Designers spend much of their time on existing buildings. Parts 10 and 11 of Division B set the rules: Part 10 for a change of major occupancy, and Part 11 for extension, material alteration and repair. Both rest on one idea: the performance level of the building must not go down. If a project would lower it, compensating construction is required. Where full compliance is impracticable, compliance alternatives may be used.
"Performance level" means the level of performance at which all or part of an existing building functions with respect to its building systems (OBC Div. A 1.4.1.2.OBC Div. A 1.4.1.2.(1) Performance levelPerformance level means the level of performance under which all or part of an existing building functions with respect to its building systems.).
Change of use (Part 10)
Part 10 applies as described in Division A 1.3.3. (OBC Div. B 10.1.1.1.OBC Div. B 10.1.1.1. Scope(1) The scope of this Part shall be as described in Subsection 1.3.3. of Division A.). Besides an actual change of major occupancy, these are deemed changes in major occupancy: one Group C suite split into more, A-2 or A-4 space converted to a gaming premises, farm building changes, a change to a post-disaster building or a retirement home, and a change where the previous occupancy cannot be determined (OBC Div. B 10.1.1.2.OBC Div. B 10.1.1.2. Change in Major Occupancy(1) The following changes of use are also deemed to be a change in major occupancy for the purposes of this Part: (a) a suite of a Group C major occupancy is converted into more than one suite of a Group C major occupancy, (b) a suite or part of a suite of a Group A, Division 2 or Group A, Division 4 major occupancy…).
What must comply. The building or part must meet listed requirements for the new occupancy, such as Subsection 3.2.6., Sections 3.7., 3.11. and 3.12., and listed Part 9 items for health, ventilation and safety (OBC Div. B 10.3.1.1.OBC Div. B 10.3.1.1. General(1) Except as provided in Section 10.4., a building or part of a building subject to a change of major occupancy shall conform to the requirements of Subsection 3.2.6., Sections 3.7., 3.11. and 3.12., Sentences 6.3.1.1.(2) and 6.3.2.7.(1), Subsections 9.5.1. and 9.5.3., 9.5.3A. to 9.5.3F. and 9.5.4., Sentences…).
Performance level. It must not be less after the change than before (OBC Div. B 10.3.2.1.OBC Div. B 10.3.2.1. General(1) The performance level of a building after the change of major occupancy shall not be less than the performance level prior to the change of major occupancy. (2) For the purposes of Sentence (1), reduction of performance level shall be determined in accordance with Article 10.3.2.2. (3) For the purpose of this…). Under OBC Div. B 10.3.2.2.OBC Div. B 10.3.2.2. Reduction in Performance Level(1) Except as provided in Sentence (2), the performance level of a building or part of a building is reduced where the existing structural floor and roof framing systems and their supporting members are not adequate to support the proposed dead loads and live loads of the new major occupancy that the building is to… it is reduced where, for example:
| Situation | Result |
|---|---|
| Floor and roof framing cannot carry the new loads | Reduced, unless the floor area is restricted to the loads it can carry and signs are posted |
| Early warning and evacuation systems fall short of Table 10.3.2.2.-A | Reduced |
| New major occupancy has a greater hazard index (H.I.) | Reduced, unless the new H.I. is not greater than the building's construction index (C.I.) |
| Combustible building changed to residential where a new building would need noncombustible construction | Reduced, unless sprinklered and not over 6 storeys |
| Fire separations between occupancies fall short | Reduced |
| Sewage flow exceeds system capacity, or prohibited sewage would be discharged | Reduced |
| Change to a retirement home without full sprinklers, required voice communication, or self-closing doors to suites and sleeping rooms | Reduced |
Small or medium buildings facing multiple streets may take a hazard index credit of 1 if they have no B-1, C or F-1 occupancy and have proper firefighting access.
Compliance alternatives in Part 10. A compliance alternative from the Part 11 tables may replace a Part 3, 4, 6 or 8 requirement if the chief building official is satisfied compliance is impracticable (structural or construction difficulties, or heritage). Alternatives for Part 9 or 12 requirements need no such finding. For a building less than five years old, alternatives are limited to the requirements referenced in 10.3.2.2.(3), (5) and Table 10.3.2.2.-B (OBC Div. B 10.4.1.1.OBC Div. B 10.4.1.1. Substitution(1) Except as provided in Sentence (3), a compliance alternative to a requirement contained in Part 3, 4, 6 or 8 that is shown in Tables 11.5.1.1.-A, 11.5.1.1.-B, 11.5.1.1.-C, 11.5.1.1.-D/E or 11.5.1.1.-F may be substituted for the requirement where the chief building official is satisfied that compliance with the…).
Renovation (Part 11)
Where an existing building is extended, materially altered or repaired, the work must comply with Section 11.3., and the performance level must be evaluated and compensating construction done under Section 11.4. (OBC Div. B 11.1.2.1.OBC Div. B 11.1.2.1. Extension, Material Alteration or Repair(1) Where an existing building is subject to extension, material alteration or repair, (a) the proposed construction shall comply with Section 11.3., and (b) the performance level of the building shall be evaluated and compensating construction shall be undertaken in accordance with Section 11.4.).
Building system means a combination of elements forming a complete major division of construction, for example the structure, roofing, windows, stairs, fire alarm, sprinklers, HVAC, plumbing, sewage system or electrical system (OBC Div. B 11.1.1.2.OBC Div. B 11.1.1.2. Definitions(1) In this Part, Building system means a combination of elements or components that form a complete major division of construction in the design of a building or part of a building, including a structural or framing system, a waterproofing system, a drainage system, an exterior cladding system, a roofing system, a…).
Classification. Where a renovation changes the major occupancy, the building is classified by its construction index (Table 11.2.1.1.-A, scale 1 to 8, with 1 the lowest fire protection performance and 8 the highest) and the hazard index of the occupancy (Tables 11.2.1.1.-B to -N) (OBC Div. B 11.2.1.1.OBC Div. B 11.2.1.1. Construction Index and Hazard Index(1) Where proposed construction will result in the change of major occupancy of all or part of an existing building to another major occupancy, the building shall be classified as to its, (a) construction on the basis of its construction index as provided for in this Part, including Table 11.2.1.1.-A, and (See Note…; Div. A 1.4.1.2.OBC Div. A 1.4.1.2.(1) Construction indexConstruction index means a level on a scale of 1 to 8 determined in accordance with Table 11.2.1.1.-A of Division B designating the expected performance level of the building structure with respect to the type of construction and fire protection of an existing building, and "C.I." has a corresponding meaning.). Group G may be calculated as Group F, Division 2.
Proposed construction (11.3.)
| Work | Rule |
|---|---|
| Material alteration or repair of a building system | Performance level at least equal to before (OBC Div. B 11.3.1.1.OBC Div. B 11.3.1.1. Material Alteration or Repair of a Building System(1) Where an existing building system is materially altered or repaired, the performance level of the building after the material alteration or repair shall be at least equal to the performance level of the building prior to the material alteration or repair. (See Note A-11.3.1.1.(1))) |
| New or extended building system | Complies with the other Parts, except as 11.3.3.1. and 11.5. allow |
| Extension of a building | Part 11 applies to the existing part; the extension complies with all other Parts (OBC Div. B 11.3.2.1.OBC Div. B 11.3.2.1. Portion of Extended Buildings(1) Where an existing building is extended, (a) this Part applies to the existing portion of the building, and (b) the extended portion of the building shall comply with all other Parts.) |
| Basic renovation | Reuse of same or similar materials to keep character or heritage value, if it does not hurt early warning, fire separations, structure or health (OBC Div. B 11.3.3.1.OBC Div. B 11.3.3.1. Basic Renovation(1) Except as provided in Sentence (2) and Article 11.3.3.2., construction may be carried out to maintain the existing performance level of all or part of an existing building, by the reuse, relocation or extension of the same or similar materials or components, to retain the existing character, structural uniqueness…) |
| Extensive renovation | Where interior walls, ceilings, floors or roofs are substantially removed and replaced, structure and fire resistance meet the other Parts; barrier-free and sprinkler rules may apply (OBC Div. B 11.3.3.2.OBC Div. B 11.3.3.2. Extensive Renovation(1) Where existing interior walls or ceilings or floor assemblies or roof assemblies are substantially removed in an existing building and new interior walls, ceilings, floor assemblies or roof assemblies are installed in the building, structural and fire-resistance elements shall be constructed in compliance with the…) |
| Plumbing and septic tanks | Part 7 for new and adversely affected plumbing; Part 8 for altered or replaced septic tanks; water table separation applies to the whole altered sewage system |
Performance level (11.4.). Not less after construction than before; if reduced, compensating construction is required (OBC Div. B 11.4.1.1.OBC Div. B 11.4.1.1. Performance Level(1) The performance level of a building after construction shall not be less than the performance level of the building prior to construction. (2) For the purposes of Sentence (1), reduction of performance level shall be determined in accordance with Subsection 11.4.2. (3) Where the proposed construction would reduce…). Main triggers:
| Trigger | Compensating construction |
|---|---|
| Structure inadequate after a change of occupancy, a 15% occupant load increase or a use-related live load increase | Strengthen, or restrict floor loads and post signs |
| Occupant load up by more than 15% (OBC Div. B 11.4.2.2.OBC Div. B 11.4.2.2. Increase in Occupant Load(1) Except as provided in Sentences 11.4.2.5.(2) and (3), the performance level of an existing building is reduced where proposed construction will increase the occupant load of an existing building by more than 15%. (2) The performance level of an existing building is reduced where proposed construction will increase…) | Evaluate and upgrade early warning and evacuation systems per Table 11.4.3.3. |
| Change to an occupancy of greater hazard index | Upgrade per Table 11.4.3.4.-A so the C.I. at least equals the new H.I. |
| Plumbing or sewage system adversely affected | Upgrade to Part 7 or Part 8 |
| Combustible building extended to more than four storeys (OBC Div. B 11.4.2.6.OBC Div. B 11.4.2.6. Extension of Buildings of Combustible Construction(1) The performance level of an existing building of combustible construction is reduced where the existing building is extended by adding a storey or storeys such that the extended building will be more than four storeys in building height.) | Sprinkler the building |
Compliance alternatives (11.5.)
A "compliance alternative" is a substitute for a requirement in another Part of Division B, listed in Part 10 or 11 (OBC Div. A 1.4.1.2.OBC Div. A 1.4.1.2.(1) Compliance alternativeCompliance alternative means a substitute for a requirement in another Part of Division B that is listed in Part 10 or 11 of Division B, and "C.A." has a corresponding meaning.). Under OBC Div. B 11.5.1.1.OBC Div. B 11.5.1.1. Compliance Alternatives(1) A compliance alternative shown in Table 11.5.1.1.-A, 11.5.1.1.-B, 11.5.1.1.-C, 11.5.1.1.-D/E or 11.5.1.1.-F may be substituted for a requirement contained in Part 3, 4, 6 or 8 where the chief building official is satisfied that compliance with the requirement is impracticable because, (a) of structural or…, alternatives from Tables 11.5.1.1.-A to -F may replace:
- a Part 3, 4, 6 or 8 requirement, if the chief building official is satisfied compliance is impracticable because of structural or construction difficulties or because it would harm the preservation of a heritage building; or
- a Part 9 or 12 requirement, without that finding.
Worked examples
Example 1. Existing C.I. is 5. The new occupancy's H.I. is 5 (up from 3). Performance level reduced? No: the new H.I. does not exceed the existing C.I. (10.3.2.2.(5)).
Example 2. Occupant load rises from 80 to 95. That is an 18.75% increase, more than 15%, so performance is reduced and early warning and evacuation systems must be evaluated and upgraded.
Example 3. A 3-year-old building changes occupancy. Can the designer use any compliance alternative? No, only those for the requirements referenced in 10.3.2.2.(3), (5) and Table 10.3.2.2.-B.
Chapter review
Chapter at a glance
One line per section: the idea to carry into the exam. Then the answers that most often catch candidates out.
- Change of use (Part 10)
Part 10 applies as described in Division A 1.3.3.. Besides an actual change of major occupancy, these are deemed changes in major occupancy: one Group C suite split into more, A-2…
- Renovation (Part 11)
Where an existing building is extended, materially altered or repaired, the work must comply with Section 11.3., and the performance level must be evaluated and compensating…
Practice this chapter
Questions on Change of use and renovation (Parts 10 and 11), in the exam format, every answer explained and cited to its article. Sign in to start; a free account gets the free questions.
Code cited in this chapter
Based on the official 2024 Building Code Compendium on ontario.ca.
© King's Printer for Ontario, 2024. Reproduced with permission.
OBC Div. A 1.4.1.2.(1) Performance level
Open OBC Div. A 1.4.1.2.(1) in the code viewerPerformance level means the level of performance under which all or part of an existing building functions with respect to its building systems.
OBC Div. B 10.1.1.1. Scope
Open OBC Div. B 10.1.1.1. in the code viewer(1)The scope of this Part shall be as described in Subsection 1.3.3. of Division A.
OBC Div. B 10.1.1.2. Change in Major Occupancy
Open OBC Div. B 10.1.1.2. in the code viewer(1)The following changes of use are also deemed to be a change in major occupancy for the purposes of this Part:
(a)a suite of a Group C major occupancy is converted into more than one suite of a Group C major occupancy,
(b)a suite or part of a suite of a Group A, Division 2 or Group A, Division 4 major occupancy is converted to a gaming premises,
(c)a farm building or part of a farm building is changed to another major occupancy other than a Group G major occupancy,
(d)a building or part of a building is changed to a post-disaster building,
(e)a building or part of a building is changed to a retirement home,
(f)the use of a building or part of a building is changed and the previous major occupancy of the building or part of the building cannot be determined, or
(g)a farm building or part of a farm building is changed to a Group G, Division 1 major occupancy.
OBC Div. B 10.3.1.1. General
Open OBC Div. B 10.3.1.1. in the code viewer(1)Except as provided in Section 10.4., a building or part of a building subject to a change of major occupancy shall conform to the requirements of Subsection 3.2.6., Sections 3.7., 3.11. and 3.12., Sentences 6.3.1.1.(2) and 6.3.2.7.(1), Subsections 9.5.1. and 9.5.3., 9.5.3A. to 9.5.3F. and 9.5.4., Sentences 9.6.1.4.(3), (4), Article 9.7.2.3., Sentences 9.8.8.1.(4) to (8) and 9.9.10.1.(1) to (7), Subsection 9.10.17., Sections 9.31. and 9.32., Sentence 9.33.6.13.(7.1), and Subsections 9.34.1. to 9.34.3. as they apply to the new major occupancy that the building or part of a building is to support.
(2)Where a major occupancy is changed to a Group B, Division 2 major occupancy, heating, ventilating, and air conditioning systems shall conform to the requirements of Sentence 6.2.1.1.(1).
(3)Where a major occupancy is changed to a Group B, Division 3 major occupancy, ventilation, air circulation, and filtration systems, shall conform to the requirements of Sentence 6.2.1.1.(1).
OBC Div. B 10.3.2.1. General
Open OBC Div. B 10.3.2.1. in the code viewer(1)The performance level of a building after the change of major occupancy shall not be less than the performance level prior to the change of major occupancy.
(2)For the purposes of Sentence (1), reduction of performance level shall be determined in accordance with Article 10.3.2.2.
(3)For the purpose of this Subsection, where a permit to construct a farm building has been applied for before January 1, 2025, the performance level of the farm building is permitted to be evaluated based on the applicable requirements of Ontario Regulation 332/12 (Building Code) made under the Act, as it read on December 31, 2024.
OBC Div. B 10.3.2.2. Reduction in Performance Level
Open OBC Div. B 10.3.2.2. in the code viewer(1)Except as provided in Sentence (2), the performance level of a building or part of a building is reduced where the existing structural floor and roof framing systems and their supporting members are not adequate to support the proposed dead loads and live loads of the new major occupancy that the building is to support.
(2)The inadequacy of the existing structural floor or roof framing system and its supporting members to support the proposed dead loads and live loads does not reduce the performance level of the building if the portion of the floor affected by the proposed loads is restricted to the loading it will support and signs stating the restrictions are posted.
(3)Except as provided in Section 10.4., the performance level of a building or part of a building is reduced where the early warning and evacuation systems requirements of the building do not meet the early warning and evacuation systems requirements set out in Table 10.3.2.2.-A for the new major occupancy that the building is to support.
(4)Except as provided in Sentence (5), the performance level of an existing building is reduced where a change in use will result in a change of the major occupancy of all or part of an existing building to another major occupancy of a greater hazard index.
(5)Except as provided in Sentence (6), if the hazard index of the new major occupancy is greater than the hazard index of the existing major occupancy, the performance level is not reduced where the hazard index of the new major occupancy is not greater than the construction index of the existing building.
(6)Small or medium sized existing buildings as determined in Tables 11.2.1.1.-B to 11.2.1.1.-N facing multiple streets may be assigned a hazard index credit of 1, which may be subtracted from the hazard index of the new major occupancy provided,
(a)the building does not contain a Group B, Division 1, a Group C, or a Group F, Division 1 occupancy, and
(b)firefighting access complying with Articles 3.2.5.1. to 3.2.5.5. or Subsection 9.10.20. is provided.
(7)Except as provided in Sentence (8), the performance level of a building or part of a building is reduced in an existing building of combustible construction where,
(a)the occupancy is changed to a residential occupancy in all or part of the building, and
(b)if the building was new, it would have been required to be of noncombustible construction or to be constructed in accordance with Article 3.2.2.51. or 3.2.2.60.
(8)A change in the occupancy of a building or part of a building to a residential occupancy does not reduce the performance level of the building or part of the building where,
(a)the building is sprinklered, and
(b)the building does not exceed 6 storeys in building height.
(9)The performance level of a building or part of a building is reduced where the new major occupancy in an existing building of multiple occupancy is not separated from adjoining major occupancies by fire separations having fire-resistance ratings conforming to Article 3.1.3.1., Subsection 9.10.9. or Table 10.3.2.2.-B.
(10)The performance level of a building is reduced where the building after the change of major occupancy will not comply with Article 3.1.3.2. or 9.10.9.14.
(11)The performance level of a building or part of a building is reduced where, after a change of major occupancy,
(a)the total daily design sanitary sewage flow of the new major occupancy, calculated in accordance with Article 8.2.1.3., exceeds the capacity of any component of a sewage system serving the building, or
(b)the type or amount of sanitary sewage that will, under the new major occupancy, be discharged to a sewage system serving the building is prohibited by Article 8.1.3.1.
(12)The performance level of an existing building or part of an existing building is reduced where,
(a)the use of the building or part of the building is changed to a retirement home, and
(b)any of the following applies:
(i)the retirement home is not sprinklered throughout,
(ii)Clause 3.2.6.8.(1)(b) or
(c)as applicable, requires that a voice communication system conforming to Article 3.2.4.22. be provided in the building and such a system is not provided in the building, or
(iii) the retirement home contains one or more doors to suites or sleeping rooms not within suites, other than doors leading directly to the exterior, that are not equipped with self-closing devices.
OBC Div. B 10.4.1.1. Substitution
Open OBC Div. B 10.4.1.1. in the code viewer(1)Except as provided in Sentence (3), a compliance alternative to a requirement contained in Part 3, 4, 6 or 8 that is shown in Tables 11.5.1.1.-A, 11.5.1.1.-B, 11.5.1.1.-C, 11.5.1.1.-D/E or 11.5.1.1.-F may be substituted for the requirement where the chief building official is satisfied that compliance with the requirement is impracticable because,
(a)of structural or construction difficulties, or
(b)it is detrimental to the preservation of a heritage building.
(2)Except as provided in Sentence (3), a compliance alternative to a requirement contained in Part 9 or 12 shown in Tables 11.5.1.1.-C, 11.5.1.1.-D/E or 11.5.1.1.-F may be substituted for the requirement without satisfying the chief building official that the requirement is impracticable.
(3)Where the building has been in existence for less than five years, compliance alternatives may only be used in respect of requirements of this Division that are referenced in Sentences 10.3.2.2.(3), (5) and Table 10.3.2.2.-B.
OBC Div. B 11.1.2.1. Extension, Material Alteration or Repair
Open OBC Div. B 11.1.2.1. in the code viewer(1)Where an existing building is subject to extension, material alteration or repair,
(a)the proposed construction shall comply with Section 11.3., and
(b)the performance level of the building shall be evaluated and compensating construction shall be undertaken in accordance with Section 11.4.
Show all 20 articles
OBC Div. B 11.1.1.2. Definitions
Open OBC Div. B 11.1.1.2. in the code viewer(1)In this Part,
Building system means a combination of elements or components that form a complete major division of construction in the design of a building or part of a building, including a structural or framing system, a waterproofing system, a drainage system, an exterior cladding system, a roofing system, a window system, a partition system, a corridor system, a stair system, a fire alarm and detection system, a sprinkler system or a heating, ventilation or air-conditioning system, a foundation system, a standpipe and hose system, a flooring system, a plumbing system, a sewage system or an electrical system.
OBC Div. B 11.2.1.1. Construction Index and Hazard Index
Open OBC Div. B 11.2.1.1. in the code viewer(1)Where proposed construction will result in the change of major occupancy of all or part of an existing building to another major occupancy, the building shall be classified as to its,
(a)construction on the basis of its construction index as provided for in this Part, including Table 11.2.1.1.-A, and (See Note A-11.2.1.1.(1)(a))
(b)occupancy on the basis of its hazard index as provided for in this Part, including Tables 11.2.1.1.-B to 11.2.1.1.-N. (See Note A-11.2.1.1.(1)(b))
(2)Small or medium sized existing buildings as determined in Tables 11.2.1.1.-B to 11.2.1.1.-N facing multiple streets may be assigned a hazard index credit of 1, which may be subtracted from the hazard index of the proposed major occupancy to reduce the additional upgrading required by Table 11.4.3.4.-A provided,
(a)the building does not contain a Group B, Division 1, a Group C, or a Group F, Division 1 occupancy, and
(b)firefighting access complying with Articles 3.2.5.1. to 3.2.5.5. or Subsection 9.10.20. is provided.
(3)The requirements of Articles 2.2.2.3. to 2.2.2.8. and 3.2.2.20. to 3.2.2.93. do not apply to this Part.
(4)For the purpose of this Part, the calculation of the construction index and hazard index for a Group G major occupancy is permitted to be based on a Group F, Division 2 major occupancy.
OBC Div. A 1.4.1.2.(1) Construction index
Open OBC Div. A 1.4.1.2.(1) in the code viewerConstruction index means a level on a scale of 1 to 8 determined in accordance with Table 11.2.1.1.-A of Division B designating the expected performance level of the building structure with respect to the type of construction and fire protection of an existing building, and "C.I." has a corresponding meaning.
OBC Div. B 11.3.1.1. Material Alteration or Repair of a Building System
Open OBC Div. B 11.3.1.1. in the code viewer(1)Where an existing building system is materially altered or repaired, the performance level of the building after the material alteration or repair shall be at least equal to the performance level of the building prior to the material alteration or repair. (See Note A-11.3.1.1.(1))
OBC Div. B 11.3.2.1. Portion of Extended Buildings
Open OBC Div. B 11.3.2.1. in the code viewer(1)Where an existing building is extended,
(a)this Part applies to the existing portion of the building, and
(b)the extended portion of the building shall comply with all other Parts.
OBC Div. B 11.3.3.1. Basic Renovation
Open OBC Div. B 11.3.3.1. in the code viewer(1)Except as provided in Sentence (2) and Article 11.3.3.2., construction may be carried out to maintain the existing performance level of all or part of an existing building, by the reuse, relocation or extension of the same or similar materials or components, to retain the existing character, structural uniqueness, heritage value, or aesthetic appearance of all or part of the building, if the construction will not adversely affect the early warning and evacuation systems, fire separations or the structural adequacy or will not create an unhealthy environment in the building.
(2)Construction in respect of a Group B, Division 3 occupancy, a hotel or a retirement home may be carried out in accordance with Sentence (1) only if the construction will be in conformance with the Fire Code made under the Fire Protection and Prevention Act, 1997.
OBC Div. B 11.3.3.2. Extensive Renovation
Open OBC Div. B 11.3.3.2. in the code viewer(1)Where existing interior walls or ceilings or floor assemblies or roof assemblies are substantially removed in an existing building and new interior walls, ceilings, floor assemblies or roof assemblies are installed in the building, structural and fire-resistance elements shall be constructed in compliance with the requirements of the other Parts.
(2)Except as provided in Section 11.5., the proposed construction within an existing suite shall comply with the requirements of Section 3.8. where,
(a)new interior walls or floor assemblies are installed,
(b)the suite has an area greater than 300 m², and
(c)the suite is located in,
(i)a floor area where the existing difference in elevation between the adjacent ground level and the floor level is not more than 200 mm, or
(ii)a normally occupied floor area which is accessible by a passenger type elevator or other platform equipped passenger elevating device from an entrance storey where the existing difference in elevation between the adjacent ground level and the entrance storey level is not more than 200 mm.
(3)Except as provided in Section 11.5., the proposed construction within an existing suite, other than a suite described in Sentence (2) or a suite in a building described in Clause 3.8.1.1.(1)(a), (b), (c) or (d), shall comply with the requirements of Sentences 3.8.1.3.(6), 3.8.2.3.(6), 3.8.3.1.(6), 3.8.3.3.(19), 3.8.3.7.(1), 3.8.3.15.(5) and 3.8.3.16.(4) where new interior walls or floor assemblies are installed. (See Note A-11.3.3.2.(3))
(4)Except as provided in Sentence (5), where existing interior walls or ceilings or floor assemblies or roof assemblies are substantially removed on any storey in an existing building and new interior walls, ceilings, floor assemblies or roof assemblies are installed, the storey shall be sprinklered if,
(a)the storey will contain a Group C major occupancy, and
(b)the building is over 3 storeys in building height.
(5)Sentence (4) does not apply where the building,
(a)conforms to Subclause 3.2.2.50.(1)(a)(ii), and
(b)contains dwelling units having means of egress conforming to Sentence 3.3.4.4.(8).
(6)Where existing interior walls or ceilings or floor assemblies or roof assemblies are substantially removed and new interior walls, ceilings, floor assemblies or roof assemblies are installed in an existing building or part of an existing building that is a retirement home, the following requirements apply:
(a)the retirement home shall be sprinklered,
(b)a voice communication system conforming to Article 3.2.4.23. shall be provided in the building, if Clause 3.2.6.8.(1)(b) or
(c)as applicable, requires that such a voice communication system be provided in the building, and
(c) doors to suites and sleeping rooms not within suites in the retirement home, other than doors leading directly to the exterior, shall be equipped with self-closing devices.
OBC Div. B 11.4.1.1. Performance Level
Open OBC Div. B 11.4.1.1. in the code viewer(1)The performance level of a building after construction shall not be less than the performance level of the building prior to construction.
(2)For the purposes of Sentence (1), reduction of performance level shall be determined in accordance with Subsection 11.4.2.
(3)Where the proposed construction would reduce the performance level of an existing building, compensating construction shall be required in conformance with Subsection 11.4.3.
(4)For the purpose of this Subsection, where a permit to construct a farm building has been applied for before January 1, 2025, the performance level of the farm building is permitted to be evaluated based on the applicable requirements of Ontario Regulation 332/12 (Building Code) made under the Act, as it read on December 31, 2024.
OBC Div. B 11.4.2.2. Increase in Occupant Load
Open OBC Div. B 11.4.2.2. in the code viewer(1)Except as provided in Sentences 11.4.2.5.(2) and (3), the performance level of an existing building is reduced where proposed construction will increase the occupant load of an existing building by more than 15%.
(2)The performance level of an existing building is reduced where proposed construction will increase the occupant load by 15% or less and the new occupant load will be more than 15% above the occupant load for which a fire alarm system is required under Sentence 3.2.4.1.(2).
(3)The performance level of an existing building is reduced where proposed construction will increase the occupant load by 15% or less and the new occupant load will be more than 15% above the existing exit capacity as required under Article 3.4.3.2.
OBC Div. B 11.4.2.6. Extension of Buildings of Combustible Construction
Open OBC Div. B 11.4.2.6. in the code viewer(1)The performance level of an existing building of combustible construction is reduced where the existing building is extended by adding a storey or storeys such that the extended building will be more than four storeys in building height.
OBC Div. A 1.4.1.2.(1) Compliance alternative
Open OBC Div. A 1.4.1.2.(1) in the code viewerCompliance alternative means a substitute for a requirement in another Part of Division B that is listed in Part 10 or 11 of Division B, and "C.A." has a corresponding meaning.
OBC Div. B 11.5.1.1. Compliance Alternatives
Open OBC Div. B 11.5.1.1. in the code viewer(1)A compliance alternative shown in Table 11.5.1.1.-A, 11.5.1.1.-B, 11.5.1.1.-C, 11.5.1.1.-D/E or 11.5.1.1.-F may be substituted for a requirement contained in Part 3, 4, 6 or 8 where the chief building official is satisfied that compliance with the requirement is impracticable because,
(a)of structural or construction difficulties, or
(b)it is detrimental to the preservation of a heritage building.
(2)A compliance alternative shown in Table 11.5.1.1.-A, 11.5.1.1.-B, 11.5.1.1.-C, 11.5.1.1.-D/E or 11.5.1.1.-F may be substituted for a requirement contained in Part 9 or 12 without satisfying the chief building official that compliance with the requirement is impracticable.