Calculation Lab, method 12

Building area, grade and height in storeys

Work out grade, the first storey, building height in storeys, building area, mezzanine limits and facing streets, then apply Part 9 and Part 3 limits.

worked examples
4
worked examples
to read
6 min
to read
exams test this
2
exams test this

Tested on:HouseSmall Buildings

Last updated

When this shows up on the exam

Many House and Small Buildings questions start with a building's size. Before you pick a Part or a table row, you need two numbers: the building height in storeys and the building area.

  • House: grade on a sloping lot, whether a walkout lower level is the first storey, how many storeys a house has, and whether the building falls under Part 9.
  • Small Buildings (SB): the same, plus mezzanines that do or do not count as storeys, firewalls that split a building, the "facing streets" count, and the maximum building area from a Subsection 3.2.2. table.

The method

  1. Find grade. Grade is the average level of the proposed or finished ground next to the building at all exterior walls (OBC Div. A 1.4.1.2. "grade"OBC Div. A 1.4.1.2.(1) GradeGrade means the average level of proposed or finished ground adjoining a building at all exterior walls.). Add up the ground elevations taken around the walls and divide by the number of readings. Never use one wall or one point alone. Readings should represent every wall fairly (equal spacing, or equal wall lengths).
  2. Find the first storey. It is the storey with its floor closest to grade and its ceiling more than 1.8 m above grade (first storeyOBC Div. A 1.4.1.2.(1) First storeyFirst storey means the storey that has its floor closest to grade and its ceiling more than 1.8 m above grade.). Compute ceiling elevation minus grade. More than 1.8 m: this level is the first storey, even if its floor is below grade. 1.8 m or less: it is a basement (basementOBC Div. A 1.4.1.2.(1) BasementBasement means a storey or storeys of a building located below the first storey.) and does not count.
  3. Count storeys. Building height in storeys is the number of storeys from the floor of the first storey up to the roof (building heightOBC Div. A 1.4.1.2.(1) Building height (in storeys)Building height (in storeys) means the number of storeys contained between the roof and the floor of the first storey.). Then remove what OBC Div. B 3.2.1.1.OBC Div. B 3.2.1.1. Exceptions in Determining Building Height(1) A rooftop enclosure provided for elevator machinery, a stairway or a service room used for no purpose other than for service to the building, shall not be considered as a storey in calculating the building height. (2) Space under tiers of seats in a building of the arena type shall not be considered as adding to… lets you ignore:
    • a rooftop enclosure used only for elevator machinery, a stairway or a service room (Sentence (1));
    • the space above mezzanines whose total area is not more than 40% of the open area of the room and which stay open above, with no partitions over 1,070 mm (Sentence (3));
    • enclosed mezzanines that total not more than 10% of the floor area, and not more than 10% of the suite they are in (Sentence (4));
    • an enclosed space on a 40% mezzanine is allowed if it is not more than 10% of the room's open area (Sentence (7)). A second mezzanine level stacked over the first counts as a storey (Sentence (5)).
  4. Find building area. Building area is the greatest horizontal area of the building above grade, measured to the outside surface of the exterior walls, or to the centre line of a firewall (building areaOBC Div. A 1.4.1.2.(1) Building areaBuilding area means the greatest horizontal area of a building above grade within the outside surface of exterior walls or within the outside surface of exterior walls and the centre line of firewalls.). Use the biggest floor plate, including cantilevers. Do not add storeys together.
  5. Split at firewalls. Each portion on either side of a firewall is a separate building, except for a few listed purposes such as the fire alarm system (OBC Div. A 1.3.3.4.(1)OBC Div. A 1.3.3.4. Building Size Determination(1) Where a firewall divides a building, each portion of the building that is divided shall be considered as a separate building, except for the purposes of (a) a determination of gross area in Section 1.2. of Division C, (b) a fire alarm and detection system in Sentence 3.2.4.2.(1) of Division B or Article 9.10.18.1…).
  6. Pick the Part. Part 9 applies to a building of 3 storeys or less with a building area not exceeding 600 m², used for Group C (not a retirement home), Group D, Group E, or Group F, Division 2 or 3 (OBC Div. A 1.3.3.3.OBC Div. A 1.3.3.3. Application of Part 9(1) Subject to Article 1.3.3.3B., Part 9 of Division B applies to all buildings described in Article 1.1.1.1. of 3 storeys or less in building height, having a building area not exceeding 600 m², and used for major occupancies classified as (a) reserved (b) Group C, residential occupancies other than buildings used…). Fail either number and the building goes to Part 3 (1.3.3.2.OBC Div. A 1.3.3.2. Application of Parts 3, 4, 5 and 6(1) Subject to Articles 1.3.3.1A., 1.3.3.3B., Parts 3, 4, 5, and 6 of Division B apply to all buildings described in Article 1.1.1.1. and (a) classified as post-disaster buildings, (b) used for major occupancies classified as (i) Group A, assembly occupancies, (ii) Group B, care, care and treatment or detention…).
  7. Part 3: count streets. A building faces 2 streets when at least 50% of its perimeter is within 15 m of a street or streets, and 3 streets at 75% (OBC Div. B 3.2.2.10.OBC Div. B 3.2.2.10. Streets(1) Every building shall face a street located in conformance with the requirements of Articles 3.2.5.4 and 3.2.5.5 for access routes. (2) For the purposes of Subsections 3.2.2. and 3.2.5. an access route conforming to Subsection 3.2.5. is permitted to be considered as a street. (3) A building conforming to Article…). Add the lengths of wall within 15 m, divide by the full perimeter.
  8. Part 3: read the table. Pick the article for the group, storeys and sprinkler status (for example 3.2.2.54.OBC Div. B 3.2.2.54. Group C, up to 3 Storeys(1) A building classified as Group C, other than a retirement home, is permitted to conform to Sentence (2) provided (a) it is not more than 3 storeys in building height, and (b) it has a building area not more than the value in Table 3.2.2.54. (2) The building referred to in Sentence (1) is permitted to be of… for Group C up to 3 storeys). In its table, go to the row for the number of storeys, then the column for the number of streets faced. The value is the maximum building area, which is a limit per floor plate, not for the whole building.

Worked example 1: grade, first storey and storeys

A house on a sloping lot has four exterior walls of equal length. The average finished ground elevation along each wall is 210.30, 210.90, 211.70 and 212.30. The lower level has its floor at 210.60 and its ceiling at 213.20. Two full storeys sit above it.

Step Working Result
Grade (210.30 + 210.90 + 211.70 + 212.30) / 4 = 845.20 / 4 211.30
Ceiling above grade 213.20 - 211.30 1.90 m
Test 1.90 m is more than 1.8 m first storey
Storeys lower level + 2 3 storeys

The lower level is the first storey even though its floor is 0.70 m below grade (first storeyOBC Div. A 1.4.1.2.(1) First storeyFirst storey means the storey that has its floor closest to grade and its ceiling more than 1.8 m above grade.). Measuring from the high side (212.30) gives 0.90 m and a false "basement, 2 storeys" answer.

Worked example 2: building area at a firewall

A 2-storey Group E building measures 36.0 m by 30.0 m to the outside faces of its walls. A firewall runs across it, with its centre line 19.6 m from the east face.

Portion Working Building area
East 19.6 × 30.0 588 m²
West (36.0 - 19.6) × 30.0 = 16.4 × 30.0 492 m²
Whole building (not used) 36.0 × 30.0 1,080 m²

Each portion is a separate building (A 1.3.3.4.(1)OBC Div. A 1.3.3.4. Building Size Determination(1) Where a firewall divides a building, each portion of the building that is divided shall be considered as a separate building, except for the purposes of (a) a determination of gross area in Section 1.2. of Division C, (b) a fire alarm and detection system in Sentence 3.2.4.2.(1) of Division B or Article 9.10.18.1…). Both are 2 storeys, Group E and not over 600 m², so both may be designed under Part 9 (A 1.3.3.3.OBC Div. A 1.3.3.3. Application of Part 9(1) Subject to Article 1.3.3.3B., Part 9 of Division B applies to all buildings described in Article 1.1.1.1. of 3 storeys or less in building height, having a building area not exceeding 600 m², and used for major occupancies classified as (a) reserved (b) Group C, residential occupancies other than buildings used…). The fire alarm system is still assessed for the whole building.

Worked example 3: does the mezzanine count?

A store room has an open area of 18 m by 40 m (720 m²). Two separate mezzanines of 150 m² and 120 m² are planned, open above with guards only.

  • 40% of 720 m² = 288 m².
  • 150 + 120 = 270 m², which is not more than 288 m².
  • Result: the space above them is not a storey (B 3.2.1.1.(3)OBC Div. B 3.2.1.1. Exceptions in Determining Building Height(1) A rooftop enclosure provided for elevator machinery, a stairway or a service room used for no purpose other than for service to the building, shall not be considered as a storey in calculating the building height. (2) Space under tiers of seats in a building of the arena type shall not be considered as adding to…). An enclosed office on a mezzanine could be up to 10% of 720 = 72 m² (Sentence (7)).

Worked example 4: Part 3 size limit with streets

A 3-storey Group D office, unsprinklered, measures 46 m by 36 m.

  • Building area: 46 × 36 = 1,656 m². Over 600 m², so Part 3.
  • Perimeter: 2 × (46 + 36) = 164 m. The 46 m front, the 36 m east side and 10 m of the west side are within 15 m of streets: 92 m.
  • 92 / 164 = 56%, at least 50% but under 75%, so it faces 2 streets (B 3.2.2.10.(4)OBC Div. B 3.2.2.10. Streets(1) Every building shall face a street located in conformance with the requirements of Articles 3.2.5.4 and 3.2.5.5 for access routes. (2) For the purposes of Subsections 3.2.2. and 3.2.5. an access route conforming to Subsection 3.2.5. is permitted to be considered as a street. (3) A building conforming to Article…).
  • Table 3.2.2.62.OBC Div. B Table 3.2.2.62. Maximum Building Area, Group D, up to 3 StoreysTable 3.2.2.62. Maximum Building Area, Group D, up to 3 Storeys Forming Part of Sentence 3.2.2.62.(1) No. of Storeys | Maximum area, m² — Facing 1 Street | Maximum area, m² — Facing 2 Streets | Maximum area, m² — Facing 3 Streets 1 | 4,800 | 6,000 | 7,200 2 | 2,400 | 3,000 | 3,600 3 | 1,600 | 2,000 | 2,400, row "3" storeys, column "Facing 2 Streets": 2,000 m². 1,656 m² is within it, so 3.2.2.62.OBC Div. B 3.2.2.62. Group D, up to 3 Storeys(1) A building classified as Group D is permitted to conform to Sentence (2) provided (a) it is not more than 3 storeys in building height, and (b) it has a building area not more than the value in Table 3.2.2.62. (2) The building referred to in Sentence (1) is permitted to be of combustible construction or… can be used.
  • Had only the front been near a street (46 / 164 = 28%), the "Facing 1 Street" value of 1,600 m² would apply and the building would be too big for this article.

Common mistakes

  • Taking grade at the front door, the lowest point or the highest point instead of the average around all walls.
  • Deciding first storey versus basement by where the floor is, instead of the ceiling height above grade.
  • Using 2 m, or "1.8 m or more", instead of "more than 1.8 m".
  • Counting a rooftop stair or elevator enclosure, or a qualifying mezzanine, as a storey.
  • Taking 40% or 10% of the mezzanine area, or forgetting mezzanines that already exist.
  • Measuring building area to the inside face of walls, or to the near or far face of a firewall instead of its centre line.
  • Adding the floor areas of all storeys and calling it building area.
  • Treating the 600 m² Part 9 limit as a per storey floor area limit, or forgetting the storey test.
  • Counting how many streets touch the lot instead of the share of perimeter within 15 m.
  • Reading the wrong row (storeys) or column (streets) in a Subsection 3.2.2. table.

Find it fast in the code PDF

  • Division A > Part 1 > 1.4.1.2. Defined Terms: Ctrl+F "average level of proposed or finished ground", "ceiling more than 1.8 m above grade", "centre line of firewalls", "between the roof and the floor of the first storey".
  • Division A > Part 1 > 1.3.3. Application of Division B: "having a building area not exceeding 600" and "considered as a separate building".
  • Division B > Part 3 > 3.2.1. General: "space above a mezzanine" and "open area of the room".
  • Division B > Part 3 > 3.2.2. Building Size and Construction Relative to Occupancy: "building perimeter is located within 15 m", then the article for your group, such as "Group C, up to 3 Storeys".

Drill these questions

Calculation questions in the exam format, each worked and cited. Pick your exam; sign in to start, a free account gets the free questions.

Code cited in this method

Based on the official 2024 Building Code Compendium on ontario.ca.

© King's Printer for Ontario, 2024. Reproduced with permission.

  • OBC Div. A 1.4.1.2.(1) Grade

    Grade means the average level of proposed or finished ground adjoining a building at all exterior walls.

    Open OBC Div. A 1.4.1.2.(1) in the code viewer
  • OBC Div. A 1.4.1.2.(1) First storey

    First storey means the storey that has its floor closest to grade and its ceiling more than 1.8 m above grade.

    Open OBC Div. A 1.4.1.2.(1) in the code viewer
  • OBC Div. A 1.4.1.2.(1) Basement

    Basement means a storey or storeys of a building located below the first storey.

    Open OBC Div. A 1.4.1.2.(1) in the code viewer
  • OBC Div. A 1.4.1.2.(1) Building height (in storeys)

    Building height (in storeys) means the number of storeys contained between the roof and the floor of the first storey.

    Open OBC Div. A 1.4.1.2.(1) in the code viewer
  • OBC Div. B 3.2.1.1. Exceptions in Determining Building Height

    (1)A rooftop enclosure provided for elevator machinery, a stairway or a service room used for no purpose other than for service to the building, shall not be considered as a storey in calculating the building height.

    (2)Space under tiers of seats in a building of the arena type shall not be considered as adding to the building height provided the space is used only for dressing rooms, concession stands and similar purposes incidental to the major occupancy of the building.

    (3)Except as required by Sentence (5), the space above a mezzanine need not be considered as a storey in calculating building height provided

    (a)the aggregate area of mezzanines that are not superimposed does not exceed 40% of the open area of the room in which they are located, and (See Note A-3.2.1.1.(3)(a))

    (b)except as permitted in Sentences (7) and 3.3.2.13.(3) the space above the mezzanine is used as an open area without partitions or subdividing walls higher than 1,070 mm above the mezzanine floor.

    (4)Except as required by Sentence (5), the space above a mezzanine need not be considered as a storey in calculating the building height provided

    (a)the aggregate area of mezzanines that are not superimposed and do not meet the conditions of Sentence (3) does not exceed 10% of the floor area in which they are located, and

    (b)the area of a mezzanine in a suite does not exceed 10% of the area of that suite.

    (5)Except as permitted by Sentence (6), each level of mezzanine that is partly or wholly superimposed above the first level of mezzanine shall be considered as a storey in calculating the building height.

    (6)Platforms intended solely for periodic inspection and elevated maintenance catwalks need not be considered as floor assemblies or mezzanines for the purpose of calculating building height, provided

    (a)they are not used for storage, and

    (b)they are constructed with noncombustible materials unless the building is permitted to be of combustible construction.

    (7)The space above a mezzanine conforming to Sentence (3) is permitted to include an enclosed space whose area does not exceed 10% of the open area of the room in which the mezzanine is located, provided the enclosed space does not obstruct visual communication between the open space above the mezzanine and the room in which it is located. (See Note A-3.2.1.1.(3)(a)

    (8)A service space in which facilities are included to permit a person to enter and to undertake maintenance and other operations pertaining to building services from within the service space need not be considered a storey if it conforms to Articles 3.2.5.14. and 3.3.1.25., and Sentences 3.2.4.18.(11), 3.2.7.3.(2), 3.3.1.3.(7), 3.4.2.4.(3) and 3.4.4.4.(9). (See Note A-3.2.1.1.(8))

    Open OBC Div. B 3.2.1.1. in the code viewer
  • OBC Div. A 1.4.1.2.(1) Building area

    Building area means the greatest horizontal area of a building above grade within the outside surface of exterior walls or within the outside surface of exterior walls and the centre line of firewalls.

    Open OBC Div. A 1.4.1.2.(1) in the code viewer
  • OBC Div. A 1.3.3.4. Building Size Determination

    (1)Where a firewall divides a building, each portion of the building that is divided shall be considered as a separate building, except for the purposes of

    (a)a determination of gross area in Section 1.2. of Division C,

    (b)a fire alarm and detection system in Sentence 3.2.4.2.(1) of Division B or Article 9.10.18.1. of Division B, and

    (c)a plumbing system interconnected through a firewall.

    (2)Except as permitted in Sentence (3), where portions of a building are completely separated by a vertical fire separation that has a fire-resistance rating of not less than 1 h and extends through all storeys and service spaces of the separated portions, each separated portion is permitted to be considered as a separate building for the purpose of determining building height, provided

    (a)each separated portion is not more than 3 storeys in building height and is used only for residential occupancies other than a retirement home, and

    (b)the unobstructed path of travel for a firefighter from the nearest street to one entrance of each separated portion is not more than 45 m.

    (See Note A-1.3.3.4.(2))

    (3)The vertical fire separation referred to in Sentence (2) may terminate at the floor assembly immediately above a basement provided the basement conforms to Article 3.2.1.2. of Division B.

    Open OBC Div. A 1.3.3.4. in the code viewer
  • OBC Div. A 1.3.3.3. Application of Part 9

    (1)Subject to Article 1.3.3.3B., Part 9 of Division B applies to all buildings described in Article 1.1.1.1. of 3 storeys or less in building height, having a building area not exceeding 600 m², and used for major occupancies classified as

    (a)reserved

    (b)Group C, residential occupancies other than buildings used for retirement homes, (See Note A-9.1.1.1.(1) of Division B)

    (c)Group D, business and personal services occupancies,

    (d)Group E, mercantile occupancies, or

    (e)Group F, Divisions 2 and 3, medium- and low-hazard industrial occupancies.

    Open OBC Div. A 1.3.3.3. in the code viewer
Show all 13 articles
  • OBC Div. A 1.3.3.2. Application of Parts 3, 4, 5 and 6

    (1)Subject to Articles 1.3.3.1A., 1.3.3.3B., Parts 3, 4, 5, and 6 of Division B apply to all buildings described in Article 1.1.1.1. and

    (a)classified as post-disaster buildings,

    (b)used for major occupancies classified as

    (i)Group A, assembly occupancies,

    (ii)Group B, care, care and treatment or detention occupancies, or

    (iii)Group F, Division 1, high-hazard industrial occupancies, or

    (c)exceeding 600 m² in building area or exceeding 3 storeys in building height used for major occupancies classified as

    (i)Group C, residential occupancies,

    (ii)Group D, business and personal services occupancies,

    (iii)Group E, mercantile occupancies, or

    (iv)Group F, Divisions 2 and 3, medium- and low-hazard industrial occupancies.

    (2)Subject to Articles 1.3.3.1A. and 1.3.3.3B., Part 4 of Division B applies to

    (a)a retaining wall exceeding 1,000 mm in exposed height adjacent to

    (i)public property,

    (ii)access to a building, or

    (iii)private property to which the public is admitted,

    (b)a pedestrian bridge appurtenant to a building,

    (c)a crane runway,

    (d)an exterior storage tank and its supporting structure that is not regulated by the Technical Standards and Safety Act, 2000,

    (e)signs regulated by Section 3.15. of Division B that are not structurally supported by a building,

    (f)a structure that supports a wind turbine generator having a rated output of more than 3 kW,

    (g)an outdoor pool that has a water depth greater than 3.5 m at any point, and

    (h)a permanent solid nutrient storage facility with supporting walls exceeding 1,000 mm in exposed height.

    (3)Section 3.11. of Division B applies to public pools.

    (4)Section 3.12. of Division B applies to public spas.

    (5)Section 3.15. of Division B applies to signs.

    (6)Section 3.17. of Division B applies to demountable stages and demountable support structures.

    Open OBC Div. A 1.3.3.2. in the code viewer
  • OBC Div. B 3.2.2.10. Streets

    (1)Every building shall face a street located in conformance with the requirements of Articles 3.2.5.4 and 3.2.5.5 for access routes.

    (2)For the purposes of Subsections 3.2.2. and 3.2.5. an access route conforming to Subsection 3.2.5. is permitted to be considered as a street.

    (3)A building conforming to Article 3.2.2.51. or 3.2.2.60. is considered to face one street, where

    (a)not less than 25% of the building perimeter is located within 15 m of a street or streets, or

    (b)not less than 10% of the building perimeter is located within 15 m of a street or streets, provided the exterior cladding conforms to Sentence 3.1.4.8.(2).

    (4)A building is considered to face 2 streets provided not less than 50% of the building perimeter is located within 15 m of the street or streets.

    (5)A building is considered to face 3 streets provided not less than 75% of the building perimeter is located within 15 m of the street or streets.

    (6)Enclosed spaces, tunnels, bridges and similar structures, even though used for vehicular or pedestrian traffic, are not considered as streets for the purpose of this Part.

    Open OBC Div. B 3.2.2.10. in the code viewer
  • OBC Div. B 3.2.2.54. Group C, up to 3 Storeys

    (1)A building classified as Group C, other than a retirement home, is permitted to conform to Sentence (2) provided

    (a)it is not more than 3 storeys in building height, and

    (b)it has a building area not more than the value in Table 3.2.2.54.

    (2)The building referred to in Sentence (1) is permitted to be of combustible construction or noncombustible construction used singly or in combination, and

    (a)except as permitted by Sentences (3) and (4), floor assemblies shall be fire separations with a fire-resistance rating not less than 45 min,

    (b)mezzanines shall have, if of combustible construction, a fire-resistance rating not less than 45 min, and

    (c)loadbearing walls, columns and arches shall have a fire-resistance rating not less than that required for the supported assembly.

    (3)In a building that contains dwelling units that have more than one storey, subject to the requirements of Sentence 3.3.4.2.(3), the floor assemblies, including floors over basements, that are entirely contained within these dwelling units, shall have a fire-resistance rating not less than 45 min but need not be constructed as fire separations.

    (4)In a building in which there is no dwelling unit above another dwelling unit, the fire-resistance rating for floor assemblies entirely within the dwelling unit is waived.

    Open OBC Div. B 3.2.2.54. in the code viewer
  • OBC Div. B Table 3.2.2.62. Maximum Building Area, Group D, up to 3 Storeys

    Table 3.2.2.62. Maximum Building Area, Group D, up to 3 Storeys Forming Part of Sentence 3.2.2.62.(1) No. of Storeys | Maximum area, m² — Facing 1 Street | Maximum area, m² — Facing 2 Streets | Maximum area, m² — Facing 3 Streets 1 | 4,800 | 6,000 | 7,200 2 | 2,400 | 3,000 | 3,600 3 | 1,600 | 2,000 | 2,400

    Open OBC Div. B Table 3.2.2.62. in the code viewer
  • OBC Div. B 3.2.2.62. Group D, up to 3 Storeys

    (1)A building classified as Group D is permitted to conform to Sentence (2) provided

    (a)it is not more than 3 storeys in building height, and

    (b)it has a building area not more than the value in Table 3.2.2.62.

    (2)The building referred to in Sentence (1) is permitted to be of combustible construction or noncombustible construction used singly or in combination, and

    (a)floor assemblies shall be fire separations and, if of combustible construction, shall have a fire-resistance rating not less than 45 min,

    (b)mezzanines shall have, if of combustible construction, a fire-resistance rating not less than 45 min,

    (c)roof assemblies shall have, if of combustible construction, a fire-resistance rating not less than 45 min, except that in a building not more than 1 storey in building height, the fire-resistance rating is permitted to be waived provided the roof assembly is constructed as a fire-retardant-treated wood roof system conforming to Article 3.1.14.1., and the building area is not more than

    (i)2,400 m² if facing one street,

    (ii)3,000 m² if facing 2 streets, or

    (iii)3,600 m² if facing 3 streets, and

    (d)loadbearing walls, columns and arches supporting an assembly required to have a fire-resistance rating shall

    (i)have a fire-resistance rating not less than 45 min, or

    (ii)be of noncombustible construction.

    Open OBC Div. B 3.2.2.62. in the code viewer