Last updated
Values this chapter turns on
- length of the stretcher an elevator car must fit
- 2,010 mm
- length of the stretcher an elevator car must fit
- lowest rating ever allowed for an elevator hoistway
- 45 min
- lowest rating ever allowed for an elevator hoistway
- fire separation around an emergency generator room
- 2 h
- fire separation around an emergency generator room
- max length of a combustible duct connector
- 4 m
- max length of a combustible duct connector
Sections 3.5. and 3.6. deal with the shafts, rooms and ducts that carry people and services through a building. The questions are mostly lookups: which rating a hoistway or shaft needs for a given floor rating, which rooms need a separation, and what a duct may be made of. For complex buildings, add the care occupancy stretcher elevator and the links back to the high building rules in 3.2.6.
Elevators and hoistways
Scope (3.5.1.1.OBC Div. B 3.5.1.1. Scope(1) This Section applies to vertical transportation facilities installed in a building, including elevators, escalators and dumbwaiters. (2) Elevators in a building within the scope of Subsection 3.2.6. shall conform to Articles 3.2.6.4. and 3.2.6.5.). Section 3.5. covers elevators, escalators and dumbwaiters. In a building under Subsection 3.2.6., elevators also follow 3.2.6.4. (emergency recall) and 3.2.6.5. (firefighter elevator).
Care occupancies (3.5.2.1.OBC Div. B 3.5.2.1. Required Elevator(1) Except as provided in Sentence (2), in a Group B, Division 2 or 3 occupancy, if sleeping rooms or patient or resident services are provided on more than one floor level and the floor levels are not connected by ramps conforming to Article 3.8.3.4., such floor levels shall be served by at least one elevator that is…). In Group B, Division 2 or 3, if sleeping rooms or patient or resident services are on more than one level, and the levels are not linked by barrier-free ramps, at least one elevator must carry a stretcher lying flat. Small Division 3 homes (up to 10 sleeping, up to six needing help) are exempt.
Stretcher size (3.5.4.1.OBC Div. B 3.5.4.1. Elevator Car Dimensions(1) Except as provided in Sentence (2), if an elevator is installed to conform to the requirements of Article 3.3.1.7., or if one or more elevators are provided in a building more than three storeys in building height, each storey having elevator service shall be served by at least one elevator that has inside…). In any building over 3 storeys with elevators, or where an elevator serves the 3.3.1.7. protection, each storey with elevator service has at least one car that fits a 2,010 mm by 610 mm stretcher. That car is identified at the main entrance level. Limited-use/limited-application elevators are exempt.
Hoistway ratings (3.5.3.1.OBC Div. B 3.5.3.1. Fire Separations for Elevator Hoistways(1) Except as permitted by Sentence (2), a vertical service space used as an elevator hoistway shall be separated from all other portions of each adjacent storey by a fire separation having a fire-resistance rating conforming to Table 3.5.3.1. for the fire-resistance rating required by Subsection 3.2.2. for (a) the…) come from Table 3.5.3.1.OBC Div. B Table 3.5.3.1. Fire Separation for Vertical Transportation SpaceTable 3.5.3.1 — Fire Separation for Vertical Transportation Space Forming Part of Sentences 3.5.3.1.(1) and 3.5.3.2.(1) Fire-Resistance Rating of Fire Separation Required for Floor Assembly | Minimum Fire-Resistance Rating of Vertical Service Space for Elevator Hoistway | Minimum Fire-Resistance Rating of Vertical…, keyed to the floor assembly rating required by 3.2.2. Read the table by finding the floor assembly rating in the first column, then reading across to the hoistway or dumbwaiter column. Two values worth remembering: a hoistway never drops below 45 min, and where the floors need 2 h or more the hoistway needs only 1.5 h, not 2 h. Dumbwaiter shafts are rated the same as or lighter than hoistways and top out at 1 h.
Passenger elevators (not firefighter elevators) may run unenclosed inside an interconnected floor space if the machine room is separated at the hoistway rating. A machine room is separated like its hoistway, or may share an enclosure with it (3.5.3.3.OBC Div. B 3.5.3.3. Fire Separations for Elevator Machine Rooms(1) Except as permitted by Sentence (2), a room containing elevator machinery shall be separated from all other parts of the building by a fire separation having a fire-resistance rating not less than that required for the vertical service space containing the elevator hoistway. (2) A room containing elevator…).
Service rooms
3.6.2.1.OBC Div. B 3.6.2.1. Fire Separations Around Service Rooms(1) Except as permitted by Sentences (2), (8), (9) and (10), fuel-fired appliances shall be installed in service rooms separated from the remainder of the building by fire separations having a fire-resistance rating not less than 1 h. (See Note A-3.6.2.1.(1)) (2) Except as required by Sentence (3), a fuel-fired… sets the default: fuel-fired appliances go in a service room with a 1 h fire separation. Exceptions and variations:
| Room or equipment | Separation |
|---|---|
| Fuel-fired appliance serving one room or suite only | none required |
| Incinerator room | 2 h |
| Equipment using liquid with flash point below 93.3°C | 1 h |
| Electrical equipment required in a service room by Electricity Act rules | 1 h |
| Other service equipment, storey not sprinklered | 1 h |
| Emergency generator room (3.6.2.8.OBC Div. B 3.6.2.8. Emergency Power Installations(1) Where a generator intended to supply emergency power for lighting, fire safety and life safety systems is located in a building, except where such building is used solely for the purpose of housing the generator and its ancillary equipment, it shall be located in a room that (a) is separated from the remainder of…) | 2 h, generator equipment only |
A service room with equipment that could explode, such as a boiler over 100 kPa gauge, may not be directly under a required exit (3.6.2.2.OBC Div. B 3.6.2.2. Service Rooms Under Exits(1) A service room containing service equipment subject to possible explosion, such as boilers operating in excess of 100 kPa (gauge) and some types of refrigerating machinery and transformers, shall not be located directly under a required exit.). Boiler and incinerator room doors swing out, except inward when they open onto a corridor or assembly room (3.6.2.6.OBC Div. B 3.6.2.6. Door Swing for Service Rooms(1) A swing-type door from a service room containing a boiler or incinerator shall swing outward from the room, except that the door shall swing inward if the door opens onto a corridor or any room used for an assembly occupancy. (See also Sentence 3.4.4.4.(7))). Service spaces may not be designed for later use as storage (3.6.1.4.OBC Div. B 3.6.1.4. Storage Use Prohibition(1) Service spaces shall not be designed to facilitate subsequent use as storage space.).
Service spaces, ducts and plenums
Vertical service spaces (3.6.3.1.OBC Div. B 3.6.3.1. Fire Separations for Vertical Service Spaces(1) Except as provided in Articles 3.6.3.3. and 3.6.3.5. and Section 3.5., a vertical service space shall be separated from all other portions of each adjacent storey by a fire separation having a fire-resistance rating conforming to Table 3.6.3.1. for the fire-resistance rating required by Subsection 3.2.2. for (a)…, Table 3.6.3.1.OBC Div. B Table 3.6.3.1. Fire Separations for Vertical Service SpaceTable 3.6.3.1 — Fire Separations for Vertical Service Space Forming Part of Sentence 3.6.3.1.(1) Fire-Resistance Rating of Fire Separation Required for Floor Assembly | Minimum Fire-Resistance Rating of Vertical Service Space less than 45 min | N/A 45 min | 45 min 1 h | 45 min 1.5 h | 1 h 2 h or more | 1 h) use their own table, which is never heavier than the hoistway table. The difference shows at 1 h floors, where a service shaft needs 45 min (a hoistway needs 1 h), and at 2 h floors, where a service shaft needs 1 h (a hoistway needs 1.5 h). The top value for a vertical service space is 1 h.
A shaft that stops short of the roof or the bottom is capped with construction of the same rating.
Linen and refuse chutes (3.6.3.3.OBC Div. B 3.6.3.3. Linen and Refuse Chutes(1) A linen chute or refuse chute shall (a) be impervious to moisture, (b) have a smooth internal surface, (c) be corrosion-resistant, (d) be constructed of noncombustible material, and (e) be located in a shaft in which there are no services other than noncombustible drain, waste and vent piping or noncombustible…):
- noncombustible, in a shaft of at least 1 h (with a fusible-link closure at the discharge) or 2 h (no closure);
- extend 1 m above the roof with a vent;
- intake openings no more than 60% of the chute cross-section, in rooms separated at 45 min;
- sprinklers at the top, at alternate floors and in the discharge room;
- linen discharge rooms at 1 h, refuse discharge rooms at 2 h.
Horizontal service spaces (3.6.4.2.OBC Div. B 3.6.4.2. Fire Separations for Horizontal Service Spaces(1) Except as provided in Article 3.6.3.5., a horizontal service space that penetrates a required vertical fire separation shall be separated from the remainder of the building it serves in conformance with Sentence (2). (2) If a horizontal service space or other concealed space is located above a required vertical…). A ceiling space above a vertical fire separation need not be divided if the ceiling below it is rated like the separation. It can be 30 min where the wall needs no more than 45 min.
Plenums (3.6.4.3.OBC Div. B 3.6.4.3. Plenum Requirements(1) A concealed space used as a plenum within a floor assembly or within a roof assembly need not conform to Sentence 3.1.5.18.(1) and Article 3.6.5.1. provided (a) all materials within the concealed space have a flame-spread rating not more than 25 and a smoke developed classification not more than 50, except for (i)…). A floor or roof space used as a plenum may hold only materials with flame-spread 25 and smoke developed 50 or less, apart from listed exceptions such as pneumatic control tubing and certain communication cables and raceways. The ceiling membrane supports are noncombustible with a melting point of at least 760°C. Return-air plenums with rated membranes need fire stop flaps.
Ducts (3.6.5.1.OBC Div. B 3.6.5.1. Duct Materials(1) Except as permitted by Sentences (2) to (5) and Article 3.6.4.3., all ducts, duct connectors, associated fittings and plenums used in air duct systems shall be constructed of steel, aluminum alloy, copper, clay or other noncombustible material. (2) Except as permitted by Sentence (3), ducts, associated fittings…) are steel, aluminum, copper, clay or other noncombustible material. Class 1 combustible ducts are allowed only within limits:
- horizontal runs only in noncombustible or EMTC buildings;
- no vertical runs over 2 storeys in combustible buildings;
- no air over 120°C.
Combustible duct connectors are at most 4 m long and may not pierce a fire separation. Duct sealants are limited to flame-spread 25 and smoke developed 50, and return ducts to flame-spread 150 (3.6.5.8.OBC Div. B 3.6.5.8. Return-Air System(1) Except as required by Sentences (2) and (3), return ducts shall be constructed of material having a flame-spread rating not more than 150. (2) If any part of a return duct will be exposed to radiation from the furnace heat exchanger or other radiating part within the furnace, that part of a return duct directly…).
Common traps
- Using the vertical service space table for an elevator hoistway. Hoistways are one step heavier at 1 h and 2 h floors.
- Giving a generator room 1 h like other service rooms. 3.6.2.8. requires 2 h.
- Putting a boiler room under an exit stair.
- Running a combustible duct vertically through 3 storeys of a combustible building.
Chapter review
Chapter at a glance
One line per section: the idea to carry into the exam. Then the answers that most often catch candidates out.
- Elevators and hoistways
Hoistway ratings come from, keyed to the floor assembly rating required by 3.2.2. Read the table by finding the floor assembly rating in the first column, then reading across to…
- Service rooms
A service room with equipment that could explode, such as a boiler over 100 kPa gauge, may not be directly under a required exit.
- Service spaces, ducts and plenums
Vertical service spaces use their own table, which is never heavier than the hoistway table.
Usual exam traps
- Using the vertical service space table for an elevator hoistway. Hoistways are one step heavier at 1 h and 2 h floors.
- Giving a generator room 1 h like other service rooms. 3.6.2.8. requires 2 h.
- Putting a boiler room under an exit stair.
- Running a combustible duct vertically through 3 storeys of a combustible building.
Practice this chapter
Questions on Vertical transportation and service facilities (3.5, 3.6), in the exam format, every answer explained and cited to its article. Sign in to start; a free account gets the free questions.
Code cited in this chapter
Based on the official 2024 Building Code Compendium on ontario.ca.
© King's Printer for Ontario, 2024. Reproduced with permission.
OBC Div. B 3.5.1.1. Scope
Open OBC Div. B 3.5.1.1. in the code viewer(1)This Section applies to vertical transportation facilities installed in a building, including elevators, escalators and dumbwaiters.
(2)Elevators in a building within the scope of Subsection 3.2.6. shall conform to Articles 3.2.6.4. and 3.2.6.5.
OBC Div. B 3.5.2.1. Required Elevator
Open OBC Div. B 3.5.2.1. in the code viewer(1)Except as provided in Sentence (2), in a Group B, Division 2 or 3 occupancy, if sleeping rooms or patient or resident services are provided on more than one floor level and the floor levels are not connected by ramps conforming to Article 3.8.3.4., such floor levels shall be served by at least one elevator that is large enough to accommodate a stretcher in a horizontal position.
(2)Sentence (1) does not apply to those parts of a floor area classified as a Group B, Division 3 occupancy if
(a)those portions of the floor area contain sleeping accommodation for not more than 10 persons, and
(b)not more than six occupants require assistance in evacuating in the case of an emergency.
OBC Div. B 3.5.4.1. Elevator Car Dimensions
Open OBC Div. B 3.5.4.1. in the code viewer(1)Except as provided in Sentence (2), if an elevator is installed to conform to the requirements of Article 3.3.1.7., or if one or more elevators are provided in a building more than three storeys in building height, each storey having elevator service shall be served by at least one elevator that has inside dimensions that will accommodate and provide adequate access for a patient stretcher 2,010 mm long and 610 mm wide in the prone position. (See Note A-3.5.4.1.(1))
(2)The inside dimensions stipulated in Sentence (1) do not apply to limited-use/limited-application elevators designed and installed in accordance with ASME A17.1 / CSA B44, "Safety Code for Elevators and Escalators."
(3)An elevator satisfying the requirements of Sentence (1) shall be clearly identified on the main entrance level of the building.
OBC Div. B 3.5.3.1. Fire Separations for Elevator Hoistways
Open OBC Div. B 3.5.3.1. in the code viewer(1)Except as permitted by Sentence (2), a vertical service space used as an elevator hoistway shall be separated from all other portions of each adjacent storey by a fire separation having a fire-resistance rating conforming to Table 3.5.3.1. for the fire-resistance rating required by Subsection 3.2.2. for
(a)the floor assembly above the storey, or
(b)the floor assembly below the storey, if there is no floor assembly above.
(2)Passenger elevators, other than those provided for firefighters in accordance with Article 3.2.6.5., are permitted to be located within interconnected floor space without being enclosed in a hoistway separated from the remainder of the building, provided the elevator machinery is located in a room separated from the remainder of the building by a fire separation having a fire-resistance rating not less than that required for hoistways by Sentence (1).
OBC Div. B Table 3.5.3.1. Fire Separation for Vertical Transportation Space
Open OBC Div. B Table 3.5.3.1. in the code viewerTable 3.5.3.1 — Fire Separation for Vertical Transportation Space Forming Part of Sentences 3.5.3.1.(1) and 3.5.3.2.(1) Fire-Resistance Rating of Fire Separation Required for Floor Assembly | Minimum Fire-Resistance Rating of Vertical Service Space for Elevator Hoistway | Minimum Fire-Resistance Rating of Vertical Service Space for Dumbwaiters less than 45 min | 45 min | N/A 45 min | 45 min | 45 min 1 h | 1 h | 45 min 1.5 h | 1 h | 1 h 2 h or more | 1.5 h | 1 h
OBC Div. B 3.5.3.3. Fire Separations for Elevator Machine Rooms
Open OBC Div. B 3.5.3.3. in the code viewer(1)Except as permitted by Sentence (2), a room containing elevator machinery shall be separated from all other parts of the building by a fire separation having a fire-resistance rating not less than that required for the vertical service space containing the elevator hoistway.
(2)A room containing elevator machinery need not be separated from the elevator hoistway that it serves provided the room and the hoistway are separated from all other parts of the building by a fire separation having a fire-resistance rating not less than that required for the vertical service space containing the elevator hoistway.
OBC Div. B 3.6.2.1. Fire Separations Around Service Rooms
Open OBC Div. B 3.6.2.1. in the code viewer(1)Except as permitted by Sentences (2), (8), (9) and (10), fuel-fired appliances shall be installed in service rooms separated from the remainder of the building by fire separations having a fire-resistance rating not less than 1 h. (See Note A-3.6.2.1.(1))
(2)Except as required by Sentence (3), a fuel-fired appliance that serves only one room or suite is not required to be installed in a service room separated from the remainder of the building.
(3)A solid-fuel-burning appliance shall not be located in a repair garage, a storage garage, or any other location where it could be exposed to flammable vapours or gases unless
(a)it is enclosed in a service room that is separated from the remainder of the building by a fire separation having a fire-resistance rating not less than 1 h,
(b)it is supplied with combustion air directly from outside the building, and
(c)the heat that it generates is supplied indirectly to the space served by means of ducts or piping.
(4)A service room containing an incinerator shall be separated from the remainder of the building by a fire separation having a fire-resistance rating not less than 2 h.
(5)Equipment that uses a liquid having a flash point below 93.3°C shall be installed in a service room separated from the remainder of the building by a fire separation having a fire-resistance rating not less than 1 h.
(6)Electrical equipment that is required to be located in a service room by a regulation made under the Electricity Act, 1998, shall be installed in a service room separated from the remainder of the building by a fire separation having a fire-resistance rating not less than 1 h.
(7)Except as permitted by Sentence (8), in a storey that is not sprinklered throughout, a service room that contains service equipment other than that addressed by Sentences (1) to (6), shall be separated from the remainder of the building by a fire separation having a fire-resistance rating not less than 1 h.
(8)Where a service room contains a limited quantity of service equipment, and the service equipment neither constitutes a fire hazard nor is essential to the operation of fire safety systems in the building, the requirements for a fire separation shall not apply.
(9)A fire separation is not required between a fireplace and the space it serves.
(10)A fire separation is not required between a rooftop appliance and the building it serves.
(11)The fire separation provisions for a fuel-fired appliance in a portable classroom shall conform to Article 3.9.3.7.
OBC Div. B 3.6.2.8. Emergency Power Installations
Open OBC Div. B 3.6.2.8. in the code viewer(1)Where a generator intended to supply emergency power for lighting, fire safety and life safety systems is located in a building, except where such building is used solely for the purpose of housing the generator and its ancillary equipment, it shall be located in a room that
(a)is separated from the remainder of the building by a fire separation with a fire-resistance rating not less than 2 h, and
(b)contains only the generating set and equipment that is related to the emergency power supply system.
Show all 18 articles
OBC Div. B 3.6.2.2. Service Rooms Under Exits
Open OBC Div. B 3.6.2.2. in the code viewer(1)A service room containing service equipment subject to possible explosion, such as boilers operating in excess of 100 kPa (gauge) and some types of refrigerating machinery and transformers, shall not be located directly under a required exit.
OBC Div. B 3.6.2.6. Door Swing for Service Rooms
Open OBC Div. B 3.6.2.6. in the code viewer(1)A swing-type door from a service room containing a boiler or incinerator shall swing outward from the room, except that the door shall swing inward if the door opens onto a corridor or any room used for an assembly occupancy. (See also Sentence 3.4.4.4.(7))
OBC Div. B 3.6.1.4. Storage Use Prohibition
Open OBC Div. B 3.6.1.4. in the code viewer(1)Service spaces shall not be designed to facilitate subsequent use as storage space.
OBC Div. B 3.6.3.1. Fire Separations for Vertical Service Spaces
Open OBC Div. B 3.6.3.1. in the code viewer(1)Except as provided in Articles 3.6.3.3. and 3.6.3.5. and Section 3.5., a vertical service space shall be separated from all other portions of each adjacent storey by a fire separation having a fire-resistance rating conforming to Table 3.6.3.1. for the fire-resistance rating required by Subsection 3.2.2. for
(a)the floor assembly above the storey, or
(b)the floor assembly below the storey, if there is no floor assembly above. (See Note A-3.6.3.1.(1))
(2)A vertical service space that does not extend through the roof of a building shall be enclosed at the top with construction having a fire-resistance rating not less than that required for the vertical service space walls.
(3)A vertical service space that does not extend to the bottom of a building shall be enclosed at the lowest level with construction having a fire-resistance rating not less than that required for the vertical service space walls.
(4)A vent from a vertical service space not extending to the roof shall be enclosed within the building with construction having a fire-resistance rating not less than that required for the vertical service space walls.
(5)Only openings that are necessary for the use of the vertical service space shall be permitted through a vertical service space enclosure.
OBC Div. B Table 3.6.3.1. Fire Separations for Vertical Service Space
Open OBC Div. B Table 3.6.3.1. in the code viewerTable 3.6.3.1 — Fire Separations for Vertical Service Space Forming Part of Sentence 3.6.3.1.(1) Fire-Resistance Rating of Fire Separation Required for Floor Assembly | Minimum Fire-Resistance Rating of Vertical Service Space less than 45 min | N/A 45 min | 45 min 1 h | 45 min 1.5 h | 1 h 2 h or more | 1 h
OBC Div. B 3.6.3.3. Linen and Refuse Chutes
Open OBC Div. B 3.6.3.3. in the code viewer(1)A linen chute or refuse chute shall
(a)be impervious to moisture,
(b)have a smooth internal surface,
(c)be corrosion-resistant,
(d)be constructed of noncombustible material, and
(e)be located in a shaft in which there are no services other than noncombustible drain, waste and vent piping or noncombustible water piping.
(2)A shaft containing a linen chute or refuse chute shall have a fire-resistance rating conforming to Sentence 3.6.3.1.(1), but not less than
(a)1 h if the chute outlet for the discharge room is protected by an automatic, self-latching closure held open by a fusible link, or
(b)2 h if no closure is provided at the chute outlet into the discharge room.
(3)An interior linen chute or refuse chute shall extend not less than 1 m above the roof and shall be vented above the roof with a vent which
(a)has an unobstructed area not less than the cross-sectional area of the chute, and
(b)is equipped with a cover that will open automatically, or that can be opened manually, in the event of a fire in the
(4)Intake openings for a linen chute or a refuse chute shall
(a)have an area not more than 60% of the cross-sectional area of the chute, and
(b)be fitted with closures designed to close automatically and latch after use.
(5)Intake openings for a linen chute or a refuse chute shall be located in rooms or compartments that
(a)have no dimension less than 750 mm,
(b)are separated from the remainder of the building by a fire separation with a fire-resistance rating not less than 45 min,
(c)are designed for no other purpose, and
(d)do not open directly into an exit.
(6)Sprinklers shall be installed at the top of each linen chute or refuse chute, at alternate floor levels and in the room or bin into which the chute discharges.
(7)The room into which a linen chute discharges shall be separated from the remainder of the building by a fire separation with a fire-resistance rating not less than 1 h.
(8)A refuse chute shall be equipped at the top with spray equipment for washing-down purposes.
(9)A refuse chute shall discharge only into a room or bin separated from the remainder of the building by a fire separation with a fire-resistance rating not less than 2 h.
(10)The room or bin into which a refuse chute discharges shall be of sufficient size to contain the refuse between normal intervals of emptying, be impervious to moisture and be equipped with a water connection and floor drain for washing-down purposes.
(11)A room into which a refuse chute discharges shall contain no service equipment that is not related to refuse handling and disposal.
OBC Div. B 3.6.4.2. Fire Separations for Horizontal Service Spaces
Open OBC Div. B 3.6.4.2. in the code viewer(1)Except as provided in Article 3.6.3.5., a horizontal service space that penetrates a required vertical fire separation shall be separated from the remainder of the building it serves in conformance with Sentence (2).
(2)If a horizontal service space or other concealed space is located above a required vertical fire separation other than a vertical shaft, this space need not be divided at the fire separation as required by Article 3.1.8.3. provided the construction between this space and the space below is a fire separation with a fire-resistance rating equivalent to that required for the vertical fire separation, except that the fire-resistance rating is permitted to be not less than 30 min if the vertical fire separation is not required to have a fire-resistance rating more than 45 min. (See Note A-3.6.4.2.(2))
OBC Div. B 3.6.4.3. Plenum Requirements
Open OBC Div. B 3.6.4.3. in the code viewer(1)A concealed space used as a plenum within a floor assembly or within a roof assembly need not conform to Sentence 3.1.5.18.(1) and Article 3.6.5.1. provided
(a)all materials within the concealed space have a flame-spread rating not more than 25 and a smoke developed classification not more than 50, except for
(i)tubing for pneumatic controls,
(ii)optical fibre cables and electrical wires and cables with combustible insulation, jackets or sheathes that are used for the transmission of voice, sound or data and conform to Sentences 3.1.4.3.(2) and 3.1.5.21.(2),
(iii)totally enclosed non-metallic raceways with an FT6 rating, when tested in accordance with Clause 3.1.5.23.(1)(a), in buildings required to be of noncombustible construction or in buildings or parts of buildings permitted to be of encapsulated mass timber construction, and
(iv)totally enclosed non-metallic raceways with an FT4 rating, when tested in accordance with Clause 3.1.5.23.(1)(a), in buildings permitted to be of combustible construction, and,
(b)the supports for the ceiling membrane are of noncombustible material having a melting point not below 760°C.
(2)If a concealed space referred to in Sentence (1) is used as a return-air plenum and incorporates a ceiling membrane that forms part of the required fire-resistance rating of the assembly, every opening through the membrane shall be protected by a fire stop flap that
(a)stops the flow of air into the concealed space in the event of a fire,
(b)is supported in a manner that will maintain the integrity of the ceiling membrane for the duration of time required to provide the required fire-resistance rating,
(c)conforms to CAN/ULC-S112.2, "Standard Method Fire Test of Ceiling Firestop Flap Assemblies," and
(d)activates at a temperature approximately 30°C above the normal maximum temperature that occurs in the return-air plenum, whether the air duct system is operating or shut down.
OBC Div. B 3.6.5.1. Duct Materials
Open OBC Div. B 3.6.5.1. in the code viewer(1)Except as permitted by Sentences (2) to (5) and Article 3.6.4.3., all ducts, duct connectors, associated fittings and plenums used in air duct systems shall be constructed of steel, aluminum alloy, copper, clay or other noncombustible material.
(2)Except as permitted by Sentence (3), ducts, associated fittings and plenums are permitted to contain combustible material provided they
(a)conform to the appropriate requirements for Class 1 duct materials in CAN/ULC-S110, "Standard Methods of Test for Air Ducts,"
(b)conform to Article 3.1.5.18. in a building required to be of noncombustible construction or in a building or part of a building permitted to be of encapsulated mass timber construction,
(c)conform to Subsection 3.1.9.,
(d)are used only in horizontal runs in a building required to be of noncombustible construction or in a building or part of a building permitted to be of encapsulated mass timber construction,
(e)are not used in vertical runs serving more than 2 storeys in a building permitted to be of combustible construction, and
(f)are not used in air duct systems in which the air temperature could be more than 120°C.
(3)Combustible ducts which are part of a duct system conveying only ventilation air and are contained entirely within a dwelling unit need not comply with the requirements of Sentences (1) and (2).
(4)Duct sealants shall have a flame-spread rating not more than 25 and a smoke developed classification not more than 50.
(5)Duct connectors that contain combustible materials and that are used between ducts and air outlet units shall
(a)conform to the appropriate requirements for Class 1 air duct materials in CAN/ULC-S110, "Standard Methods of Test for Air Ducts,"
(b)be not more than 4 m long,
(c)be used only in horizontal runs, and
(d)not penetrate a required fire separation.
OBC Div. B 3.6.5.8. Return-Air System
Open OBC Div. B 3.6.5.8. in the code viewer(1)Except as required by Sentences (2) and (3), return ducts shall be constructed of material having a flame-spread rating not more than 150.
(2)If any part of a return duct will be exposed to radiation from the furnace heat exchanger or other radiating part within the furnace, that part of a return duct directly above or within 600 mm of the outside furnace casing shall be noncombustible.
(3)Return ducts serving solid-fuel-burning furnaces shall be constructed of noncombustible material.
(4)Combustible return ducts shall be lined with noncombustible material
(a)below floor registers,
(b)at the bottom of vertical ducts, and
(c)under furnaces having a bottom return.