Fire Protection study guideLarge and complex buildings

Part 9 egress and fire protection

Part 9 application items, window and door requirements, means of egress (except stair geometry), almost all of 9.10 fire protection (except spatial separation and flame spread), crawl space fire protection, CO alarms, heating and air-conditioning, wiring, emergency lighting and cottages.

chapters in this guide
13 of 14
chapters in this guide
to read
6 min
to read
code articles cited
52
code articles cited

Last updated

Values this chapter turns on

minimum open area of a bedroom egress window
0.35 m²
minimum open area of a bedroom egress window
no bedroom window opening dimension below this
380 mm
no bedroom window opening dimension below this
Part 9 fire separation between suites
45 min
Part 9 fire separation between suites
max glazing in doors and sidelights to an exit
0.8 m²
max glazing in doors and sidelights to an exit

Fire protection inspectors also cover small buildings, so the syllabus reaches into Part 9: egress (except stair geometry), most of Section 9.10. fire protection (not spatial separation or flame spread), crawl space plenums, heating, wiring, emergency lighting, CO alarms and seasonal cottages. Many Part 9 rules are short versions of the Part 3 rules you already know, with different numbers. The exam likes those differences.

Means of egress: exits, protection of exits and obstructions

Part 9 applies to buildings up to 3 storeys and 600 m² of the listed occupancies (OBC Div. B 9.1.1.1.OBC Div. B 9.1.1.1. Application(1) The application of this Part shall be as described in Subsection 1.3.3. of Division A.); self-storage, tents, air-supported structures and rack storage still go to Part 3 Sections (9.1.1.3.OBC Div. B 9.1.1.3. Self-Service Storage Buildings(1) Self-service storage buildings shall conform to the requirements in Section 3.10., 9.1.1.4.OBC Div. B 9.1.1.4. Tents and Air-Supported Structures(1) Tents shall conform to the requirements in Subsection 3.14.1. (2) Air-supported structures shall conform to the requirements in Subsection 3.14.2., 9.1.1.11.OBC Div. B 9.1.1.11. Shelf and Rack Storage Systems(1) Shelf and rack storage systems shall conform to the requirements of Section 3.16.). Factory-built buildings certified to CSA A277 (or Z240.2.1 for narrow sections) are deemed to comply, but site work still follows the code (9.1.1.9.OBC Div. B 9.1.1.9. Site Assembled and Factory-Built Buildings(1) Except as provided in Sentence (2) and in Sentence 12.2.1.2.(2), a manufactured building is deemed to comply with this Code if it is designed and constructed in compliance with, (a) CSA Z240.2.1, "Structural requirements for manufactured homes," if the building is constructed in sections not wider than 4.88 m, or…). Section 9.7. sends egress doors and windows to 9.9. and firefighter access windows to 9.10.20. (9.7.2.2.OBC Div. B 9.7.2.2. Other Requirements for Windows, Doors and Skylights(1) Minimum sizes of doorways and doors within a barrier-free path of travel shall conform to Section 9.5. (2) The protection of window and door openings to protect persons from falling through them shall conform to Article 9.8.8.1. (3) Properties of windows and doors within exits shall conform to Section 9.9. (4)…).

Exits are the same list as Part 3, but fire escapes are for existing buildings only, and elevators, slide escapes and windows never count as required egress (9.9.2.1.OBC Div. B 9.9.2.1. Types of Exits(1) Except as otherwise provided in this Section, an exit from any floor area shall be one of the following used singly or in combination: (a) an exterior doorway, (b) an exterior passageway, (c) an exterior ramp, (d) an exterior stairway, (e) a fire escape, (f) a horizontal exit, (g) an interior passageway, (h) an…, 9.9.2.3.OBC Div. B 9.9.2.3. Elevators, Slide Escapes and Windows as Means of Egress(1) Elevators, slide escapes or windows shall not be considered as part of a required means of egress. (2) Except for floor areas of mercantile occupancy, casement windows not less than 1,060 mm high, 560 mm wide, with a sill height not more than 900 mm above the inside floor, are permitted to be considered part of a…).

Exit protection (9.9.4.2.OBC Div. B 9.9.4.2. Fire Separation for Exits(1) Except as provided in Sentence (5) and Article 9.9.8.5., every exit other than an exit doorway shall be separated from each adjacent floor area or from another exit by a fire separation having a fire-resistance rating not less than that required for the floor assembly above the floor area. (2) Where there is no…): rated as the floor above, or if none, the floor below but at least 45 min; separations between two exits are smoke-tight and unpierced; only exit-serving services, sprinkler and standpipe piping, exit doors and permitted glazing may penetrate. Glazing in doors plus sidelights to an exit enclosure is limited to 0.8 m² in total unless a 45 min vestibule intervenes (9.9.4.3.OBC Div. B 9.9.4.3. Wired Glass or Glass Block)(1) This Article applies to wired glass in doors, and wired glass or glass block in sidelights, where these are installed in fire separations between exit enclosures and floor areas. (2) Except as provided in Sentence (3), the combined area of glazing in doors and sidelights shall not exceed 0.8 m². (3) Where an exit…). Openings near unenclosed exterior exit stairs, and near exit doors at inside corners under 135°, need wired glass or glass block (9.9.4.4.OBC Div. B 9.9.4.4. Openings Near Unenclosed Exterior Exit Stairs and Ramps(1) Where an unenclosed exterior exit stair or ramp provides the only means of egress from a suite, and is exposed to fire from openings in the exterior walls of another fire compartment, or another dwelling unit, ancillary space or common space in a house with a secondary suite, the openings in the exterior walls of… to 9.9.4.6.OBC Div. B 9.9.4.6. Openings Near Exit Doors(1) This Article applies to (a) exit doors serving other than an individual dwelling unit, and (b) exit doors serving an individual dwelling unit where there is no second and separate exit from the dwelling unit. (2) Where an exterior exit door described in Sentence (1) in one fire compartment is within 3 m…).

Obstructions (9.9.5.OBC Div. B 9.9.5.3. Obstructions in Public Corridors(1) Except as permitted in Sentence (2), obstructions located within 1,980 mm of the floor shall not project horizontally more than 100 mm into exit passageways, corridors used by the public or public corridors in a manner that would create a hazard for visually impaired persons travelling adjacent to walls. (2) The…): wall-mounted items within 1,980 mm of the floor may project 100 mm into public corridors (more if lower than 680 mm); posts and turnstiles may not narrow egress below 750 mm; fuel-fired appliances never go in exits or access-to-exit corridors; pressure boilers never sit under exits; storage, washroom and service rooms never open into an exit.

Doors open without keys, with one hand and one operation, hardware at 900 mm to 1,100 mm, and exit doors open under 90 N (9.9.6.7.OBC Div. B 9.9.6.7. Door Latching, Locking and Opening Mechanisms(1) Principal entrance doors, exit doors and doors to suites, including exterior doors of dwelling units, and other doors in an access to exit shall (a) be openable from the inside or in travelling to an exit without requiring keys, special devices or specialized knowledge of the door-opening mechanism, or (b) be…, 9.9.6.8.OBC Div. B 9.9.6.8. Effort Required to Open(1) Except as required by Sentence 3.8.3.3.(7), every exit door, except doors serving a single dwelling unit or a house with a secondary suite, shall be designed and installed so that when the latch is released the door will open in the direction of exit travel under a force of not more than 90 N applied to the door…).

Practice this topic

Access to exits, exits from floor areas and dwelling unit egress

Item Part 9 value
Two egress doors from a room or suite area over 200 m² (D, E, F2, F3) or 150 m² (C), or travel over 25 m (9.9.7.4.OBC Div. B 9.9.7.4. Number and Spacing of Egress Doors(1) Except for dwelling units, at least two egress doors shall be provided where (a) the area of a room or suite exceeds 200 m² in a Group D, E, F2 and F3 occupancy, or 150 m² in a Group C occupancy, or (b) the distance measured from any point within a room or suite to the nearest egress door exceeds 25 m. (2) Doors…)
Travel to exit 40 m business, 45 m sprinklered, 30 m others (9.9.8.2.OBC Div. B 9.9.8.2. Number of Required Exits(1) Except as provided in Sentences (2) and (3) and Subsection 9.9.9., at least 2 exits shall be provided from every floor area, spaced so that the travel distance to the nearest exit is not more than (a) 40 m in the case of business and personal services occupancies, (b) 45 m for all occupancies where the floor area…)
Single exit 1 and 2 storey buildings within 9.9.7.4. limits and max 60 persons
Roof for more than 60 persons 2 separate means of egress (9.9.7.1.OBC Div. B 9.9.7.1. Egress from Roof Area, Podiums, Terraces, Platforms and Contained Open Spaces(1) An access to exit shall be provided from every roof intended for occupancy and from every podium, terrace, platform or contained open space. (2) Where a roof is intended for an occupant load of more than 60 persons, at least 2 separate means of egress shall be provided from the roof to stairs designed in…)
Exit through a lobby only one; lobby max 4.5 m above grade, 15 m through (9.9.8.5.OBC Div. B 9.9.8.5. Exiting Through a Lobby(1) Not more than one exit from a floor area is permitted to lead through a lobby. (2) The lobby referred to in Sentence (1) shall be not more than 4.5 m above grade, and the path of travel through the lobby to the outdoors shall not exceed 15 m. (3) The lobby referred to in Sentence (1) shall conform in all respects…)

From a suite door on a public corridor you must be able to go two ways to two exits, unless a dead-end corridor meets 9.9.7.3. or the suite has a second egress (9.9.7.2.OBC Div. B 9.9.7.2. Means of Egress from Suites(1) Except as required in Sentence 9.9.9.3.(1), each suite in a floor area occupied by more than one suite shall have (a) an exterior exit doorway, (b) a doorway to a public corridor, or (c) a doorway to an exterior passageway. (2) Except as provided in Sentences 9.9.7.3.(1) and 9.9.8.2.(2), from the point where a…, 9.9.9.2.OBC Div. B 9.9.9.2. Two Separate Exits(1) Except as provided in Sentence 9.9.7.3.(1) and except for dwelling units in a house with a secondary suite, where an egress door from a dwelling unit opens onto a public corridor or exterior passageway it shall be possible from the location where the egress door opens onto the corridor or exterior passageway to go…). A multi-level dwelling unit must not need more than one storey of travel to an egress door, unless the level has direct access to a balcony or, where no other suite is above or below the unit, an escape window (opening at least 1 m by 0.55 m, sill not more than 1 m above the floor and 7 m above ground) (9.9.9.1.OBC Div. B 9.9.9.1. Travel Limit to Exits or Egress Doors(1) Except as provided in Sentences (2) and (3), every dwelling unit containing more than 1 storey shall have exits or egress doors located so that it shall not be necessary to travel up or down more than 1 storey to reach a level served by (a) an egress door to a public corridor, enclosed exit stair or exterior…).

Bedroom windows (9.9.10.1.OBC Div. B 9.9.10.1. Egress Windows or Doors for Bedrooms(1) Except where a door on the same floor level as the bedroom provides direct access to the exterior, every floor level containing a bedroom in a suite shall be provided with at least one outside window that (a) is openable from the inside without the use of tools, (b) provides an individual, unobstructed open…): every floor level with a bedroom needs an outside window openable without tools giving at least 0.35 m² with no dimension under 380 mm, sill max 1,000 mm (except basements), with 550 mm clearance in a window well.

Exit signs (9.9.11.3.OBC Div. B 9.9.11.3. Exit Signs(1) Except as required in Sentence (7), every exit door shall have an exit sign placed over it or adjacent to it if the exit serves (a) a building that is 3 storeys in building height, (b) a building having an occupant load of more than 150, or (c) a room or floor area that has a fire escape as part of a required…) are needed where the building is 3 storeys, holds over 150 persons, or has a fire escape. Egress lighting averages 50 lx; emergency lighting gives 10 lx average and 1 lx minimum for at least 30 min from a separate source (9.9.12.2.OBC Div. B 9.9.12.2. Required Lighting in Egress Facilities(1) Every exit, public corridor or corridor providing access to exit for the public shall be equipped to provide illumination to an average level of not less than 50 lx at floor or tread level and at all points such as angles and intersections at changes of level where there are stairs or ramps. (2) The minimum value…, 9.9.12.3.OBC Div. B 9.9.12.3. Emergency Lighting(1) Emergency lighting shall be provided in (a) exits. (b) principal routes providing access to exit in an open floor area, (c) corridors used by the public, (d) underground walkways, and (e) public corridors. (2) Emergency lighting required in Sentence (1) shall be provided from a source of energy separate from the…), and 9.34.3. points to the same rules (9.34.3.1.OBC Div. B 9.34.3.1. Criteria for Emergency Lighting(1) Emergency lighting shall conform to Subsection 9.9.12.).

Practice this topic

Part 9 fire separations, service rooms and closures

Separation Rating
Suite to suite (not D) 45 min (9.10.9.15.OBC Div. B 9.10.9.15. Separation of Suites(1) Except as required in Article 9.10.9.16. and as permitted by Sentence (2), each suite in other than business and personal services occupancies shall be separated from adjoining suites by a fire separation having a fire-resistance rating of not less than 45 min. (2) In sprinklered buildings, suites of business and…)
Residential suites; multi-level dwelling units to rest 45 min; 1 h (9.10.9.16.OBC Div. B 9.10.9.16. Separation of Residential Suites(1) Except as provided in Sentences (2) and (3) and Article 9.10.21.2., suites in residential occupancies shall be separated from adjacent rooms and suites by a fire separation having a fire-resistance rating of not less than 45 min. (2) Sleeping rooms in boarding, lodging or rooming houses where sleeping…)
Residential to other occupancies 1 h (9.10.9.13.OBC Div. B 9.10.9.13. Separation of Residential Occupancies(1) Except as provided in Sentences (2) and (4), residential occupancies shall be separated from all other major occupancies by a fire separation having a fire-resistance rating of not less than 1 h. (2) Except as provided in Sentence (3), a major occupancy classified as a residential occupancy, including live/work…)
Residential to mercantile or F2 2 h (1 h with not more than 2 dwelling units and mercantile)
Public corridor 45 min; none in sprinklered, supervised non-residential floors (9.10.9.17.OBC Div. B 9.10.9.17. Separation of Public Corridors(1) Except as otherwise required by this Part and as provided in Sentences (2) to (5), public corridors shall be separated from the remainder of the building by a fire separation having not less than a 45 min fire-resistance rating. (2) In other than residential occupancies, no fire-resistance rating is required for…)
Storage garage 1.5 h; 1 h for 5 vehicles or fewer (9.10.9.18.OBC Div. B 9.10.9.18. Separation of Storage Garages(1) Except as provided in Sentences (2) and (3), a storage garage shall be separated from other occupancies by a fire separation having not less than a 1.5 h fire-resistance rating. (2) Except as permitted in Sentence (3), storage garages containing 5 motor vehicles or fewer shall be separated from other occupancies…)
Repair garage 2 h, sometimes 1 h (9.10.9.19.OBC Div. B 9.10.9.19. Separation of Repair Garages(1) Except as provided in Sentences (2) and (3), a repair garage shall be separated from other occupancies by a fire separation having a fire-resistance rating of not less than 2 h. (2) Ancillary spaces directly serving a repair garage, including waiting rooms, reception rooms, tool and parts storage areas and…)
Service room (unsprinklered) and fuel-fired appliance room 1 h (9.10.10.3.OBC Div. B 9.10.10.3. Separation of Service Rooms(1) Except as provided in Sentence (2) and Articles 9.10.10.5. and 9.10.10.6., service rooms shall be separated from the remainder of the building by a fire separation having a fire-resistance rating of not less than 1 h when the floor area containing the service room is not sprinklered. (2) Where a room contains a…, 9.10.10.4.OBC Div. B 9.10.10.4. Locations of Fuel-Fired Appliances(1) Except as provided in Sentences (2) and (3) and Article 9.10.10.5., fuel-fired appliances shall be located in a service room separated from the remainder of the building by a fire separation having not less than a 1 h fire-resistance rating. (2) Except as required in the appliance installation standards referenced…)
Incinerator; emergency generator 2 h; 1 h or 2 h by floor rating (9.10.10.5.OBC Div. B 9.10.10.5. Incinerators(1) Service rooms containing incinerators shall be separated from the remainder of the building by a fire separation having a fire-resistance rating of not less than 2 h. (2) The design, construction, installation and alteration of each indoor incinerator shall conform to NFPA 82, "Standard on Incinerators and Waste…, 9.10.10.7.OBC Div. B 9.10.10.7. Emergency Power Installation(1) Where a generator intended to supply emergency power for lighting, fire safety and life safety systems is located in a building, it shall be located in a room that, (a) is separated from the remainder of the building by a fire separation with a fire-resistance rating not less than (i) 1 h, if the floor assembly is…)

Fuel-fired heating, cooling and water heating appliances need no service room if they serve one room or suite, or a building of max 400 m² and 2 storeys. Penetrations get an F-rated firestop, cast-in metal or a sealed fit (9.10.9.6.OBC Div. B 9.10.9.6. General Requirements for Penetrations of Fire Separations(1) Except as required by Sentence (2) and Articles 9.10.9.7. and 9.10.9.8. and as permitted by Article 9.10.9.9., penetrations of a required fire separation or a membrane forming part of an assembly required to be a fire separation shall be (a) sealed by a firestop that, when subjected to the fire test method in…).

Closures follow Table 9.10.13.1.OBC Div. B Table 9.10.13.1. Fire-Protection Ratings for Closures — Forming Part of Sentence 9.10.13.1.(1)Table 9.10.13.1 — Fire-Protection Ratings for Closures — Forming Part of Sentence 9.10.13.1.(1) Forming Part of Sentence 9.10.13.1.(1) Required Fire-Resistance Rating of Fire Separation | Required Fire-Protection Rating of Closure 30 or 45 min | 20 min[1] 1 h | 45 min[1] 1.5 h | 1 h 2 h | 1.5 h 3 h | 2 h 4 h | 3 h…: 20 min doors for 30 or 45 min separations, 45 min for 1 h. A 45 mm solid core wood door to CAN/ULC-S113 may replace a 20 min door or serve between a corridor and a suite (9.10.13.2.OBC Div. B 9.10.13.2. Solid Core Wood Door as a Closure(1) A 45 mm thick solid core wood door is permitted to be used where a minimum fire-protection rating of 20 min is permitted or between a public corridor and a suite provided the door conforms to CAN/ULC-S113, "Standard Specification for Wood Core Doors Meeting the Performance Required by CAN/ULC-S104 for Twenty…). Doors in fire separations latch and self-close; garage-to-dwelling doors are weather-stripped, self-closing and never open into a bedroom (9.10.13.15.OBC Div. B 9.10.13.15. Doors Between Garages and Dwelling Units(1) A door between an attached or built-in garage and a dwelling unit shall be tight-fitting and weather-stripped to provide an effective barrier against the passage of gases and exhaust fumes and shall be fitted with a self-closing device. (2) A doorway between an attached or built-in garage and a dwelling unit shall…).

Practice this topic

Part 9 alarm systems, smoke alarms and firefighting

A fire alarm is required in a Part 9 building with more than 3 storeys counting basements, total occupant load over 300, or the Table 9.10.18.2.OBC Div. B Table 9.10.18.2. Maximum Occupant Load for Buildings Without Fire Alarm Systems — Forming Part of Sentence 9.10.18.2.(2)Table 9.10.18.2 — Maximum Occupant Load for Buildings Without Fire Alarm Systems — Forming Part of Sentence 9.10.18.2.(2) Forming Part of Sentence 9.10.18.2.(2) Major Occupancy Classification | Occupant Load Residential | 10 (sleeping accommodation) Business and personal services, mercantile | 150 above or below the… limits: residential sleeping for more than 10, business or mercantile 150 above or below the first storey, F2 or F3 75 above or below (9.10.18.2.OBC Div. B 9.10.18.2. Fire Alarm System Required(1) Reserved. (2) Except as provided in Sentence (5), a fire alarm system shall be installed (a) in every building that contains more than 3 storeys, including storeys below the first storey, (b) where the total occupant load exceeds 300, or (c) when the occupant load for any major occupancy in Table 9.10.18.2. is…). Residential buildings where an exit or corridor serves not more than 4 suites are exempt. Hotels use a single-stage system (9.10.18.9.OBC Div. B 9.10.18.9. Fire Alarm System in a Hotel(1) If a fire alarm system is required in a building containing a hotel, a single stage fire alarm system shall be provided.).

Smoke alarms (9.10.19.OBC Div. B 9.10.19.3. Location of Smoke Alarms(1) Except as permitted in Article 9.10.19.8., within dwelling units, sufficient smoke alarms shall be installed so that (a) there is at least one smoke alarm installed on each storey, including basements, and (b) on any storey of a dwelling unit containing sleeping rooms, a smoke alarm is installed (i) in each…): in every dwelling unit and sleeping room outside one; on every storey including basements; in each bedroom and the hallway; interconnected; hard-wired with 7 days of battery back-up then 4 minutes of alarm; visual component of 175 cd in bedrooms; 10 minute hush. Seasonal cottages also need them (9.37.2.4.OBC Div. B 9.37.2.4. Smoke Alarms(1) Every dwelling unit within the scope of this Section shall be provided with a smoke alarm in accordance with Subsection 9.10.19.).

Firefighting: access windows 1,100 mm by 550 mm on unsprinklered second and third storeys in a wall facing a street; direct access to unsprinklered basements over 25 m; fire department access by street, roadway or yard (9.10.20.OBC Div. B 9.10.20.1. Windows or Access Panels Required(1) Except as provided in Sentence (3), a window or access panel providing an opening not less than 1,100 mm high and 550 mm wide and having a sill height of not more than 900 mm above the floor shall be provided on the second and third storeys of every building in at least one wall facing on a street if such storeys…).

Practice this topic

Heating systems, wiring, emergency lighting and CO alarms

Only crawl spaces under 1-storey portions of dwelling units may be warm air plenums, lined with materials of flame spread 150 or less (9.18.7.1.OBC Div. B 9.18.7.1. Crawl Spaces as Warm Air Plenums(1) Only crawl spaces under 1-storey portions of dwelling units shall be used as warm air plenums. (2) Enclosing material in crawl spaces described in Sentence (1), including insulation, shall have a surface flame-spread rating not greater than 150. (3) Combustible ground cover used as enclosing material in Sentence…). Ducts are noncombustible, or Class 1 combustible ducts not in vertical runs over 2 storeys and not above 120°C (9.33.6.2.OBC Div. B 9.33.6.2. Materials in Air Duct Systems(1) Except as provided in Sentences (2) to (6.2) and in Article 3.6.4.3., all ducts, duct connectors, associated fittings and plenums used in air duct systems shall be constructed of steel, aluminum alloy, copper, clay or similar noncombustible material. (2) Ducts, associated fittings and plenums are permitted to…); return air from one dwelling unit is not recirculated to another (9.33.6.13.OBC Div. B 9.33.6.13. Return-Air System(1) The return-air system shall be designed to handle the entire air supply. (1.1) Except as provided in Sentences (2) and (3), return ducts shall be constructed of material having a surface flame-spread rating of not more than 150. (2) Where any part of a return duct will be exposed to radiation from the furnace heat…). Cables in combustible buildings meet FT1 or are enclosed, and plenum cables follow 3.6.4.3. (9.34.1.5.OBC Div. B 9.34.1.5. Wiring and Cables(1) Except for dwelling units and except as required in Sentence (2), optical fibre cables and electrical wires and cables installed in buildings permitted to be of combustible construction shall (a) not convey flame or continue to burn for more than 1 min when tested in conformance with the Vertical Flame Test in…). CO alarms follow 9.32.3.9. and the same placement logic as Part 6 (9.32.3.9.OBC Div. B 9.32.3.9. Application of Carbon Monoxide Alarms(1) Article 9.32.3.9A. applies to every building that (a) contains a supply duct, and contains a fuel-burning appliance or a storage garage, or (b) contains a residential occupancy and is served by a forced-air fuel-burning appliance not contained within the building. (2) Articles 9.32.3.9B. and 9.32.3.9C. apply to…).

Common traps: Part 9 suite separations are 45 min, not Part 3's 1 h; the bedroom egress window (0.35 m², 380 mm) is not the firefighter access window (1,100 mm by 550 mm); the mercantile-residential separation jumps to 2 h at three dwelling units.

Practice this topic

Chapter review

Chapter at a glance

One line per section: the idea to carry into the exam. Then the answers that most often catch candidates out.

Practice this chapter

Questions on Part 9 egress and fire protection, in the exam format, every answer explained and cited to its article. Sign in to start; a free account gets the free questions.

Code cited in this chapter

Based on the official 2024 Building Code Compendium on ontario.ca.

© King's Printer for Ontario, 2024. Reproduced with permission.

  • OBC Div. B 9.1.1.1. Application

    (1)The application of this Part shall be as described in Subsection 1.3.3. of Division A.

    Open OBC Div. B 9.1.1.1. in the code viewer
  • OBC Div. B 9.1.1.3. Self-Service Storage Buildings

    (1)Self-service storage buildings shall conform to the requirements in Section 3.10.

    Open OBC Div. B 9.1.1.3. in the code viewer
  • OBC Div. B 9.1.1.4. Tents and Air-Supported Structures

    (1)Tents shall conform to the requirements in Subsection 3.14.1.

    (2)Air-supported structures shall conform to the requirements in Subsection 3.14.2.

    Open OBC Div. B 9.1.1.4. in the code viewer
  • OBC Div. B 9.1.1.11. Shelf and Rack Storage Systems

    (1)Shelf and rack storage systems shall conform to the requirements of Section 3.16.

    Open OBC Div. B 9.1.1.11. in the code viewer
  • OBC Div. B 9.1.1.9. Site Assembled and Factory-Built Buildings

    (1)Except as provided in Sentence (2) and in Sentence 12.2.1.2.(2), a manufactured building is deemed to comply with this Code if it is designed and constructed in compliance with,

    (a)CSA Z240.2.1, "Structural requirements for manufactured homes," if the building is constructed in sections not wider than 4.88 m, or

    (b)CSA A277, "Procedure for certification of prefabricated buildings, modules, and panels."

    (2)The requirements of this Code shall apply to,

    (a)building components designed and constructed outside the place of manufacture, and

    (b)site installation of such buildings.

    Open OBC Div. B 9.1.1.9. in the code viewer
  • OBC Div. B 9.7.2.2. Other Requirements for Windows, Doors and Skylights

    (1)Minimum sizes of doorways and doors within a barrier-free path of travel shall conform to Section 9.5.

    (2)The protection of window and door openings to protect persons from falling through them shall conform to Article 9.8.8.1.

    (3)Properties of windows and doors within exits shall conform to Section 9.9.

    (4)Windows and doors installed to provide the required means of egress from bedrooms shall conform to Subsection 9.9.10.

    (5)The location and protection of windows, doors and skylights in order to control the spread of fire shall conform to Subsection 9.10.12.

    (6)Doors between dwelling units and attached garages shall conform to Article 9.10.13.15.

    (7)The surface flame-spread rating for doors and skylights shall conform to Article 9.10.17.1.

    (8)Windows and doors installed to provide the required access to a building for firefighting purposes shall conform to Subsection 9.10.20.

    (9)Windows and skylights installed to provide required non-heating season ventilation shall conform to Article 9.32.2.2.

    Open OBC Div. B 9.7.2.2. in the code viewer
  • OBC Div. B 9.9.2.1. Types of Exits

    (1)Except as otherwise provided in this Section, an exit from any floor area shall be one of the following used singly or in combination:

    (a)an exterior doorway,

    (b)an exterior passageway,

    (c)an exterior ramp,

    (d)an exterior stairway,

    (e)a fire escape,

    (f)a horizontal exit,

    (g)an interior passageway,

    (h)an interior ramp, or

    (i)an interior stairway.

    (2)Fire escapes shall only be used as exits on existing buildings and shall be designed and installed in conformance with Subsection 3.4.7.

    (2.1)Fire escapes shall not be installed on any new building.

    (3)Where a horizontal exit is used, it shall conform to Sentence 3.4.1.6.(1) and Article 3.4.6.10.

    Open OBC Div. B 9.9.2.1. in the code viewer
  • OBC Div. B 9.9.2.3. Elevators, Slide Escapes and Windows as Means of Egress

    (1)Elevators, slide escapes or windows shall not be considered as part of a required means of egress.

    (2)Except for floor areas of mercantile occupancy, casement windows not less than 1,060 mm high, 560 mm wide, with a sill height not more than 900 mm above the inside floor, are permitted to be considered part of a required means of egress to provide access to fire escapes, when fire escapes are permitted.

    Open OBC Div. B 9.9.2.3. in the code viewer
Show all 52 articles
  • OBC Div. B 9.9.4.2. Fire Separation for Exits

    (1)Except as provided in Sentence (5) and Article 9.9.8.5., every exit other than an exit doorway shall be separated from each adjacent floor area or from another exit by a fire separation having a fire-resistance rating not less than that required for the floor assembly above the floor area.

    (2)Where there is no floor assembly above, the fire-resistance rating required in Sentence (1) shall not be less than that required by Subsection 9.10.8. for the floor assembly below, but in no case shall the fire-resistance rating be less than 45 min.

    (3)A fire separation common to 2 exits shall be smoke-tight and not be pierced by doorways, duct work, piping or any other opening that may affect the continuity of the separation.

    (4)A fire separation that separates an exit from the remainder of the building shall have no openings except those for electrical wiring, noncombustible conduit and noncombustible piping that serve only the exit, and for standpipes, sprinkler piping, exit doorways and wired glass and glass block permitted in Article 9.9.4.3.

    (5)The requirements in Sentence (1) do not apply to an exterior exit passageway provided the passageway has at least 50% of its exterior sides open to the outdoors and is served by an exit stair at each end of the passageway.

    Open OBC Div. B 9.9.4.2. in the code viewer
  • OBC Div. B 9.9.4.3. Wired Glass or Glass Block)

    (1)This Article applies to wired glass in doors, and wired glass or glass block in sidelights, where these are installed in fire separations between exit enclosures and floor areas.

    (2)Except as provided in Sentence (3), the combined area of glazing in doors and sidelights shall not exceed 0.8 m².

    (3)Where an exit enclosure connects with a floor area through an enclosed vestibule or corridor separated from the floor area by fire separations having not less than a 45 min fire-resistance rating, the glazed areas described in Sentence (1) need not be limited as required in Sentence (2).

    Open OBC Div. B 9.9.4.3. in the code viewer
  • OBC Div. B 9.9.4.4. Openings Near Unenclosed Exterior Exit Stairs and Ramps

    (1)Where an unenclosed exterior exit stair or ramp provides the only means of egress from a suite, and is exposed to fire from openings in the exterior walls of another fire compartment, or another dwelling unit, ancillary space or common space in a house with a secondary suite, the openings in the exterior walls of the building shall be protected with wired glass in fixed steel frames or glass block conforming to Articles 9.10.13.5. and 9.10.13.7. when the openings in the exterior walls of the building are within 3 m horizontally and less than 10 m below or less than 5 m above the exit stair or ramp.

    Open OBC Div. B 9.9.4.4. in the code viewer
  • OBC Div. B 9.9.4.6. Openings Near Exit Doors

    (1)This Article applies to

    (a)exit doors serving other than an individual dwelling unit, and

    (b)exit doors serving an individual dwelling unit where there is no second and separate exit from the dwelling unit.

    (2)Where an exterior exit door described in Sentence (1) in one fire compartment is within 3 m horizontally of an unprotected opening in another fire compartment and the exterior walls of these fire compartments intersect at an exterior angle of less than 135°, the opening shall be protected with wired glass in fixed steel frames or glass block conforming to Articles 9.10.13.5. and 9.10.13.7. or with a rated closure conforming to Table 9.10.13.1. with respect to the rating of the fire separation between the two compartments.

    Open OBC Div. B 9.9.4.6. in the code viewer
  • OBC Div. B 9.9.5.3. Obstructions in Public Corridors

    (1)Except as permitted in Sentence (2), obstructions located within 1,980 mm of the floor shall not project horizontally more than 100 mm into exit passageways, corridors used by the public or public corridors in a manner that would create a hazard for visually impaired persons travelling adjacent to walls.

    (2)The horizontal projection of an obstruction referred to in Sentence (1) is permitted to exceed 100 mm where the obstruction extends to less than 680 mm above the floor. (See Note A-3.3.1.8.(2) and (3))

    Open OBC Div. B 9.9.5.3. in the code viewer
  • OBC Div. B 9.9.6.7. Door Latching, Locking and Opening Mechanisms

    (1)Principal entrance doors, exit doors and doors to suites, including exterior doors of dwelling units, and other doors in an access to exit shall

    (a)be openable from the inside or in travelling to an exit without requiring keys, special devices or specialized knowledge of the door-opening mechanism, or

    (b)be controlled by electromagnetic locking mechanisms in accordance with Sentence 3.4.6.16.(5).

    (2)Except for doors serving a single dwelling unit or a house with a secondary suite, and doors to accessory buildings and to garages serving a single dwelling unit, door release hardware on doors in a means of egress shall be operable with one hand and the door shall be openable with not more than one releasing operation. (See also Sentence 3.8.3.6.(4) and Note A-3.3.1.13.(4))

    (3)Door release hardware on doors in a means of egress shall be installed 900 mm to 1,100 mm above the finished floor.

    (4)Except for hotels, a door opening onto a public corridor that provides access to exit from suites shall be designed not to lock automatically when such doors are equipped with an automatic self-closing device. (See Note A-3.3.4.5.(1))

    Open OBC Div. B 9.9.6.7. in the code viewer
  • OBC Div. B 9.9.6.8. Effort Required to Open

    (1)Except as required by Sentence 3.8.3.3.(7), every exit door, except doors serving a single dwelling unit or a house with a secondary suite, shall be designed and installed so that when the latch is released the door will open in the direction of exit travel under a force of not more than 90 N applied to the door release hardware. (See Sentence 3.8.3.6.(8) for door opening forces in a barrier-free path of travel.)

    Open OBC Div. B 9.9.6.8. in the code viewer
  • OBC Div. B 9.9.7.4. Number and Spacing of Egress Doors

    (1)Except for dwelling units, at least two egress doors shall be provided where

    (a)the area of a room or suite exceeds 200 m² in a Group D, E, F2 and F3 occupancy, or 150 m² in a Group C occupancy, or

    (b)the distance measured from any point within a room or suite to the nearest egress door exceeds 25 m.

    (2)Doors required in Sentence (1) shall be spaced so that in the event one door is made inaccessible by a fire within such a room or suite, the other door will provide safe egress.

    Open OBC Div. B 9.9.7.4. in the code viewer
  • OBC Div. B 9.9.8.2. Number of Required Exits

    (1)Except as provided in Sentences (2) and (3) and Subsection 9.9.9., at least 2 exits shall be provided from every floor area, spaced so that the travel distance to the nearest exit is not more than

    (a)40 m in the case of business and personal services occupancies,

    (b)45 m for all occupancies where the floor area is sprinklered, and

    (c)30 m for all other occupancies.

    (2)Except as provided in Subsection 9.9.9., a single exit is permitted from each storey in buildings of 1 and 2 storeys in building height provided the floor area and travel distance requirements conform to those required in Article 9.9.7.4. and the total occupant load served by an exit facility does not exceed 60 persons.

    (3)In boarding, lodging or rooming houses,

    (a)where sleeping accommodation is provided for not more than eight persons, a single exit is permitted from each floor area, or

    (b)where sleeping accommodation is not provided in the basement, a single exit is permitted from the basement floor area.

    Open OBC Div. B 9.9.8.2. in the code viewer
  • OBC Div. B 9.9.7.1. Egress from Roof Area, Podiums, Terraces, Platforms and Contained Open Spaces

    (1)An access to exit shall be provided from every roof intended for occupancy and from every podium, terrace, platform or contained open space.

    (2)Where a roof is intended for an occupant load of more than 60 persons, at least 2 separate means of egress shall be provided from the roof to stairs designed in conformance with the requirements for exit stairs and located remote from each other.

    (3)Where a podium, terrace, platform or contained open space is provided, egress requirements shall conform to the appropriate requirements for rooms or suites in Article 9.9.7.4.

    Open OBC Div. B 9.9.7.1. in the code viewer
  • OBC Div. B 9.9.8.5. Exiting Through a Lobby

    (1)Not more than one exit from a floor area is permitted to lead through a lobby.

    (2)The lobby referred to in Sentence (1) shall be not more than 4.5 m above grade, and the path of travel through the lobby to the outdoors shall not exceed 15 m.

    (3)The lobby referred to in Sentence (1) shall conform in all respects to the requirements for exits, except that rooms other than service rooms, storage rooms and rooms of residential or industrial occupancy are permitted to open directly onto such lobby.

    (3.1)Except as provided in Sentence (6), an exit is permitted to lead through a lobby referred to in Sentence (1) provided the lobby is not located within an interconnected floor space other than as described in Sentence 3.2.8.2.(6).

    (4)Where the lobby referred to in Sentence (1) and adjacent occupancies that are permitted to open into the lobby are sprinklered, the fire separation between such occupancies and the lobby need not have a fire-resistance rating. (See Note A-3.4.4.2.(2) (e))

    (5)Passenger elevators are permitted to open onto the lobby referred to in Sentence (1) provided the elevator doors are designed to remain closed except while loading and unloading passengers.

    (6)An exit that serves a hotel is permitted to lead through a lobby referred to in Sentence (1) provided the lobby is not located within an interconnected floor space.

    Open OBC Div. B 9.9.8.5. in the code viewer
  • OBC Div. B 9.9.7.2. Means of Egress from Suites

    (1)Except as required in Sentence 9.9.9.3.(1), each suite in a floor area occupied by more than one suite shall have

    (a)an exterior exit doorway,

    (b)a doorway to a public corridor, or

    (c)a doorway to an exterior passageway.

    (2)Except as provided in Sentences 9.9.7.3.(1) and 9.9.8.2.(2), from the point where a doorway described in Clause(1)(b) or (c) enters the public corridor or exterior passageway, it shall be possible to go in opposite directions to each of 2 separate exits.

    Open OBC Div. B 9.9.7.2. in the code viewer
  • OBC Div. B 9.9.9.2. Two Separate Exits

    (1)Except as provided in Sentence 9.9.7.3.(1) and except for dwelling units in a house with a secondary suite, where an egress door from a dwelling unit opens onto a public corridor or exterior passageway it shall be possible from the location where the egress door opens onto the corridor or exterior passageway to go in opposite directions to 2 separate exits unless the dwelling unit has a second and separate means of egress.

    Open OBC Div. B 9.9.9.2. in the code viewer
  • OBC Div. B 9.9.9.1. Travel Limit to Exits or Egress Doors

    (1)Except as provided in Sentences (2) and (3), every dwelling unit containing more than 1 storey shall have exits or egress doors located so that it shall not be necessary to travel up or down more than 1 storey to reach a level served by

    (a)an egress door to a public corridor, enclosed exit stair or exterior passageway, or

    (b)an exit doorway not more than 1.5 m above adjacent ground level.

    (2)Where a dwelling unit is not located above or below another suite, the travel limit from a floor level in the dwelling unit to an exit or egress door may exceed 1 storey where that floor level is served by an openable window or door

    (a)providing an unobstructed opening of not less than 1 m in height and 0.55 m in width, and

    (b)located so that the sill is not more than

    (i)1 m above the floor, and

    (ii)7 m above adjacent ground level.

    (3)The travel limit from a floor level in a dwelling unit to an exit or egress door may exceed 1 storey where that floor level has direct access to a balcony.

    Open OBC Div. B 9.9.9.1. in the code viewer
  • OBC Div. B 9.9.10.1. Egress Windows or Doors for Bedrooms

    (1)Except where a door on the same floor level as the bedroom provides direct access to the exterior, every floor level containing a bedroom in a suite shall be provided with at least one outside window that

    (a)is openable from the inside without the use of tools,

    (b)provides an individual, unobstructed open portion having a minimum area of 0.35 m² with no dimension less than 380 mm, and

    (c)maintains the required opening described in Clause (b) without the need for additional support. (See Note A-9.9.10.1.(1))

    (2)Except for basement areas, the window required in Sentence (1) shall have a maximum sill height of 1,000 mm above the floor. (See Note A-9.9.10.1.(2))

    (3)Where a window required in Sentence (1) opens into a window well, a clearance of not less than 550 mm shall be provided in front of the window. (See Note A-9.9.10.1.(3))

    (4)Where the sash of a window referred to in Sentence (3) swings towards the window well, the operation of the sash shall not reduce the clearance in a manner that would restrict escape in an emergency.

    (5)Where a protective enclosure is installed over the window well referred to in Sentence (3), the enclosure shall be openable from the inside without the use of keys, tools or special knowledge of the opening mechanism.

    (6)When sliding windows are used, the minimum dimension described in Sentence (1) shall apply to the openable portion of the window.

    (7)Where the sleeping area within a live/work unit is on a mezzanine with no obstructions more than 1,070 mm above the floor, the window required in Sentence (1) may be provided on the main level of the live/work unit provided the mezzanine is not more than 25% of the area of the live/work unit or 20 m², whichever is less, and an unobstructed direct path of travel is provided from the mezzanine to this window.

    Open OBC Div. B 9.9.10.1. in the code viewer
  • OBC Div. B 9.9.11.3. Exit Signs

    (1)Except as required in Sentence (7), every exit door shall have an exit sign placed over it or adjacent to it if the exit serves

    (a)a building that is 3 storeys in building height,

    (b)a building having an occupant load of more than 150, or

    (c)a room or floor area that has a fire escape as part of a required means of egress.

    (2)Except as required in Sentence (6), every exit sign shall

    (a)be visible on approach to the exit,

    (b)consist of a green pictogram and a white or lightly tinted graphical symbol meeting the colour specifications referred to in ISO 3864-1, "Graphical symbols – Safety colours and safety signs – Part 1: Design principles for safety signs and safety markings," and

    (c)conform to ISO 7010, "Graphical symbols – Safety colours and safety signs – Registered safety signs," for the following symbols: (See Note A-3.4.5.1.(2) (c))

    (i)E001 emergency exit left,

    (ii)E002 emergency exit right,

    (iii)E005 90-degree directional arrow, and

    (iv)E006 45-degree directional arrow.

    (3)Internally illuminated exit signs shall be continuously illuminated, and

    (a)where illumination of the sign is powered by an electrical circuit, be constructed in conformance with CSA C22.2 No. 141, "Emergency lighting equipment," or

    (b)where illumination of the sign is not powered by an electrical circuit, be

    (i)constructed in conformance with CAN/ULC-S572, "Standard for Photoluminescent and Self-Luminous Exit Signs and Path Marking Systems," and

    (ii)labelled in accordance with the time duration for which they have been tested and listed.

    (4)Externally illuminated exit signs shall be continuously illuminated at all times by a light fixture supplied by an electrical circuit.

    (5)The circuitry serving lighting for externally and internally illuminated exit signs shall

    (a)serve no equipment other than emergency lighting in the area where the exit signs are installed, and

    (b)be connected to an emergency power supply as described in Sentences 9.9.12.3.(2), (3) and (7).

    (6)An exit sign conforming to Clauses (2)(b) and (c) with an arrow or other indicator pointing at the direction of egress shall be provided where no exit is visible from

    (a)a public corridor,

    (b)a corridor used by the public, or

    (c)a principal route serving an open floor area having an occupant load of more than 150.

    (7)Except for suite doors opening directly to the exterior, every exit serving a hotel shall have an exit sign placed over it or adjacent to it.

    Open OBC Div. B 9.9.11.3. in the code viewer
  • OBC Div. B 9.9.12.2. Required Lighting in Egress Facilities

    (1)Every exit, public corridor or corridor providing access to exit for the public shall be equipped to provide illumination to an average level of not less than 50 lx at floor or tread level and at all points such as angles and intersections at changes of level where there are stairs or ramps.

    (2)The minimum value of the illumination required by Sentence (1) shall be not less than 10 lx.

    Open OBC Div. B 9.9.12.2. in the code viewer
  • OBC Div. B 9.9.12.3. Emergency Lighting

    (1)Emergency lighting shall be provided in

    (a)exits.

    (b)principal routes providing access to exit in an open floor area,

    (c)corridors used by the public,

    (d)underground walkways, and

    (e)public corridors.

    (2)Emergency lighting required in Sentence (1) shall be provided from a source of energy separate from the electrical supply for the building.

    (3)Lighting required in Sentence (1) shall be designed to be automatically actuated for a period of at least 30 min when the electric lighting in the affected area is interrupted.

    (4)Illumination from lighting required in Sentence (1) shall be provided to average levels of not less than 10 lx at floor or tread level.

    (5)The minimum value of the illumination required by Sentence (4) shall be not less than 1 1x.

    (6)Where incandescent lighting is provided, lighting equal to 1 W/m² of floor area shall be considered to meet the requirement in Sentence (4).

    (7)Where self-contained emergency lighting units are used, they shall conform to CSA C22.2 No. 141, "Emergency lighting equipment."

    Open OBC Div. B 9.9.12.3. in the code viewer
  • OBC Div. B 9.34.3.1. Criteria for Emergency Lighting

    (1)Emergency lighting shall conform to Subsection 9.9.12.

    Open OBC Div. B 9.34.3.1. in the code viewer
  • OBC Div. B 9.10.9.15. Separation of Suites

    (1)Except as required in Article 9.10.9.16. and as permitted by Sentence (2), each suite in other than business and personal services occupancies shall be separated from adjoining suites by a fire separation having a fire-resistance rating of not less than 45 min.

    (2)In sprinklered buildings, suites of business and personal services occupancy and mercantile occupancy that are served by public corridors conforming with Clause 3.3.1.4.(4)(b) are not required to be separated from each other by fire separations.

    Open OBC Div. B 9.10.9.15. in the code viewer
  • OBC Div. B 9.10.9.16. Separation of Residential Suites

    (1)Except as provided in Sentences (2) and (3) and Article 9.10.21.2., suites in residential occupancies shall be separated from adjacent rooms and suites by a fire separation having a fire-resistance rating of not less than 45 min.

    (2)Sleeping rooms in boarding, lodging or rooming houses where sleeping accommodation is provided for not more than 8 boarders or lodgers need not be separated from the remainder of the floor area as required in Sentence (1) where the sleeping rooms form part of the proprietor's residence and do not contain cooking facilities.

    (3)Except as provided in Sentences (4) and (5), dwelling units that contain 2 or more storeys including basements shall be separated from the remainder of the building by a fire separation having a fire-resistance rating of not less than 1 h. (See Note A-3.3.4.4.(1))

    (4)Walls and floor-ceiling framing in a house with a secondary suite that separate dwelling units from each other or dwelling units from ancillary spaces and common spaces need not comply with Sentence (1), where the walls and floor-ceiling framing are protected by a continuous smoke-tight barrier of not less than 15.9 mm thick Type X gypsum board installed on

    (a)both sides of walls, and

    (b)the underside of floor-ceiling framing.

    (5)The fire-resistance rating of the fire separation required in Sentence (4) is permitted to be waived where the house with a secondary suite is sprinklered.

    Open OBC Div. B 9.10.9.16. in the code viewer
  • OBC Div. B 9.10.9.13. Separation of Residential Occupancies

    (1)Except as provided in Sentences (2) and (4), residential occupancies shall be separated from all other major occupancies by a fire separation having a fire-resistance rating of not less than 1 h.

    (2)Except as provided in Sentence (3), a major occupancy classified as a residential occupancy, including live/work units, shall be separated from other major occupancies classified as mercantile or medium hazard industrial occupancies by a fire separation having a fire-resistance rating of not less than 2 h.

    (3)Where not more than two dwelling units or live/work units are located in a building containing a mercantile occupancy, such mercantile occupancy shall be separated from the dwelling units or live/work units by a fire separation having not less than 1 h fire-resistance rating.

    (4)The requirement for fire separations between major occupancies in Sentence (1) is waived for the occupancies allowed within live/work units.

    Open OBC Div. B 9.10.9.13. in the code viewer
  • OBC Div. B 9.10.9.17. Separation of Public Corridors

    (1)Except as otherwise required by this Part and as provided in Sentences (2) to (5), public corridors shall be separated from the remainder of the building by a fire separation having not less than a 45 min fire-resistance rating.

    (2)In other than residential occupancies, no fire-resistance rating is required for fire separations between a public corridor and the remainder of the building if

    (a)the floor area is sprinklered,

    (b)the sprinkler system is electrically supervised in conformance with Sentence 3.2.4.9.(3), and

    (c)the operation of the sprinkler system will cause a signal to be transmitted to the fire department in conformance with Sentence 3.2.4.7.(4).

    (3)In other than residential occupancies, no fire separation is required between a public corridor and the remainder of the building if

    (a)the floor area is sprinklered,

    (b)the sprinkler system is electrically supervised in conformance with Sentence 3.2.4.9.(3),

    (c)the operation of the sprinkler system will cause a signal to be transmitted to the fire department in conformance with Sentence 3.2.4.7.(4), and

    (d)the corridor exceeds 5 m in width.

    (4)Where a public corridor is located in a house with a secondary suite, a continuous smoke-tight barrier of not less than 15.9 mm thick Type X gypsum board shall be installed on

    (a)both sides of walls separating the corridor from the remainder of the building, and

    (b)the underside of floor-ceiling framing separating the corridor from the remainder of the building.

    (5)No fire separation is required in a sprinklered floor area between a public corridor and a space containing plumbing fixtures required by Article 3.7.4.2. and Section 9.31., provided

    (a)the space and the public corridor are separated from the remainder of the storey by a fire separation having a fire-resistance rating not less than that required between the public corridor and the remainder of the storey, and

    (b)the plumbing fixtures are not located within a dwelling unit or suite.

    Open OBC Div. B 9.10.9.17. in the code viewer
  • OBC Div. B 9.10.9.18. Separation of Storage Garages

    (1)Except as provided in Sentences (2) and (3), a storage garage shall be separated from other occupancies by a fire separation having not less than a 1.5 h fire-resistance rating.

    (2)Except as permitted in Sentence (3), storage garages containing 5 motor vehicles or fewer shall be separated from other occupancies by a fire separation of not less than 1 h.

    (3)Where a storage garage serves only the dwelling unit to which it is attached or in which it is built, it shall be considered as part of that dwelling unit and the fire separation required in Sentence (2) need not be provided between the garage and the dwelling unit.

    (4)Except as provided in Sentence (5), where a storage garage is attached to or built into a building of residential occupancy

    (a)an air barrier system conforming to Subsection 9.25.3. shall be installed between the garage and the remainder of the building to provide an effective barrier to gas and exhaust fumes, and

    (b)every door between the garage and the remainder of the building shall conform to Article 9.10.13.15. (See Note A-9.10.9.18.(4))

    (5)Where membrane materials are used to provide the required airtightness in the air barrier system, all joints shall be sealed and structurally supported.

    Open OBC Div. B 9.10.9.18. in the code viewer
  • OBC Div. B 9.10.9.19. Separation of Repair Garages

    (1)Except as provided in Sentences (2) and (3), a repair garage shall be separated from other occupancies by a fire separation having a fire-resistance rating of not less than 2 h.

    (2)Ancillary spaces directly serving a repair garage, including waiting rooms, reception rooms, tool and parts storage areas and supervisory office space, need not be separated from the repair garage but shall be separated from other occupancies as required in Sentence (1).

    (3)The fire separation referred to in Sentence (1) shall have a fire-resistance rating of not less than 1 h, where

    (a)the building is not more than one storey in building height,

    (b)the building is operated as a single suite, and

    (c)the only occupancy other than the repair garage is a mercantile occupancy.

    (4)Except as provided in Sentence (5), where a building containing a repair garage also contains a dwelling unit, an air barrier system conforming to Subsection 9.25.3. shall be installed between the dwelling unit and the suite containing the garage to provide an effective barrier to gas and exhaust fumes. (See Note A-9.10.9.18.(4))

    (5)Where membrane materials are used to provide the required airtightness in the air barrier system, all joints shall be sealed and structurally supported.

    Open OBC Div. B 9.10.9.19. in the code viewer
  • OBC Div. B 9.10.10.3. Separation of Service Rooms

    (1)Except as provided in Sentence (2) and Articles 9.10.10.5. and 9.10.10.6., service rooms shall be separated from the remainder of the building by a fire separation having a fire-resistance rating of not less than 1 h when the floor area containing the service room is not sprinklered.

    (2)Where a room contains a limited quantity of service equipment and the service equipment does not constitute a fire hazard, the requirements in Sentence (1) shall not apply.

    Open OBC Div. B 9.10.10.3. in the code viewer
  • OBC Div. B 9.10.10.4. Locations of Fuel-Fired Appliances

    (1)Except as provided in Sentences (2) and (3) and Article 9.10.10.5., fuel-fired appliances shall be located in a service room separated from the remainder of the building by a fire separation having not less than a 1 h fire-resistance rating.

    (2)Except as required in the appliance installation standards referenced in Sentences 6.2.1.5.(1) and 9.10.10.5.(1), fuel-fired space-heating appliances, space-cooling appliances and service water heaters need not be separated from the remainder of the building as required in Sentence (1),

    (a)where the appliances serve

    (i)not more than one room or suite, or

    (ii)a building with a building area of not more than 400 m² and a building height of not more than 2 storeys, or

    (b)where the appliances

    (i)serve a house with a secondary suite including their common spaces, and

    (ii)are located in a service room where both sides of any wall assemblies and the underside of any floor-ceiling framing separating this room from both dwelling units or their common spaces are protected by a continuous smoke-tight barrier consisting of not less than 15.9 mm thick Type X gypsum board.

    (3)Sentence (1) does not apply to fireplaces and cooking appliances.

    Open OBC Div. B 9.10.10.4. in the code viewer
  • OBC Div. B 9.10.10.5. Incinerators

    (1)Service rooms containing incinerators shall be separated from the remainder of the building by a fire separation having a fire-resistance rating of not less than 2 h.

    (2)The design, construction, installation and alteration of each indoor incinerator shall conform to NFPA 82, "Standard on Incinerators and Waste and Linen Handling Systems and Equipment."

    (3)Every incinerator shall be connected to a chimney flue conforming to the requirements in Section 9.21. and serving no other appliance.

    (4)An incinerator shall not be located in a room with other fuel-fired appliances.

    Open OBC Div. B 9.10.10.5. in the code viewer
  • OBC Div. B 9.10.10.7. Emergency Power Installation

    (1)Where a generator intended to supply emergency power for lighting, fire safety and life safety systems is located in a building, it shall be located in a room that,

    (a)is separated from the remainder of the building by a fire separation with a fire-resistance rating not less than

    (i)1 h, if the floor assembly is not required to have a fire-resistance rating of more than 1 h, and

    (ii)2 h, if the floor assembly is required to have a fire-resistance rating of more than 1 h, and

    (b)contains only the generating set and equipment that is related to the emergency power supply system.

    Open OBC Div. B 9.10.10.7. in the code viewer
  • OBC Div. B 9.10.9.6. General Requirements for Penetrations of Fire Separations

    (1)Except as required by Sentence (2) and Articles 9.10.9.7. and 9.10.9.8. and as permitted by Article 9.10.9.9., penetrations of a required fire separation or a membrane forming part of an assembly required to be a fire separation shall be

    (a)sealed by a firestop that, when subjected to the fire test method in CAN/ULC-S115, "Standard Method of Fire Tests of Firestop Systems," has an F rating not less than the required fire-resistance rating for the fire separation,

    (b)tightly fitted or cast in place, provided the penetrating item is made of steel, ferrous, copper, concrete or masonry, or

    (c)sealed to maintain the integrity of the fire separation. (See Note A-9.10.9.6.(1))

    (2)Penetrations of a firewall shall be sealed at the penetration by a firestop that, when subjected to the fire test method in "CAN/ULC-S115, "Standard Method of Fire Tests of Firestop Systems," has an FT rating not less than the fire-resistance rating for the fire separation.

    Open OBC Div. B 9.10.9.6. in the code viewer
  • OBC Div. B Table 9.10.13.1. Fire-Protection Ratings for Closures — Forming Part of Sentence 9.10.13.1.(1)

    Table 9.10.13.1 — Fire-Protection Ratings for Closures — Forming Part of Sentence 9.10.13.1.(1) Forming Part of Sentence 9.10.13.1.(1) Required Fire-Resistance Rating of Fire Separation | Required Fire-Protection Rating of Closure 30 or 45 min | 20 min[1] 1 h | 45 min[1] 1.5 h | 1 h 2 h | 1.5 h 3 h | 2 h 4 h | 3 h Notes to Table 9.10.13.1.: (1) See Article 9.10.13.2.

    Open OBC Div. B Table 9.10.13.1. in the code viewer
  • OBC Div. B 9.10.13.2. Solid Core Wood Door as a Closure

    (1)A 45 mm thick solid core wood door is permitted to be used where a minimum fire-protection rating of 20 min is permitted or between a public corridor and a suite provided the door conforms to CAN/ULC-S113, "Standard Specification for Wood Core Doors Meeting the Performance Required by CAN/ULC-S104 for Twenty Minute Fire Rated Closure Assemblies." (See Note A-9.10.13.2.(1))

    (2)Doors described in Sentence (1) shall have not more than a 6 mm clearance beneath and not more than 3 mm at the sides and top.

    Open OBC Div. B 9.10.13.2. in the code viewer
  • OBC Div. B 9.10.13.15. Doors Between Garages and Dwelling Units

    (1)A door between an attached or built-in garage and a dwelling unit shall be tight-fitting and weather-stripped to provide an effective barrier against the passage of gases and exhaust fumes and shall be fitted with a self-closing device.

    (2)A doorway between an attached or built-in garage and a dwelling unit shall not be located in a room intended for sleeping.

    Open OBC Div. B 9.10.13.15. in the code viewer
  • OBC Div. B Table 9.10.18.2. Maximum Occupant Load for Buildings Without Fire Alarm Systems — Forming Part of Sentence 9.10.18.2.(2)

    Table 9.10.18.2 — Maximum Occupant Load for Buildings Without Fire Alarm Systems — Forming Part of Sentence 9.10.18.2.(2) Forming Part of Sentence 9.10.18.2.(2) Major Occupancy Classification | Occupant Load Residential | 10 (sleeping accommodation) Business and personal services, mercantile | 150 above or below the first storey Low-or medium-hazard industrial | 75 above or below the first storey

    Open OBC Div. B Table 9.10.18.2. in the code viewer
  • OBC Div. B 9.10.18.2. Fire Alarm System Required

    (1)Reserved.

    (2)Except as provided in Sentence (5), a fire alarm system shall be installed

    (a)in every building that contains more than 3 storeys, including storeys below the first storey,

    (b)where the total occupant load exceeds 300, or

    (c)when the occupant load for any major occupancy in Table 9.10.18.2. is exceeded.

    (3)Reserved.

    (4)Reserved.

    (5)A fire alarm system is not required in a residential occupancy where an exit or public corridor serves not more than 4 suites or where each suite has direct access to an exterior exit facility leading to ground level.

    Open OBC Div. B 9.10.18.2. in the code viewer
  • OBC Div. B 9.10.18.9. Fire Alarm System in a Hotel

    (1)If a fire alarm system is required in a building containing a hotel, a single stage fire alarm system shall be provided.

    Open OBC Div. B 9.10.18.9. in the code viewer
  • OBC Div. B 9.10.19.3. Location of Smoke Alarms

    (1)Except as permitted in Article 9.10.19.8., within dwelling units, sufficient smoke alarms shall be installed so that

    (a)there is at least one smoke alarm installed on each storey, including basements, and

    (b)on any storey of a dwelling unit containing sleeping rooms, a smoke alarm is installed

    (i)in each sleeping room, and

    (ii)in a location between the sleeping rooms and the remainder of the storey, and if the sleeping rooms are served by a hallway, the smoke alarm shall be located in the hallway. (See Note A-9.10.19.3.(1))

    (1.1)Except as permitted in Article 9.10.19.8., within a house with a secondary suite that contains an interior shared means of egress or common area, a smoke alarm shall be installed in each shared means of egress and common area.

    (2)A smoke alarm required in Sentences (1) and (1.1) shall be installed in conformance with CAN/ULC-S553, "Standard for Installation of Smoke Alarms."

    (3)Smoke alarms required in Article 9.10.19.1. and Sentences (1) and (1.1) shall be installed on or near the ceiling.

    (4)A smoke alarm required in Sentences (1) and (1.1) shall have a visual signalling component conforming to the requirements in 18.5.3. (Light, Color and Pulse Characteristics) of NFPA 72, "National Fire Alarm and Signaling Code."

    (5)The visual signalling component required in Sentence (4) need not

    (a)be integrated with the smoke alarm provided it is interconnected to it,

    (b)be on battery backup, or

    (c)have synchronized flash rates, when installed in a house with a secondary suite or an individual dwelling unit.

    (6)The luminous intensity for visual signalling components required in Sentence (4) that are installed in sleeping rooms shall be a minimum of 175 cd.

    Open OBC Div. B 9.10.19.3. in the code viewer
  • OBC Div. B 9.37.2.4. Smoke Alarms

    (1)Every dwelling unit within the scope of this Section shall be provided with a smoke alarm in accordance with Subsection 9.10.19.

    Open OBC Div. B 9.37.2.4. in the code viewer
  • OBC Div. B 9.10.20.1. Windows or Access Panels Required

    (1)Except as provided in Sentence (3), a window or access panel providing an opening not less than 1,100 mm high and 550 mm wide and having a sill height of not more than 900 mm above the floor shall be provided on the second and third storeys of every building in at least one wall facing on a street if such storeys are not sprinklered.

    (2)Access panels required in Sentence (1) shall be readily openable from both inside and outside or be glazed with plain glass.

    (3)Access panels required in Sentence (1) need not be provided in

    (a)buildings containing only dwelling units where there is no dwelling unit above another dwelling unit, or

    (b)houses with a secondary suite.

    Open OBC Div. B 9.10.20.1. in the code viewer
  • OBC Div. B 9.18.7.1. Crawl Spaces as Warm Air Plenums

    (1)Only crawl spaces under 1-storey portions of dwelling units shall be used as warm air plenums.

    (2)Enclosing material in crawl spaces described in Sentence (1), including insulation, shall have a surface flame-spread rating not greater than 150.

    (3)Combustible ground cover used as enclosing material in Sentence (2) shall be covered with noncombustible material. (See Note A-9.18.7.1.(3) and (4))

    (4)Noncombustible material described in Sentence (3) shall

    (a)extend not less than 300 mm beyond the projection of a register opening, and

    (b)have turned-up edges. (See Note A-9.18.7.1.(3) and (4))

    Open OBC Div. B 9.18.7.1. in the code viewer
  • OBC Div. B 9.33.6.2. Materials in Air Duct Systems

    (1)Except as provided in Sentences (2) to (6.2) and in Article 3.6.4.3., all ducts, duct connectors, associated fittings and plenums used in air duct systems shall be constructed of steel, aluminum alloy, copper, clay or similar noncombustible material.

    (2)Ducts, associated fittings and plenums are permitted to contain combustible material provided they

    (a)conform to the appropriate requirements for Class 1 duct materials in CAN/ULC-S110, "Standard Methods of Test for Air Ducts,"

    (b)conform to Article 3.1.5.18. and Subsection 3.1.9.,

    (c)are not used in vertical runs serving more than 2 storeys, and

    (d)are not used in air duct systems in which the air temperature may exceed 120°C.

    (3)Duct sealants shall have a flame-spread rating of not more than 25 and a smoke developed classification of not more than 50.

    (4)Duct connectors that contain combustible materials and that are used between ducts and air outlet units shall

    (a)conform to the appropriate requirements for Class 1 air duct materials in CAN/ULC-S110, "Standard Methods of Test for Air Ducts,"

    (b)be limited to 4 m in length,

    (c)be used only in horizontal runs, and

    (d)not penetrate required fire separations.

    (5)Combustibleducts that are part of a duct system carrying only ventilation air and that are contained entirely within a dwelling unit need not comply with the requirements of Sentences (1) to (4).

    (6)Except as provided in Sentences 9.33.6.13.(2) and (3), ducts that are part of a return-air duct system and that are contained entirely within a dwelling unit need not comply with the requirements of Sentences (1) to (4).

    (6.1)All ductwork and fittings shall be constructed and installed in conformance with SMACNA Manuals and ASHRAE Handbooks.

    (6.2)All duct materials and fittings shall be

    (a)suitable for exposure to the temperature and humidity of the air being conveyed, and

    (b)resistant to corrosion due to contaminants in the air being conveyed in the duct.

    (7)Materials referred to in Sentences (1) to (6.2), when used in a location where they may be subjected to excessive moisture, shall

    (a)have no appreciable loss of strength when wet, and

    (b)be corrosion-resistant.

    Open OBC Div. B 9.33.6.2. in the code viewer
  • OBC Div. B 9.33.6.13. Return-Air System

    (1)The return-air system shall be designed to handle the entire air supply.

    (1.1)Except as provided in Sentences (2) and (3), return ducts shall be constructed of material having a surface flame-spread rating of not more than 150.

    (2)Where any part of a return duct will be exposed to radiation from the furnace heat exchanger or other radiating part within the furnace, such part of a return duct directly above or within 600 mm of the outside furnace casing shall be noncombustible.

    (3)Return ducts serving solid-fuel-burning furnaces shall be constructed of noncombustible material.

    (4)Combustible return ducts shall be lined with noncombustible material

    (a)below floor registers,

    (b)at the bottom of vertical ducts, and

    (c)under furnaces having a bottom return.

    (5)Spaces between studs or joists used as return ducts shall be separated from the unused portions of such spaces by tight-fitting metal stops or wood blocking.

    (6)A vertical return duct shall have openings to return air on not more than one floor.

    (6.1)A public corridor shall comply with Sentences 6.3.2.7.(4) and (5).

    (7)The return-air system shall be designed so that the negative pressure from the circulating fan cannot

    (a)affect the furnace combustion air supply, nor

    (b)draw combustion products from joints or openings in the furnace or flue pipe.

    (7.1)Return-air from a dwelling unit shall not be recirculated to any other dwelling unit.

    Open OBC Div. B 9.33.6.13. in the code viewer
  • OBC Div. B 9.34.1.5. Wiring and Cables

    (1)Except for dwelling units and except as required in Sentence (2), optical fibre cables and electrical wires and cables installed in buildings permitted to be of combustible construction shall

    (a)not convey flame or continue to burn for more than 1 min when tested in conformance with the Vertical Flame Test in Clause 4.11.1. of CSA C22.2 No. 0.3, "Test Methods for Electrical Wires and Cables," (FT1 Rating), or

    (b)be located in

    (i)totally enclosed noncombustible raceways, (See Note A-3.1.4.3.(1) (b)(i))

    (ii)masonry walls,

    (iii)concrete slabs, or

    (iv)totally enclosed non metallic raceways conforming to Clause 3.1.5.23.(1)(b).

    (2)Where a concealed space in a floor or ceiling assembly is used as a plenum, electrical wires and cables within the plenum shall conform to Clause 3.6.4.3.(1)(a).

    Open OBC Div. B 9.34.1.5. in the code viewer
  • OBC Div. B 9.32.3.9. Application of Carbon Monoxide Alarms

    (1)Article 9.32.3.9A. applies to every building that

    (a)contains a supply duct, and contains a fuel-burning appliance or a storage garage, or

    (b)contains a residential occupancy and is served by a forced-air fuel-burning appliance not contained within the building.

    (2)Articles 9.32.3.9B. and 9.32.3.9C. apply to every building.

    Open OBC Div. B 9.32.3.9. in the code viewer