Skip to content

Plumbing - All Buildings study guidePlumbing and septic

Part 9 plumbing facilities and related Part 9 items

All of 9.31, plus factory-built buildings, pools, glass, exits and service rooms, penetrations, drainage, notching and drilling, roof drains, sealants, cottages, park model trailers and change of use. (The guide also lists 9.36.1.1, but 9.36 is Reserved in the 2024 Code.)

chapters in this guide
12 of 13
chapters in this guide
to read
5 min
to read
code articles cited
32
code articles cited

Last updated

Values this chapter turns on

minimum depth of a foundation sump pit
750 mm
minimum depth of a foundation sump pit
load a dwelling unit grab bar must resist
1.3 kN
load a dwelling unit grab bar must resist
min set temperature, electric storage water heater
60°C
min set temperature, electric storage water heater
min distance from a dry well to the foundation
5 m
min distance from a dry well to the foundation

Plumbing inspectors work in Part 9 buildings every day: houses, but also small apartment buildings, stacked townhouses, small offices and stores. This chapter gathers the Part 9 Articles a plumber or plumbing inspector touches: the plumbing facilities of Section 9.31., the fire separation rules a pipe has to respect, foundation drainage and sumps, how far you may notch or drill framing, and a few special building types. (The Ministry guide also lists 9.36.1.1., but Section 9.36. is Reserved in the 2024 Code, so we skip it.)

Plumbing facilities, water supply and hot water (9.31.)

Section 9.31. applies to plumbing inside dwelling units. Everywhere else in a Part 9 building, plumbing facilities, grab bars, floor drains and the finishes around urinals follow Part 3 Subsection 3.7.4., and barrier-free fixtures follow Section 3.8. (OBC Div. B 9.31.1.1.OBC Div. B 9.31.1.1. Application(1) This Section applies to the plumbing facilities and plumbing systems within dwelling units. (2) In occupancies other than dwelling units, plumbing facilities, grab bars, floor drains, and floor and wall finishes around urinals shall conform to Subsection 3.7.4. (See also Section 3.8. regarding barrier-free…). So a Part 9 restaurant counts its fixtures with the Part 3 tables, not with 9.31. Medical gas piping goes to 3.7.5. All plumbing work itself conforms to Part 7 (9.31.2.1.OBC Div. B 9.31.2.1. General(1) The construction, extension, alteration, renewal or repair of plumbing systems and sewage disposal systems shall conform to Part 7.).

Dwelling unit item Requirement Article
Fixtures (where a water distribution system is available) Kitchen sink, lavatory, bathtub or shower, water closet 9.31.4.1.OBC Div. B 9.31.4.1. Required Fixtures(1) A kitchen sink, lavatory, bathtub or shower, and water closet shall be provided for every dwelling unit where a water distribution system is available.
Laundry Facilities or space in each unit, or grouped elsewhere and conveniently accessible 9.31.4.1A.OBC Div. B 9.31.4.1A. Laundry Fixtures(1) Laundry facilities or a space for laundry facilities shall be provided in every dwelling unit or grouped elsewhere in the building in a location conveniently accessible to occupants of every dwelling unit.
Hot and cold water To kitchen sink, lavatory, bathtub, shower, slop sink and laundry area; cold only to the water closet 9.31.3.2.OBC Div. B 9.31.3.2. Required Connections(1) Where a water distribution system is available, piping for hot and cold water shall be connected to every kitchen sink, lavatory, bathtub, shower, slop sink and laundry area. (2) Piping for cold water shall be run to every water closet.
Floor drain In a basement of a dwelling unit where gravity drainage is possible 9.31.4.3.OBC Div. B 9.31.4.3. Floor Drains(1) Where gravity drainage to a sewer, drainage ditch or dry well is possible, a floor drain shall be installed in a basement forming part of a dwelling unit.
Grab bars, when provided Resist 1.3 kN vertically or horizontally 9.31.2.3.OBC Div. B 9.31.2.3. Grab Bars(1) When provided, grab bars shall be capable of resisting a load of not less than 1.3 kN applied vertically or horizontally.
Hot water temperature 45°C to 60°C delivered; electric storage heaters set at least 60°C 9.31.6.1A.OBC Div. B 9.31.6.1A. Hot Water Temperature(1) Where a hot water supply is required by Article 9.31.4.3., equipment shall be installed to provide to every dwelling unit an adequate supply of service hot water with a temperature range from 45°C to 60°C. (2) An electric storage-type service water heater shall have a minimum set storage temperature of 60°C.

Service water heaters conform to Part 7. In locations where the spectral response acceleration Sa(0.2) is greater than 0.55, they are secured against overturning (9.31.6.2.OBC Div. B 9.31.6.2. Equipment and Installation(1) Every service water heater and its installation shall conform to Part 7. (2) Reserved (3) Where the building is in a location where the spectral response acceleration, S_a(0.2) , is greater than 0.55, service water heaters shall be secured to the structure to resist overturning. (See Note A-9.31.6.2.(3))). Steel tanks need a corrosion-resistant lining such as glass, zinc or hydraulic cement, fuel-burning heaters connect to a chimney flue, and heating coils may not sit in a flue or a furnace combustion chamber. Metal pipe in contact with cinders gets a heavy coat of bitumen or similar protection (9.31.2.2.OBC Div. B 9.31.2.2. Corrosion Protection(1) Metal pipes in contact with cinders or other corrosive material shall be protected by a heavy coating of bitumen or other corrosion protection.).

Practice this topic

Penetrations of fire separations and fire blocks

This is where Part 9 apartment buildings differ from houses. Penetrations of a fire separation are sealed with a firestop tested to CAN/ULC-S115 with an F rating at least equal to the required rating, or tightly fitted or cast in place where the item is steel, ferrous, copper, concrete or masonry (9.10.9.6.OBC Div. B 9.10.9.6. General Requirements for Penetrations of Fire Separations(1) Except as required by Sentence (2) and Articles 9.10.9.7. and 9.10.9.8. and as permitted by Article 9.10.9.9., penetrations of a required fire separation or a membrane forming part of an assembly required to be a fire separation shall be (a) sealed by a firestop that, when subjected to the fire test method in…). A firewall penetration needs an FT rating.

For pipes, 9.10.9.7.OBC Div. B 9.10.9.7. Piping Penetrations(1) Except as provided in Sentences (2) and (5), piping for drain, waste, vent and central vacuum systems that is not located in a vertical shaft is permitted to penetrate a fire separation required to have a fire-resistance rating or a membrane that forms part of an assembly required to have a fire-resistance rating… adds:

  • DWV and central vacuum piping not in a vertical shaft may penetrate a rated fire separation or membrane if protected by a tested firestop or, for steel, copper, concrete or masonry pipe, a tight fit.
  • A combustible water closet drain through a concrete slab needs a tested firestop.
  • Combustible DWV piping may sit on one side of a vertical fire separation if it is not in a vertical shaft. On one side of a horizontal fire separation, this is allowed only in buildings with two dwelling units.
  • Combustible water distribution piping may penetrate if it is not in a vertical shaft and is sealed with a tested firestop.

Sprinkler piping may penetrate a fire separation where both sides are sprinklered (9.10.9.9.OBC Div. B 9.10.9.9. Penetrations by Raceways, Sprinklers and Fire Dampers(1) Combustible totally enclosed raceways that are embedded in a concrete floor slab are permitted in an assembly required to have a fire-resistance rating, provided the concrete cover between the raceway and the bottom of the slab is not less than 50 mm. (2) Totally enclosed raceways are permitted to penetrate a fire…). Where fire blocks are pierced by pipes, their effectiveness must be maintained around the pipe (9.10.16.4.OBC Div. B 9.10.16.4. Penetration of Fire Blocks(1) Where fire blocks are pierced by pipes, ducts or other elements, the effectiveness of the fire blocks shall be maintained around such elements.).

Exits are stricter. A fire separation around an exit may be pierced only by wiring, noncombustible conduit and noncombustible piping serving only the exit, plus standpipes, sprinkler piping, exit doors and permitted glass (9.9.4.2.(4)OBC Div. B 9.9.4.2. Fire Separation for Exits(1) Except as provided in Sentence (5) and Article 9.9.8.5., every exit other than an exit doorway shall be separated from each adjacent floor area or from another exit by a fire separation having a fire-resistance rating not less than that required for the floor assembly above the floor area. (2) Where there is no…). Washrooms and service rooms may not open directly into an exit (except in a house with a secondary suite), and a service room with a boiler over 100 kPa may not be under a required exit (9.9.5.8.OBC Div. B 9.9.5.8. Service Rooms(1) Service rooms containing equipment subject to possible explosion, such as boilers designed to operate at a pressure in excess of 100 kPa, and certain types of refrigerating and transformer equipment, shall not be located under required exits., 9.9.5.9.OBC Div. B 9.9.5.9. Ancillary Rooms(1) Except in houses with a secondary suite, ancillary rooms such as storage rooms, washrooms, toilet rooms, laundry rooms and service rooms shall not open directly into an exit.).

Practice this topic

Foundation and surface drainage

Foundation drain tile or pipe is at least 100 mm in diameter, laid with its top below the slab or crawl space ground cover, with butt joints open 6 mm to 10 mm and covered on top, and with at least 150 mm of clean crushed stone over the top and sides (9.14.3.2.OBC Div. B 9.14.3.2. Minimum Size(1) Drain tile or pipe used for foundation drainage shall be not less than 100 mm in diam., 9.14.3.3.OBC Div. B 9.14.3.3. Installation(1) Drain tile or pipe shall be laid on undisturbed or well-compacted soil so that the top of the tile or pipe is below the bottom of the floor slab or the ground cover of the crawl space. (2) Drain tile or pipe with but joints shall be laid with 6 mm to 10 mm open joints. (3) The top half of joints referred to in…). Foundation drains discharge to a sewer, drainage ditch or dry well (9.14.5.1.OBC Div. B 9.14.5.1. Drainage Disposal(1) Foundation drains shall drain to a sewer, drainage ditch or dry well.).

Item Minimum
Sump pit depth 750 mm
Sump pit area 0.25 m²
Sump cover Childproof and airtight
Dry well distance from foundation 5 m, and only where groundwater is below its bottom

Where gravity drainage is not practical, an automatic sump pump is required (9.14.5.2.OBC Div. B 9.14.5.2. Sump Pits(1) Where a sump pit is provided it shall be (a) not less than 750 mm deep, (b) not less than 0.25 m² in area, and (c) provided with a cover. (2) Covers for sump pits shall be designed (a) to resist removal by children, and (b) to be airtight in accordance with Sentence 9.25.3.3.(7) (3) Where gravity drainage is not…). Surface drainage is directed away from a water supply well or leaching bed, and a catch basin is installed where driveway runoff could collect or enter a garage (9.14.6.4.OBC Div. B 9.14.6.4. Catch Basin(1) Where runoff water from a driveway is likely to accumulate or enter a garage, a catch basin shall be installed to provide adequate drainage.).

Practice this topic

Notching, drilling, roof drains and sealants

Plumbers cut framing, so these numbers are tested with arithmetic (9.23.5.1. to 9.23.5.5.OBC Div. B 9.23.5.1. Holes Drilled in Framing Members(1) Holes drilled in roof, floor or ceiling framing members shall be not larger than one-quarter the depth of the member and shall be located not less than 50 mm from the edges, unless the depth of the member is increased by the size of the hole.).

Member Limit
Joist or rafter hole Not over 1/4 of member depth, at least 50 mm from edges
Joist notch On top, within half the depth from the bearing, not over 1/3 of the depth
Loadbearing stud Keep at least 2/3 of the depth undamaged
Non-loadbearing stud Keep at least 40 mm undamaged
Top plate Keep at least 50 mm of width undamaged
Roof truss No cuts unless the truss design allows them

Roof drains, when provided, conform to Part 7 (9.26.18.1.OBC Div. B 9.26.18.1. Roof Drains(1) When roof drains are provided they shall conform to Part 7.). Sealants are non-hardening exterior types that resist weathering and adhere to the substrate (9.27.4.2.OBC Div. B 9.27.4.2. Materials(1) Sealants shall be (a) non-hardening type suitable for exterior use, (b) selected for their ability to resist the effects of weathering, and (c) compatible with and adhere to the substrate to which they are applied. (See Note A-9.27.4.2.(1)) (2) Sealants shall conform to (a) ASTM C834, "Standard Specification for…).

Practice this topic

  • Glass in shower or bathtub enclosures must be Class A safety glazing under CAN/CGSB-12.1 (9.6.1.4.(6)OBC Div. B 9.6.1.4. Types of Glass and Protection of Glass(1) Glass sidelights greater than 500 mm wide that could be mistaken for doors, glass in storm doors and glass in sliding doors within or at every entrance to a dwelling unit and in public areas shall be (a) safety glazing of the tempered or laminated type conforming to CAN/CGSB-12.1, "Safety Glazing," or (b) wired…).
  • Factory-built buildings certified under CSA A277, or CSA Z240.2.1 for sections not wider than 4.88 m, are deemed to comply, but site work is under the Code (9.1.1.9.OBC Div. B 9.1.1.9. Site Assembled and Factory-Built Buildings(1) Except as provided in Sentence (2) and in Sentence 12.2.1.2.(2), a manufactured building is deemed to comply with this Code if it is designed and constructed in compliance with, (a) CSA Z240.2.1, "Structural requirements for manufactured homes," if the building is constructed in sections not wider than 4.88 m, or…).
  • Public pools and spas in Part 9 buildings follow Sections 3.11. and 3.12. (9.1.1.10.OBC Div. B 9.1.1.10. Public Pools and Public Spas(1) Public pools shall conform to the requirements of Section 3.11. and public spas shall conform to the requirements of Section 3.12.).
  • Seasonal recreational buildings need not have plumbing, but any plumbing provided must comply (9.37.2.1.(3)OBC Div. B 9.37.2.1. Exclusions(1) Except as provided in Subsection 9.10.15. and Articles 9.37.2.4. and 9.37.3.1., buildings used or intended to be used as seasonal recreational buildings need not comply with Sections 9.5. to 9.7. and 9.9. to 9.11. (2) Flooring need not comply with Section 9.30., but tight-fitting floors shall be provided to…).
  • Park model trailers built to CAN/CSA-Z241 are deemed to comply, though site-built components do not get the exemption (9.39.2.1.OBC Div. B 9.39.2.1. General(1) Except as provided in Subsection 9.39.3., a manufactured building used or intended to be used as a seasonal recreational building of residential occupancy is deemed to comply with this Code if it is designed and constructed in conformance with CAN/CSA-Z241 Series, "Park model trailers.", 9.39.3.1.OBC Div. B 9.39.3.1. Other Building Components(1) The requirements of this Code shall apply to building components designed and constructed outside the place of manufacture of a building described in Article 9.39.1.1.).
  • A change of use under Section 9.41. brings in, among others, Section 9.31. for the new major occupancy (9.41.2.1.OBC Div. B 9.41.2.1. Change of Use and Compensating Construction(1) Where proposed construction will result in a change of use described in Clauses 9.40.1.1.(1)(a) to (f), additional construction shall be required in order that the building or part of a building subject to the change of use conforms to the requirements of Subsections 9.5.1. and 9.5.3. to 9.5.10., Section 9.6.…).

Practice this topic

Common traps

  • Using 9.31. to count fixtures in a Part 9 store. Non-dwelling plumbing facilities are under 3.7.4.
  • Allowing combustible DWV on one side of a horizontal fire separation in a fourplex. That relief is only for two dwelling units.
  • Measuring a stud cut as the amount removed. The rule states what must remain.

Chapter review

Chapter at a glance

One line per section: the idea to carry into the exam. Then the answers that most often catch candidates out.

Usual exam traps

  • Using 9.31. to count fixtures in a Part 9 store. Non-dwelling plumbing facilities are under 3.7.4.
  • Allowing combustible DWV on one side of a horizontal fire separation in a fourplex. That relief is only for two dwelling units.
  • Measuring a stud cut as the amount removed. The rule states what must remain.

Practice this chapter

Questions on Part 9 plumbing facilities and related Part 9 items, in the exam format, every answer explained and cited to its article. Sign in to start; a free account gets the free questions.

Code cited in this chapter

Based on the official 2024 Building Code Compendium on ontario.ca.

© King's Printer for Ontario, 2024. Reproduced with permission.

  • OBC Div. B 9.31.1.1. Application

    (1)This Section applies to the plumbing facilities and plumbing systems within dwelling units.

    (2)In occupancies other than dwelling units, plumbing facilities, grab bars, floor drains, and floor and wall finishes around urinals shall conform to Subsection 3.7.4. (See also Section 3.8. regarding barrier-free plumbing facilities.)

    (3)Medical gas piping systems shall conform to Subsection 3.7.5.

    Open OBC Div. B 9.31.1.1. in the code viewer
  • OBC Div. B 9.31.2.1. General

    (1)The construction, extension, alteration, renewal or repair of plumbing systems and sewage disposal systems shall conform to Part 7.

    Open OBC Div. B 9.31.2.1. in the code viewer
  • OBC Div. B 9.31.4.1. Required Fixtures

    (1)A kitchen sink, lavatory, bathtub or shower, and water closet shall be provided for every dwelling unit where a water distribution system is available.

    Open OBC Div. B 9.31.4.1. in the code viewer
  • OBC Div. B 9.31.4.1A. Laundry Fixtures

    (1)Laundry facilities or a space for laundry facilities shall be provided in every dwelling unit or grouped elsewhere in the building in a location conveniently accessible to occupants of every dwelling unit.

    Open OBC Div. B 9.31.4.1A. in the code viewer
  • OBC Div. B 9.31.3.2. Required Connections

    (1)Where a water distribution system is available, piping for hot and cold water shall be connected to every kitchen sink, lavatory, bathtub, shower, slop sink and laundry area.

    (2)Piping for cold water shall be run to every water closet.

    Open OBC Div. B 9.31.3.2. in the code viewer
  • OBC Div. B 9.31.4.3. Floor Drains

    (1)Where gravity drainage to a sewer, drainage ditch or dry well is possible, a floor drain shall be installed in a basement forming part of a dwelling unit.

    Open OBC Div. B 9.31.4.3. in the code viewer
  • OBC Div. B 9.31.2.3. Grab Bars

    (1)When provided, grab bars shall be capable of resisting a load of not less than 1.3 kN applied vertically or horizontally.

    Open OBC Div. B 9.31.2.3. in the code viewer
  • OBC Div. B 9.31.6.1A. Hot Water Temperature

    (1)Where a hot water supply is required by Article 9.31.4.3., equipment shall be installed to provide to every dwelling unit an adequate supply of service hot water with a temperature range from 45°C to 60°C.

    (2)An electric storage-type service water heater shall have a minimum set storage temperature of 60°C.

    Open OBC Div. B 9.31.6.1A. in the code viewer
Show all 32 articles
  • OBC Div. B 9.31.6.2. Equipment and Installation

    (1)Every service water heater and its installation shall conform to Part 7.

    (2)Reserved

    (3)Where the building is in a location where the spectral response acceleration, S_a(0.2) , is greater than 0.55, service water heaters shall be secured to the structure to resist overturning. (See Note A-9.31.6.2.(3))

    Open OBC Div. B 9.31.6.2. in the code viewer
  • OBC Div. B 9.31.2.2. Corrosion Protection

    (1)Metal pipes in contact with cinders or other corrosive material shall be protected by a heavy coating of bitumen or other corrosion protection.

    Open OBC Div. B 9.31.2.2. in the code viewer
  • OBC Div. B 9.10.9.6. General Requirements for Penetrations of Fire Separations

    (1)Except as required by Sentence (2) and Articles 9.10.9.7. and 9.10.9.8. and as permitted by Article 9.10.9.9., penetrations of a required fire separation or a membrane forming part of an assembly required to be a fire separation shall be

    (a)sealed by a firestop that, when subjected to the fire test method in CAN/ULC-S115, "Standard Method of Fire Tests of Firestop Systems," has an F rating not less than the required fire-resistance rating for the fire separation,

    (b)tightly fitted or cast in place, provided the penetrating item is made of steel, ferrous, copper, concrete or masonry, or

    (c)sealed to maintain the integrity of the fire separation. (See Note A-9.10.9.6.(1))

    (2)Penetrations of a firewall shall be sealed at the penetration by a firestop that, when subjected to the fire test method in "CAN/ULC-S115, "Standard Method of Fire Tests of Firestop Systems," has an FT rating not less than the fire-resistance rating for the fire separation.

    Open OBC Div. B 9.10.9.6. in the code viewer
  • OBC Div. B 9.10.9.7. Piping Penetrations

    (1)Except as provided in Sentences (2) and (5), piping for drain, waste, vent and central vacuum systems that is not located in a vertical shaft is permitted to penetrate a fire separation required to have a fire-resistance rating or a membrane that forms part of an assembly required to have a fire-resistance rating, provided the penetration is protected in accordance with Clause 9.10.9.6.(1)(a) or (b).

    (2)Drain piping leading directly from a water closet through a concrete floor slab is permitted to penetrate a horizontal fire separation or a membrane that contributes to the required fire-resistance rating of a horizontal fire separation, provided

    (a)the piping is noncombustible and the penetration is protected in accordance with Sentence 9.10.9.6.(1), or

    (b)the piping is combustible and the penetration is sealed by a firestop conforming to Clause 9.10.9.6.(1)(a).

    (3)Combustibledrain, waste and vent piping is permitted on one side of a vertical fire separation, provided it is not located in a vertical shaft.

    (4)In buildings containing two dwelling units only, combustible drain, waste and vent piping is permitted on one side of a horizontal fire separation.

    (5)Water distribution piping is permitted to partly or wholly penetrate a fire separation required to have a fire-resistance rating, provided

    (a)the piping is noncombustible and the penetration is protected in accordance with Sentence 9.10.9.6.(1), or

    (b)the piping is combustible and is not located in a vertical shaft, and the penetration is sealed by a firestop conforming to Clause 9.10.9.6.(1)(a).

    Open OBC Div. B 9.10.9.7. in the code viewer
  • OBC Div. B 9.10.9.9. Penetrations by Raceways, Sprinklers and Fire Dampers

    (1)Combustible totally enclosed raceways that are embedded in a concrete floor slab are permitted in an assembly required to have a fire-resistance rating, provided the concrete cover between the raceway and the bottom of the slab is not less than 50 mm.

    (2)Totally enclosed raceways are permitted to penetrate a fire separation, provided they are sealed at the penetration by a firestop conforming to Clause 9.10.9.6.(1)(a).

    (3)Sprinkler piping is permitted to penetrate a fire separation, provided the fire compartments on each side of the fire separation are sprinklered.

    (4)Sprinklers are permitted to penetrate a fire separation or a membrane forming part of an assembly required to have a fire-resistance rating without having to meet the firestop requirements of Article 9.10.9.6. and Clause 9.10.9.8.(6)(a), provided the annular space created by the penetration of a fire sprinkler is covered by a metal escutcheon plate in accordance with NFPA 13, "Standard for the Installation of Sprinkler Systems."

    (5)Fire dampers are permitted to penetrate a fire separation or a membrane forming part of an assembly required to have a fire-resistance rating without having to meet the firestop requirements of Sentence 9.10.9.6.(1), provided the fire damper is

    (a)installed in conformance with NFPA 80, "Standard for Fire Doors and Other Opening Protectives,"

    (b)specifically designed with a firestop, or

    (c)provided in conformance with Sentence 9.10.5.1.(3). (See also Note A-3.1.9.2.(1).)

    Open OBC Div. B 9.10.9.9. in the code viewer
  • OBC Div. B 9.10.16.4. Penetration of Fire Blocks

    (1)Where fire blocks are pierced by pipes, ducts or other elements, the effectiveness of the fire blocks shall be maintained around such elements.

    Open OBC Div. B 9.10.16.4. in the code viewer
  • OBC Div. B 9.9.4.2. Fire Separation for Exits

    (1)Except as provided in Sentence (5) and Article 9.9.8.5., every exit other than an exit doorway shall be separated from each adjacent floor area or from another exit by a fire separation having a fire-resistance rating not less than that required for the floor assembly above the floor area.

    (2)Where there is no floor assembly above, the fire-resistance rating required in Sentence (1) shall not be less than that required by Subsection 9.10.8. for the floor assembly below, but in no case shall the fire-resistance rating be less than 45 min.

    (3)A fire separation common to 2 exits shall be smoke-tight and not be pierced by doorways, duct work, piping or any other opening that may affect the continuity of the separation.

    (4)A fire separation that separates an exit from the remainder of the building shall have no openings except those for electrical wiring, noncombustible conduit and noncombustible piping that serve only the exit, and for standpipes, sprinkler piping, exit doorways and wired glass and glass block permitted in Article 9.9.4.3.

    (5)The requirements in Sentence (1) do not apply to an exterior exit passageway provided the passageway has at least 50% of its exterior sides open to the outdoors and is served by an exit stair at each end of the passageway.

    Open OBC Div. B 9.9.4.2. in the code viewer
  • OBC Div. B 9.9.5.8. Service Rooms

    (1)Service rooms containing equipment subject to possible explosion, such as boilers designed to operate at a pressure in excess of 100 kPa, and certain types of refrigerating and transformer equipment, shall not be located under required exits.

    Open OBC Div. B 9.9.5.8. in the code viewer
  • OBC Div. B 9.9.5.9. Ancillary Rooms

    (1)Except in houses with a secondary suite, ancillary rooms such as storage rooms, washrooms, toilet rooms, laundry rooms and service rooms shall not open directly into an exit.

    Open OBC Div. B 9.9.5.9. in the code viewer
  • OBC Div. B 9.14.3.2. Minimum Size

    (1)Drain tile or pipe used for foundation drainage shall be not less than 100 mm in diam.

    Open OBC Div. B 9.14.3.2. in the code viewer
  • OBC Div. B 9.14.3.3. Installation

    (1)Drain tile or pipe shall be laid on undisturbed or well-compacted soil so that the top of the tile or pipe is below the bottom of the floor slab or the ground cover of the crawl space.

    (2)Drain tile or pipe with but joints shall be laid with 6 mm to 10 mm open joints.

    (3)The top half of joints referred to in Sentence (2) shall be covered with sheathing paper, 0.10 mm polyethylene or No. 15 asphalt or tar-saturated felt.

    (4)The top and sides of drain pipe or tile shall be covered with not less than 150 mm of crushed stone or other coarse clean granular material containing not more than 10% of material that will pass a 4 mm sieve.

    Open OBC Div. B 9.14.3.3. in the code viewer
  • OBC Div. B 9.14.5.1. Drainage Disposal

    (1)Foundation drains shall drain to a sewer, drainage ditch or dry well.

    Open OBC Div. B 9.14.5.1. in the code viewer
  • OBC Div. B 9.14.5.2. Sump Pits

    (1)Where a sump pit is provided it shall be

    (a)not less than 750 mm deep,

    (b)not less than 0.25 m² in area, and

    (c)provided with a cover.

    (2)Covers for sump pits shall be designed

    (a)to resist removal by children, and

    (b)to be airtight in accordance with Sentence 9.25.3.3.(7)

    (3)Where gravity drainage is not practical, an automatic sump pump shall be provided to discharge the water from the sump pit described in Sentence (1) into a sewer, drainage ditch or dry well.

    Open OBC Div. B 9.14.5.2. in the code viewer
  • OBC Div. B 9.14.6.4. Catch Basin

    (1)Where runoff water from a driveway is likely to accumulate or enter a garage, a catch basin shall be installed to provide adequate drainage.

    Open OBC Div. B 9.14.6.4. in the code viewer
  • OBC Div. B 9.23.5.1. Holes Drilled in Framing Members

    (1)Holes drilled in roof, floor or ceiling framing members shall be not larger than one-quarter the depth of the member and shall be located not less than 50 mm from the edges, unless the depth of the member is increased by the size of the hole.

    Open OBC Div. B 9.23.5.1. in the code viewer
  • OBC Div. B 9.26.18.1. Roof Drains

    (1)When roof drains are provided they shall conform to Part 7.

    Open OBC Div. B 9.26.18.1. in the code viewer
  • OBC Div. B 9.27.4.2. Materials

    (1)Sealants shall be

    (a)non-hardening type suitable for exterior use,

    (b)selected for their ability to resist the effects of weathering, and

    (c)compatible with and adhere to the substrate to which they are applied.

    (See Note A-9.27.4.2.(1))

    (2)Sealants shall conform to

    (a)ASTM C834, "Standard Specification for Latex Sealants,"

    (b)ASTM C920, "Standard Specification for Elastomeric Joint Sealants,"

    (c)ASTM C1184, "Standard Specification for Structural Silicone Sealants," or

    (d)ASTM C1311, "Standard Specification for Solvent Release Sealants."

    (3)Backer rod shall conform to ASTM C1330, "Standard Specification for Cylindrical Sealant Backing for Use with Cold Liquid-Applied Sealants." (See Note A-9.27.4.2.(1))

    Open OBC Div. B 9.27.4.2. in the code viewer
  • OBC Div. B 9.6.1.4. Types of Glass and Protection of Glass

    (1)Glass sidelights greater than 500 mm wide that could be mistaken for doors, glass in storm doors and glass in sliding doors within or at every entrance to a dwelling unit and in public areas shall be

    (a)safety glazing of the tempered or laminated type conforming to CAN/CGSB-12.1, "Safety Glazing," or

    (b)wired glass conforming to CAN/CGSB-12.11-M, "Wired Safety Glass."

    (2)Except as provided in Sentence (4), glass in entrance doors to dwelling units and in public areas, other than the entrance doors described in Sentence (1), shall be safety glazing or wired glass of the type described in Sentence (1) where the glass area exceeds 0.5m^2 and extends to less than 900 mm from the bottom of the door.

    (3)Except as provided in Sentence (4), transparent panels that could be mistaken as a means of egress shall be protected by barriers or railings.

    (4)Sliding glass partitions that separate a public corridor from an adjacent occupancy and that are open during normal working hours need not conform to Sentences (2), (3) and (5), except that such partitions shall be suitably marked to indicate their existence and position.

    (5)Except as provided in Sentence (4), every glass or transparent door accessible to the public shall be equipped with hardware, bars or other permanent fixtures designed so that the existence and position of such doors is readily apparent.

    (6)Glazing used for a shower or bathtub enclosure shall conform to Class A of CAN/CGSB-12.1, "Safety Glazing."

    Open OBC Div. B 9.6.1.4. in the code viewer
  • OBC Div. B 9.1.1.9. Site Assembled and Factory-Built Buildings

    (1)Except as provided in Sentence (2) and in Sentence 12.2.1.2.(2), a manufactured building is deemed to comply with this Code if it is designed and constructed in compliance with,

    (a)CSA Z240.2.1, "Structural requirements for manufactured homes," if the building is constructed in sections not wider than 4.88 m, or

    (b)CSA A277, "Procedure for certification of prefabricated buildings, modules, and panels."

    (2)The requirements of this Code shall apply to,

    (a)building components designed and constructed outside the place of manufacture, and

    (b)site installation of such buildings.

    Open OBC Div. B 9.1.1.9. in the code viewer
  • OBC Div. B 9.1.1.10. Public Pools and Public Spas

    (1)Public pools shall conform to the requirements of Section 3.11. and public spas shall conform to the requirements of Section 3.12.

    Open OBC Div. B 9.1.1.10. in the code viewer
  • OBC Div. B 9.37.2.1. Exclusions

    (1)Except as provided in Subsection 9.10.15. and Articles 9.37.2.4. and 9.37.3.1., buildings used or intended to be used as seasonal recreational buildings need not comply with Sections 9.5. to 9.7. and 9.9. to 9.11.

    (2)Flooring need not comply with Section 9.30., but tight-fitting floors shall be provided to support the live and dead loads.

    (3)Except as provided in Sentence (4), thermal insulation, vapour barrier, air barrier construction, interior finishes, plumbing, heating, mechanical ventilation, air-conditioning and electrical facilities, need not be provided, but where any of these are provided, they shall comply with the requirements of this Part.

    (4)Where heating and air-conditioning are provided, Article 9.33.3.1. need not be complied with.

    Open OBC Div. B 9.37.2.1. in the code viewer
  • OBC Div. B 9.39.2.1. General

    (1)Except as provided in Subsection 9.39.3., a manufactured building used or intended to be used as a seasonal recreational building of residential occupancy is deemed to comply with this Code if it is designed and constructed in conformance with CAN/CSA-Z241 Series, "Park model trailers."

    Open OBC Div. B 9.39.2.1. in the code viewer
  • OBC Div. B 9.39.3.1. Other Building Components

    (1)The requirements of this Code shall apply to building components designed and constructed outside the place of manufacture of a building described in Article 9.39.1.1.

    Open OBC Div. B 9.39.3.1. in the code viewer
  • OBC Div. B 9.41.2.1. Change of Use and Compensating Construction

    (1)Where proposed construction will result in a change of use described in Clauses 9.40.1.1.(1)(a) to (f), additional construction shall be required in order that the building or part of a building subject to the change of use conforms to the requirements of Subsections 9.5.1. and 9.5.3. to 9.5.10., Section 9.6., Article 9.7.2.3. Sentences 9.7.5.1.(2) and 9.7.6.2.(1) and (3), Articles 9.8.8.1. and 9.9.10.1., Subsection 9.10.17. and Sections 9.31., 9.32. and 9.34. as they apply to the new major occupancy that the building or part of a building is to support.

    (2)For the purposes of this Article, existing buildings shall be classified as to their construction and occupancy as provided for in Sentence 11.2.1.1.(1).

    Open OBC Div. B 9.41.2.1. in the code viewer