Values this chapter turns on
- indoor design temperature for living spaces
- 22°C
- indoor design temperature for living spaces
- indoor design temperature for unfinished basements
- 18°C
- indoor design temperature for unfinished basements
- indoor design temperature for heated crawl spaces
- 15°C
- indoor design temperature for heated crawl spaces
- Sa(0.2) above which equipment must be secured
- 0.55
- Sa(0.2) above which equipment must be secured
Subsections 9.33.1. to 9.33.5. set the ground rules for heating and cooling a house: which buildings need heat, what temperatures the system must hold, how the system is designed and sized, and which installation standards apply. Sizing is where the code leans on an outside document, CSA F280. This chapter explains what the code requires and when F280 applies, without teaching F280 itself.
Required heating systems and design temperatures
Scope OBC Div. B 9.33.1.1.OBC Div. B 9.33.1.1. Application(1) This Section applies to the design and installation of (a) heating systems, including requirements for combustion air, and air-conditioning systems serving only one dwelling unit, and (b) radiant heating systems in houses with a secondary suite including their common spaces. (2) The design and installation of…. Section 9.33. covers heating systems (including combustion air) and air-conditioning systems serving only one dwelling unit, plus radiant heating in a house with a secondary suite and its common spaces. Anything else (for example one forced-air system serving both units of a house with a secondary suite) follows Part 6. Two more rules in the same Article:
- Repairs or component replacements that change the capacity or safety of an existing system and alter how it operates must conform to the code.
- Air duct systems serving one unit of a house with a secondary suite must not be directly interconnected with other parts of the house.
Who needs heat. Residential buildings intended for use through the winter on a continuing basis must have heating facilities OBC Div. B 9.33.2.1.OBC Div. B 9.33.2.1. Residential Heating Systems(1) Residential buildings intended for use in the winter months on a continuing basis shall be equipped with heating facilities conforming to this Section..
Indoor design temperatures at the outside design temperature OBC Div. B 9.33.3.1.OBC Div. B 9.33.3.1. Indoor Design Temperatures(1) At the outside design temperature, required heating facilities shall be capable of maintaining an indoor air temperature of not less than (a) 22°C in all living spaces, (b) 18°C in unfinished basements, (c) 18°C in common service rooms, ancillary spaces and exits in houses with a secondary suite, and (d) 15°C in…:
| Space | Minimum indoor temperature |
|---|---|
| Living spaces | 22°C |
| Unfinished basements | 18°C |
| Common service rooms, ancillary spaces and exits in a house with a secondary suite | 18°C |
| Heated crawl spaces | 15°C |
Outdoor design temperatures come from SB-1 using the 2.5 percent criteria OBC Div. B 9.33.3.2.OBC Div. B 9.33.3.2. Outdoor Design Temperatures(1) The outdoor conditions to be used in designing heating, ventilating and air-conditioning systems shall be the appropriate values for the location as set out in MMAH Supplementary Standard SB-1, "Climatic and Seismic Data," using 2.5 percent design temperature criteria..
General requirements and system sizing
Design basis OBC Div. B 9.33.4.1.OBC Div. B 9.33.4.1. Design of Heating and Air-Conditioning Systems(1) Heating, ventilating and air-conditioning systems, including related mechanical refrigeration systems, shall be designed, constructed and installed to conform to good engineering practice appropriate to the circumstances such as described in (a) the ASHRAE Handbooks and Standards, (b) CSA F280, "Determining the…. HVAC systems, including related refrigeration, must follow good engineering practice such as:
- ASHRAE Handbooks and Standards,
- CSA F280, "Determining the required capacity of residential space heating and cooling appliances", with outside winter design temperatures from SB-1,
- CAN/CSA-F326-M (residential mechanical ventilation),
- NFPA Standards, HRAI Digest, Hydronics Institute Manuals and SMACNA Manuals.
Sizing OBC Div. B 9.33.5.1.OBC Div. B 9.33.5.1. Capacity of Heating Appliances(1) The heating system capacity shall be based on the heating load calculated in accordance with Sentence 9.33.4.1.(1). (2) Where a cooling system is installed, the cooling system capacity shall be based on the cooling load calculated in accordance with Sentence 9.33.4.1.(1). (3) The oversizing and undersizing of…:
| Item | What the code says |
|---|---|
| Heating capacity | Based on the heating load calculated under Sentence 9.33.4.1.(1) |
| Cooling capacity (if cooling installed) | Based on the cooling load calculated the same way |
| Oversizing and undersizing | Determined under CSA F280 |
What the candidate must know about F280. The code makes F280 the reference for residential heating and cooling capacity, and makes it the rule for how much a furnace or air conditioner may be oversized or undersized. The code does not reproduce F280's method, room-by-room factors or tolerances. On this exam, expect to identify that F280 governs equipment sizing, that SB-1 supplies the winter design temperature, and that sizing must be based on a calculated load (not on floor area rules of thumb). Questions that would need F280's internal numbers are outside the code text. Our question bank does not test them.
Other general rules:
| Article | Rule in plain words |
|---|---|
| 9.33.4.2.OBC Div. B 9.33.4.2. Installation of Hydronic Heating Systems(1) The design and installation of hydronic heating systems shall conform to (a) CSA B214, "Installation code for hydronic heating systems", or (b) good engineering practice appropriate to the circumstances such as described in Article 9.33.4.1. | Hydronic heating to CSA B214 or good engineering practice |
| 9.33.4.3.OBC Div. B 9.33.4.3. Heating System Control(1) Each dwelling unit shall be provided with a temperature control in accordance with Article 12.3.1.3. (See Note A-9.33.4.3.(1)) | Each dwelling unit has a temperature control meeting Article 12.3.1.3. (programmable thermostat) |
| 9.33.4.4.OBC Div. B 9.33.4.4. Access(1) Equipment forming part of a heating or air-conditioning system, with the exception of embedded pipes or ducts, shall be installed with provision for access for inspection, maintenance, repair and cleaning. | Equipment accessible for inspection, maintenance, repair and cleaning (embedded pipes and ducts excepted) |
| 9.33.4.5.OBC Div. B 9.33.4.5. Protection from Freezing(1) Equipment forming part of a heating or air-conditioning system that may be adversely affected by freezing temperatures and that is located in an unheated area shall be protected from freezing. | Protect equipment in unheated areas from freezing |
| 9.33.4.6.OBC Div. B 9.33.4.6. Expansion, Contraction and System Pressure(1) Heating and cooling systems shall be designed to allow for expansion and contraction of the heat transfer fluid and to maintain the system pressure within the rated working pressure limits of all components of the system. | Allow for fluid expansion; keep within rated working pressures |
| 9.33.4.7.OBC Div. B 9.33.4.7. Structural Movement(1) Mechanical systems and equipment shall be designed and installed to accommodate the maximum amount of structural movement provided for in the construction of the building. (2) Where the building is in a location where the spectral acceleration, S_a(0.2) , is greater than 0.55, heating and air-conditioning… | Accommodate structural movement; where Sa(0.2) exceeds 0.55, secure equipment with fuel or power connections against overturning |
| 9.33.4.8.OBC Div. B 9.33.4.8. Asbestos(1) Asbestos shall not be used in air distribution systems or equipment. | No asbestos in air distribution systems or equipment |
| 9.33.4.9.OBC Div. B 9.33.4.9. Contaminant Transfer(1) Systems serving garages, and systems serving other occupied parts of a dwelling unit but located in or running through a garage, shall be designed and constructed in a manner such that means are not provided for the transfer of contaminants from the garage into other spaces in the dwelling unit. | Systems serving or passing through a garage must not transfer garage contaminants to the dwelling |
Appliances, equipment and installation standards
Earth energy systems OBC Div. B 9.33.5.2.OBC Div. B 9.33.5.2. Installation Standards (See also Article 9.33.5.3.)(1) The design and installation of earth energy systems shall conform to CAN/CSA-C448.2, "Design and installation of earth energy systems for residential and other small buildings," where such systems use groundwater, submerged heat exchangers or ground heat exchangers to serve, (a) a house with or without a secondary…. Systems using groundwater, submerged or ground heat exchangers that serve a house (with or without a secondary unit), or another building with not more than 1,400 m² of conditioned space, follow CAN/CSA-C448.2. Buildings other than houses conditioning more than 1,400 m² follow C448.1.
Solid-fuel appliances OBC Div. B 9.33.5.3.OBC Div. B 9.33.5.3. Design, Construction and Installation Standard for Solid-Fuel-Burning Appliances(1) The design, construction and installation, including the provision of combustion air, of solid-fuel-burning appliances and equipment, including stoves, cooktops, ovens and space heaters, shall conform to CSA B365, "Installation Code for Solid-Fuel-Burning Appliances and Equipment." (See Note A-9.33.5.3.(1)) (2)…. Design, construction and installation, including combustion air, of stoves, cooktops, ovens and space heaters burning solid fuel follow CSA B365. Solid-fuel stoves, furnaces and hydronic systems (other than coal-burning) must meet particulate emission limits of CSA B415.1 or the US EPA new residential wood heater standard.
Fireplaces conform to Section 9.22. OBC Div. B 9.33.5.4.OBC Div. B 9.33.5.4. Fireplaces(1) Fireplaces shall conform to Section 9.22..
Common traps
- Designing an unfinished basement to 22°C (overkill) or a finished basement to 18°C (non-compliant). The finish decides.
- Treating a single furnace serving both units of a house with a secondary suite as a 9.33 system. It goes to Part 6.
- Saying the code lets designers oversize freely for comfort. Oversizing limits come from F280.
- Forgetting the seismic securing rule only applies where Sa(0.2) is greater than 0.55.
Chapter review
Chapter at a glance
One line per section: the idea to carry into the exam. Then the answers that most often catch candidates out.
- Required heating systems and design temperatures
Outdoor design temperatures come from SB-1 using the 2.5 percent criteria.
- General requirements and system sizing
What the candidate must know about F280. The code makes F280 the reference for residential heating and cooling capacity, and makes it the rule for how much a furnace or air…
- Appliances, equipment and installation standards
Fireplaces conform to Section 9.22..
Usual exam traps
- Designing an unfinished basement to 22°C (overkill) or a finished basement to 18°C (non-compliant). The finish decides.
- Treating a single furnace serving both units of a house with a secondary suite as a 9.33 system. It goes to Part 6.
- Saying the code lets designers oversize freely for comfort. Oversizing limits come from F280.
- Forgetting the seismic securing rule only applies where Sa(0.2) is greater than 0.55.
Practice this chapter
Questions on Heating and air-conditioning systems (9.33.1 to 9.33.5), in the exam format, every answer explained and cited to its article. Sign in to start; a free account gets the free questions.
Code cited in this chapter
Based on the official 2024 Building Code Compendium on ontario.ca.
© King's Printer for Ontario, 2024. Reproduced with permission.
OBC Div. B 9.33.1.1. Application
Open OBC Div. B 9.33.1.1. in the code viewer(1)This Section applies to the design and installation of
(a)heating systems, including requirements for combustion air, and air-conditioning systems serving only one dwelling unit, and
(b)radiant heating systems in houses with a secondary suite including their common spaces.
(2)The design and installation of heating systems, including requirements for combustion air, and air-conditioning systems other than those described in Sentence (1) shall conform to Part 6. (See Note A-9.33.1.1.(2) and Subsection 9.10.10.)
(2.1)Repairs or component replacements that change the capacity or extent of safety of an existing heating, ventilating or air-conditioning system and that alter the method of operation shall conform to this Code.
(3)Air duct distribution systems serving one of the dwelling units in a house with a secondary suite shall not be directly interconnected with other parts of the house.
OBC Div. B 9.33.2.1. Residential Heating Systems
Open OBC Div. B 9.33.2.1. in the code viewer(1)Residential buildings intended for use in the winter months on a continuing basis shall be equipped with heating facilities conforming to this Section.
OBC Div. B 9.33.3.1. Indoor Design Temperatures
Open OBC Div. B 9.33.3.1. in the code viewer(1)At the outside design temperature, required heating facilities shall be capable of maintaining an indoor air temperature of not less than
(a)22°C in all living spaces,
(b)18°C in unfinished basements,
(c)18°C in common service rooms, ancillary spaces and exits in houses with a secondary suite, and
(d)15°C in heated crawl spaces.
OBC Div. B 9.33.3.2. Outdoor Design Temperatures
Open OBC Div. B 9.33.3.2. in the code viewer(1)The outdoor conditions to be used in designing heating, ventilating and air-conditioning systems shall be the appropriate values for the location as set out in MMAH Supplementary Standard SB-1, "Climatic and Seismic Data," using 2.5 percent design temperature criteria.
OBC Div. B 9.33.4.1. Design of Heating and Air-Conditioning Systems
Open OBC Div. B 9.33.4.1. in the code viewer(1)Heating, ventilating and air-conditioning systems, including related mechanical refrigeration systems, shall be designed, constructed and installed to conform to good engineering practice appropriate to the circumstances such as described in
(a)the ASHRAE Handbooks and Standards,
(b)CSA F280, "Determining the required capacity of residential space heating and cooling appliances," and the outside winter design temperatures shall conform to MMAH Supplementary Standard SB-1, "Climatic and Seismic Data,"
(c)CAN/CSA-F326-M, "Residential Mechanical Ventilation Systems,"
(d)the NFPA Standards,
(e)the HRAI Digest,
(f)the Hydronics Institute Manuals, and
(g)the SMACNA Manuals. (See also Subsection 9.32.3. for the design of systems that also provide ventilation.)
OBC Div. B 9.33.5.1. Capacity of Heating Appliances
Open OBC Div. B 9.33.5.1. in the code viewer(1)The heating system capacity shall be based on the heating load calculated in accordance with Sentence 9.33.4.1.(1).
(2)Where a cooling system is installed, the cooling system capacity shall be based on the cooling load calculated in accordance with Sentence 9.33.4.1.(1).
(3)The oversizing and undersizing of heating and cooling equipment capacities shall be determined in accordance with the requirements of CSA F280, "Determining the required capacity of residential space heating and cooling appliances."
OBC Div. B 9.33.4.2. Installation of Hydronic Heating Systems
Open OBC Div. B 9.33.4.2. in the code viewer(1)The design and installation of hydronic heating systems shall conform to
(a)CSA B214, "Installation code for hydronic heating systems", or
(b)good engineering practice appropriate to the circumstances such as described in Article 9.33.4.1.
OBC Div. B 9.33.4.3. Heating System Control
Open OBC Div. B 9.33.4.3. in the code viewer(1)Each dwelling unit shall be provided with a temperature control in accordance with Article 12.3.1.3. (See Note A-9.33.4.3.(1))
Show all 17 articles
OBC Div. B 9.33.4.4. Access
Open OBC Div. B 9.33.4.4. in the code viewer(1)Equipment forming part of a heating or air-conditioning system, with the exception of embedded pipes or ducts, shall be installed with provision for access for inspection, maintenance, repair and cleaning.
OBC Div. B 9.33.4.5. Protection from Freezing
Open OBC Div. B 9.33.4.5. in the code viewer(1)Equipment forming part of a heating or air-conditioning system that may be adversely affected by freezing temperatures and that is located in an unheated area shall be protected from freezing.
OBC Div. B 9.33.4.6. Expansion, Contraction and System Pressure
Open OBC Div. B 9.33.4.6. in the code viewer(1)Heating and cooling systems shall be designed to allow for expansion and contraction of the heat transfer fluid and to maintain the system pressure within the rated working pressure limits of all components of the system.
OBC Div. B 9.33.4.7. Structural Movement
Open OBC Div. B 9.33.4.7. in the code viewer(1)Mechanical systems and equipment shall be designed and installed to accommodate the maximum amount of structural movement provided for in the construction of the building.
(2)Where the building is in a location where the spectral acceleration, S_a(0.2) , is greater than 0.55, heating and air-conditioning equipment with fuel or power connections shall be secured to the structure to resist overturning and displacement. (See Note A-9.31.6.2.(3))
OBC Div. B 9.33.4.8. Asbestos
Open OBC Div. B 9.33.4.8. in the code viewer(1)Asbestos shall not be used in air distribution systems or equipment.
OBC Div. B 9.33.4.9. Contaminant Transfer
Open OBC Div. B 9.33.4.9. in the code viewer(1)Systems serving garages, and systems serving other occupied parts of a dwelling unit but located in or running through a garage, shall be designed and constructed in a manner such that means are not provided for the transfer of contaminants from the garage into other spaces in the dwelling unit.
OBC Div. B 9.33.5.2. Installation Standards (See also Article 9.33.5.3.)
Open OBC Div. B 9.33.5.2. in the code viewer(1)The design and installation of earth energy systems shall conform to CAN/CSA-C448.2, "Design and installation of earth energy systems for residential and other small buildings," where such systems use groundwater, submerged heat exchangers or ground heat exchangers to serve,
(a)a house with or without a secondary unit, or,
(b)a building, other than a house with or without a secondary unit, where the conditioned space is not more than 1,400 m².
(2)Except for a house with or without a secondary unit, the design and installation of earth energy systems shall conform to CAN/CSA-C448.1, "Design and installation of earth energy systems for commercial and institutional buildings," where such systems use groundwater, submerged heat exchangers or ground heat exchangers to condition a floor space area more than 1,400 m².
OBC Div. B 9.33.5.3. Design, Construction and Installation Standard for Solid-Fuel-Burning Appliances
Open OBC Div. B 9.33.5.3. in the code viewer(1)The design, construction and installation, including the provision of combustion air, of solid-fuel-burning appliances and equipment, including stoves, cooktops, ovens and space heaters, shall conform to CSA B365, "Installation Code for Solid-Fuel-Burning Appliances and Equipment." (See Note A-9.33.5.3.(1))
(2)Solid fuel-burning stoves, furnaces and hydronic heating systems designed to burn solid fuels, other than coal, shall conform to the particulate emission limits of,
(a)CSA B415.1, "Performance Testing of Solid-Fuel-Burning Heating Appliances", or
(b)the "Standards of Performance for New Residential Wood Heaters", set out in Subpart AAA of Part 60 of Title 40 of the Code of Federal Regulations, published by the United States Environmental Protection Agency, as it read on March 16, 2015. (See Note A-9.33.5.3.(2))
OBC Div. B 9.33.5.4. Fireplaces
Open OBC Div. B 9.33.5.4. in the code viewer(1)Fireplaces shall conform to Section 9.22.