate for the occupancy of a building not fully completed issued by the registered code agency in respect of the building.
(5)Where applicable, the chief building official or a person designated by the chief building official shall not issue a permit authorizing occupation of the building or part of it, unless compliance with section 168.3.1 of the Environmental Protection Act has been achieved.
OBC Div. C 2.1.1.1. Documentation
Open OBC Div. C 2.1.1.1. in the code viewer(1)The person proposing the use of an alternative solution shall provide documentation to the chief building official or registered code agency that,
(a)identifies applicable objectives, functional statements and acceptable solutions, and
(b)establishes on the basis of past performance, tests described in Article 2.1.1.2. or other evaluation that the proposed alternative solution will achieve the level of performance required under Article 1.2.1.1. of Division A.
(2)The documentation described in Sentence (1) shall include information about relevant assumptions, limiting or restricting factors, testing procedures, studies or building performance parameters, including any commissioning, operational and maintenance requirements.
OBC Div. C 2.1.1.2. Tests
Open OBC Div. C 2.1.1.2. in the code viewer(1)Where no published test method to establish the suitability of an alternative solution proposed under Article 2.1.1.1. exists, then the tests used for the purposes of that Article shall be designed to simulate or exceed anticipated service conditions or shall be designed to compare the performance of the material or system with a similar material or system that is known to be acceptable.
(2)The results of tests or evaluations based on test standards, other than as described in this Code, may be used for the purposes of Sentence (1), if the alternate test standards provide comparable results.
OBC Div. C 2.4.2.1. Criteria
Open OBC Div. C 2.4.2.1. in the code viewer(1)Sentence (2) sets out criteria to be followed by the Minister when making a ruling under clause 29(1)(c) of the Act to approve the use of an alternative material, system or building design.
(2)The Minister’s approval of the use of an alternative material, system or building design referred to in Sentence (1) may be granted only if the approval is consistent with,
(a)a decision of the Building Code Commission in respect of a dispute described in clause 24(1)(a) of the Act,
(b)an approval of the use of the material, system or building design in the whole of another province or territory in accordance with the law of that province or territory, or
(c)a revision of the NRCC-CONST-56435E 2020, “National Building Code of Canada”, or the NRCC-CONST-56436E 2020, “National Plumbing Code of Canada”, that has been approved by the Canadian Commission on Building and Fire Codes.
OBC Div. C 2.4.3.1. Interpretations By Minister
Open OBC Div. C 2.4.3.1. in the code viewer(1)Every interpretation issued by the Minister under section 28.1 of the Act shall be made available to the public,
(a)by posting the interpretation on the Building Code website, and
(b)by providing a written copy of the interpretation on receipt of a request for it.