Values this chapter turns on
- washroom exhaust per water closet, urinal or shower
- 24 L/s
- washroom exhaust per water closet, urinal or shower
- max carbon monoxide in a ventilated storage garage
- 100 ppm
- max carbon monoxide in a ventilated storage garage
- indoor design temperature, Group B-2, B-3 and C
- 22°C
- indoor design temperature, Group B-2, B-3 and C
- max surface temperature of exposed hot piping
- 52°C
- max surface temperature of exposed hot piping
Part 6 governs heating, ventilating and air-conditioning for every building that is not a single dwelling unit handled by Part 9. It is short, but it leans heavily on other documents: ASHRAE 62.1 for ventilation rates, NFPA 96 for kitchen exhaust, CSA B52 for refrigeration, NFPA 211 for large chimneys, and Subsection 3.6.5. for the fire safety of ducts. The exam will not ask what those standards say. It asks when Part 6 sends you to them, plus the handful of numbers Part 6 states itself.
General, design and installation (6.1 and 6.2)
Part 6 applies to all HVAC systems and equipment OBC Div. B 6.1.1.2.OBC Div. B 6.1.1.2. Application(1) This Part applies to systems and equipment for heating, ventilating and air-conditioning services.. Where an existing system's method of operation is altered, any repair or replacement that changes its capacity or safety must meet the code OBC Div. B 6.1.1.1.OBC Div. B 6.1.1.1. Scope(1) The scope of this Part shall be as described in Subsection 1.3.3. of Division A. (2) Where the method of operation of an existing heating, ventilating or air-conditioning system is altered, the repair or component replacements that change the capacity or extent of safety of the system shall conform to this Code….
Design follows good engineering practice such as ASHRAE Handbooks and Standards, the HRAI Digest, SMACNA Manuals, NFPA Standards, the ACGIH Industrial Ventilation manual and CAN/CSA-Z317.2 for health care facilities OBC Div. B 6.2.1.1.OBC Div. B 6.2.1.1. Good Engineering Practice(1) Heating, ventilating and air-conditioning systems, including mechanical refrigeration equipment, shall be designed, constructed and installed in conformance with good engineering practice such as that described in, but not limited to, (a) the ASHRAE Handbooks and Standards, (b) the HRAI Digest, (c) the Hydronics….
| Building | Minimum indoor design temperature at outdoor winter design |
|---|---|
| Group B, Division 2 or 3, and Group C, occupied all winter | 22°C (and the building must be insulated) |
| All other buildings occupied all winter | 18°C, or a temperature suited to the use |
Source: OBC Div. B 6.2.1.1A.OBC Div. B 6.2.1.1A. Design Indoor Air Temperatures(1) Buildings classified as Group B, Division 2 or 3 occupancies or Group C residential occupancies that are intended for use in the winter months on a continuing basis shall be insulated and be equipped with heating facilities that are capable of maintaining an indoor air temperature of 22°C at the outside winter…. Outdoor design values come from SB-1 OBC Div. B 6.2.1.2.OBC Div. B 6.2.1.2. Outdoor Design Conditions(1) The outdoor conditions to be used in designing heating, ventilating and air-conditioning systems shall be determined in conformance with MMAH Supplementary Standard SB-1, "Climatic and Seismic Data.".
Which installation standard applies OBC Div. B 6.2.1.5.OBC Div. B 6.2.1.5. Installation Standards(1) The installation of solid fuel-burning appliances for central heating systems shall comply with CSA B365, "Installation code for solid-fuel-burning appliances and equipment" and the manufacturer's installation instructions. (2) The solid fuel-fired appliances in Sentence (1) shall conform to CSA B366.1…:
| Equipment | Standard named in the code |
|---|---|
| Solid-fuel central heating appliances (installation) | CSA B365 plus manufacturer's instructions; appliance built to CSA B366.1 |
| Earth energy system, house or building up to 1,400 m² conditioned | CAN/CSA-C448.2 |
| Earth energy system, other building over 1,400 m² | CAN/CSA-C448.1 |
| Hydronic heating | CSA B214 or good engineering practice |
| Indoor incinerator | NFPA 82 OBC Div. B 6.2.2.1.OBC Div. B 6.2.2.1. Applicable Standard(1) The design, construction, installation and material alteration of every indoor incinerator shall conform to NFPA 82, "Standard on Incinerators and Waste and Linen Handling Systems and Equipment." |
Other general items: maintenance access to equipment, guards on mechanical equipment, freeze protection OBC Div. B 6.2.1.6.OBC Div. B 6.2.1.6. Installation — General(1) Equipment requiring periodic maintenance and forming part of a heating, ventilating or air-conditioning system shall be installed with provision for access for inspection, maintenance, repair and cleaning. (See Note A-6.2.1.6.(1)) (2) Mechanical equipment shall be provided with guards so as to prevent injury. (3)…; no asbestos OBC Div. B 6.2.1.7.OBC Div. B 6.2.1.7. Asbestos(1) Asbestos shall not be used in heating, ventilating or air-conditioning systems or equipment.; combustible pneumatic control tubing is allowed in noncombustible buildings up to 10 mm outside diameter OBC Div. B 6.2.1.8.OBC Div. B 6.2.1.8. Combustible Tubing(1) Combustible tubing for pneumatic controls may be used in buildings required to be of noncombustible construction provided it has an outside diameter not exceeding 10 mm..
Ventilation and air duct systems (6.3.1 and 6.3.2)
Outdoor air rates come from ANSI/ASHRAE 62.1 (Ventilation Rate Procedure, Indoor Air Quality Procedure, or Natural Ventilation Procedure except for residential occupancies), and exhaust from its Section 6.5 as a minimum OBC Div. B 6.3.1.1.OBC Div. B 6.3.1.1. Required Ventilation(1) Except as provided in Sentence (4), all buildings shall be ventilated in accordance with this Section. (2) Except in storage garages and repair garages covered by Article 6.3.1.3., outdoor air shall be supplied to buildings for ventilation purposes in accordance with one of the following Sections of ANSI/ASHRAE…. Garages are the exception: they have their own rules. A self-contained heating-season system for one dwelling unit goes to 9.32.3.
Mechanical is the default. Natural ventilation is allowed only for non-residential buildings with no more than one person per 40 m², industrial buildings whose process needs large openings, seasonal buildings, or where engineering data shows natural ventilation works OBC Div. B 6.3.1.1A.OBC Div. B 6.3.1.1A. Natural Ventilation(1) Except as permitted by Sentence (2), the ventilation required by Article 6.3.1.1. shall be provided by mechanical ventilation except that it can be provided by natural ventilation or a combination of natural and mechanical ventilation in (a) buildings of other than residential occupancy having an occupant load of….
Storage garages for 5 or more vehicles need mechanical ventilation designed to one of three criteria OBC Div. B 6.3.1.3.OBC Div. B 6.3.1.3. Ventilation of Storage and Repair Garages(1) Except as provided in Sentences (4) and (6), an enclosed storage garage for five or more motor vehicles shall have a mechanical ventilation system designed to (a) limit the concentration of carbon monoxide to not more than 100 parts per million parts of air, (b) limit the concentration of nitrogen dioxide to not…:
| Option | Limit or rate | Control |
|---|---|---|
| Carbon monoxide | Not more than 100 ppm | CO monitors |
| Nitrogen dioxide (mostly diesel vehicles) | Not more than 3 ppm | NO₂ monitors |
| Continuous outdoor air | At least 3.9 L/s per m² of floor area during operating hours | Runs continuously |
The garage is kept at lower pressure than adjoining occupancies; mechanical parking halves the requirement; open-air storeys are exempt. A repair garage bay not next to an outside door needs at least 700 L/s of general ventilation per internal bay, unless tailpipes connect to local exhaust.
Commercial cooking ventilation follows NFPA 96 OBC Div. B 6.3.1.6.OBC Div. B 6.3.1.6. Commercial Cooking Equipment(1) Except as provided in Article 3.6.3.5., all commercial cooking equipment shall be provided with ventilation systems designed, constructed and installed to conform to NFPA 96, "Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations.". Refrigeration machinery rooms are ventilated per CSA B52 OBC Div. B 6.3.1.5.OBC Div. B 6.3.1.5. Indoor Air Contaminants(1) Air contaminants of concern within buildings shall (a) be removed insofar as is possible at their points of origin, and (b) not be permitted to accumulate in concentrations greater than those permitted by good engineering practice such as that described in the publications listed in Sentence 6.2.1.1.(1), measured…. HRVs of 25 to 200 L/s are installed per 9.32.3. OBC Div. B 6.3.1.4.OBC Div. B 6.3.1.4. Heat Recovery Ventilators(1) Heat recovery ventilators with rated capacities of not less than 25 L/s and not more than 200 L/s shall be installed in accordance with Subsection 9.32.3..
Air duct systems. Materials, linings, clearances, tape and vibration connectors all point to Subsection 3.6.5. OBC Div. B 6.3.2.3.OBC Div. B 6.3.2.3. Materials in Air Duct Systems(1) All ducts, duct connectors, associated fittings and plenums used in air duct systems shall be constructed of materials as described in Article 3.6.5.1. (2) Ducts that are used in a location where they may be subjected to excessive moisture shall have no appreciable loss of strength when wet and shall be resistant…. Rules stated in Part 6 itself:
- In a residential occupancy, air from one suite is not circulated to another suite or a public corridor; garage duct systems are not directly interconnected with the rest of the building OBC Div. B 6.3.2.7.OBC Div. B 6.3.2.7. Interconnection of Systems(1) In a residential occupancy, air from one suite shall not be circulated to any other suite or to a public corridor. (2) Except as permitted by Sentences (3) and 6.3.2.10.(6), air duct systems serving storage garages shall not be directly interconnected with other parts of the building. (3) Exhaust ducts referred to….
- A public corridor or exit is never a return-air plenum OBC Div. B 6.3.2.11.OBC Div. B 6.3.2.11. Return-Air System(1) Return-air systems shall comply with Article 3.6.5.8. (2) Where a ceiling space is used as a return-air plenum, the requirements of Article 3.6.4.3. shall apply. (3) A public corridor or exit shall not be used as a return-air plenum. (4) The return-air system shall be designed to handle the entire air supply. (5)….
- Makeup air must be interlocked with the exhaust it serves, and tempered if it enters occupied areas in winter OBC Div. B 6.3.2.8.OBC Div. B 6.3.2.8. Makeup Air(1) In ventilating systems that exhaust air to the outdoors, provision shall be made for the admission of a supply of makeup air in sufficient quantity so that the operation of the exhaust system and other exhaust equipment or combustion equipment is not adversely affected. (2) Makeup air facilities required by….
- Openings less than 2 m above the floor get grilles that stop a 15 mm sphere; outdoor intakes sit at least 0.3 m above roofs or grade (allowing for snow) OBC Div. B 6.3.2.9.OBC Div. B 6.3.2.9. Supply, Return, Intake and Exhaust Air Openings(1) Supply, return and exhaust air openings located less than 2 m above the floor in rooms or spaces in buildings shall be protected by grilles having openings of a size that will not allow the passage of a 15 mm diam sphere. (2) Outdoor air intakes shall be located so that (a) the quality of the air entering the….
- Intake separation from contaminant sources comes from the intake distance table: for example 3.5 m from a sanitary vent, 3.0 m from a kitchen exhaust outlet, 7.6 m from a truck loading dock OBC Div. B Table 6.3.2.9.OBC Div. B Table 6.3.2.9. Minimum Distances of Air Intakes from Sources of Contaminants — Forming Part of Sentence 6.3.2.9.(2)Table 6.3.2.9. Minimum Distances of Air Intakes from Sources of Contaminants — Forming Part of Sentence 6.3.2.9.(2) Source of Contaminants | Minimum Distance of Outdoor Air Intake, m Garage entry of a garage for 5 or more motor vehicles, automobile loading area and drive-in queue | 4.5 Truck loading area or dock, and….
- Washroom exhaust is at least 24 L/s per water closet, urinal, shower or slop sink, in ducts independent of other exhaust unless interconnected at a fan inlet with backdraft protection or into a continuously exhausted shaft OBC Div. B 6.3.2.10.OBC Div. B 6.3.2.10. Exhaust Ducts and Outlets(1) Except as provided in Sentence (2), exhaust ducts of non-mechanical ventilating systems serving separate rooms or spaces shall not be combined. (2) Exhaust ducts of non-mechanical ventilating systems serving similar occupancies may be combined immediately below the point of final delivery to the outdoors, such as….
- Filters are Class 2 under CAN/ULC-S111 OBC Div. B 6.3.2.13.OBC Div. B 6.3.2.13. Filters(1) Air filters for air duct systems shall conform to the requirements for Class 2 air filter units as described in CAN/ULC-S111, "Standard Method of Fire Tests for Air Filter Units." (2) When electrostatic-type filters are used, they shall be installed so as to ensure that the electric circuit is automatically….
- Cooling tower (evaporative heat rejection) discharge is kept 7.6 m from outdoor air intakes and 3 m from operable windows and doors OBC Div. B 6.3.2.15.OBC Div. B 6.3.2.15. Evaporative Heat Rejection Systems(1) Evaporative heat rejection systems shall (a) incorporate a drift eliminator or other means to minimize the dispersion of entrained water droplets, and (b) have a design discharge velocity that does not exceed the maximum discharge velocity recommended by the manufacturer. (2) Evaporative heat rejection systems….
Chimneys, venting and laboratory ventilation (6.3.3 and 6.3.4)
Oil, gas and solid-fuel appliances are vented under their installation standards OBC Div. B 6.3.3.1.OBC Div. B 6.3.3.1. Requirement for Venting(1) Except as provided in Articles 6.3.3.2. and 6.3.3.3., the products of combustion from oil-, gas and solid-fuel-burning appliances shall be vented in conformance with the requirements in the applicable appliance installation standard listed in Article 6.2.1.5. (2) Except as provided in Article 6.2.1.5., vented…. Other vented combustion products discharge at least 2.15 m above sidewalks and driveways and 3 m from air intakes, doors, operable windows and occupiable outdoor spaces.
A rectangular masonry or concrete chimney up to 12 m high serving appliances totalling 120 kW output or less, or serving fireplaces, is built to Part 9; any other masonry chimney, and every single-wall metal smoke stack, follows NFPA 211 OBC Div. B 6.3.3.2.OBC Div. B 6.3.3.2. Masonry or Concrete Chimneys(1) Rectangular masonry or concrete chimneys not more than 12 m in height shall conform to Part 9 if they serve (a) appliances with a combined total rated heat output of 120 kW or less, or (b) fireplaces. (2) Masonry or concrete chimneys other than those described in Sentence (1) shall be designed and installed in… OBC Div. B 6.3.3.3.OBC Div. B 6.3.3.3. Metal Smoke Stacks(1) Single wall metal smoke stacks shall be designed and installed in conformance with NFPA 211, "Standard for Chimneys, Fireplaces, Vents and Solid Fuel-Burning Appliances.". External chimney ladder rungs start at least 2.5 m above ground OBC Div. B 6.3.3.4.OBC Div. B 6.3.3.4. Access Ladders(1) Access ladders for chimneys, when provided, shall consist of steel or bronze rungs, built into the walls of the chimneys. (2) Rungs for external ladders shall begin at not less than 2.5 m from ground level..
Laboratories using dangerous goods in hazardous quantities need continuous mechanical ventilation that exhausts outdoors and never returns air to the building, with monitors that show the system is running and alarm on malfunction OBC Div. B 6.3.4.2.OBC Div. B 6.3.4.2. General Ventilation(1) A laboratory shall be provided with continuous mechanical ventilation designed to ensure that dangerous goods vapours and particles (a) do not accumulate in the laboratory, (b) are prevented from migrating to other parts of the building, (c) do not accumulate in the ventilation system, (d) are exhausted to the…. A power-ventilated enclosure exhaust follows NFPA 91, with control switches outside the enclosure OBC Div. B 6.3.4.3.OBC Div. B 6.3.4.3. Enclosure Exhaust Ventilation(1) The ventilation system for a power-ventilated enclosure referred to in Article 6.3.4.2A. shall (a) conform to NFPA 91, "Standard for Exhaust Systems for Air Conveying of Vapors, Gases, Mists, and Particulate Solids." (b) provide continuous exhaust ventilation at an air velocity sufficient to prevent the…; combustible enclosure materials (allowed only where the dangerous goods require them) need a flame-spread rating of 25 or less unless an automatic fire suppression system is provided inside the enclosure and its exhaust duct system OBC Div. B 6.3.4.4.OBC Div. B 6.3.4.4. Enclosure Construction(1) The power-ventilated enclosure referred to in Article 6.3.4.2A. and its exhaust duct system shall (a) except as provided in Sentences (2) and (3), be constructed of noncombustible materials compatible with and chemically resistant to the dangerous goods vapours and particles being exhausted, and (b) be provided….
Heating appliances, insulation and refrigeration (6.4 to 6.6)
- Fuel-fired heating appliances (outside dwelling units) are located or separated per Section 3.6 OBC Div. B 6.4.1.1.OBC Div. B 6.4.1.1. Location of Appliances(1) Except for appliances installed in dwelling units, fuel-fired heating appliances shall be located, enclosed or separated from the remainder of the building in conformance with Section 3.6. (See also Subsection 9.10.10.).
- An appliance outside the building must be rated for outdoor use, at least 1,200 mm from the property line, and at least 3 m from a wall with openings within 3 storeys above and 5 m horizontally, unless those openings have 45 min closures or wired glass OBC Div. B 6.4.1.2.OBC Div. B 6.4.1.2. Appliances Installed Outside the Building(1) Fuel-fired appliances installed outside a building shall be (a) designed and constructed for outdoor use, (b) installed not less than 1,200 mm from the property line, measured horizontally, and (c) installed not less than 3 m from an adjacent wall of the same building when such wall contains an opening or openings….
- Radiators in a recess or on a combustible or encapsulated mass timber wall need a noncombustible backing OBC Div. B 6.4.3.1.OBC Div. B 6.4.3.1. Lining or Backing(1) A noncombustible lining or backing shall be provided for every steam or hot water radiator and convector (a) located in a recess or concealed space, or (b) attached to the face of a wall of combustible construction or encapsulated mass timber construction. (2) Every steam or hot water radiator and convector shall….
- Exposed piping or equipment that people can touch is insulated to keep the surface at 52°C or less OBC Div. B 6.5.1.1.OBC Div. B 6.5.1.1. Insulation and Coverings(1) Insulation and coverings on pipes shall comply with Article 3.6.5.5. (2) Insulation and coverings on pipes shall be composed of material that will withstand deterioration from softening, melting, mildew and mould at the operating temperature of the system. (3) Exposed piping or equipment subject to human contact….
- A cooling coil with a fuel-fired furnace goes in parallel, upstream (furnace designed for it) or downstream (coil protected against excess temperature and pressure) OBC Div. B 6.6.1.1.OBC Div. B 6.6.1.1. Cooling Units(1) Where a cooling unit is combined with a fuel-fired furnace in the same duct system, the cooling unit shall be installed (a) in parallel with the heating furnace, (b) upstream of the furnace provided the furnace is designed for such application, or (c) downstream of the furnace provided the cooling unit is designed….
Piping, equipment access and fire safety systems (6.7 to 6.9)
Pipe clearance to combustibles: none up to 95°C, 15 mm above 95°C to 120°C, 25 mm above 120°C OBC Div. B Table 6.7.1.2.OBC Div. B Table 6.7.1.2. Clearance Between Steam or Hot Water Pipes and Combustible Material — Forming Part of Article 6.4.2.1., Sentence 6.4.3.1.(2) and Article 6.7.1.2.Table 6.7.1.2. Clearance Between Steam or Hot Water Pipes and Combustible Material — Forming Part of Article 6.4.2.1., Sentence 6.4.3.1.(2) and Article 6.7.1.2. Steam or Water Temperature, °C | Minimum Clearance, mm Up to 95 | No clearance Above 95 to 120 | 15 mm Above 120 | 25 mm. A pipe above 120°C through combustible construction gets a noncombustible sleeve at least 50 mm larger in diameter OBC Div. B 6.7.1.4.OBC Div. B 6.7.1.4. Protection(1) Where a pipe carrying steam or hot water at a temperature above 120°C passes through a combustible floor, ceiling or wall, the construction shall be protected by a sleeve of metal or other noncombustible material not less than 50 mm larger in diameter than the pipe.. Radiator surfaces stay at or below 70°C unless guarded OBC Div. B 6.7.1.3.OBC Div. B 6.7.1.3. Surface Temperature(1) The exposed surface temperature of a steam or hot water radiator shall not exceed 70°C unless precautions are taken to prevent human contact. (See Note A-6.5.1.1.(3)).
An access opening a person could enter must open from inside without keys where it could close accidentally during service OBC Div. B 6.8.1.1.OBC Div. B 6.8.1.1. Access Openings(1) Any covering of an access opening through which a person could enter shall be openable from the inside without the use of keys where there is a possibility of the opening being accidentally closed while the system or equipment is being serviced..
Fire safety of HVAC systems is in Subsection 3.6.5. OBC Div. B 6.9.1.1.OBC Div. B 6.9.1.1. Fire Safety Requirements(1) The fire safety characteristics of heating, ventilating and air-conditioning systems shall comply with Subsection 3.6.5. (2) Characteristics referred to in Sentence (1) include but are not limited to (a) use of combustible materials in duct systems, (b) flame-spread ratings and smoke-developed ratings of duct and…. Fire dampers follow 3.1.8.10. OBC Div. B 6.9.2.1.OBC Div. B 6.9.2.1. Fire Dampers(1) Fire dampers shall conform to Article 3.1.8.10., duct smoke detectors follow 3.2.4.12. OBC Div. B 6.9.2.2.OBC Div. B 6.9.2.2. Smoke Detectors(1) Air handling systems shall incorporate smoke detectors where and as required by Article 3.2.4.12., and smoke-removal exhaust in high buildings follows 3.2.6.6. OBC Div. B 6.9.2.3.OBC Div. B 6.9.2.3. Exhaust Ducts and Outlets(1) Where an exhaust duct system is used for smoke removal in a high building, the requirements of Article 3.2.6.6. shall apply. (2) Where exhaust duct systems from more than one fire compartment are connected to an exhaust duct in a vertical service space, the requirements of Article 3.6.3.4. shall apply.. A duct may penetrate an exit fire separation only if it serves Subsection 3.2.6. or serves only the exit from a dedicated rooftop make-up air unit OBC Div. B 6.9.2.4.OBC Div. B 6.9.2.4. Ducts in Exits(1) Where ducts penetrate fire separations separating exits from the remainder of the building, they shall be in accordance with Article 3.4.4.4. (2) Duct penetration of fire separations separating exits from the remainder of the building is permitted if the duct (a) is designed for the purposes of Subsection 3.2.6.…. Kitchen extinguishing systems for oil or fat cooking are tested to ANSI/CAN/UL/ULC 300 or ULC/ORD-C1254.6 OBC Div. B 6.9.1.3.OBC Div. B 6.9.1.3. Commercial Cooking Equipment(1) Fire protection systems for commercial cooking equipment referred to in Sentence 6.3.1.6.(1) using vegetable oil or animal fat shall conform to (a) ANSI/CAN/UL/ULC 300, "Standard for Fire Testing of Fire Extinguishing Systems for Protection of Commercial Cooking Equipment," or (b) ULC/ORD-C1254.6, "Fire Testing of….
Carbon monoxide alarms in Part 6 buildings mirror the Part 9 rules, extended to care occupancies: in suites with or next to fuel-burning appliances or a storage garage, adjacent to each sleeping room, in public corridors heated by forced-air fuel-burning appliances at no more than 25 m spacing, and in service rooms with fuel-burning appliances outside suites OBC Div. B 6.9.3.2.OBC Div. B 6.9.3.2. Location of Carbon Monoxide Alarms(1) A carbon monoxide alarm shall be installed in a suite of residential occupancy or care occupancy where (a) a fuel-burning appliance or a flue is installed in the suite, (b) a forced-air fuel-burning appliance provides heated air directly to the suite, (c) a fuel-burning appliance or a flue is located in a room… OBC Div. B 6.9.3.3.OBC Div. B 6.9.3.3. Location of Carbon Monoxide Alarms in All Buildings(1) A carbon monoxide alarm shall be installed in service rooms or other areas of a building where the service room or other area (a) contains a fuel-burning appliance used for building services or laundry drying equipment, and (b) is not located within a suite of residential occupancy..
Common traps
- Looking for ventilation rates in Part 6 itself. They are in ASHRAE 62.1, except garages and washroom exhaust.
- Using a public corridor as a return plenum. Never permitted in Part 6.
- Halving the garage ventilation for an ordinary self-park garage. Only mechanical parking qualifies.
- Applying Part 9 chimney rules to a 15 m masonry chimney. Over 12 m, NFPA 211 governs.
- Forgetting that CO alarms in Part 6 also cover care occupancies.
Chapter review
Chapter at a glance
One line per section: the idea to carry into the exam. Then the answers that most often catch candidates out.
- General, design and installation (6.1 and 6.2)
Part 6 applies to all HVAC systems and equipment.
- Ventilation and air duct systems (6.3.1 and 6.3.2)
Outdoor air rates come from ANSI/ASHRAE 62.1 (Ventilation Rate Procedure, Indoor Air Quality Procedure, or Natural Ventilation Procedure except for residential occupancies), and…
- Chimneys, venting and laboratory ventilation (6.3.3 and 6.3.4)
Oil, gas and solid-fuel appliances are vented under their installation standards.
- Piping, equipment access and fire safety systems (6.7 to 6.9)
Pipe clearance to combustibles: none up to 95°C, 15 mm above 95°C to 120°C, 25 mm above 120°C. A pipe above 120°C through combustible construction gets a noncombustible sleeve at…
Usual exam traps
- Looking for ventilation rates in Part 6 itself. They are in ASHRAE 62.1, except garages and washroom exhaust.
- Using a public corridor as a return plenum. Never permitted in Part 6.
- Halving the garage ventilation for an ordinary self-park garage. Only mechanical parking qualifies.
- Applying Part 9 chimney rules to a 15 m masonry chimney. Over 12 m, NFPA 211 governs.
- Forgetting that CO alarms in Part 6 also cover care occupancies.
Practice this chapter
Questions on Heating, ventilating and air-conditioning (Part 6), in the exam format, every answer explained and cited to its article. Sign in to start; a free account gets the free questions.
Code cited in this chapter
Based on the official 2024 Building Code Compendium on ontario.ca.
© King's Printer for Ontario, 2024. Reproduced with permission.
OBC Div. B 6.1.1.2. Application
Open OBC Div. B 6.1.1.2. in the code viewer(1)This Part applies to systems and equipment for heating, ventilating and air-conditioning services.
OBC Div. B 6.1.1.1. Scope
Open OBC Div. B 6.1.1.1. in the code viewer(1)The scope of this Part shall be as described in Subsection 1.3.3. of Division A.
(2)Where the method of operation of an existing heating, ventilating or air-conditioning system is altered, the repair or component replacements that change the capacity or extent of safety of the system shall conform to this Code. (See Note A-6.1.1.1.(2))
OBC Div. B 6.2.1.1. Good Engineering Practice
Open OBC Div. B 6.2.1.1. in the code viewer(1)Heating, ventilating and air-conditioning systems, including mechanical refrigeration equipment, shall be designed, constructed and installed in conformance with good engineering practice such as that described in, but not limited to,
(a)the ASHRAE Handbooks and Standards,
(b)the HRAI Digest,
(c)the Hydronics Institute Manuals,
(d)the NFPA Standards,
(e)the SMACNA Manuals,
(f)the ACGIH manual entitled "Industrial Ventilation: A Manual of Recommended Practice for Design,"
(g)CSA B214, "Installation code for hydronic heating systems,"
(h)CAN/CSA-Z317.2, "Special requirements for heating, ventilation, and air-conditioning (HVAC) systems in health care facilities,"
(i)EPA 625/R-92/016, "Radon Prevention in the Design and Construction of Schools and Other Large Buildings," and
(j)ASHRAE Guideline 12, "Minimizing the Risk of Legionellosis Associated with Building Water Systems."
OBC Div. B 6.2.1.1A. Design Indoor Air Temperatures
Open OBC Div. B 6.2.1.1A. in the code viewer(1)Buildings classified as Group B, Division 2 or 3 occupancies or Group C residential occupancies that are intended for use in the winter months on a continuing basis shall be insulated and be equipped with heating facilities that are capable of maintaining an indoor air temperature of 22°C at the outside winter design temperature referred to in Article 6.2.1.2.
(2)All other buildings intended for occupancy in the winter months on a continuing basis should be insulated and shall be equipped with heating facilities to maintain a minimum indoor air temperature of 18°C or commensurate with the use of the building at the outside winter design temperature described in Article 6.2.1.2.
OBC Div. B 6.2.1.2. Outdoor Design Conditions
Open OBC Div. B 6.2.1.2. in the code viewer(1)The outdoor conditions to be used in designing heating, ventilating and air-conditioning systems shall be determined in conformance with MMAH Supplementary Standard SB-1, "Climatic and Seismic Data."
OBC Div. B 6.2.1.5. Installation Standards
Open OBC Div. B 6.2.1.5. in the code viewer(1)The installation of solid fuel-burning appliances for central heating systems shall comply with CSA B365, "Installation code for solid-fuel-burning appliances and equipment" and the manufacturer's installation instructions.
(2)The solid fuel-fired appliances in Sentence (1) shall conform to CSA B366.1, "Solid-fuel-fired central heating appliances."
(3)The design and installation of earth energy systems shall conform to CAN/CSA-C448.2, "Design and installation of earth energy systems for residential and other small buildings," where such systems use groundwater, submerged heat exchangers or ground heat exchangers to serve,
(a)a house with or without a secondary unit, or,
(b)a building, other than a house with or without a secondary unit, where the conditioned space is not more than 1,400 m².
(4)Except for a house with or without a secondary unit, the design and installation of earth energy systems shall conform to CAN/CSA-C448.1, "Design and installation of earth energy systems for commercial and institutional buildings," where such systems use groundwater, submerged heat exchangers or ground heat exchangers to condition a floor space area more than 1,400 m².
(5)The design and installation of solid fuel-burning stoves, ranges and space heaters, including the requirements for combustion air, shall conform to the requirements of CSA B365, "Installation code for solid-fuel-burning appliances and equipment" and the manufacturer's installation instructions.
(6)The design and installation of hydronic heating systems shall conform to
(a)CSA B214, "Installation code for hydronic heating systems," or
(b)good engineering practice appropriate to the circumstances such as described in Article 6.2.1.1.
(7)Solid fuel-burning stoves, furnaces and hydronic heating systems designed to burn solid fuels, other than coal, shall conform to the particulate emission limits of,
(a)CSA B415.1, "Performance Testing of Solid-Fuel-Burning Heating Appliances," or
(b)the "Standards of Performance for New Residential Wood Heaters," set out in Subpart AAA of Part 60 of Title 40 of the Code of Federal Regulations, published by the United States Environmental Protection Agency, as it read on March 16, 2015.
OBC Div. B 6.2.2.1. Applicable Standard
Open OBC Div. B 6.2.2.1. in the code viewer(1)The design, construction, installation and material alteration of every indoor incinerator shall conform to NFPA 82, "Standard on Incinerators and Waste and Linen Handling Systems and Equipment."
OBC Div. B 6.2.1.6. Installation — General
Open OBC Div. B 6.2.1.6. in the code viewer(1)Equipment requiring periodic maintenance and forming part of a heating, ventilating or air-conditioning system shall be installed with provision for access for inspection, maintenance, repair and cleaning. (See Note A-6.2.1.6.(1))
(2)Mechanical equipment shall be provided with guards so as to prevent injury.
(3)Heating, ventilating or air-conditioning systems shall be protected from freezing if they may be adversely affected by freezing temperatures.
Show all 49 articles
OBC Div. B 6.2.1.7. Asbestos
Open OBC Div. B 6.2.1.7. in the code viewer(1)Asbestos shall not be used in heating, ventilating or air-conditioning systems or equipment.
OBC Div. B 6.2.1.8. Combustible Tubing
Open OBC Div. B 6.2.1.8. in the code viewer(1)Combustible tubing for pneumatic controls may be used in buildings required to be of noncombustible construction provided it has an outside diameter not exceeding 10 mm.
OBC Div. B 6.3.1.1. Required Ventilation
Open OBC Div. B 6.3.1.1. in the code viewer(1)Except as provided in Sentence (4), all buildings shall be ventilated in accordance with this Section.
(2)Except in storage garages and repair garages covered by Article 6.3.1.3., outdoor air shall be supplied to buildings for ventilation purposes in accordance with one of the following Sections of ANSI/ASHRAE 62.1, "Ventilation for Acceptable Indoor Air Quality,"
(a)Section 6.2, Ventilation Rate Procedure, excluding the exception stated in Section 6.2.7.1.2 and note H of Table 6.2.2.1.
(b)Section 6.3, Indoor Air Quality Procedure, or
(c)Section 6.4, Natural Ventilation Procedure, excluding residential occupancies.
(3)Except in storage garages and repair garages covered by Article 6.3.1.3., exhaust ventilation shall be provided in accordance with Section 6.5, Exhaust Ventilation, of ANSI/ASHRAE 62.1, "Ventilation for Acceptable Indoor Air Quality," as a minimum.
(4)Self-contained heating-season mechanical ventilation systems serving only one dwelling unit shall comply with Subsection 9.32.3.
(5)Live/work units shall be mechanically ventilated in accordance with the requirements of Sentence (1).
OBC Div. B 6.3.1.1A. Natural Ventilation
Open OBC Div. B 6.3.1.1A. in the code viewer(1)Except as permitted by Sentence (2), the ventilation required by Article 6.3.1.1. shall be provided by mechanical ventilation except that it can be provided by natural ventilation or a combination of natural and mechanical ventilation in
(a)buildings of other than residential occupancy having an occupant load of not more than one person per 40 m² during normal use.
(b)buildings of industrial occupancy where the nature of the process contained in them permits or requires the use of large openings in the building envelope even during the winter, or
(c)seasonal buildings not intended to be occupied during the winter.
(2)Where climatic conditions permit, buildings containing occupancies other than residential occupancies, may be ventilated by natural ventilation methods in lieu of mechanical ventilation where engineering data demonstrates that such a method will provide the required ventilation for the type of occupancy.
OBC Div. B 6.3.1.3. Ventilation of Storage and Repair Garages
Open OBC Div. B 6.3.1.3. in the code viewer(1)Except as provided in Sentences (4) and (6), an enclosed storage garage for five or more motor vehicles shall have a mechanical ventilation system designed to
(a)limit the concentration of carbon monoxide to not more than 100 parts per million parts of air,
(b)limit the concentration of nitrogen dioxide to not more than 3 parts per million parts of air, where the majority of the vehicles stored are powered by diesel-fuelled engines, or
(c)provide, during operating hours, a continuous supply of outdoor air at a rate of not less than 3.9 L/s for each square metre of floor area (see Article 3.3.1.21.).
(See Note A-6.3.1.3.(1)) (See also Sentence 3.3.5.4.(4).)
(2)Mechanical ventilation systems provided in accordance with Clause (1)(a) shall be controlled automatically by carbon monoxide monitoring devices, and systems provided in accordance with Clause (1)(b) shall be controlled by nitrogen dioxide or other acceptable monitoring devices. (See Note A-6.3.1.3.(2))
(3)Mechanical ventilation systems provided in accordance with Sentence (1) shall be designed such that the pressure in the storage garage is less than the pressure in adjoining buildings of other occupancy, or in adjacent portions of the same building having a different occupancy.
(4)In storage garages subject to the requirements of Sentence (1), where motor vehicles are parked by mechanical means, the ventilation requirements may be reduced by one half.
(5)Except as provided in Sentence (6), ticket and attendant booths of storage garages shall be pressurized with a supply of uncontaminated air.
(6)The requirements of Sentences (1) to (5) shall not apply to open-air storeys in a storage garage.
(7)A repair garage shall have a mechanical ventilation system designed to limit the exposure of workers to,
(a)carbon monoxide to below the time weighted average concentration of 25 parts per million for a normal 8 hour workday or 40 hour work week, and
(b)nitrogen dioxide from diesel powered vehicles to below 0.72 parts per million for a normal 8 hour workday or 40 hour work week.
(8)In a repair garage, when a repair bay is not immediately adjacent to an outside garage door opening, a system capable of providing continuous general ventilation of not less than 700 L/s per internal bay shall be provided.
(9)The general ventilation system described in Sentence (8) shall be designed to,
(a)operate continuously, or
(b)be controlled automatically by carbon monoxide monitoring devices, located so as to provide full protection throughout the repair garage.
(10)The general ventilation system described in Sentence (8) is not required when tail pipes of vehicles are directly connected to local mechanical exhaust systems that terminate outdoors.
OBC Div. B 6.3.1.6. Commercial Cooking Equipment
Open OBC Div. B 6.3.1.6. in the code viewer(1)Except as provided in Article 3.6.3.5., all commercial cooking equipment shall be provided with ventilation systems designed, constructed and installed to conform to NFPA 96, "Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations."
OBC Div. B 6.3.1.5. Indoor Air Contaminants
Open OBC Div. B 6.3.1.5. in the code viewer(1)Air contaminants of concern within buildings shall
(a)be removed insofar as is possible at their points of origin, and
(b)not be permitted to accumulate in concentrations greater than those permitted by good engineering practice such as that described in the publications listed in Sentence 6.2.1.1.(1), measured using the methodology described therein.
(2)Systems serving spaces that contain sources of contamination and systems serving other occupied parts of the building but located in or running through spaces that contain sources of contamination shall be designed in such a manner as to prevent the spread of such contamination to other occupied parts of the building.
(3)Heating, ventilating and air-conditioning systems shall be designed to minimize the growth and spread of biocontaminants.
(4)Mechanical rooms containing refrigeration equipment shall be ventilated in accordance with CSA B52, "Mechanical refrigeration code".
OBC Div. B 6.3.1.4. Heat Recovery Ventilators
Open OBC Div. B 6.3.1.4. in the code viewer(1)Heat recovery ventilators with rated capacities of not less than 25 L/s and not more than 200 L/s shall be installed in accordance with Subsection 9.32.3.
OBC Div. B 6.3.2.3. Materials in Air Duct Systems
Open OBC Div. B 6.3.2.3. in the code viewer(1)All ducts, duct connectors, associated fittings and plenums used in air duct systems shall be constructed of materials as described in Article 3.6.5.1.
(2)Ducts that are used in a location where they may be subjected to excessive moisture shall have no appreciable loss of strength when wet and shall be resistant to moisture-induced corrosion.
(3)All ductwork and fittings shall be constructed and installed as recommended in SMACNA Manuals and ASHRAE Standards.
(4)All duct materials shall be suitable for exposure to the temperature and humidity of the air being carried and shall be resistant to corrosion caused by contaminants in the air being conveyed in the duct.
OBC Div. B 6.3.2.7. Interconnection of Systems
Open OBC Div. B 6.3.2.7. in the code viewer(1)In a residential occupancy, air from one suite shall not be circulated to any other suite or to a public corridor.
(2)Except as permitted by Sentences (3) and 6.3.2.10.(6), air duct systems serving storage garages shall not be directly interconnected with other parts of the building.
(3)Exhaust ducts referred to in Sentence 6.3.2.10.(10) are permitted to exhaust through an enclosed storage garage prior to exhausting to the outdoors, provided
(a)the storage garage exhaust system runs continuously,
(b)the capacity of the storage garage exhaust system is equal to or exceeds the volume of the exhaust entering the garage, and
(c)a leakage rate 1 smoke/fire damper rated in accordance with CAN/ULC-S112.1, "Standard for Leakage Rated Dampers for Use in Smoke Control Systems," is provided near the duct outlet location in the storage garage to prevent air from the storage garage from entering the exhaust ductwork system in the event the building's exhaust fan is shut down.
(4)Except for corridors conforming to Sentence 3.3.1.4.(4) or as permitted in Sentences and (6), a public corridor or corridor serving the public shall not be used as a portion of a supply, return or exhaust air system serving adjoining areas, other than as part of a supply air system serving toilet rooms, bathrooms, shower rooms and similar auxiliary spaces opening directly to the public corridor or corridor used by the public.(5)
(5)A public corridor may be used as part of an engineered smoke control system.
(6)Infiltration due to corridor pressurization is permitted into a residential occupancy from a public corridor.
OBC Div. B 6.3.2.11. Return-Air System
Open OBC Div. B 6.3.2.11. in the code viewer(1)Return-air systems shall comply with Article 3.6.5.8.
(2)Where a ceiling space is used as a return-air plenum, the requirements of Article 3.6.4.3. shall apply.
(3)A public corridor or exit shall not be used as a return-air plenum.
(4)The return-air system shall be designed to handle the entire air supply.
(5)The return-air system shall be designed so that the negative pressure from the circulating fan cannot affect the furnace combustion air supply nor draw combustion products from joints or openings in the furnace or flue pipe.
(6)Return-air inlets shall not be installed in an enclosed room or crawl space that provides combustion air to a fuel-fired appliance.
OBC Div. B 6.3.2.8. Makeup Air
Open OBC Div. B 6.3.2.8. in the code viewer(1)In ventilating systems that exhaust air to the outdoors, provision shall be made for the admission of a supply of makeup air in sufficient quantity so that the operation of the exhaust system and other exhaust equipment or combustion equipment is not adversely affected.
(2)Makeup air facilities required by Sentence (1) shall be interlocked with the exhaust devices they serve so that both operate together.
(3)Where makeup air facilities are intended to introduce air directly from the outdoors to occupied parts of the building in winter, they shall incorporate means of tempering that air to maintain the indoor design temperature.
OBC Div. B 6.3.2.9. Supply, Return, Intake and Exhaust Air Openings
Open OBC Div. B 6.3.2.9. in the code viewer(1)Supply, return and exhaust air openings located less than 2 m above the floor in rooms or spaces in buildings shall be protected by grilles having openings of a size that will not allow the passage of a 15 mm diam sphere.
(2)Outdoor air intakes shall be located so that
(a)the quality of the air entering the building complies with Sentence 6.2.1.2.(1), and
(b)they are separated a minimum distance from sources of contaminants in accordance with Table 6.3.2.9.
(3)Outdoor air intakes shall be installed not less than 0.3 m above roofs, landscape grades or other surfaces, taking into account anticipated snow accumulation levels.
(4)Exterior openings for outdoor air intakes and exhaust outlets shall be shielded from the entry of snow and rain and shall be fitted with corrosion-resistant screens of mesh having openings not larger than 15 mm, except where experience has shown that climatic conditions require larger openings to prevent the screen openings from icing over.
(5)Screens required in Sentence (4) shall be accessible for maintenance.
(6)Combustible grilles, diffusers and other devices covering supply, return, intake and exhaust openings shall comply with Article 3.6.5.7.
OBC Div. B Table 6.3.2.9. Minimum Distances of Air Intakes from Sources of Contaminants — Forming Part of Sentence 6.3.2.9.(2)
Open OBC Div. B Table 6.3.2.9. in the code viewerTable 6.3.2.9. Minimum Distances of Air Intakes from Sources of Contaminants — Forming Part of Sentence 6.3.2.9.(2) Source of Contaminants | Minimum Distance of Outdoor Air Intake, m Garage entry of a garage for 5 or more motor vehicles, automobile loading area and drive-in queue | 4.5 Truck loading area or dock, and bus parking | 7.6 Driveway, parking space, lane, road and similar locations that carry a low volume of traffic | 1.5 Thoroughfare, arterial road, freeway, highway and similar locations that carry a high volume of traffic | 7.6 Garbage storage/pick-up area and dumpsters | 4.5 Discharge from evaporative heat rejection systems | 7.6 Sanitary vent | 3.5 Kitchen exhaust outlet | 3.0 Vent for combustion products from solid fuel-burning appliances | 3.0
OBC Div. B 6.3.2.10. Exhaust Ducts and Outlets
Open OBC Div. B 6.3.2.10. in the code viewer(1)Except as provided in Sentence (2), exhaust ducts of non-mechanical ventilating systems serving separate rooms or spaces shall not be combined.
(2)Exhaust ducts of non-mechanical ventilating systems serving similar occupancies may be combined immediately below the point of final delivery to the outdoors, such as at the base of a roof ventilator.
(3)Exhaust ducts of ventilating systems shall have provision for the removal of condensation where this may be a problem.
(4)Exhaust outlets shall be designed to prevent back draft under wind conditions.
(5)Except as permitted in Sentence (6), exhaust systems shall discharge directly to the outdoors. (See Note A-6.3.2.10.(5) and (6))
(6)Exhaust systems are permitted to exhaust into a storage garage, provided
(a)they serve rooms that are accessible only from that storage garage,
(b)the exhaust contains no contaminants that would adversely affect the air quality in the storage garage, and (See Note A-6.3.2.10.(6)(b))
(c)they are designed in accordance with Sentence 6.3.2.7.(3). (See Note A-6.3.2.10.(5) and (6))
(7)Exhaust ducts connected to laundry drying equipment shall be,
(a)independent of other exhaust ducts,
(b)designed and installed so that the entire duct can be cleaned, and
(c)constructed of smooth corrosion-resistant material. (See Note A-6.3.2.10.(7) and (8))
(8)Where collective venting of multiple installations of laundry-drying equipment is used, the ventilation system shall
(a)be connected to a common exhaust duct that is vented by one central exhaust fan,
(b)include an interlock to activate the central exhaust fan when laundry-drying equipment is in use, and
(c)be provided with make-up air. (See Note A-6.3.2.10.(7) and (8))
(9)Exhaust ducts or vents connected to laundry-drying equipment shall discharge directly to the outdoors.
(10)Except as provided in Sentence (12) and except for self-contained systems serving individual dwelling units, exhaust ducts serving rooms containing water closets, urinals, basins, showers or slop sinks shall be independent of other exhaust ducts.
(11)Except as provided in Sentence (12) and except for self-contained systems serving individual dwelling units, exhaust ducts serving rooms containing residential cooking equipment shall be independent of other exhaust ducts.
(12)Two or more exhaust systems described in Sentences (10) and (11) may be interconnected or connected with exhaust ducts serving other areas of the building, provided
(a)the connections are made at the inlet of an exhaust fan, and all interconnected systems are equipped with suitable back pressure devices to prevent the passage of odours from one system to another when the fan is not in operation, or
(b)the exhaust ducts discharge to a shaft that is served by an exhaust fan having a capacity that is equal to or greater than the combined capacity of the exhaust fans discharging to the plenum multiplied by the operation diversity factor, provided that the exhaust fan serving the shaft operates continuously. (See Note A-6.3.2.10.(12)(b))
(13)Where exhaust ducts containing air from conditioned spaces pass through or are adjacent to unconditioned spaces, the ducts shall be constructed to prevent condensation from forming on the inside or outside of the ducts.
(14)Except as provided in Sentence (15), exhaust air shall be provided at a rate not less than 24 L/s for each water closet, urinal, shower or slop sink.
(15)Except as provided in Sentence 6.3.1.1.(4), exhaust air shall be provided for fixtures in dwelling units in accordance with ANSI/ASHRAE 62.1, "Ventilation for Acceptable Indoor Air Quality."
(16)Except for wash basins (lavatories), sanitary facilities in a food premises shall be mechanically ventilated and shall be capable of exhausting air at the rate of not less than 24 L/s for each sanitary fixture listed in Sentence (17).
(17)The mechanical ventilation described in Sentence (16) applies to rooms containing water closets, urinals, basins, showers or slop sinks.
OBC Div. B 6.3.2.13. Filters
Open OBC Div. B 6.3.2.13. in the code viewer(1)Air filters for air duct systems shall conform to the requirements for Class 2 air filter units as described in CAN/ULC-S111, "Standard Method of Fire Tests for Air Filter Units."
(2)When electrostatic-type filters are used, they shall be installed so as to ensure that the electric circuit is automatically de-energized when filter access doors are opened or, in dwelling units, when the furnace circulation fan is not operating.
OBC Div. B 6.3.2.15. Evaporative Heat Rejection Systems
Open OBC Div. B 6.3.2.15. in the code viewer(1)Evaporative heat rejection systems shall
(a)incorporate a drift eliminator or other means to minimize the dispersion of entrained water droplets, and
(b)have a design discharge velocity that does not exceed the maximum discharge velocity recommended by the manufacturer.
(2)Evaporative heat rejection systems shall be designed so that water continuously circulates through all parts of the system that are normally wetted when the system is operating.
(3)Evaporative heat rejection systems and their components shall be constructed of corrosion-resistant, non-porous materials that do not promote the proliferation of disease-causing micro-organisms and that are compatible with disinfectants, biocides and other cleaning agents.
(4)Evaporative heat rejection systems shall be installed such that
(a)no discharge air bypasses the drift eliminator or other means referred to in Clause (1)(a), and
(b)the systems are accessible for cleaning, inspection and maintenance.
(5)Except as provided in Sentence (6), air discharged from evaporative heat rejection systems shall discharge away from the building, so as to not re-enter it, to a distance not less than
(a)2.15 m above sidewalks and driveways,
(b)7.6 m from outdoor air intakes,
(c)3 m horizontally or vertically from exterior doors and operable windows, and
(d)3 m horizontally or vertically from occupiable outdoor spaces, excluding maintenance spaces. (See Note A-6.3.2.15.(5) and (6))
(6)Air discharged from evaporative heat rejection systems in health care facilities shall discharge away from the building in compliance with CAN/CSA-Z317.2, "Special requirements for heating, ventilation, and air-conditioning (HVAC) systems in health care facilities." (See Note A-6.3.2.15.(5) and (6))
(7)Air intakes of evaporative heat rejection systems shall incorporate protective measures to minimize the entrainment of vegetation and other organic matter.
(8)Make-up water connections shall be equipped with backflow prevention devices that conform to Article 7.6.2.1. (See Note A-6.3.2.15.(8) and (9))
(9)Water treatment systems and equipment for controlling the proliferation of disease-causing micro-organisms shall
(a)be provided in accordance with Section 7.6.2. of ASHRAE Guideline 12, "Minimizing the Risk of Legionellosis Associated with Building Water Systems," and
(b)include means for drainage, dilution, cleaning, and application of chemicals for the control of scale, corrosion and biological contamination. (See Note A-6.3.2.15.(8) and (9))
(10)Drains, overflows and blow-downs shall be connected to the building's drainage system in accordance with Clause 7.4.2.1.(1)(d).
(11)Evaporative heat rejection systems shall be provided with access openings, service platforms, fixed ladders and fall-restraint connections to allow inspection, maintenance and testing.
OBC Div. B 6.3.3.1. Requirement for Venting
Open OBC Div. B 6.3.3.1. in the code viewer(1)Except as provided in Articles 6.3.3.2. and 6.3.3.3., the products of combustion from oil-, gas and solid-fuel-burning appliances shall be vented in conformance with the requirements in the applicable appliance installation standard listed in Article 6.2.1.5.
(2)Except as provided in Article 6.2.1.5., vented products of combustion, other than those referred to in Sentence (1), shall be discharged away from the building, so as not to re-enter it, to a distance not less than
(a)2.15 m above sidewalks and driveways,
(b)3 m from outdoor air intakes,
(c)3 m horizontally or vertically from doors and operable windows, and
(d)3 m horizontally or vertically from occupiable outdoor spaces, excluding maintenance spaces. (See Note A-6.3.3.1.(2))
OBC Div. B 6.3.3.2. Masonry or Concrete Chimneys
Open OBC Div. B 6.3.3.2. in the code viewer(1)Rectangular masonry or concrete chimneys not more than 12 m in height shall conform to Part 9 if they serve
(a)appliances with a combined total rated heat output of 120 kW or less, or
(b)fireplaces.
(2)Masonry or concrete chimneys other than those described in Sentence (1) shall be designed and installed in conformance with the appropriate requirements in NFPA 211, "Standard for Chimneys, Fireplaces, Vents and Solid Fuel-Burning Appliances."
OBC Div. B 6.3.3.3. Metal Smoke Stacks
Open OBC Div. B 6.3.3.3. in the code viewer(1)Single wall metal smoke stacks shall be designed and installed in conformance with NFPA 211, "Standard for Chimneys, Fireplaces, Vents and Solid Fuel-Burning Appliances."
OBC Div. B 6.3.3.4. Access Ladders
Open OBC Div. B 6.3.3.4. in the code viewer(1)Access ladders for chimneys, when provided, shall consist of steel or bronze rungs, built into the walls of the chimneys.
(2)Rungs for external ladders shall begin at not less than 2.5 m from ground level.
OBC Div. B 6.3.4.2. General Ventilation
Open OBC Div. B 6.3.4.2. in the code viewer(1)A laboratory shall be provided with continuous mechanical ventilation designed to ensure that dangerous goods vapours and particles
(a)do not accumulate in the laboratory,
(b)are prevented from migrating to other parts of the building,
(c)do not accumulate in the ventilation system,
(d)are exhausted to the outdoors, and
(e)are not returned to the building.
(2)A ventilation system required by this Subsection shall be provided with monitoring devices to
(a)indicate that the ventilation system is in operation, and
(b)sound an alarm if the ventilation system is malfunctioning.
(3)A ventilation system required by this Subsection shall be maintained in conformance with Section 4.12. of the Fire Code made under the Fire Protection and Prevention Act, 1997.
OBC Div. B 6.3.4.3. Enclosure Exhaust Ventilation
Open OBC Div. B 6.3.4.3. in the code viewer(1)The ventilation system for a power-ventilated enclosure referred to in Article 6.3.4.2A. shall
(a)conform to NFPA 91, "Standard for Exhaust Systems for Air Conveying of Vapors, Gases, Mists, and Particulate Solids."
(b)provide continuous exhaust ventilation at an air velocity sufficient to prevent the accumulation of combustible or reactive deposits in the power-ventilated enclosure and its exhaust duct system,
(c)confine dangerous goods vapours and particles to the area where they are generated and exhaust them to the outdoors.
(d)not return the exhausted air to the building, and
(e)be provided with well identified control switches that are
(i)located outside the power-ventilated enclosure, and
(ii)readily accessible in case of an emergency.
OBC Div. B 6.3.4.4. Enclosure Construction
Open OBC Div. B 6.3.4.4. in the code viewer(1)The power-ventilated enclosure referred to in Article 6.3.4.2A. and its exhaust duct system shall
(a)except as provided in Sentences (2) and (3), be constructed of noncombustible materials compatible with and chemically resistant to the dangerous goods vapours and particles being exhausted, and
(b)be provided with access doors to permit inspection and maintenance of the fan assembly and exhaust ducts.
(2)Combustible materials are permitted in the power-ventilated enclosure described in Sentence (1) and its exhaust duct systems if
(a)such materials are required by the corrosive or reactive properties of the dangerous goods being used, and
(b)their flame-spread rating is not more than 25.
(3)The flame-spread rating required by Sentence (2) is permitted to be greater than 25 if an automatic fire suppression system is provided inside the power-ventilated enclosure and its exhaust duct system.
OBC Div. B 6.4.1.1. Location of Appliances
Open OBC Div. B 6.4.1.1. in the code viewer(1)Except for appliances installed in dwelling units, fuel-fired heating appliances shall be located, enclosed or separated from the remainder of the building in conformance with Section 3.6. (See also Subsection 9.10.10.)
OBC Div. B 6.4.1.2. Appliances Installed Outside the Building
Open OBC Div. B 6.4.1.2. in the code viewer(1)Fuel-fired appliances installed outside a building shall be
(a)designed and constructed for outdoor use,
(b)installed not less than 1,200 mm from the property line, measured horizontally, and
(c)installed not less than 3 m from an adjacent wall of the same building when such wall contains an opening or openings within 3 storeys above and 5 m horizontally from the appliance, unless such openings are protected by a closure assembly having a 45 min fire-protection rating determined in conformance with Article 3.1.8.4., or by wired glass conforming to Article 3.1.8.14.
OBC Div. B 6.4.3.1. Lining or Backing
Open OBC Div. B 6.4.3.1. in the code viewer(1)A noncombustible lining or backing shall be provided for every steam or hot water radiator and convector
(a)located in a recess or concealed space, or
(b)attached to the face of a wall of combustible construction or encapsulated mass timber construction.
(2)Every steam or hot water radiator and convector shall be installed so as to conform to the clearance requirements of Table 6.7.1.2.
OBC Div. B 6.5.1.1. Insulation and Coverings
Open OBC Div. B 6.5.1.1. in the code viewer(1)Insulation and coverings on pipes shall comply with Article 3.6.5.5.
(2)Insulation and coverings on pipes shall be composed of material that will withstand deterioration from softening, melting, mildew and mould at the operating temperature of the system.
(3)Exposed piping or equipment subject to human contact shall be insulated so that the temperature of the exposed surface does not exceed 52° C. (See Note A-6.5.1.1.(3))
OBC Div. B 6.6.1.1. Cooling Units
Open OBC Div. B 6.6.1.1. in the code viewer(1)Where a cooling unit is combined with a fuel-fired furnace in the same duct system, the cooling unit shall be installed
(a)in parallel with the heating furnace,
(b)upstream of the furnace provided the furnace is designed for such application, or
(c)downstream of the furnace provided the cooling unit is designed to prevent excessive temperature or pressure in the refrigeration system.
OBC Div. B Table 6.7.1.2. Clearance Between Steam or Hot Water Pipes and Combustible Material — Forming Part of Article 6.4.2.1., Sentence 6.4.3.1.(2) and Article 6.7.1.2.
Open OBC Div. B Table 6.7.1.2. in the code viewerTable 6.7.1.2. Clearance Between Steam or Hot Water Pipes and Combustible Material — Forming Part of Article 6.4.2.1., Sentence 6.4.3.1.(2) and Article 6.7.1.2. Steam or Water Temperature, °C | Minimum Clearance, mm Up to 95 | No clearance Above 95 to 120 | 15 mm Above 120 | 25 mm
OBC Div. B 6.7.1.4. Protection
Open OBC Div. B 6.7.1.4. in the code viewer(1)Where a pipe carrying steam or hot water at a temperature above 120°C passes through a combustible floor, ceiling or wall, the construction shall be protected by a sleeve of metal or other noncombustible material not less than 50 mm larger in diameter than the pipe.
OBC Div. B 6.7.1.3. Surface Temperature
Open OBC Div. B 6.7.1.3. in the code viewer(1)The exposed surface temperature of a steam or hot water radiator shall not exceed 70°C unless precautions are taken to prevent human contact. (See Note A-6.5.1.1.(3))
OBC Div. B 6.8.1.1. Access Openings
Open OBC Div. B 6.8.1.1. in the code viewer(1)Any covering of an access opening through which a person could enter shall be openable from the inside without the use of keys where there is a possibility of the opening being accidentally closed while the system or equipment is being serviced.
OBC Div. B 6.9.1.1. Fire Safety Requirements
Open OBC Div. B 6.9.1.1. in the code viewer(1)The fire safety characteristics of heating, ventilating and air-conditioning systems shall comply with Subsection 3.6.5.
(2)Characteristics referred to in Sentence (1) include but are not limited to
(a)use of combustible materials in duct systems,
(b)flame-spread ratings and smoke-developed ratings of duct and pipe materials and coverings,
(c)installation of equipment relative to property lines, and
(d)requirements for fire dampers and fire stop flaps.
OBC Div. B 6.9.2.1. Fire Dampers
Open OBC Div. B 6.9.2.1. in the code viewer(1)Fire dampers shall conform to Article 3.1.8.10.
OBC Div. B 6.9.2.2. Smoke Detectors
Open OBC Div. B 6.9.2.2. in the code viewer(1)Air handling systems shall incorporate smoke detectors where and as required by Article 3.2.4.12.
OBC Div. B 6.9.2.3. Exhaust Ducts and Outlets
Open OBC Div. B 6.9.2.3. in the code viewer(1)Where an exhaust duct system is used for smoke removal in a high building, the requirements of Article 3.2.6.6. shall apply.
(2)Where exhaust duct systems from more than one fire compartment are connected to an exhaust duct in a vertical service space, the requirements of Article 3.6.3.4. shall apply.
OBC Div. B 6.9.2.4. Ducts in Exits
Open OBC Div. B 6.9.2.4. in the code viewer(1)Where ducts penetrate fire separations separating exits from the remainder of the building, they shall be in accordance with Article 3.4.4.4.
(2)Duct penetration of fire separations separating exits from the remainder of the building is permitted if the duct
(a)is designed for the purposes of Subsection 3.2.6., or
(b)only serves the exit from a dedicated rooftop air make-up unit.
OBC Div. B 6.9.1.3. Commercial Cooking Equipment
Open OBC Div. B 6.9.1.3. in the code viewer(1)Fire protection systems for commercial cooking equipment referred to in Sentence 6.3.1.6.(1) using vegetable oil or animal fat shall conform to
(a)ANSI/CAN/UL/ULC 300, "Standard for Fire Testing of Fire Extinguishing Systems for Protection of Commercial Cooking Equipment," or
(b)ULC/ORD-C1254.6, "Fire Testing of Restaurant Cooking Area Fire Extinguishing System Units."
OBC Div. B 6.9.3.2. Location of Carbon Monoxide Alarms
Open OBC Div. B 6.9.3.2. in the code viewer(1)A carbon monoxide alarm shall be installed in a suite of residential occupancy or care occupancy where
(a)a fuel-burning appliance or a flue is installed in the suite,
(b)a forced-air fuel-burning appliance provides heated air directly to the suite,
(c)a fuel-burning appliance or a flue is located in a room, suite or area that shares a common wall or floor or ceiling assembly with the suite, or
(d)a storage garage shares a common wall or floor or ceiling assembly with the suite.
(2)Where a carbon monoxide alarm is required by Sentence (1) to be installed in a suite of residential occupancy or care occupancy, other than a suite that consists of a combined living and sleeping area, a carbon monoxide alarm shall be installed
(a)adjacent to each sleeping room in the suite, and
(b)on each storey without a sleeping room in the suite.
(3)Where a carbon monoxide alarm is required by Sentence (1) to be installed in a suite of residential occupancy or care occupancy that consists of a combined living and sleeping area, a carbon monoxide alarm shall be installed in the combined living and sleeping area.
(4)In addition to the carbon monoxide alarms required to be installed in a suite of residential occupancy or care occupancy in accordance with Sentence (2), a carbon monoxide alarm shall be installed in each sleeping room within the suite where the sleeping room
(a)contains a fuel-burning appliance or a flue, or
(b)shares a common wall or floor or ceiling assembly with
(i)a room, suite or area that is located outside the suite and contains a fuel-burning appliance or a flue, or
(ii)a storage garage.
(5)Carbon monoxide alarms shall be installed in public corridors serving suites of residential occupancy where the corridor is directly heated by a forced-air fuel-burning appliance.
(6)Where carbon monoxide alarms are required by Sentence (5) to be installed in a public corridor, the carbon monoxide alarms shall be installed such that
(a)there is at least one carbon monoxide alarm in each portion of a divided corridor, and
(b)each carbon monoxide alarm in an undivided portion of a corridor is spaced not more than 25 m apart.
OBC Div. B 6.9.3.3. Location of Carbon Monoxide Alarms in All Buildings
Open OBC Div. B 6.9.3.3. in the code viewer(1)A carbon monoxide alarm shall be installed in service rooms or other areas of a building where the service room or other area
(a)contains a fuel-burning appliance used for building services or laundry drying equipment, and
(b)is not located within a suite of residential occupancy.