Part 8 general: scope, classes and limits on discharge

Scope and application of Part 8, its definitions, and limits on what may be discharged into a sewage system.

chapters in this guide
5 of 11
chapters in this guide
to read
4 min
to read
code articles cited
8
code articles cited

Last updated

Values this chapter turns on

of sewage system under Part 8
5 classes
of sewage system under Part 8
minimum thickness for Part 8 soil
100 mm
minimum thickness for Part 8 soil
max share of daily design flow from laundry
20%
max share of daily design flow from laundry
drain down time for sizing a grease interceptor
60 s
drain down time for sizing a grease interceptor

Section 8.1. is short, but almost every Part 8 question depends on it. It tells you what "soil" means in Part 8, sorts every sewage system into one of five classes, and limits what may be sent into a system. Learn the five classes cold. Many scenario questions are really asking "which class is this?".

Scope and the Part 8 meaning of soil

Part 8's scope is set by Division A, Subsection 1.3.3. (OBC Div. B 8.1.1.1.OBC Div. B 8.1.1.1. Scope(1) The scope of this Part shall be as described in Subsection 1.3.3. of Division A.), which applies it to the design, construction, operation and maintenance of all sewage systems and to buildings built near them (OBC Div. A 1.3.3.2A.OBC Div. A 1.3.3.2A. Application of Part 8(1) Subject to Article 1.3.3.3B., Part 8 of Division B applies to the design, construction, operation and maintenance of all sewage systems and to the construction of buildings in the vicinity of sewage systems.).

Italic words are defined in Division A 1.4.1.2. and in the Building Code Act, except that Part 8 has its own definition of soil (OBC Div. B 8.1.1.2.OBC Div. B 8.1.1.2. Definitions(1) Except as provided in Sentence (2), words that appear in italics are defined in Article 1.4.1.2. of Division A and in the Building Code Act, 1992. (2) In this Part, Soil means in-situ, naturally occurring, unconsolidated mineral or organic material, at the earth's surface that is at least 100 mm thick and capable…). In Part 8, soil is:

  • in-situ, naturally occurring, unconsolidated mineral or organic material at the earth's surface,
  • at least 100 mm thick,
  • capable of supporting plant growth,
  • including material compacted or cemented by soil forming processes,
  • but not displaced material such as gravel dumps, mine spoils or similar deposits.

So a pile of trucked-in gravel is not "soil" for Part 8. Material placed to build a bed is "leaching bed fill", which has its own definition (def.OBC Div. A 1.4.1.2.(1) Leaching bed fillLeaching bed fill means unconsolidated material suitable for the construction of a leaching bed, placed in the area of the leaching bed in order to obtain the required unsaturated zone below the distribution pipes or leaching chambers and the required lateral extent such that the effluent is absorbed.).

Practice this topic

The five classes

Every sewage system falls into one class (OBC Div. B 8.1.2.1.OBC Div. B 8.1.2.1. Classification of Systems(1) All sewage systems shall be classed as one of the following: (a) Class 1 — a chemical toilet, an incinerating toilet, a recirculating toilet, a self-contained portable toilet and all forms of privy including a portable privy, an earth pit privy, a pail privy, a privy vault and a composting toilet system, (b) Class…):

Class What it is Where the rules are
1 Chemical, incinerating, recirculating and self-contained portable toilets, and all privies (portable, earth pit, pail, privy vault) and composting toilet systems Section 8.3.
2 Greywater system Section 8.4.
3 Cesspool Section 8.5.
4 Leaching bed system (treatment unit plus leaching bed) Sections 8.6. and 8.7.
5 System that uses a holding tank to keep hauled sewage on site until it is collected by a hauled sewage system Section 8.8.

Operation and maintenance of every class is governed by Section 8.9. (OBC Div. B 8.1.2.2.OBC Div. B 8.1.2.2. Operation and Maintenance(1) Operation and maintenance of sewage systems shall comply with Section 8.9.).

Memory aid: the number rises as the system gets more "engineered", except Class 5, which is the holding tank fallback. A composting toilet is Class 1, not Class 4, even though it treats waste.

Worked example: classify the system

Situation Class
Outhouse over a pit at a hunting camp 1 (earth pit privy)
Rented portable toilets at a fair 1 (portable privy)
Pit taking only kitchen sink and shower water at a cottage 2 (greywater)
Covered pit receiving the contents of a privy 3 (cesspool)
Septic tank and trenches for a house 4
Tank pumped out by a hauler for a seasonal trailer office on a tiny lot 5

Practice this topic

Limitations on discharge

The basic rule: a sewage system is designed and built to receive only sanitary sewage of domestic origin (OBC Div. B 8.1.3.1.(1)OBC Div. B 8.1.3.1. Discharge(1) Except as provided in Sentences (2) to (6), the sewage system shall be designed and constructed to receive only sanitary sewage of domestic origin. (See Note A-8.1.3.1.(1)) (2) Where laundry waste is not more than 20% of the total daily design sanitary sewage flow, it may discharge to a sewage system. (3) Where…). Then come the exceptions, each with a condition:

Waste Allowed if
Laundry waste it is not more than 20% of the total daily design sanitary sewage flow
Industrial process waste water treated to the contaminant levels of domestic sanitary sewage, and the treatment unit and system are designed to good engineering practice (to a leaching bed)
Restaurant kitchen waste water it has passed through an operating grease interceptor, and the system is designed to good engineering practice (to a leaching bed)
Kitchen waste with a garbage grinder the system was designed to accept it
Water softener and iron filter discharge the system was designed to accept it
Storm sewage never

The grease interceptor required for restaurant waste must have a minimum flow rate per Sentence 7.4.4.3.(8) using a 60 second drain down time, and must conform to CSA B481.1 or B481.2 (Sentence (8)). You only need to know which standards are named, not what they contain.

Worked example: laundromat on a septic

A small motel has a total daily design flow of 5,000 L, of which laundry waste is estimated at 1,200 L. The limit is 20% of 5,000 L = 1,000 L. At 1,200 L the laundry waste exceeds the limit, so it may not discharge to the sewage system as designed.

Worked example: sump pump into the septic

A homeowner wants to run the basement sump pump (rain and snow melt water) into the septic tank. Storm sewage is water discharged from a surface because of rainfall, snow melt or snowfall (def.OBC Div. A 1.4.1.2.(1) Storm sewageStorm sewage means water that is discharged from a surface as a result of rainfall, snow melt or snowfall.), and it shall not be discharged into a sewage system (Sentence 8.1.3.1.(7)). The answer is no, with no exceptions.

Practice this topic

Common traps

  • Part 8 soil must be at least 100 mm thick and support plant growth. Gravel dumps and mine spoils are excluded.
  • A cesspool is Class 3, and it only takes Class 1 contents (Chapter 7).
  • A leaching bed system is Class 4, whatever the treatment unit.
  • The laundry limit is 20% of the total daily design flow, not of the tank size.
  • Softener and grinder waste are allowed only if the system was designed for them.
  • There is no exception at all for storm sewage.

Chapter review

Chapter at a glance

One line per section: the idea to carry into the exam. Then the answers that most often catch candidates out.

  • Scope and the Part 8 meaning of soil

    Part 8's scope is set by Division A, Subsection 1.3.3., which applies it to the design, construction, operation and maintenance of all sewage systems and to buildings built near…

  • The five classes

    Operation and maintenance of every class is governed by Section 8.9..

  • Limitations on discharge

    The basic rule: a sewage system is designed and built to receive only sanitary sewage of domestic origin.

Usual exam traps

  • Part 8 soil must be at least 100 mm thick and support plant growth. Gravel dumps and mine spoils are excluded.
  • A cesspool is Class 3, and it only takes Class 1 contents (Chapter 7).
  • A leaching bed system is Class 4, whatever the treatment unit.
  • The laundry limit is 20% of the total daily design flow, not of the tank size.
  • Softener and grinder waste are allowed only if the system was designed for them.
  • There is no exception at all for storm sewage.

Practice this chapter

Questions on Part 8 general: scope, application, definitions and limitations, in the exam format, every answer explained and cited to its article. Sign in to start; a free account gets the free questions.

Code cited in this chapter

Based on the official 2024 Building Code Compendium on ontario.ca.

© King's Printer for Ontario, 2024. Reproduced with permission.

  • OBC Div. B 8.1.1.1. Scope

    (1)The scope of this Part shall be as described in Subsection 1.3.3. of Division A.

    Open OBC Div. B 8.1.1.1. in the code viewer
  • OBC Div. A 1.3.3.2A. Application of Part 8

    (1)Subject to Article 1.3.3.3B., Part 8 of Division B applies to the design, construction, operation and maintenance of all sewage systems and to the construction of buildings in the vicinity of sewage systems.

    Open OBC Div. A 1.3.3.2A. in the code viewer
  • OBC Div. B 8.1.1.2. Definitions

    (1)Except as provided in Sentence (2), words that appear in italics are defined in Article 1.4.1.2. of Division A and in the Building Code Act, 1992.

    (2)In this Part,

    Soil means in-situ, naturally occurring, unconsolidated mineral or organic material, at the earth's surface that is at least 100 mm thick and capable of supporting plant growth, and includes material compacted or cemented by soil forming processes, but does not include displaced materials such as gravel dumps, mine spoils, or like deposits.

    Open OBC Div. B 8.1.1.2. in the code viewer
  • OBC Div. A 1.4.1.2.(1) Leaching bed fill

    Leaching bed fill means unconsolidated material suitable for the construction of a leaching bed, placed in the area of the leaching bed in order to obtain the required unsaturated zone below the distribution pipes or leaching chambers and the required lateral extent such that the effluent is absorbed.

    Open OBC Div. A 1.4.1.2.(1) in the code viewer
  • OBC Div. B 8.1.2.1. Classification of Systems

    (1)All sewage systems shall be classed as one of the following:

    (a)Class 1 — a chemical toilet, an incinerating toilet, a recirculating toilet, a self-contained portable toilet and all forms of privy including a portable privy, an earth pit privy, a pail privy, a privy vault and a composting toilet system,

    (b)Class 2 — a greywater system,

    (c)Class 3 — a cesspool,

    (d)Class 4 — a leaching bed system, or

    (e)Class 5 — a system that requires or uses a holding tank for the retention of hauled sewage at the site where it is produced prior to its collection by a hauled sewage system.

    Open OBC Div. B 8.1.2.1. in the code viewer
  • OBC Div. B 8.1.2.2. Operation and Maintenance

    (1)Operation and maintenance of sewage systems shall comply with Section 8.9.

    Open OBC Div. B 8.1.2.2. in the code viewer
  • OBC Div. B 8.1.3.1. Discharge

    (1)Except as provided in Sentences (2) to (6), the sewage system shall be designed and constructed to receive only sanitary sewage of domestic origin. (See Note A-8.1.3.1.(1))

    (2)Where laundry waste is not more than 20% of the total daily design sanitary sewage flow, it may discharge to a sewage system.

    (3)Where industrial process waste water is treated to the contaminant levels found in domestic sanitary sewage, it may discharge to a leaching bed provided the treatment unit and sewage system are designed in accordance with good engineering practice. (See Note A-8.1.3.1.(3))

    (4)Where kitchen waste water from a restaurant has passed through an operating grease interceptor, it may discharge to a leaching bed provided the sewage system has been designed in accordance with good engineering practice.

    (5)Waste water from a kitchen equipped with a garbage grinder may be directed to the sewage system provided the system has been designed to accept such waste water.

    (6)Water softener and iron filter discharge may be directed to the sewage system provided the system has been designed to accept such discharges.

    (7)Storm sewage shall not be discharged into a sewage system.

    (8)The interceptor required in Sentence (4) shall

    (a)have a minimum flow rate as required by Sentence 7.4.4.3.(8) using a 60 second drain down time, and

    (b)conform to,

    (i)CSA B481.1, "Testing and rating of grease interceptors using lard," or

    (ii)CSA B481.2, "Testing and rating of grease interceptors using oil."

    Open OBC Div. B 8.1.3.1. in the code viewer
  • OBC Div. A 1.4.1.2.(1) Storm sewage

    Storm sewage means water that is discharged from a surface as a result of rainfall, snow melt or snowfall.

    Open OBC Div. A 1.4.1.2.(1) in the code viewer