Fire alarm and detection systems

All of 3.2.4: when a fire alarm is required, single and two stage systems, zoning and annunciators, electrical supervision, detectors, smoke alarms, residential warning systems, signals, audibility, visible signals and voice communication.

chapters in this guide
4 of 13
chapters in this guide
to read
7 min
to read
code articles cited
19
code articles cited

Last updated

Values this chapter turns on

total occupant load that triggers a fire alarm
300 persons
total occupant load that triggers a fire alarm
max annunciator zone, unsprinklered building
2,000 m²
max annunciator zone, unsprinklered building
min alarm level in a residential sleeping room
75 dBA
min alarm level in a residential sleeping room
occupant load needing one-way voice, 2-stage
1,000 persons
occupant load needing one-way voice, 2-stage

Subsection 3.2.4. is the core of this exam: when a fire alarm is required, its type, zoning, supervision, detectors, signals, smoke alarms and voice communication. Installation follows CAN/ULC-S524 and verification follows CAN/ULC-S537 OBC Div. B 3.2.4.5.OBC Div. B 3.2.4.5. Installation and Verification of Fire Alarm Systems(1) Fire alarm systems, including those with voice communication capability where provided, shall be installed in conformance with CAN/ULC-S524, "Standard for Installation of Fire Alarm Systems." (2) Fire alarm systems shall be verified in conformance with CAN/ULC-S537, "Verification of Fire Alarm Systems," to ensure…. The exam asks when the Code calls for those standards, not what they contain.

When a fire alarm system is required and system types

Sprinklered buildings need a fire alarm system. The exceptions are NFPA 13D systems and buildings with fewer than 9 sprinklers fed under 3.2.5.12.(4) OBC Div. B 3.2.4.1.(1) to (3)OBC Div. B 3.2.4.1. Determination of Requirement for a Fire Alarm System(1) Except as permitted in Sentences (2) and (3), a fire alarm system shall be installed in buildings in which an automatic sprinkler system is installed. (2) Buildings in which a sprinkler system is installed in accordance with NFPA 13D, "Standard for the Installation of Sprinkler Systems in One- and Two-Family….

Buildings not sprinklered throughout need one if they contain any of the following OBC Div. B 3.2.4.1.(4)OBC Div. B 3.2.4.1. Determination of Requirement for a Fire Alarm System(1) Except as permitted in Sentences (2) and (3), a fire alarm system shall be installed in buildings in which an automatic sprinkler system is installed. (2) Buildings in which a sprinkler system is installed in accordance with NFPA 13D, "Standard for the Installation of Sprinkler Systems in One- and Two-Family…:

Trigger Threshold
Contained use area or impeded egress zone Any
Storeys (including storeys below the first storey) More than 3
Total occupant load More than 300
Occupant load above or below the first storey More than 150
School, college or child care facility More than 40
Licensed beverage establishment or licensed restaurant More than 150
Low- or medium-hazard industrial, above or below the first storey More than 75
High-hazard industrial More than 25
Residential sleeping accommodation More than 10 persons
Care, or care and treatment, occupancy More than 10 persons receiving care or treatment

Exemptions:

  • a hotel of 3 storeys or less where each suite has direct access to an exterior exit facility,
  • an unsprinklered residential occupancy where not more than 4 suites share a common means of egress, or each suite has direct exterior access,
  • an open-air storage garage with no other occupancy.

Continuity OBC Div. B 3.2.4.2.OBC Div. B 3.2.4.2. Continuity of Fire Alarm System(1) Except as permitted by Sentence (6), if there are openings through a firewall, other than those for piping, tubing, wiring and totally enclosed noncombustible raceways, the requirements in this Subsection shall apply to the floor areas on both sides of the firewall as if they were in the same building. (2) Except…:

  • One system serves all occupancies, throughout the building.
  • Openings through a firewall (other than for piping, tubing, wiring and enclosed noncombustible raceways) join both sides into one system.
  • A portion of 3 storeys or less, cut off by a 1 h vertical separation with no such openings, may be treated as a separate building. This does not apply to service rooms and storage rooms.

Type OBC Div. B 3.2.4.3.OBC Div. B 3.2.4.3. Types of Fire Alarm Systems(1) A fire alarm system shall be (a) a single-stage system in a Group F, Division 1 occupancy, (b) except as permitted in Clause (c), a 2-stage system in a Group B occupancy, (c) a single- or 2-stage system in a Group B, Division 3 occupancy where the building is 3 storeys or less in building height, (d) a…:

  • single-stage in Group F, Division 1 and in elementary and secondary schools (except special needs facilities),
  • 2-stage in Group B (single- or 2-stage allowed in Group B, Division 3 buildings of 3 storeys or less),
  • either type everywhere else.

A single-stage system sounds the alarm signal everywhere. A 2-stage system first sounds an alert signal, and the alarm sounds automatically if nobody acknowledges the alert within 5 min (except in Group B, Division 2). Its manual stations take a key for direct alarm. In a building containing a hotel, the system sounds the alarm in the zone where it started and an alert elsewhere OBC Div. B 3.2.4.4.OBC Div. B 3.2.4.4. Description of Fire Alarm Systems(1) A single-stage fire alarm system shall, upon the operation of any manual station, waterflow detecting device, or fire detector, cause an alarm signal to sound on all audible signal devices in the system. (See Note A-3.2.4.4.(1)) (2) A 2-stage fire alarm system shall (a) cause an alert signal to sound upon the….

Worked example

An unsprinklered 2-storey building has a day care for 45 children and staff on the first storey and offices with 120 people on the second storey. The total is 165.

  • Total 165 is not over 300. The 120 above the first storey is not over 150.
  • But the child care facility has more than 40 occupants, so a fire alarm is required.
  • Type: either is allowed. One system serves both occupancies throughout.

Practice this topic

Annunciators, zones and electrical supervision

An annunciator goes near a building entrance facing a street or a fire department access route OBC Div. B 3.2.4.8.OBC Div. B 3.2.4.8. Annunciator and Zone Indication(1) Except as permitted by Sentences (3) to (5), an annunciator shall be installed in close proximity to a building entrance that faces a street or an access route for fire department vehicles that complies with Sentence 3.2.5.5.(1). (2) Except as permitted by Sentence (6), the annunciator required by Sentence (1)…. It needs separate zones for:

  • each floor area, at not more than 2,000 m² per zone if unsprinklered, or one storey and the NFPA 13 system area limit if sprinklered,
  • shafts and air-handling systems required to have detectors,
  • NFPA 96 extinguishing systems,
  • contained use areas, impeded egress zones, and certain fire compartments.

The annunciator is waived for an unsprinklered building of not more than 2,000 m² aggregate area and not more than 3 storeys. A visible and audible trouble signal device then goes inside the main entrance. A control unit at the entrance with all the indicators counts as the annunciator. Arenas, rinks and pools may exceed the 2,000 m² zone limit for the open space.

Every fire alarm system is electrically supervised OBC Div. B 3.2.4.9.OBC Div. B 3.2.4.9. Electrical Supervision(1) Electrical supervision shall be provided for a fire alarm system. (2) If a fire alarm system in a building is required to have an annunciator by Sentence 3.2.4.8.(1), except for hose valves, all valves controlling water supplies in a standpipe system, shall be equipped with an electrically supervised switch for…. Sprinkler systems must show supervisory signals for:

  • valve movement,
  • loss of wet-pipe excess pressure, dry-pipe air pressure or pressure-tank air pressure,
  • a change in water storage level,
  • loss of power to an automatic fire pump,
  • near-freezing temperature in dry pipe valve enclosures or water tanks.

Loss of power to heat tracing on standpipe risers, sprinkler lines or exits kept free of ice is also supervised. Signals go to the fire department through a CAN/ULC-S561 connection OBC Div. B 3.2.4.7.OBC Div. B 3.2.4.7. Signals to Fire Department(1) A single-stage fire alarm system shall be designed to notify the fire department in conformance with Sentence (4) that an alarm signal has been initiated in (a) a building of a Group A occupancy having an occupant load more than 300, or (b) a retirement home. (2) A fire alarm system that includes waterflow….

Automatic silencing of an alarm signal is not allowed before 5 min in a building not required to have an annunciator, or 20 min in any other building. Manual silencing switches are allowed only inside the control unit (with stated exceptions) OBC Div. B 3.2.4.6.OBC Div. B 3.2.4.6. Silencing of Alarm Signals(1) Except as permitted by Sentence (3), a fire alarm system shall be designed so that when an alarm signal is actuated, it cannot be silenced automatically before a period of time has elapsed that is not less than (a) 5 min for a building not required to be equipped with an annunciator, and (b) 20 min for any other….

Practice this topic

Heat and smoke detectors

In an unsprinklered building with a required fire alarm, fire detectors go in OBC Div. B 3.2.4.10.OBC Div. B 3.2.4.10. Fire Detectors(1) Fire detectors required by this Code shall be connected to the fire alarm system. (2) Except as permitted by Sentence (3), if a fire alarm system is required in a building that is not sprinklered, fire detectors shall be installed in the following spaces: (a) storage rooms not within dwelling units, (b) service…:

  • storage rooms and service rooms not within dwelling units,
  • janitors' rooms,
  • rooms for hazardous substances,
  • elevator hoistways and dumbwaiter shafts (unless sprinklered),
  • residential laundry rooms outside dwelling units,
  • hazardous classrooms and change rooms in schools.

Wherever a fire alarm is installed, smoke detectors go in OBC Div. B 3.2.4.11.OBC Div. B 3.2.4.11. Smoke and Heat Detectors(1) If a fire alarm system is installed, smoke detectors shall be installed in (a) each sleeping room and each corridor serving as part of a means of egress from sleeping rooms in portions of a building classified as Group B major occupancy, (b) each room in a contained use area and corridors serving those rooms, (c)…:

  • Group B sleeping rooms and the corridors serving them,
  • contained use area rooms,
  • Group A, Division 1 corridors,
  • Group C public corridors,
  • exit stair shafts (except those serving only Group A, Division 4 or an open storage garage),
  • near draft stops,
  • elevator machine rooms (these recall the elevators they serve),
  • school classroom corridors.

Unsprinklered hotel floor areas get heat detectors in every room except washrooms in suites, saunas, refrigerated areas and pools.

A duct-type smoke detector must stop smoke circulation in any air-handling system serving more than one storey, more than one suite on a storey, or more than one required fire compartment, or lacking fire dampers under 3.1.8.8.(4) OBC Div. B 3.2.4.12.OBC Div. B 3.2.4.12. Prevention of Smoke Circulation(1) If a fire alarm system is installed, an air-handling system shall be designed to prevent the circulation of smoke upon a signal from a duct-type smoke detector if the air handling system (a) serves more than one storey, (b) serves more than one suite in a storey, (c) serves more than one fire compartment required….

Practice this topic

Manual stations, alert and alarm signals, audibility and visible signals

Manual stations go in every floor area near each principal entrance and each exit, plus the main reception area of a hotel OBC Div. B 3.2.4.16.OBC Div. B 3.2.4.16. Manual Stations(1) Except as permitted by Sentences (2) and (3), where a fire alarm system is installed, a manual station shall be installed in every floor area near (a) every principal entrance to the building, and (b) every exit. (See Note A-3.2.4.16.(1)) (2) In a building that is sprinklered throughout, a manual station is not….

Audibility OBC Div. B 3.2.4.18.OBC Div. B 3.2.4.18. Audibility of Alarm Systems(1) Except as permitted by Sentence 3.2.4.19.(2) and except as required by Clause 3.2.4.4.(2)(d), audible signal devices forming part of a fire alarm system shall be installed in a building so that (a) alarm signals are clearly audible throughout the floor area, and (b) alert signals are clearly audible in…:

Item Value
Alarm pattern Temporal pattern of ISO 8201
General floor area At least 10 dBA above ambient and at least 65 dBA
Residential sleeping room, doors closed At least 75 dBA, low frequency signal
Upper limit Not more than 110 dBA at 3 m (or 100 dBA at 2,000 mm above the floor)
In-suite manual silence Not more than 10 min

Visible signals are added where ambient noise exceeds 87 dBA, where performance sound may exceed 100 dBA, in public corridors of Group A to E, in at least 10% of hotel or motel suites, and in other listed places OBC Div. B 3.2.4.19.OBC Div. B 3.2.4.19. Visible Signals(1) Except as permitted by Sentence (4), where a fire alarm system is installed, visible signal devices shall be installed in addition to alarm signal devices (a) in a building or portions thereof intended for use primarily by persons with a hearing impairment, (b) in assembly occupancies in which music and other….

Practice this topic

Smoke alarms and residential fire warning systems

Smoke alarms (CAN/ULC-S531 products, installed to CAN/ULC-S553) go in each dwelling unit and each sleeping room not within a dwelling unit OBC Div. B 3.2.4.20.OBC Div. B 3.2.4.20. Smoke Alarms(1) Except as provided in Article 3.2.4.21., smoke alarms shall be installed in accordance with this Article. (2) Except as permitted by Sentence (10), smoke alarms conforming to CAN/ULC-S531, "Standard for Smoke Alarms," shall be installed in each dwelling unit and, except for care, care and treatment or detention…. Within each dwelling unit, they go on every storey and mezzanine, in each sleeping room, and between the sleeping rooms and the rest of the storey. Further rules:

  • mount on or near the ceiling,
  • hard-wire with no disconnect switch,
  • provide a battery for 7 days normal followed by 4 minutes of alarm,
  • interconnect multiple alarms within the unit,
  • allow 10 min manual silencing,
  • provide a visual component, at least 175 cd in sleeping rooms.

System smoke detectors (S524 and S537, 75 to 110 dBA in the suite) may replace smoke alarms and may sound locally. A CAN/ULC-S540 residential fire warning system may replace them where no fire alarm is installed or required OBC Div. B 3.2.4.21.OBC Div. B 3.2.4.21. Residential Fire Warning Systems(1) Except where a fire alarm system is installed or required in a building, smoke detectors forming part of a residential fire warning system installed in conformance with CAN/ULC-S540, "Standard for Residential Fire and Life Safety Warning Systems: Installation, Inspection, Testing and Maintenance," are permitted to….

Practice this topic

Voice communication systems

A two-way system (required by 3.2.6. and certain Section 3.3. provisions) must provide OBC Div. B 3.2.4.22.OBC Div. B 3.2.4.22. Two-Way Voice Communication Systems(1) A voice communication system required by Subsection 3.2.6., Clause 3.3.2.4.(14)(f) or Sentence 3.3.4.11.(12) shall (a) consist of a two-way means of communication with the central alarm and control facility and to the mechanical control centre from each floor area, and (b) be capable of broadcasting pre-recorded…:

  • talk-back from each floor area to the central alarm and control facility,
  • emergency telephones near exit stair shafts,
  • broadcast messages audible in all parts of the building except elevator cars,
  • silencing for voice only after 30 s (10 s for the alert in hospitals with 24-hour supervisory staff).

A one-way system is required where a 2-stage system is installed and the occupant load exceeds 1,000, except in Group B, Division 1 and Group F, Division 1 OBC Div. B 3.2.4.23.OBC Div. B 3.2.4.23. One-Way Voice Communication Systems(1) Except for Group B, Division 1 and Group F, Division 1 major occupancies, where a fire alarm system is required under Subsection 3.2.4., a one-way voice communication system shall be installed in buildings where a 2-stage fire alarm system is installed and whose occupant load exceeds 1,000. (2) The one-way voice….

Practice this topic

Common traps

  • Using "3 storeys" as the trigger. It is more than 3, and storeys below the first storey count.
  • Swapping silencing times: 5 min applies only where no annunciator is required.
  • Forgetting that one-way voice needs both a 2-stage system and more than 1,000 occupants.

Chapter review

Chapter at a glance

One line per section: the idea to carry into the exam. Then the answers that most often catch candidates out.

Usual exam traps

  • Using "3 storeys" as the trigger. It is more than 3, and storeys below the first storey count.
  • Swapping silencing times: 5 min applies only where no annunciator is required.
  • Forgetting that one-way voice needs both a 2-stage system and more than 1,000 occupants.

Practice this chapter

Questions on Fire alarm and detection systems (3.2.4), in the exam format, every answer explained and cited to its article. Sign in to start; a free account gets the free questions.

Code cited in this chapter

Based on the official 2024 Building Code Compendium on ontario.ca.

© King's Printer for Ontario, 2024. Reproduced with permission.

  • OBC Div. B 3.2.4.5. Installation and Verification of Fire Alarm Systems

    (1)Fire alarm systems, including those with voice communication capability where provided, shall be installed in conformance with CAN/ULC-S524, "Standard for Installation of Fire Alarm Systems."

    (2)Fire alarm systems shall be verified in conformance with CAN/ULC-S537, "Verification of Fire Alarm Systems," to ensure satisfactory operation.

    Open OBC Div. B 3.2.4.5. in the code viewer
  • OBC Div. B 3.2.4.1. Determination of Requirement for a Fire Alarm System

    (1)Except as permitted in Sentences (2) and (3), a fire alarm system shall be installed in buildings in which an automatic sprinkler system is installed.

    (2)Buildings in which a sprinkler system is installed in accordance with NFPA 13D, "Standard for the Installation of Sprinkler Systems in One- and Two-Family Dwellings and Manufactured Homes," need not comply with Sentence (1).

    (3)Buildings that contain fewer than 9 sprinklers conforming to Sentence 3.2.5.12.(4) need not comply with Sentence (1).

    (4)Except as permitted by Sentences (5), (6) and 3.2.4.2.(4), a fire alarm system shall be installed in a building that is not sprinklered throughout and that contains

    (a)a contained use area,

    (b)an impeded egress zone,

    (c)more than 3 storeys, including storeys below the first storey,

    (d)a total occupant load more than 300, other than in open air seating areas,

    (e)an occupant load more than 150 above or below the first storey, other than in open air seating areas,

    (f)a school, college or child care facility, including a day care facility, with an occupant load more than 40,

    (g)a licensed beverage establishment or a licenced restaurant, with an occupant load more than 150,

    (h)a low-hazard industrial occupancy with an occupant load more than 75 above or below the first storey,

    (i)a medium-hazard industrial occupancy with an occupant load more than 75 above or below the first storey,

    (j)a residential occupancy with sleeping accommodation for more than 10 persons,

    (k)a high-hazard industrial occupancy with an occupant load more than 25,

    (l)an occupant load more than 300 below an open air seating area,

    (m)a care and treatment occupancy for more than 10 persons receiving care or treatment, or

    (n)a care occupancy for more than 10 persons receiving care.

    (4.1)A fire alarm system is not required in a hotel 3 storeys or less in building height provided each suite has direct access to an exterior exit facility leading to ground level.

    (5)A fire alarm system is not required in a residential occupancy that is not sprinklered, where

    (a)not more than 4 suites share a common means of egress, or

    (b)each suite has direct access to an exterior exit facility leading to ground level.

    (6)A fire alarm system is not required in a storage garage conforming to Article 3.2.2.92. that is contained in a building that is not sprinklered provided there are no other occupancies in the building.

    Open OBC Div. B 3.2.4.1. in the code viewer
  • OBC Div. B 3.2.4.2. Continuity of Fire Alarm System

    (1)Except as permitted by Sentence (6), if there are openings through a firewall, other than those for piping, tubing, wiring and totally enclosed noncombustible raceways, the requirements in this Subsection shall apply to the floor areas on both sides of the firewall as if they were in the same building.

    (2)Except as permitted by Sentence (4), if a building contains more than one major occupancy and a fire alarm system is required, a single system shall serve all occupancies.

    (3)Except as permitted by Sentence (4), if a fire alarm system is required in any portion of a building, it shall be installed throughout the building.

    (4)Except as required by Sentence (5), the requirements in this Subsection are permitted to be applied to each portion of a building not more than 3 storeys in building height, in which a vertical fire separation having a fire-resistance rating not less than 1 h separates the portion from the remainder of the building as if it were a separate building, provided there are no openings through the fire separation, other than those for piping, tubing, wiring and totally enclosed noncombustible raceways.

    (5)The permission in Sentence (4) to consider separated portions of a building as separate buildings does not apply to service rooms and storage rooms.

    (6)Buildings interconnected by walkways permitted in Articles 3.2.3.19. and 3.2.3.20. or by vestibules provided in conformance with Article 3.2.6.3. shall be treated as separate buildings for the purpose of fire alarm installation required by this Subsection.

    Open OBC Div. B 3.2.4.2. in the code viewer
  • OBC Div. B 3.2.4.3. Types of Fire Alarm Systems

    (1)A fire alarm system shall be

    (a)a single-stage system in a Group F, Division 1 occupancy,

    (b)except as permitted in Clause (c), a 2-stage system in a Group B occupancy,

    (c)a single- or 2-stage system in a Group B, Division 3 occupancy where the building is 3 storeys or less in building height,

    (d)a single-stage system in elementary and secondary schools, except for a special needs facility, and

    (e)a single- or 2-stage system in all other cases.

    Open OBC Div. B 3.2.4.3. in the code viewer
  • OBC Div. B 3.2.4.4. Description of Fire Alarm Systems

    (1)A single-stage fire alarm system shall, upon the operation of any manual station, waterflow detecting device, or fire detector, cause an alarm signal to sound on all audible signal devices in the system. (See Note A-3.2.4.4.(1))

    (2)A 2-stage fire alarm system shall

    (a)cause an alert signal to sound upon the operation of any manual station, waterflow detecting device, or fire detector,

    (b)except for a Group B, Division 2 occupancy, automatically cause an alarm signal to sound if the alert signal is not acknowledged within 5 min of its initiation,

    (c)have manual stations, each of which is equipped so that the use of a key or other similar device causes an alarm signal to sound that continues to sound upon removal of the key or similar device from the manual station, and (See Note A-3.2.4.4.(2)(c))

    (d)in a building containing a hotel,

    (i)cause an alarm signal to sound in the initiating fire zone in the hotel, and

    (ii)cause an alert signal to sound throughout the hotel and such parts of the building as is necessary to alert hotel staff. (See Note A-3.2.4.4.(2))

    (3)A 2-stage fire alarm system is permitted to be zone coded so that, upon the operation of any manual station, waterflow detecting device, or fire detector,

    (a)a coded alert signal is sounded indicating the zone of alarm initiation,

    (b)the coded alert signal is repeated in its entirety not less than 4 times, and

    (c)a continuous alert signal is sounded upon completion of the coded signals referred to in Clause (b) and Sentence (4).

    (4)If a second manual station, waterflow detecting device, or fire detector is operated in a fire alarm system with zone coding as permitted by Sentence (3), in a zone other than that for which the first alert signal was sounded, the coded alert signal for the first zone shall be completed before the coded alert signal for the second zone is repeated not less than 4 times.

    Open OBC Div. B 3.2.4.4. in the code viewer
  • OBC Div. B 3.2.4.8. Annunciator and Zone Indication

    (1)Except as permitted by Sentences (3) to (5), an annunciator shall be installed in close proximity to a building entrance that faces a street or an access route for fire department vehicles that complies with Sentence 3.2.5.5.(1).

    (2)Except as permitted by Sentence (6), the annunciator required by Sentence (1) shall have separate zone indication of the actuation of the alarm initiating devices in each

    (a)floor area so that the area of coverage for each zone in a building that is not sprinklered is not more than 2,000 m²,

    (b)floor area so that the area of coverage for each zone is neither

    (i)more than one storey, nor

    (ii)more than the system area limits as specified in NFPA 13, "Standard for the Installation of Sprinkler Systems,"

    (c)shaft required to be equipped with fire detectors,

    (d)air-handling system required to be equipped with smoke detectors,

    (e)fire extinguishing system required by NFPA 96, "Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations,"

    (f)contained use area,

    (g)impeded egress zone, and

    (h)fire compartment required by Sentence 3.3.3.5.(2) or Sentence 3.3.4.11.(2).(See Note A-3.2.4.8.(2))

    (3)An annunciator need not be provided for a fire alarm system if not more than one zone indicator is required in Sentence (2).

    (4)If an annunciator is not installed as part of a fire alarm system in conformance with Sentence (1), a visible and audible trouble signal device shall be provided inside the main entrance of the building.

    (5)The requirements in Sentence (1) are waived in a building

    (a)in which an automatic sprinkler system is not installed,

    (b)that has an aggregate area for all storeys of not more than 2,000 m², and

    (c)that is not more than 3 storeys in building height.

    (6)The area limits of Clause (2)(a) are waived for an interior undivided open space used as an arena, a rink or a swimming pool provided that other spaces in the building that are separated from the open space are individually zoned in accordance with the requirements of Sentence (2).

    (7)A fire alarm control unit installed in close proximity to a building entrance that faces a street or an access route for fire department vehicles that complies with Sentence 3.2.5.5.(1), is deemed to satisfy the requirement for an annunciator provided all indicators required for an annunciator or trouble signal device are included on the control unit. (See Note A-3.2.4.8.(7))

    (8)In a building containing a hotel in which a trouble signal sounding device has a silencing switch, a trouble light shall be installed in

    (a)the main reception area serving the hotel, or

    (b)another continually-supervised location.

    (9)In a long-term care home, a remote audiovisual fire alarm trouble signal shall be located at the main nursing station.

    Open OBC Div. B 3.2.4.8. in the code viewer
  • OBC Div. B 3.2.4.9. Electrical Supervision

    (1)Electrical supervision shall be provided for a fire alarm system.

    (2)If a fire alarm system in a building is required to have an annunciator by Sentence 3.2.4.8.(1), except for hose valves, all valves controlling water supplies in a standpipe system, shall be equipped with an electrically supervised switch for transmitting a trouble signal to the annunciator in the event of movement of the valve handle.

    (3)An automatic sprinkler system shall be electrically supervised to indicate a supervisory signal on the building fire alarm system annunciator for each of the following:

    (a)movement of a valve handle that controls the supply of water to sprinklers,

    (b)loss of excess water pressure required to prevent false alarms in a wet pipe system,

    (c)loss of air pressure in a dry pipe system,

    (d)loss of air pressure in a pressure tank,

    (e)a significant change in water level in any water storage container used for firefighting purposes,

    (f)loss of power to any automatically starting fire pump, and (See Note A-3.2.4.9.(3)(f))

    (g)a temperature approaching the freezing point in any dry pipe valve enclosure or water storage container used for firefighting purposes.

    (4)A fire pump shall be electrically supervised as stipulated in NFPA 20, "Standard for the Installation of Stationary Pumps for Fire Protection."

    (5)Electrical supervision shall be provided to indicate, on the fire alarm system annunciator, a loss of power to a heat tracing cable that is installed to heat

    (a)a standpipe riser,

    (b)a sprinkler line as part of a fire suppression system, or

    (c)an exit or means of egress to keep it free of ice and snow.

    (6)Indication of a supervisory signal in accordance with Sentences (3) and (5) shall be transmitted to the fire department in conformance with Sentence 3.2.4.7.(4).

    Open OBC Div. B 3.2.4.9. in the code viewer
  • OBC Div. B 3.2.4.7. Signals to Fire Department

    (1)A single-stage fire alarm system shall be designed to notify the fire department in conformance with Sentence (4) that an alarm signal has been initiated in

    (a)a building of a Group A occupancy having an occupant load more than 300, or

    (b)a retirement home.

    (2)A fire alarm system that includes waterflow indicating devices shall be designed to notify the fire department in conformance with Sentence (4), when an alarm is initiated.

    (3)A 2-stage fire alarm system shall be designed to notify the fire department, in conformance with Sentence (4), that an alert signal has been initiated.

    (4)Notification of the fire department, as required by Sentences (1) to (3), shall be provided in conformance with CAN/ULC-S561, "Standard for Installation and Services for Fire Signal Receiving Centres and Systems." (See Note A-3.2.4.7.(4))

    (5)Where a single-stage fire alarm system is installed in a building that is not sprinklered throughout and Sentence (1) does not apply, a legible notice that is not easily removed shall be affixed to the wall near each manual station stating

    (a)that the fire department is to be notified in the event of a fire emergency, and

    (b)the emergency telephone number for the municipality or for the fire department. (See Note A-3.2.4.7.(5)(b))

    (6)Helicopter landing areas on roofs shall be provided with telephone extensions or means to notify the fire department.

    Open OBC Div. B 3.2.4.7. in the code viewer
Show all 19 articles
  • OBC Div. B 3.2.4.6. Silencing of Alarm Signals

    (1)Except as permitted by Sentence (3), a fire alarm system shall be designed so that when an alarm signal is actuated, it cannot be silenced automatically before a period of time has elapsed that is not less than

    (a)5 min for a building not required to be equipped with an annunciator, and

    (b)20 min for any other building.

    (2)Except as permitted by Sentences 3.2.4.18.(8) and Sentences 3.2.4.22.(2) and (3), a fire alarm system shall not incorporate manual silencing switches other than those installed inside the fire alarm control unit. (See Note A-3.2.4.6.(2))

    (3)Except as provided by Clause 3.2.4.22.(3)(a), in a care and treatment occupancy an alert signal is permitted to be silenced automatically after 1 min.

    Open OBC Div. B 3.2.4.6. in the code viewer
  • OBC Div. B 3.2.4.10. Fire Detectors

    (1)Fire detectors required by this Code shall be connected to the fire alarm system.

    (2)Except as permitted by Sentence (3), if a fire alarm system is required in a building that is not sprinklered, fire detectors shall be installed in the following spaces:

    (a)storage rooms not within dwelling units,

    (b)service rooms not within dwelling units,

    (c)janitors' rooms,

    (d)rooms in which hazardous substances are to be used or stored, (See Note A-3.3.1.2.(1)),

    (e)elevator hoistways or dumbwaiter shafts,

    (f)laundry rooms in buildings of residential occupancy, but not those within dwelling units, and

    (g)hazardous classrooms and change rooms in elementary or secondary schools.

    (3)Fire detectors required by Sentence (2) need not be provided within floor areas that are sprinklered.

    (4)Fire detectors required by Sentence (2) shall be installed in elevator hoistways and dumbwaiter shafts where a sprinkler system is not installed within the hoistway or shaft.

    Open OBC Div. B 3.2.4.10. in the code viewer
  • OBC Div. B 3.2.4.11. Smoke and Heat Detectors

    (1)If a fire alarm system is installed, smoke detectors shall be installed in

    (a)each sleeping room and each corridor serving as part of a means of egress from sleeping rooms in portions of a building classified as Group B major occupancy,

    (b)each room in a contained use area and corridors serving those rooms,

    (c)each corridor in portions of a building classified as Group A, Division 1 major occupancy,

    (d)each public corridor in portions of a building classified as Group C major occupancy,

    (e)each exit stair shaft, other than those serving only a Group A, Division 4 major occupancy or an open storage garage.

    (f)the vicinity of draft stops required by Article 3.2.8.6.,

    (g)each elevator machine room, and

    (h)each corridor serving classrooms in elementary and secondary schools.(See Note A-3.2.4.11.(1))

    (2)In a floor area containing a hotel, where a fire alarm system is installed and the floor area is not sprinklered, heat detectors shall be installed in every room in a suite and in every room not located in a suite other than washrooms within a suite, saunas, refrigerated areas and swimming pools.

    (3)Smoke detectors required in sleeping rooms of a care, care and treatment or detention occupancy shall, upon actuation, provide an audible and visible signal to staff serving those rooms so that the room or location containing the smoke detector can be easily identified. (See Note A-3.2.4.11.(3))

    (4)Smoke detectors required in Clause (1)(g) shall, upon actuation, recall the elevators served by the elevator machine room in which the smoke detector is installed.

    (5)Except as permitted in Sentences (6) and (7), smoke detectors installed in buildings required to be equipped with a fire alarm system shall be located near the entrance to walkways described in Articles 3.2.3.19. and 3.2.3.20. or vestibules provided in conformance with Article 3.2.6.3.

    (6)Smoke detectors installed at the entrance to the walkways in conformance with Article 3.1.8.14. shall be deemed to meet the requirements of Sentence (5).

    (7)Smoke detectors required by Sentence (5) may be replaced with fire detectors in Group F occupancies where the smoke detectors may be subjected to false alarms due to the activities within the building.

    Open OBC Div. B 3.2.4.11. in the code viewer
  • OBC Div. B 3.2.4.12. Prevention of Smoke Circulation

    (1)If a fire alarm system is installed, an air-handling system shall be designed to prevent the circulation of smoke upon a signal from a duct-type smoke detector if the air handling system

    (a)serves more than one storey,

    (b)serves more than one suite in a storey,

    (c)serves more than one fire compartment required by Sentence 3.3.3.5.(2) or Sentence 3.3.4.11.(2), or

    (d)is not provided with fire dampers as permitted by Sentence 3.1.8.8.(4).

    Open OBC Div. B 3.2.4.12. in the code viewer
  • OBC Div. B 3.2.4.16. Manual Stations

    (1)Except as permitted by Sentences (2) and (3), where a fire alarm system is installed, a manual station shall be installed in every floor area near

    (a)every principal entrance to the building, and

    (b)every exit. (See Note A-3.2.4.16.(1))

    (2)In a building that is sprinklered throughout, a manual station is not required at an exterior egress doorway from a suite that does not lead to an interior shared means of egress in a hotel not more than 3 storeys in building height, provided each suite is served by an exterior exit facility leading directly to ground level.

    (3)In a building that is sprinklered throughout, a manual station is not required at an exterior egress doorway from a dwelling unit that does not lead to an interior shared means of egress in a building not more than 3 storeys in building height containing only dwelling units, provided each dwelling unit is served by an exterior exit facility leading directly to ground level.

    (4)In a building referred to in Sentence (2) or (3), manual stations shall be installed near doorways leading from shared interior corridors to the exterior.

    (5)Where a fire alarm system is installed, a manually operated fire alarm station shall be installed on the roof at each exit from a helicopter landing area.

    (6)In a building containing a hotel, a manual station shall be installed in the main reception area serving the hotel.

    (7)Except as permitted by Sentence (3), in Group C apartment buildings other than retirement homes, if a manual station is not installed on a floor area in accordance with Sentence (1) or (4),

    (a)a manual station shall be installed in every dwelling unit in the floor area near each egress door leading from the dwelling unit,

    (b)smoke detectors shall be installed in the floor area in public corridors and stairwells, and

    (c)fire detectors shall be installed in the floor area in all common public areas and in rooms not located within dwelling units.

    (8)In floor areas where the manual stations are located in dwelling units, a legible sign stating fire alarm manual stations located in apartment units shall be posted near every exit in a public corridor.

    (9)Key switch activated manual stations are permitted in an impeded egress zone and a contained use area in Group B, Division 1 and 2 occupancies.

    Open OBC Div. B 3.2.4.16. in the code viewer
  • OBC Div. B 3.2.4.18. Audibility of Alarm Systems

    (1)Except as permitted by Sentence 3.2.4.19.(2) and except as required by Clause 3.2.4.4.(2)(d), audible signal devices forming part of a fire alarm system shall be installed in a building so that

    (a)alarm signals are clearly audible throughout the floor area, and

    (b)alert signals are clearly audible in continuously staffed locations, and where there are no continuously staffed locations, throughout the floor area. (See Note A-3.2.4.18.(1))

    (2)The sound pattern of an alarm signal shall conform to the temporal pattern defined in Clause 4.2 of ISO 8201, "Acoustics Audible emergency evacuation signal." (See Note A-3.2.4.18.(2))

    (3)The sound patterns of alert signals shall be significantly different from the temporal patterns of alarm signals. (See Note A-3.2.4.18.(3))

    (4)In all normally occupied spaces, the fire alarm signal sound pressure level

    (a)shall be not more than 110 dBA when measured at a distance of 3 m from the device, or

    (b)is permitted to be more than 100 dBA provided the sound pressure level measured 2,000 mm above floor level is not more than 100 dBA. (See Note A-3.2.4.18.(4))

    (5)The sound pressure level in a sleeping room from a fire alarm audible signal device shall be not less than 75 dBA in a building of residential occupancy when any intervening doors between the device and the sleeping room are closed. (See Note A-3.2.4.18.(5))

    (6)Audible signal devices in sleeping rooms in a building of residential or care occupancy shall emit a low frequency signal. (See Note A-3.2.4.18.(6))

    (7)Except as required by Sentence (5), the sound pressure level from a fire alarm system's audible signal device within a floor area shall be not less than 10 dBA above the ambient noise level and not less than 65 dBA, when any intervening doors between the device and the rest of the floor area are closed.

    (8)Except as permitted by Sentence (12), audible signal devices located within a dwelling unit shall include a means for them to be manually silenced for a period of not more than 10 min, after which time the devices shall restore themselves to normal operation. (See Note A-3.2.4.18.(8))

    (9)Audible signal devices within a dwelling unit or a suite of residential occupancy shall be connected to the fire alarm system

    (a)in a manner such that a single open circuit at one device will not impair the operation of other audible signal devices on that same circuit that serve the other dwelling units or suites of residential occupancy, or

    (b)on separate signal circuits that are not connected to the devices in any other dwelling unit, public corridor or suite of residential occupancy. (See Note A-3.2.4.18.(9) and (10))

    (10)In a building or part thereof classified as a residential occupancy,

    (a)separate circuits shall be provided for audible signal devices on each floor area, and

    (b)audible signal devices within dwelling units or suites of residential occupancy shall be wired on separate signal circuits from those not within suites of residential occupancy or dwelling units. (See Note A-3.2.4.18.(9) and (10))

    (11)Audible signal devices shall be installed in a service space referred to in Sentence 3.2.1.1.(8) and shall be connected to the fire alarm system.

    (12)Audible signal devices within dwelling units that are wired on separate signal circuits in accordance with Clause (10)(b) need not include a means for manual signal silencing as required by Sentence (8), provided the fire alarm system includes a provision for the automatic signal silence within dwelling units, where

    (a)the automatic signal silence cannot occur within the first 60 s of operation or within the zone of initiation,

    (b)a subsequent alarm elsewhere in the building will reactuate the silenced audible signal devices within dwelling units,

    (c)after a period of not more than 10 min, the silenced audible signal devices will be restored to continuous audible signal if the alarm is not acknowledged, and

    (d)the voice communication systems referred to in Article 3.2.4.22. and 3.2.4.23. has a provision to override the automatic signal silence to allow the transmission of voice messages through silenced audible signal device circuits that serve the dwelling units. (See Note A-3.2.4.18.(12))

    (13)If a 2-stage fire alarm system has been installed with an automatic signal silence as described in Sentence (12), the system shall be designed so that any silenced audible signal devices serving dwelling units are reactuated whenever an alarm signal is required to be transmitted as part of the second stage. (See Note A-3.2.4.18.(8))

    Open OBC Div. B 3.2.4.18. in the code viewer
  • OBC Div. B 3.2.4.19. Visible Signals

    (1)Except as permitted by Sentence (4), where a fire alarm system is installed, visible signal devices shall be installed in addition to alarm signal devices

    (a)in a building or portions thereof intended for use primarily by persons with a hearing impairment,

    (b)in assembly occupancies in which music and other sounds associated with performances could exceed 100 dBA,

    (c)in any floor area in which the ambient noise level is more than 87 dBA,

    (d)in any floor area in which the occupants

    (i)use ear protection devices,

    (ii)are located in an audiometric booth, or

    (iii)are located in sound-insulating enclosures,

    (e)in public corridors serving a Group A, B, C, D or E major occupancy,

    (f)in a corridor used by the public and in a floor area or part of a floor area where the public may congregate in a Group A occupancy,

    (g)in not less than 10% of the suites of a hotel or motel, (See Note A-3.2.4.19.(1)(g))

    (h)in washrooms for public use described in Sentence 3.8.2.3.(2), (3), (4) or (6), and

    (i)in living spaces in a suite of residential occupancy in a Group C major occupancy apartment building.

    (2)Visible signal devices are permitted to be installed in lieu of audible signal devices in the compartments referred to in Article 3.3.3.6. (See Note A-3.2.4.19.(2))

    (3)Visible signal devices required by Sentence (1) shall be installed so that the signal from at least one device is visible throughout the floor area or portion thereof in which they are installed. (See Note A-3.2.4.19.(3))

    (4)Visible signal devices required by Clauses (1)(e) and (f) are not required in

    (a)a classroom, and

    (b)a Group B, Division 3 occupancy that contains sleeping accommodation for not more than 10 persons and not more than six occupants require assistance in evacuation in case of an emergency.

    Open OBC Div. B 3.2.4.19. in the code viewer
  • OBC Div. B 3.2.4.20. Smoke Alarms

    (1)Except as provided in Article 3.2.4.21., smoke alarms shall be installed in accordance with this Article.

    (2)Except as permitted by Sentence (10), smoke alarms conforming to CAN/ULC-S531, "Standard for Smoke Alarms," shall be installed in each dwelling unit and, except for care, care and treatment or detention occupancies required to have a fire alarm system, in each sleeping room not within a dwelling unit.

    (3)At least one smoke alarm shall be installed on each storey and mezzanine of a dwelling unit.

    (4)On any storey of a dwelling unit containing sleeping rooms, a smoke alarm shall be installed

    (a)in each sleeping room, and

    (b)in a location between the sleeping rooms and the remainder of the storey, and if the sleeping rooms are served by a hallway, the smoke alarm shall be located in the hallway.

    (5)Reserved.

    (6)A smoke alarm shall be installed on or near the ceiling.

    (7)Reserved.

    (8)Reserved.

    (9)Except as permitted by Sentence (10), smoke alarms referred in Sentence (2) shall

    (a)be installed with permanent connections to an electrical circuit,

    (b)have no disconnect switch between the overcurrent device and the smoke alarm, and

    (c)in case the regular power supply to the smoke alarm is interrupted, be provided with a battery as an alternative power source that can continue to provide power to the smoke alarm for a period of not less than 7 days in the normal condition, followed by 4 minutes of alarm. (See Note A-3.2.4.20.(9))

    (10)Suites of residential occupancy are permitted to be equipped with smoke detectors in lieu of smoke alarms, provided the smoke detectors

    (a)are capable of independently sounding audible signals with a sound pressure level between 75 dBA and 110 dBA within the individual suites, (See also Note A-3.2.4.18.(4))

    (b)except as permitted by Sentence (11), are installed in conformance with CAN/ULC-S524, "Standard for the Installation of Fire Alarm Systems," and verified in conformance with CAN/ULC-S537, "Standard for the Verification of Fire Alarm Systems,"

    (c)form part of the fire alarm system, and

    (d)are equipped with visual signalling components that meet the requirements of Sentences (17) to (19). (See Note A-3.2.4.20.(10))

    (11)Smoke detectors permitted to be installed in lieu of smoke alarms as stated in Sentence (10) are permitted to sound localized alarms within individual suites, and need not sound an alarm throughout the rest of the building.

    (12)If more than one smoke alarm is required in a dwelling unit, the smoke alarms shall be interconnected so that the actuation of one smoke alarm will cause all smoke alarms within the dwelling unit to sound.

    (13)A smoke alarm required by Sentence (2) shall be installed in conformance with CAN/ULC-S553, "Standard for Installation of Smoke Alarms."

    (14)Except as permitted in Sentence (15), a manually operated silencing device shall be incorporated within the circuitry of a smoke alarm installed in a dwelling unit so that it will silence the signal emitted by the smoke alarm for a period of not more than 10 min, after which the smoke alarm will reset and again sound the alarm if the level of smoke in the vicinity is sufficient to reactuate the smoke alarm.

    (15)Suites of residential occupancy equipped with smoke detectors installed in conformance with CAN/ULC-S524, "Standard for Installation of Fire Alarm Systems," as part of the fire alarm system in lieu of smoke alarms as permitted by Sentence (10), need not incorporate the manually operated silencing device required by Sentence (14). (See Note A-3.2.4.20.(10))

    (16)The sound patterns of smoke alarms shall

    (a)meet the temporal patterns of alarm signals, or (See Note A-3.2.4.18.(2))

    (b)be a combination of temporal pattern and voice relay.

    (17)Smoke alarms required by Sentence (2) shall have a visual signalling component conforming to the requirements in 18.5.3. (Light, Color and Pulse Characteristics) of NFPA 72, "National Fire Alarm and Signaling Code." (See Note A-3.2.4.20.(17))

    (18)The visual signalling component required by Sentence (17) need not

    (a)be integrated with the smoke alarm provided it is interconnected to it,

    (b)be on battery backup, or

    (c)have synchronized flash rates, when installed in a dwelling unit.

    (19)The luminous intensity for visual signalling components required by Sentence (17) that are installed in sleeping rooms shall be a minimum of 175 cd.

    (20)Smoke alarms required in suites in a retirement home or smoke detectors permitted to be installed in lieu of smoke alarms as provided in Sentence (10) shall upon actuation provide an audible and visual signal to staff serving those suites, so that the suite containing the actuated smoke alarm or smoke detector can be easily identified.

    Open OBC Div. B 3.2.4.20. in the code viewer
  • OBC Div. B 3.2.4.21. Residential Fire Warning Systems

    (1)Except where a fire alarm system is installed or required in a building, smoke detectors forming part of a residential fire warning system installed in conformance with CAN/ULC-S540, "Standard for Residential Fire and Life Safety Warning Systems: Installation, Inspection, Testing and Maintenance," are permitted to be installed in lieu of all smoke alarms required by Article 3.2.4.20., provided that the system is

    (a)capable of sounding audible signals in accordance with Sentences 3.2.4.20.(12) and (16),

    (b)provided with a visual signalling component in accordance with Sentences 3.2.4.22.(17) to (19),

    (c)powered in accordance with Sentence 3.2.4.20.(9), and

    (d)provided with a silencing device in accordance with Sentences 3.2.4.20.(14) and (15).

    Open OBC Div. B 3.2.4.21. in the code viewer
  • OBC Div. B 3.2.4.22. Two-Way Voice Communication Systems

    (1)A voice communication system required by Subsection 3.2.6., Clause 3.3.2.4.(14)(f) or Sentence 3.3.4.11.(12) shall

    (a)consist of a two-way means of communication with the central alarm and control facility and to the mechanical control centre from each floor area, and

    (b)be capable of broadcasting pre-recorded, synthesized or live messages from the central alarm and control facility that are audible and intelligible in all parts of the building, except elevator cars. (See Note A-3.2.4.22.(1)(b))

    (2)The voice communication system referred to in Sentence (1) shall include a means to silence the alarm signal in a single-stage fire alarm system while voice instructions are being transmitted, but only after the alarm signal has initially sounded for not less than 30 s.

    (3)The voice communication system referred to in Sentence (1) shall include a means to silence the alert signal and the alarm signal in a 2-stage fire alarm system while voice instructions are being transmitted, but only after the alert signal has initially sounded for not less than

    (a)10 s in hospitals that have supervisory personnel on duty for twenty-four hours each day, or

    (b)30 s for all other occupancies.

    (4)The voice communication system referred to in Clause (1)(b) shall be designed so that the alarm signal in a 2-stage fire alarm system can be selectively transmitted to any zone or zones while maintaining an alert signal or selectively transmitting voice instructions to any other zone or zones in the building.

    (5)The 2-way communication system referred to in Clause (1)(a) shall be installed so that emergency telephones are located in each floor area near exit stair shafts.

    (6)Visible signal devices required by Sentence 3.2.4.19.(1) shall continue to emit a visible signal while voice instructions are being transmitted.

    (7)Where the facility is not equipped with staff trained to provide instructions over the loudspeakers, a pre-recorded message shall be provided.

    Open OBC Div. B 3.2.4.22. in the code viewer
  • OBC Div. B 3.2.4.23. One-Way Voice Communication Systems

    (1)Except for Group B, Division 1 and Group F, Division 1 major occupancies, where a fire alarm system is required under Subsection 3.2.4., a one-way voice communication system shall be installed in buildings where a 2-stage fire alarm system is installed and whose occupant load exceeds 1,000.

    (2)The one-way voice communication system required by Sentence (1) shall consist of loudspeakers that are

    (a)operated from the central alarm and control facility or, in the absence of a central alarm and control facility, from a designated area, and

    (b)except in elevator cars, designed and located so that transmitted messages are audible and intelligible in all parts of the building. (See Note A-3.2.4.22.(1)(b))

    (3)Where the facility is not equipped with staff trained to provide instructions over the loudspeakers, a pre-recorded message shall be provided.

    (4)The voice communication system required by Sentence (1) shall meet the silencing and transmission requirements of Sentences 3.2.4.22.(2) to (4) and (6).

    Open OBC Div. B 3.2.4.23. in the code viewer