Part 9 fire protection for HVAC services

Occupancy classification, permitted openings, penetrations of fire separations, exhaust ducts serving more than one fire compartment, central vacuum systems, service rooms and fuel-fired appliances, closures, fire dampers and fire stop flaps, openings in exposing faces, fire blocks and smoke alarms.

chapters in this guide
6 of 13
chapters in this guide
to read
6 min
to read
code articles cited
31
code articles cited

Last updated

Values this chapter turns on

fire separation around a fuel-fired appliance room
1 h
fire separation around a fuel-fired appliance room
exposing face opening needing no closure in a house
130 cm²
exposing face opening needing no closure in a house
building area limit for the small building exception
400 m²
building area limit for the small building exception
smoke alarm battery standby before 4 min of alarm
7 days
smoke alarm battery standby before 4 min of alarm

HVAC work keeps crossing fire separations. The syllabus picks out the Section 9.10. Articles that control these crossings, plus smoke alarms.

Background items

  • Occupant load in a dwelling unit is two persons per sleeping room or sleeping area OBC Div. B 9.9.1.3.OBC Div. B 9.9.1.3. Occupant Load(1) The occupant load of a floor area or part of a floor area shall be based on (a) two persons per sleeping room or sleeping area in a dwelling unit or suite, and (b) for occupancies other than as described in Clause (a), the number of persons (i) for which the area is designed, or (ii) determined from Table 3.1.17.1..
  • Every building is classified by major occupancy as Group C, D, E, or F Division 2 or 3 for Part 9 OBC Div. B 9.10.2.1.OBC Div. B 9.10.2.1. Occupancy Classification(1) Every building or part of it shall be classified according to its major occupancy as belonging to one of the groups or divisions described in Table 9.10.2.1..
  • From the Part 3 jurisdiction list, three items are on this syllabus: basements of more than one storey or over 600 m² follow Part 3; sprinkler systems follow Articles 3.2.5.12. to 3.2.5.15. and 3.2.5.17.; and fuel-fired appliances on a roof follow Article 3.6.1.5. OBC Div. B 9.10.1.3.OBC Div. B 9.10.1.3. Items Under Part 3 Jurisdiction(1) Tents, air-supported structures, transformer vaults, walkways, elevators and escalators shall conform to Part 3. (2) Where rooms or spaces are intended for an assembly occupancy, such rooms or spaces shall conform to Part 3. (3) Basements containing more than 1 storey or exceeding 600 m² in area shall conform to….
  • Lay-in ceiling panels that contribute to a fire-resistance rating need hold-down clips OBC Div. B 9.10.3.4.OBC Div. B 9.10.3.4. Suspended Membrane Ceiling(1) Where a ceiling construction has a suspended membrane ceiling with lay-in panels or tiles that contribute to the required fire-resistance rating, hold down clips or other means shall be provided to prevent the lifting of such panels or tiles in the event of a fire..

Practice this topic

Penetrations of fire separations by ducts, pipes and service equipment

Openings in membranes. A membrane of a rated assembly must not be pierced unless the assembly was tested with those openings, except for outlet boxes meeting 9.10.9.8., and duct openings in a ceiling rated under SB-3 Table 2 when protected as 9.10.13.14. and SB-2 require OBC Div. B 9.10.5.1.OBC Div. B 9.10.5.1. Permitted Openings in Wall and Ceiling Membranes(1) Except as permitted in Sentences (2) and (3), a membrane forming part of an assembly required to have a fire-resistance rating shall not be pierced by openings into the assembly unless the assembly has been tested and rated for such openings. (2) A wall or ceiling membrane forming part of an assembly required to…. Boxes on both sides of a rated wall are offset where needed.

General penetration rule OBC Div. B 9.10.9.6.OBC Div. B 9.10.9.6. General Requirements for Penetrations of Fire Separations(1) Except as required by Sentence (2) and Articles 9.10.9.7. and 9.10.9.8. and as permitted by Article 9.10.9.9., penetrations of a required fire separation or a membrane forming part of an assembly required to be a fire separation shall be (a) sealed by a firestop that, when subjected to the fire test method in…. A penetration of a fire separation must be one of:

  1. sealed by a firestop with an F rating (CAN/ULC-S115) not less than the required fire-resistance rating,
  2. tightly fitted or cast in place, if the item is steel, ferrous, copper, concrete or masonry, or
  3. otherwise sealed to keep the separation's integrity.

Firewall penetrations need an FT rating, not just F.

Piping OBC Div. B 9.10.9.7.OBC Div. B 9.10.9.7. Piping Penetrations(1) Except as provided in Sentences (2) and (5), piping for drain, waste, vent and central vacuum systems that is not located in a vertical shaft is permitted to penetrate a fire separation required to have a fire-resistance rating or a membrane that forms part of an assembly required to have a fire-resistance rating…. Drain, waste, vent and central vacuum piping may penetrate if protected under the F-rated firestop or tight-fit options. Combustible DWV piping is allowed on one side of a vertical fire separation if not in a shaft. Combustible water distribution piping may penetrate if not in a vertical shaft and sealed by an F-rated firestop.

Outlet boxes OBC Div. B 9.10.9.8.OBC Div. B 9.10.9.8. Penetrations by Outlet Boxes or Service Equipment in Concealed Spaces(1) Except as provided in Sentences (2) to (5), outlet boxes are permitted to penetrate the membrane of an assembly required to have a fire-resistance rating, provided they are sealed at the penetration by a firestop that, when subjected to the fire test method in CAN/ULC-S115, "Standard Method of Fire Tests of…. Noncombustible boxes need no tested firestop if each is not more than 0.016 m², total not more than 0.065 m² in any 9.3 m² of surface, with an annular gap of not more than 3 mm. Boxes on opposite sides of a vertical separation are at least 600 mm apart horizontally, or enclosed, or in an insulated space.

Raceways, sprinklers and fire dampers OBC Div. B 9.10.9.9.OBC Div. B 9.10.9.9. Penetrations by Raceways, Sprinklers and Fire Dampers(1) Combustible totally enclosed raceways that are embedded in a concrete floor slab are permitted in an assembly required to have a fire-resistance rating, provided the concrete cover between the raceway and the bottom of the slab is not less than 50 mm. (2) Totally enclosed raceways are permitted to penetrate a fire…. Sprinkler piping may cross a fire separation only if both fire compartments are sprinklered. A fire damper may penetrate without the firestop rules of 9.10.9.6. if installed to NFPA 80, specifically designed with a firestop, or provided under 9.10.5.1.(3).

Practice this topic

Exhaust ducts and central vacuum systems

  • A vertical service space containing an exhaust duct serving more than one fire compartment needs a fan at or near the exhaust outlet so the duct is under negative pressure; individual compartments must not have fans that blow into that duct OBC Div. B 9.10.9.20.OBC Div. B 9.10.9.20. Exhaust Ducts Serving More Than One Fire Compartment(1) Where a vertical service space contains an exhaust duct that serves more than one fire compartment, the duct shall have a fan located at or near the exhaust outlet to ensure that the duct is under negative pressure. (2) Individual fire compartments referred to in Sentence (1) shall not have fans that exhaust….
  • A central vacuum system serves not more than one suite OBC Div. B 9.10.9.21.OBC Div. B 9.10.9.21. Central Vacuum Systems(1) Except as permitted by Sentence 9.10.18.7.(1), a central vacuum system shall serve not more than one suite., except a system in a building with a fire alarm system that shuts down when the alarm activates OBC Div. B 9.10.18.7.OBC Div. B 9.10.18.7. Central Vacuum Systems(1) Central vacuum cleaning systems serving more than one suite or storey in a building equipped with a fire alarm system shall be designed to shut down upon activation of the fire alarm system..

Practice this topic

Service rooms and fuel-fired appliance locations

Service rooms in an unsprinklered floor area need a 1 h fire separation, unless the room holds only a limited amount of equipment that is not a fire hazard OBC Div. B 9.10.10.3.OBC Div. B 9.10.10.3. Separation of Service Rooms(1) Except as provided in Sentence (2) and Articles 9.10.10.5. and 9.10.10.6., service rooms shall be separated from the remainder of the building by a fire separation having a fire-resistance rating of not less than 1 h when the floor area containing the service room is not sprinklered. (2) Where a room contains a….

Fuel-fired appliances go in a service room with a 1 h fire separation OBC Div. B 9.10.10.4.OBC Div. B 9.10.10.4. Locations of Fuel-Fired Appliances(1) Except as provided in Sentences (2) and (3) and Article 9.10.10.5., fuel-fired appliances shall be located in a service room separated from the remainder of the building by a fire separation having not less than a 1 h fire-resistance rating. (2) Except as required in the appliance installation standards referenced…, except space-heating, space-cooling appliances and service water heaters that:

Exception Condition
Small service area Serve not more than one room or suite
Small building Serve a building of not more than 400 m² building area and not more than 2 storeys
House with a secondary suite Serve the house and common spaces, in a service room lined on both sides of walls and under floor framing with a continuous smoke-tight barrier of at least 15.9 mm Type X gypsum board

Fireplaces and cooking appliances are not caught by the service room rule at all.

Practice this topic

Closures, fire dampers and fire stop flaps

  • Openings in fire separations need closures rated per the closure table and installed to NFPA 80 OBC Div. B 9.10.13.1.OBC Div. B 9.10.13.1. Closures(1) Except as provided in Article 9.10.13.2., openings in required fire separations shall be protected with a closure conforming to Table 9.10.13.1. and shall be installed in conformance with NFPA 80, "Standard for Fire Doors and Other Opening Protectives," unless otherwise specified in this Part. (See also Article…. A 1 h separation needs a 45 min closure.
  • Openings in interior fire separations are capped at 11 m² (no dimension over 3.7 m) if either side is unsprinklered, or 22 m² (no dimension over 6 m) if both sides are sprinklered OBC Div. B 9.10.13.8.OBC Div. B 9.10.13.8. Maximum Size of Opening(1) The size of an opening in an interior fire separation, even where protected with a closure, shall not exceed 11 m², with no dimension greater than 3.7 m, if a fire compartment on either side of the fire separation is not sprinklered. (2) The size of an opening in an interior fire separation, even where protected….

Fire dampers OBC Div. B 9.10.13.13.OBC Div. B 9.10.13.13. Fire Dampers(1) Except as permitted in Sentences (2) to (5), 9.10.5.1.(3) and 9.10.9.9.(5), a duct that penetrates an assembly required to be a fire separation with a fire-resistance rating shall be equipped with a fire damper in conformance with Articles 3.1.8.4. and 3.1.8.10. (2) A fire damper is not required where a…. A duct through a rated fire separation needs a fire damper meeting 3.1.8.4. and 3.1.8.10., except:

Exception Conditions
Small noncombustible branch Melting point not below 760°C, cross-section less than 130 cm², supplies only AC or AC/heating units discharging not more than 1.2 m above the floor
Branch into upward exhaust riser Melting point not below 760°C, carried up inside the riser at least 500 mm, riser under negative pressure
Shaft ducts exhausting at top Melting point above 760°C, each duct exhausts directly outside at the top of the shaft
Commercial cooking duct No damper at the separation

Fire stop flaps in rated ceiling membranes conform to CAN/ULC-S112.2 and activate about 30°C above the normal maximum duct temperature OBC Div. B 9.10.13.14.OBC Div. B 9.10.13.14. Fire Stop Flaps(1) Fire stop flaps in ceiling membranes required in Sentence 9.10.5.1.(3) shall (a) conform to CAN/ULC-S112.2, "Standard Method of Fire Test of Ceiling Firestop Flap Assemblies," and (b) activate at a temperature approximately 30°C above the normal maximum temperature that occurs in the ducts, whether the air duct….

Practice this topic

Fire blocks and openings in exposing building faces

  • Two Subsections split the spatial separation rules. Subsection 9.10.15. covers houses (buildings with only dwelling units and none above another) and houses with a secondary suite; Subsection 9.10.14. covers other Part 9 buildings. In 9.10.14., unprotected openings are limited by the table, by Subsection 3.2.3., or (with limiting distance at least 1.2 m) to the limiting distance squared for residential, business and low-hazard industrial occupancies OBC Div. B 9.10.14.4.OBC Div. B 9.10.14.4. Openings in Exposing Building Face(1) Except as provided in Sentences (6) to (10) and Sentence 9.10.14.6.(1), the maximum aggregate area of unprotected openings in an exposing building face shall (a) conform to Table 9.10.14.4., (b) conform to Subsection 3.2.3., or (c) where the limiting distance is not less than 1.2 m, be equal to or less than (i)…. Houses use the parallel glazed-opening rules in 9.10.15.4.
  • In a house, an opening of not more than 130 cm² in an exposing building face need not be protected by a closure OBC Div. B 9.10.15.4.OBC Div. B 9.10.15.4. Glazed Openings in Exposing Building Face(1) Except as provided in Sentences (6) to (9), the maximum area of glazed openings in an exposing building face shall (a) conform to Table 9.10.15.4., (b) conform to Subsection 3.2.3. as if the glazed openings were unprotected openings, or (c) where the limiting distance is not less than 1.2 m, be equal to or less…. This is the Sentence that lets small vent and duct terminations pass through a wall with limiting distance under 1.2 m. Subsection 9.10.14. has no matching exemption.
  • Where fire blocks are pierced by pipes or ducts, their effectiveness must be maintained OBC Div. B 9.10.16.4.OBC Div. B 9.10.16.4. Penetration of Fire Blocks(1) Where fire blocks are pierced by pipes, ducts or other elements, the effectiveness of the fire blocks shall be maintained around such elements.. Wall fire blocks go at each floor and at maximum 20 m horizontal and 3 m vertical spacing OBC Div. B 9.10.16.2.OBC Div. B 9.10.16.2. Required Fire Blocks in Wall Assemblies(1) Except as permitted in Sentence (2), fire blocks shall be provided to block off concealed spaces within wall assemblies, including spaces created by furring, (a) at each floor level, (b) at each ceiling level where the ceiling contributes to part of the required fire-resistance rating, and (c) at other locations….
  • Light diffusers with higher flame spread than the ceiling finish follow Part 3 OBC Div. B 9.10.17.8.OBC Div. B 9.10.17.8. Light Diffusers and Lenses(1) Light diffusers and lenses having flame-spread ratings that exceed those permitted for the ceiling finish, shall conform to the requirements of Sentence 3.1.13.4.(1)..
  • Fire protection equipment in unheated areas must be protected from freezing OBC Div. B 9.10.20.5.OBC Div. B 9.10.20.5. Freeze Protection for Fire Protection Systems(1) Equipment forming part of a fire protection system that may be adversely affected by freezing temperatures and that is located in an unheated area shall be protected from freezing..

Practice this topic

Smoke alarms, including cottages

Topic Requirement
Where required Each dwelling unit, each sleeping room not in a dwelling unit, and ancillary and common spaces in a house with a secondary suite OBC Div. B 9.10.19.1.OBC Div. B 9.10.19.1. Required Smoke Alarms(1) Except as permitted by Article 9.10.19.8., smoke alarms conforming to CAN/ULC-S531, "Standard for Smoke Alarms," shall be installed in (a) each dwelling unit, (b) each sleeping room not within a dwelling unit, and (c) ancillary spaces and common spaces not in dwelling units in a house with a secondary suite. (2)…
Location Every storey including basements; in each sleeping room; and between sleeping rooms and the rest of the storey (in the hallway if there is one) OBC Div. B 9.10.19.3.OBC Div. B 9.10.19.3. Location of Smoke Alarms(1) Except as permitted in Article 9.10.19.8., within dwelling units, sufficient smoke alarms shall be installed so that (a) there is at least one smoke alarm installed on each storey, including basements, and (b) on any storey of a dwelling unit containing sleeping rooms, a smoke alarm is installed (i) in each…
Mounting On or near the ceiling, installed to CAN/ULC-S553
Power Permanently connected, no disconnect switch, battery for 7 days then 4 minutes of alarm OBC Div. B 9.10.19.4.OBC Div. B 9.10.19.4. Power Supply(1) Except as provided in Sentences (2) and (3), smoke alarms described in Sentence 9.10.19.1.(1) and 9.10.19.3.(1.1) shall (a) be installed with permanent connections to an electrical circuit, (See Note A-3.2.4.20.(9) (a)) (b) have no disconnect switch between the overcurrent device and the smoke alarm, and (c) in…
Interconnection All alarms in a dwelling unit; all alarms throughout a house with a secondary suite OBC Div. B 9.10.19.5.OBC Div. B 9.10.19.5. Interconnection of Smoke Alarms(1) Where more than one smoke alarm is required in a dwelling unit, the smoke alarms shall be wired so that the activation of one alarm will cause all alarms within the dwelling unit to sound. (2) Smoke alarms in a house with a secondary suite shall be wirelessly interconnected or interconnected by hard-wiring so that…
Silencing Manual device, silence not more than 10 min OBC Div. B 9.10.19.6.OBC Div. B 9.10.19.6. Silencing of Smoke Alarms(1) Except as permitted in Sentence (2), a manually operated device shall be incorporated within the circuitry of a smoke alarm installed in a dwelling unit so that the signal emitted by the smoke alarm can be silenced for a period of not more than 10 min, after which the smoke alarm will reset and sound again if the…
Visual signal NFPA 72 characteristics, at least 175 cd in sleeping rooms

Seasonal recreational buildings (cottages) may skip heating, ventilation and similar systems, but whatever is provided must meet Part 9, and the 9.33.3.1. indoor design temperatures need not be met OBC Div. B 9.37.2.1.OBC Div. B 9.37.2.1. Exclusions(1) Except as provided in Subsection 9.10.15. and Articles 9.37.2.4. and 9.37.3.1., buildings used or intended to be used as seasonal recreational buildings need not comply with Sections 9.5. to 9.7. and 9.9. to 9.11. (2) Flooring need not comply with Section 9.30., but tight-fitting floors shall be provided to…. Every cottage dwelling unit still needs smoke alarms to Subsection 9.10.19. OBC Div. B 9.37.2.4.OBC Div. B 9.37.2.4. Smoke Alarms(1) Every dwelling unit within the scope of this Section shall be provided with a smoke alarm in accordance with Subsection 9.10.19..

Practice this topic

Common traps

  • Assuming every duct through a fire separation needs a damper. Check the four exceptions.
  • Mixing F and FT ratings: FT is for firewalls and tested outlet box firestops.
  • Forgetting the 130 cm² exemption for a house vent near a property line.

Chapter review

Chapter at a glance

One line per section: the idea to carry into the exam. Then the answers that most often catch candidates out.

Usual exam traps

  • Assuming every duct through a fire separation needs a damper. Check the four exceptions.
  • Mixing F and FT ratings: FT is for firewalls and tested outlet box firestops.
  • Forgetting the 130 cm² exemption for a house vent near a property line.

Practice this chapter

Questions on Part 9 fire protection for HVAC services, in the exam format, every answer explained and cited to its article. Sign in to start; a free account gets the free questions.

Code cited in this chapter

Based on the official 2024 Building Code Compendium on ontario.ca.

© King's Printer for Ontario, 2024. Reproduced with permission.

  • OBC Div. B 9.9.1.3. Occupant Load

    (1)The occupant load of a floor area or part of a floor area shall be based on

    (a)two persons per sleeping room or sleeping area in a dwelling unit or suite, and

    (b)for occupancies other than as described in Clause (a), the number of persons

    (i)for which the area is designed, or

    (ii)determined from Table 3.1.17.1.

    Open OBC Div. B 9.9.1.3. in the code viewer
  • OBC Div. B 9.10.2.1. Occupancy Classification

    (1)Every building or part of it shall be classified according to its major occupancy as belonging to one of the groups or divisions described in Table 9.10.2.1.

    Open OBC Div. B 9.10.2.1. in the code viewer
  • OBC Div. B 9.10.1.3. Items Under Part 3 Jurisdiction

    (1)Tents, air-supported structures, transformer vaults, walkways, elevators and escalators shall conform to Part 3.

    (2)Where rooms or spaces are intended for an assembly occupancy, such rooms or spaces shall conform to Part 3.

    (3)Basements containing more than 1 storey or exceeding 600 m² in area shall conform to Part 3.

    (4)Where rooms or spaces are intended for the storage, manufacture or use of hazardous or explosive material, such rooms or spaces shall conform to Part 3.

    (5)Reserved.

    (6)Openings through floors that are not protected by shafts or closures shall be protected in conformance with Subsection 3.2.8. (See also Sentence 9.9.4.7.(1))

    (7)Chutes and shafts shall conform to Subsection 3.6.3. except where they are entirely contained within a dwelling unit.

    (8)Sprinkler systems shall be designed, constructed and installed in conformance with Articles 3.2.5.12. to 3.2.5.15. and 3.2.5.17. (See Note A-9.10.1.3.(8) and (9))

    (9)Standpipe and hose systems shall be designed, constructed and installed in conformance with Articles 3.2.5.8. to 3.2.5.11. and 3.2.5.17. (See Note A-9.10.1.3.(8) and (9))

    (10)Fire pumps shall be installed in conformance with Articles 3.2.5.17. and 3.2.5.18.

    (11)Where fuel-fired appliances are installed on a roof, such appliances shall be installed in conformance with Article 3.6.1.5.

    Open OBC Div. B 9.10.1.3. in the code viewer
  • OBC Div. B 9.10.3.4. Suspended Membrane Ceiling

    (1)Where a ceiling construction has a suspended membrane ceiling with lay-in panels or tiles that contribute to the required fire-resistance rating, hold down clips or other means shall be provided to prevent the lifting of such panels or tiles in the event of a fire.

    Open OBC Div. B 9.10.3.4. in the code viewer
  • OBC Div. B 9.10.5.1. Permitted Openings in Wall and Ceiling Membranes

    (1)Except as permitted in Sentences (2) and (3), a membrane forming part of an assembly required to have a fire-resistance rating shall not be pierced by openings into the assembly unless the assembly has been tested and rated for such openings.

    (2)A wall or ceiling membrane forming part of an assembly required to have a fire-resistance rating is permitted to be pierced by openings for electrical and similar service outlet boxes, provided such outlet boxes and the penetrations conform to Article 9.10.9.8.

    (2.1)Where boxes referred to in Sentence (2) are located on both sides of walls required to provide a fire-resistance rating, they shall be offset where necessary to maintain the integrity of the fire separation.

    (3)A membrane ceiling forming part of an assembly assigned a fire-resistance rating on the basis of Table 2 of MMAH Supplementary Standard SB-3, "Fire and Sound Resistance Tables," is permitted to be pierced by openings leading to ducts within the ceiling space provided the ducts, the amount of openings and their protection conform to Sentence 9.10.13.14.(1) and the requirements in MMAH Supplementary Standard SB-2, "Fire Performance Ratings."

    Open OBC Div. B 9.10.5.1. in the code viewer
  • OBC Div. B 9.10.9.6. General Requirements for Penetrations of Fire Separations

    (1)Except as required by Sentence (2) and Articles 9.10.9.7. and 9.10.9.8. and as permitted by Article 9.10.9.9., penetrations of a required fire separation or a membrane forming part of an assembly required to be a fire separation shall be

    (a)sealed by a firestop that, when subjected to the fire test method in CAN/ULC-S115, "Standard Method of Fire Tests of Firestop Systems," has an F rating not less than the required fire-resistance rating for the fire separation,

    (b)tightly fitted or cast in place, provided the penetrating item is made of steel, ferrous, copper, concrete or masonry, or

    (c)sealed to maintain the integrity of the fire separation. (See Note A-9.10.9.6.(1))

    (2)Penetrations of a firewall shall be sealed at the penetration by a firestop that, when subjected to the fire test method in "CAN/ULC-S115, "Standard Method of Fire Tests of Firestop Systems," has an FT rating not less than the fire-resistance rating for the fire separation.

    Open OBC Div. B 9.10.9.6. in the code viewer
  • OBC Div. B 9.10.9.7. Piping Penetrations

    (1)Except as provided in Sentences (2) and (5), piping for drain, waste, vent and central vacuum systems that is not located in a vertical shaft is permitted to penetrate a fire separation required to have a fire-resistance rating or a membrane that forms part of an assembly required to have a fire-resistance rating, provided the penetration is protected in accordance with Clause 9.10.9.6.(1)(a) or (b).

    (2)Drain piping leading directly from a water closet through a concrete floor slab is permitted to penetrate a horizontal fire separation or a membrane that contributes to the required fire-resistance rating of a horizontal fire separation, provided

    (a)the piping is noncombustible and the penetration is protected in accordance with Sentence 9.10.9.6.(1), or

    (b)the piping is combustible and the penetration is sealed by a firestop conforming to Clause 9.10.9.6.(1)(a).

    (3)Combustibledrain, waste and vent piping is permitted on one side of a vertical fire separation, provided it is not located in a vertical shaft.

    (4)In buildings containing two dwelling units only, combustible drain, waste and vent piping is permitted on one side of a horizontal fire separation.

    (5)Water distribution piping is permitted to partly or wholly penetrate a fire separation required to have a fire-resistance rating, provided

    (a)the piping is noncombustible and the penetration is protected in accordance with Sentence 9.10.9.6.(1), or

    (b)the piping is combustible and is not located in a vertical shaft, and the penetration is sealed by a firestop conforming to Clause 9.10.9.6.(1)(a).

    Open OBC Div. B 9.10.9.7. in the code viewer
  • OBC Div. B 9.10.9.8. Penetrations by Outlet Boxes or Service Equipment in Concealed Spaces

    (1)Except as provided in Sentences (2) to (5), outlet boxes are permitted to penetrate the membrane of an assembly required to have a fire-resistance rating, provided they are sealed at the penetration by a firestop that, when subjected to the fire test method in CAN/ULC-S115, "Standard Method of Fire Tests of Firestop Systems," has an FT rating not less than the fire-resistance rating of the fire separation. (See Note A-9.10.9.8.(1))

    (2)Except as provided in Sentence 9.10.9.6.(2), noncombustible outlet boxes that penetrate a fire separation or a membrane forming part of an assembly required to have a fire-resistance rating need not conform to Sentence (1), provided

    (a)they do not exceed

    (i)0.016 m² in area, and

    (ii)an aggregate area of 0.065 m² in any 9.3 m² of surface area, and

    (b)the annular space between the membrane and the noncombustible outlet boxes does not exceed 3 mm.

    (3)Except as provided in Sentence 9.10.9.6.(2), combustible outlet boxes that penetrate a fire separation or a membrane forming part of an assembly required to have a fire-resistance rating need not conform to Sentence (1), provided

    (a)the outlet boxes are

    (i)separated from the remainder of the space within the assembly by an enclosure of not more than 0.3 m² in area made of fire block material conforming to Article 9.10.16.3., or (See Note A-9.10.9.8.(3) (a)(i))

    (ii)located in a space within the assembly that is filled with preformed fibre insulation processed from rock or slag conforming to CAN/ULC-S702.1, "Standard for Mineral Fibre Thermal Insulation for Buildings, Part 1: Material Specification," and having a mass per unit area of not less than 1.22 kg/m² of wall surface such that the exposed sides and back of the outlet box are encapsulated by the noncombustible insulation, and

    (b)the outlet boxes do not exceed an aggregate area of 0.016 m² in any individual enclosure as described in Subclause (a)(i) or any individual insulated space as described in Subclause (a)(ii).

    (4)Noncombustible outlet boxes conforming to Sentence (2) are permitted to be located on opposite sides of a vertical fire separation having a fire-resistance rating and need not conform to Sentence (1), provided they are

    (a)separated from each other by a horizontal distance of not less than 600 mm,

    (b)separated from each other and the remainder of the wall space by an enclosure conforming to Subclause (3)(a)(i), or

    (c)located in an insulated wall space in accordance with Subclause (3)(a)(ii).

    (5)Combustible outlet boxes conforming to Sentence (3) are permitted to be located on opposite sides of a vertical fire separation having a fire-resistance rating and need not conform to Sentence (1).

    (6)Service equipment is permitted to penetrate a horizontal fire separation conforming to Sentence 9.10.9.12.(2), provided the penetration is sealed by

    (a)a firestop that, when subjected to the fire test method in CAN/ULC-S115, "Standard Method of Fire Tests of Firestop Systems," has an FT rating not less than the required fire-resistance rating for the fire separation,

    (b)a firestop conforming to Clause 9.10.9.6.(1)(a), where the service equipment is located entirely within the cavity of a wall assembly above and below the horizontal fire separation having a required fire-resistance rating, or

    (c)a firestop conforming to Clause 9.10.9.6.(1)(a), where the penetration is

    (i)contained within the concealed space of a floor or ceiling assembly having a fire-resistance rating,

    (ii)located above a ceiling membrane providing a horizontal fire separation, or

    (iii)contained within a horizontal service space conforming to Sentence 9.10.9.12.(2) that is directly above or below a floor or ceiling.

    Open OBC Div. B 9.10.9.8. in the code viewer
Show all 31 articles
  • OBC Div. B 9.10.9.9. Penetrations by Raceways, Sprinklers and Fire Dampers

    (1)Combustible totally enclosed raceways that are embedded in a concrete floor slab are permitted in an assembly required to have a fire-resistance rating, provided the concrete cover between the raceway and the bottom of the slab is not less than 50 mm.

    (2)Totally enclosed raceways are permitted to penetrate a fire separation, provided they are sealed at the penetration by a firestop conforming to Clause 9.10.9.6.(1)(a).

    (3)Sprinkler piping is permitted to penetrate a fire separation, provided the fire compartments on each side of the fire separation are sprinklered.

    (4)Sprinklers are permitted to penetrate a fire separation or a membrane forming part of an assembly required to have a fire-resistance rating without having to meet the firestop requirements of Article 9.10.9.6. and Clause 9.10.9.8.(6)(a), provided the annular space created by the penetration of a fire sprinkler is covered by a metal escutcheon plate in accordance with NFPA 13, "Standard for the Installation of Sprinkler Systems."

    (5)Fire dampers are permitted to penetrate a fire separation or a membrane forming part of an assembly required to have a fire-resistance rating without having to meet the firestop requirements of Sentence 9.10.9.6.(1), provided the fire damper is

    (a)installed in conformance with NFPA 80, "Standard for Fire Doors and Other Opening Protectives,"

    (b)specifically designed with a firestop, or

    (c)provided in conformance with Sentence 9.10.5.1.(3). (See also Note A-3.1.9.2.(1).)

    Open OBC Div. B 9.10.9.9. in the code viewer
  • OBC Div. B 9.10.9.20. Exhaust Ducts Serving More Than One Fire Compartment

    (1)Where a vertical service space contains an exhaust duct that serves more than one fire compartment, the duct shall have a fan located at or near the exhaust outlet to ensure that the duct is under negative pressure.

    (2)Individual fire compartments referred to in Sentence (1) shall not have fans that exhaust directly into the duct in the vertical service space.

    Open OBC Div. B 9.10.9.20. in the code viewer
  • OBC Div. B 9.10.9.21. Central Vacuum Systems

    (1)Except as permitted by Sentence 9.10.18.7.(1), a central vacuum system shall serve not more than one suite.

    Open OBC Div. B 9.10.9.21. in the code viewer
  • OBC Div. B 9.10.18.7. Central Vacuum Systems

    (1)Central vacuum cleaning systems serving more than one suite or storey in a building equipped with a fire alarm system shall be designed to shut down upon activation of the fire alarm system.

    Open OBC Div. B 9.10.18.7. in the code viewer
  • OBC Div. B 9.10.10.3. Separation of Service Rooms

    (1)Except as provided in Sentence (2) and Articles 9.10.10.5. and 9.10.10.6., service rooms shall be separated from the remainder of the building by a fire separation having a fire-resistance rating of not less than 1 h when the floor area containing the service room is not sprinklered.

    (2)Where a room contains a limited quantity of service equipment and the service equipment does not constitute a fire hazard, the requirements in Sentence (1) shall not apply.

    Open OBC Div. B 9.10.10.3. in the code viewer
  • OBC Div. B 9.10.10.4. Locations of Fuel-Fired Appliances

    (1)Except as provided in Sentences (2) and (3) and Article 9.10.10.5., fuel-fired appliances shall be located in a service room separated from the remainder of the building by a fire separation having not less than a 1 h fire-resistance rating.

    (2)Except as required in the appliance installation standards referenced in Sentences 6.2.1.5.(1) and 9.10.10.5.(1), fuel-fired space-heating appliances, space-cooling appliances and service water heaters need not be separated from the remainder of the building as required in Sentence (1),

    (a)where the appliances serve

    (i)not more than one room or suite, or

    (ii)a building with a building area of not more than 400 m² and a building height of not more than 2 storeys, or

    (b)where the appliances

    (i)serve a house with a secondary suite including their common spaces, and

    (ii)are located in a service room where both sides of any wall assemblies and the underside of any floor-ceiling framing separating this room from both dwelling units or their common spaces are protected by a continuous smoke-tight barrier consisting of not less than 15.9 mm thick Type X gypsum board.

    (3)Sentence (1) does not apply to fireplaces and cooking appliances.

    Open OBC Div. B 9.10.10.4. in the code viewer
  • OBC Div. B 9.10.13.1. Closures

    (1)Except as provided in Article 9.10.13.2., openings in required fire separations shall be protected with a closure conforming to Table 9.10.13.1. and shall be installed in conformance with NFPA 80, "Standard for Fire Doors and Other Opening Protectives," unless otherwise specified in this Part. (See also Article 9.10.3.1.)

    Open OBC Div. B 9.10.13.1. in the code viewer
  • OBC Div. B 9.10.13.8. Maximum Size of Opening

    (1)The size of an opening in an interior fire separation, even where protected with a closure, shall not exceed 11 m², with no dimension greater than 3.7 m, if a fire compartment on either side of the fire separation is not sprinklered.

    (2)The size of an opening in an interior fire separation, even where protected with a closure, shall not exceed 22 m², with no dimension greater than 6 m, when the fire compartments on both sides of the fire separation are sprinklered.

    Open OBC Div. B 9.10.13.8. in the code viewer
  • OBC Div. B 9.10.13.13. Fire Dampers

    (1)Except as permitted in Sentences (2) to (5), 9.10.5.1.(3) and 9.10.9.9.(5), a duct that penetrates an assembly required to be a fire separation with a fire-resistance rating shall be equipped with a fire damper in conformance with Articles 3.1.8.4. and 3.1.8.10.

    (2)A fire damper is not required where a noncombustible branch duct pierces a required fire separation provided the duct

    (a)has a melting point not below 760°C,

    (b)has a cross-sectional area less than 130 cm², and

    (c)supplies only air-conditioning units or combined air-conditioning and heating units discharging air at not more than 1.2 m above the floor.

    (3)A fire damper is not required where a noncombustible branch duct pierces a required fire separation around an exhaust duct riser in which the air flow is upward provided

    (a)the melting point of the branch duct is not below 760°C,

    (b)the branch duct is carried up inside the riser at least 500 mm, and

    (c)the exhaust duct is under negative pressure as described in Article 9.10.9.20.

    (4)Noncombustible ducts that penetrate a fire separation separating a vertical service space from the remainder of the building need not be equipped with a fire damper at the fire separation provided

    (a)the ducts have a melting point above 760°C, and

    (b)each individual duct exhausts directly to the outside at the top of the vertical service space.

    (5)A duct serving commercial cooking equipment and piercing a required fire separation need not be equipped with a fire damper at the fire separation.

    Open OBC Div. B 9.10.13.13. in the code viewer
  • OBC Div. B 9.10.13.14. Fire Stop Flaps

    (1)Fire stop flaps in ceiling membranes required in Sentence 9.10.5.1.(3) shall

    (a)conform to CAN/ULC-S112.2, "Standard Method of Fire Test of Ceiling Firestop Flap Assemblies," and

    (b)activate at a temperature approximately 30°C above the normal maximum temperature that occurs in the ducts, whether the air duct system is operating or shut down.

    Open OBC Div. B 9.10.13.14. in the code viewer
  • OBC Div. B 9.10.14.4. Openings in Exposing Building Face

    (1)Except as provided in Sentences (6) to (10) and Sentence 9.10.14.6.(1), the maximum aggregate area of unprotected openings in an exposing building face shall

    (a)conform to Table 9.10.14.4.,

    (b)conform to Subsection 3.2.3., or

    (c)where the limiting distance is not less than 1.2 m, be equal to or less than

    (i)the limiting distance squared, for residential occupancies, business and personal services occupancies and low-hazard industrial occupancies, and

    (ii)half the limiting distance squared, for mercantile occupancies and medium-hazard industrial occupancies.

    (2)Except as provided in Sentence 9.10.14.6.(1), openings in a wall having a limiting distance of less than 1.2 m shall be protected by closures, of other than wired glass or glass block, whose fire protection rating is in conformance with the fire-resistance rating required for the wall.

    (3)Reserved.

    (4)Reserved.

    (5)Reserved.

    (6)The maximum aggregate area of unprotected openings is permitted to be up to twice the area determined according to Sentence (1), where the unprotected openings are glazed with

    (a)wired glass in steel frames as described in Article 9.10.13.5., or

    (b)glass blocks, as described in Article 9.10.13.7.

    (7)Where the building is sprinklered, the maximum aggregate area of unprotected openings is permitted to be up to twice the area determined according to Sentence (1), provided all rooms, including closets and bathrooms, that are adjacent to the exposing building face and that have unprotected openings are sprinklered, notwithstanding any exemptions in the sprinkler standards referenced in Article 3.2.5.12.

    (8)The maximum aggregate area of unprotected openings in an exposing building face of a storage garage need not comply with Sentence (1), where

    (a)all storeys are constructed as open-air storeys, and

    (b)the storage garage has a limiting distance of not less than 3 m.

    (9)The maximum aggregate area of unprotected openings in an exposing building face of a storey that faces a street and is the same level as the street need not comply with Sentence (1) where the limiting distance is not less than 9 m.

    (10)Except as provided in Sentence (11), for garages or accessory buildings that serve a single dwelling unit only and are detached from any building, the maximum aggregate area of glazed openings shall comply with the requirements for unprotected openings.

    (11)The limits on the area of glazed openings need not apply to the exposing building face of a detached garage or accessory building facing a dwelling unit, where

    (a)the detached garage or accessory building serves only one dwelling unit,

    (b)the detached garage or accessory building is located on the same property as that dwelling unit, and

    (c)the dwelling unit served by the detached garage or accessory building is the only major occupancy on the property.

    Open OBC Div. B 9.10.14.4. in the code viewer
  • OBC Div. B 9.10.15.4. Glazed Openings in Exposing Building Face

    (1)Except as provided in Sentences (6) to (9), the maximum area of glazed openings in an exposing building face shall

    (a)conform to Table 9.10.15.4.,

    (b)conform to Subsection 3.2.3. as if the glazed openings were unprotected openings, or

    (c)where the limiting distance is not less than 1.2 m, be equal to or less than the limiting distance squared.

    (2)Where the limits on the area of glazed openings are determined for individual portions of the exposing building face, as described in Subclause 9.10.15.2.(1)(b)(iii), the maximum aggregate area of glazed openings for any portion shall be determined using the values in Table 9.10.15.4. corresponding to

    (a)the maximum total area of exposing building face, which is equal to the sum of all portions of the exposing building face, and

    (b)the limiting distance of each portion. (See Note A-9.10.15.4.(2))

    (3)Reserved.

    (4)Reserved.

    (5)Reserved

    (6)The limits on the area of glazed openings shall not apply to the exposing building face of a dwelling unit facing a detached garage or accessory building, where

    (a)the detached garage or accessory building serves only one dwelling unit,

    (b)the detached garage or accessory building is located on the same property as that dwelling unit, and

    (c)the dwelling unit served by the detached garage or accessory building is the only major occupancy on the property.

    (7)The maximum aggregate area of glazed openings in an exposing building face is permitted to be up to twice the area determined in accordance with Sentence (1), where

    (a)the glazed openings consist of glass blocks, as described in Article 9.10.13.7., or

    (b)the building is sprinklered, provided all rooms, including closets, bathrooms and attached garages, that are adjacent to the exposing building face and that have glazed openings are sprinklered, notwithstanding any exemptions in the sprinkler standards referenced in Article 3.2.5.12.

    (8)Except as provided in Sentence (9), openings in a wall having a limiting distance of less than 1.2 m shall be protected by closures, of other than wired glass or glass block, whose fire-protection rating is in conformance with the fire-resistance rating required for the wall.

    (9)An opening in an exposing building face not more than 130 cm² need not be protected by a closure.

    Open OBC Div. B 9.10.15.4. in the code viewer
  • OBC Div. B 9.10.16.4. Penetration of Fire Blocks

    (1)Where fire blocks are pierced by pipes, ducts or other elements, the effectiveness of the fire blocks shall be maintained around such elements.

    Open OBC Div. B 9.10.16.4. in the code viewer
  • OBC Div. B 9.10.16.2. Required Fire Blocks in Wall Assemblies

    (1)Except as permitted in Sentence (2), fire blocks shall be provided to block off concealed spaces within wall assemblies, including spaces created by furring,

    (a)at each floor level,

    (b)at each ceiling level where the ceiling contributes to part of the required fire-resistance rating, and

    (c)at other locations within the wall, so that the distance between fire blocks does not exceed 20 m horizontally and 3 m vertically.

    (2)Fire blocks described in Sentence (1) are not required, provided

    (a)the insulated wall assembly contains not more than one concealed air space whose horizontal thickness is not more than 25 mm,

    (b)the exposed construction materials within the space are noncombustible, or

    (c)the exposed construction materials within the space, including insulation, but not including wiring, piping or similar services, have a flame-spread rating of not more than 25, or

    (d)the concealed wall space is filled with insulation.

    Open OBC Div. B 9.10.16.2. in the code viewer
  • OBC Div. B 9.10.17.8. Light Diffusers and Lenses

    (1)Light diffusers and lenses having flame-spread ratings that exceed those permitted for the ceiling finish, shall conform to the requirements of Sentence 3.1.13.4.(1).

    Open OBC Div. B 9.10.17.8. in the code viewer
  • OBC Div. B 9.10.20.5. Freeze Protection for Fire Protection Systems

    (1)Equipment forming part of a fire protection system that may be adversely affected by freezing temperatures and that is located in an unheated area shall be protected from freezing.

    Open OBC Div. B 9.10.20.5. in the code viewer
  • OBC Div. B 9.10.19.1. Required Smoke Alarms

    (1)Except as permitted by Article 9.10.19.8., smoke alarms conforming to CAN/ULC-S531, "Standard for Smoke Alarms," shall be installed in

    (a)each dwelling unit,

    (b)each sleeping room not within a dwelling unit, and

    (c)ancillary spaces and common spaces not in dwelling units in a house with a secondary suite.

    (2)Smoke alarms required in Sentence (1) shall have a visual signalling component conforming to the requirements in 18.5.3. (Light, Color and Pulse Characteristics) of NFPA 72, "National Fire Alarm and Signaling Code."

    (3)The visual signalling component required in Sentence (2) need not

    (a)be integrated with the smoke alarm provided it is interconnected to it,

    (b)be on battery backup, or

    (c)have synchronized flash rates, when installed in a house with a secondary suite or an individual dwelling unit.

    (4)The luminous intensity for visual signalling components required in Sentence (2) that are installed in sleeping rooms shall be a minimum of 175 cd.

    Open OBC Div. B 9.10.19.1. in the code viewer
  • OBC Div. B 9.10.19.3. Location of Smoke Alarms

    (1)Except as permitted in Article 9.10.19.8., within dwelling units, sufficient smoke alarms shall be installed so that

    (a)there is at least one smoke alarm installed on each storey, including basements, and

    (b)on any storey of a dwelling unit containing sleeping rooms, a smoke alarm is installed

    (i)in each sleeping room, and

    (ii)in a location between the sleeping rooms and the remainder of the storey, and if the sleeping rooms are served by a hallway, the smoke alarm shall be located in the hallway. (See Note A-9.10.19.3.(1))

    (1.1)Except as permitted in Article 9.10.19.8., within a house with a secondary suite that contains an interior shared means of egress or common area, a smoke alarm shall be installed in each shared means of egress and common area.

    (2)A smoke alarm required in Sentences (1) and (1.1) shall be installed in conformance with CAN/ULC-S553, "Standard for Installation of Smoke Alarms."

    (3)Smoke alarms required in Article 9.10.19.1. and Sentences (1) and (1.1) shall be installed on or near the ceiling.

    (4)A smoke alarm required in Sentences (1) and (1.1) shall have a visual signalling component conforming to the requirements in 18.5.3. (Light, Color and Pulse Characteristics) of NFPA 72, "National Fire Alarm and Signaling Code."

    (5)The visual signalling component required in Sentence (4) need not

    (a)be integrated with the smoke alarm provided it is interconnected to it,

    (b)be on battery backup, or

    (c)have synchronized flash rates, when installed in a house with a secondary suite or an individual dwelling unit.

    (6)The luminous intensity for visual signalling components required in Sentence (4) that are installed in sleeping rooms shall be a minimum of 175 cd.

    Open OBC Div. B 9.10.19.3. in the code viewer
  • OBC Div. B 9.10.19.4. Power Supply

    (1)Except as provided in Sentences (2) and (3), smoke alarms described in Sentence 9.10.19.1.(1) and 9.10.19.3.(1.1) shall

    (a)be installed with permanent connections to an electrical circuit, (See Note A-3.2.4.20.(9) (a))

    (b)have no disconnect switch between the overcurrent device and the smoke alarm, and

    (c)in case the regular power supply to the smoke alarm is interrupted, be provided with a battery as an alternative power source that can continue to provide power to the smoke alarm for a period of not less than 7 days in the normal condition, followed by 4 minutes of alarm.

    (2)Where the building is not supplied with electrical power, smoke alarms are permitted to be battery-operated.

    (3)Suites of residential occupancy are permitted to be equipped with smoke detectors in lieu of smoke alarms, provided the smoke detectors

    (a)are capable of independently sounding audible signals with a sound pressure level between 75 dBA and 110 dBA within the individual suites, (See also Note A-3.2.4.18.(4))

    (b)except as permitted in Sentence (4), are installed in conformance with CAN/ULC-S524, "Standard for Installation of Fire Alarm Systems," and

    (c)form part of the fire alarm system. (See Note A-9.10.19.5.(2))

    (4)Smoke detectors permitted to be installed in lieu of smoke alarms as stated in Sentence (3) are permitted to sound localized alarms within individual suites, and need not sound an alarm throughout the rest of the building.

    Open OBC Div. B 9.10.19.4. in the code viewer
  • OBC Div. B 9.10.19.5. Interconnection of Smoke Alarms

    (1)Where more than one smoke alarm is required in a dwelling unit, the smoke alarms shall be wired so that the activation of one alarm will cause all alarms within the dwelling unit to sound.

    (2)Smoke alarms in a house with a secondary suite shall be wirelessly interconnected or interconnected by hard-wiring so that the activation of any one smoke alarm causes all smoke alarms within the house with a secondary suite to sound. (See Note A-9.10.19.5.(2))

    Open OBC Div. B 9.10.19.5. in the code viewer
  • OBC Div. B 9.10.19.6. Silencing of Smoke Alarms

    (1)Except as permitted in Sentence (2), a manually operated device shall be incorporated within the circuitry of a smoke alarm installed in a dwelling unit so that the signal emitted by the smoke alarm can be silenced for a period of not more than 10 min, after which the smoke alarm will reset and sound again if the level of smoke in the vicinity is sufficient to reactuate it.

    (2)Suites of residential occupancy equipped with smoke detectors installed to CAN/ULC-S524, "Standard for Installation of Fire Alarm Systems," which are part of the fire alarm system in lieu of smoke alarms as permitted in Sentence 9.10.19.4.(3), need not incorporate the manually operated device required in Sentence (1).

    Open OBC Div. B 9.10.19.6. in the code viewer
  • OBC Div. B 9.37.2.1. Exclusions

    (1)Except as provided in Subsection 9.10.15. and Articles 9.37.2.4. and 9.37.3.1., buildings used or intended to be used as seasonal recreational buildings need not comply with Sections 9.5. to 9.7. and 9.9. to 9.11.

    (2)Flooring need not comply with Section 9.30., but tight-fitting floors shall be provided to support the live and dead loads.

    (3)Except as provided in Sentence (4), thermal insulation, vapour barrier, air barrier construction, interior finishes, plumbing, heating, mechanical ventilation, air-conditioning and electrical facilities, need not be provided, but where any of these are provided, they shall comply with the requirements of this Part.

    (4)Where heating and air-conditioning are provided, Article 9.33.3.1. need not be complied with.

    Open OBC Div. B 9.37.2.1. in the code viewer
  • OBC Div. B 9.37.2.4. Smoke Alarms

    (1)Every dwelling unit within the scope of this Section shall be provided with a smoke alarm in accordance with Subsection 9.10.19.

    Open OBC Div. B 9.37.2.4. in the code viewer